Thermal energy meter (BTU calculator) · BACnet points list

Integra Metering CALEC ST III (BACnet MS/TP) BACnet points list

Updated 12 November 2026Unofficial source

Short answer

The CALEC ST III is a heat and cooling energy calculator that pairs two temperature sensors with a flow meter. Its BACnet MS/TP interface reports energy, volume, mass, auxiliary counters, power, flows, hot/cold temperatures, temperature difference, density, a second power and flow channel and eight tariff registers as Analog Inputs, plus two commandable relay Binary Outputs. Which objects are present depends on the CALEC configuration.

This page lists 27 BACnet objects for the Integra Metering CALEC ST III (BACnet MS/TP) — 2 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Integra Metering’s documentation hosted by BACnet International, not by Integra Metering itself, so treat it as unofficial.

Manufacturer
Integra Metering
Model
CALEC ST III (BACnet MS/TP)
Equipment
Thermal energy meter (BTU calculator)
Equipment type
Thermostats, sensors & meters
BACnet objects
27 (2 writable)
Transport
BACnet MS/TP
Firmware
BACnet firmware V3.00.01, application V3.01.11 (PICS-03)
Also known as
CALEC ST III, CALEC ST 3, CALEC STIII, CALEC ST3, Calec ST III BACnet, CALEC ST FAMILY BACnet MSTP
Source document
CALEC ST III - BACnet MS/TP Protocol Implementation Conformance Statement · PICS-03 · rev. 2026-09-04 (unofficial copy, hosted by BACnet International)
Download CSV 27 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Integra Metering’s current documentation and the live device before use. Not official Integra Metering information. Terms of use.

BMS integration notes: Integra Metering CALEC ST III (BACnet MS/TP)

Integration in brief

Set the MS/TP address and baud on the CALEC, then read energy, power, flow and the two temperatures. Check each AI's Units property since units are selectable.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 0AI-0-EnergyAccumulated energyRead
AI 8AI-8-PowerThermal powerRead
AI 9AI-9-Volume flowVolume flowRead
AI 11AI-11-Temperature hotHot side temperatureRead
AI 12AI-12-Temperature coldCold side temperatureRead
AI 13AI-13-Temperature differenceTemperature difference, KRead
AI 2AI-2-VolumeAccumulated volumeRead

Network setup

Watch out for

Integra Metering CALEC ST III (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

27 of 27 shown
Type
AnalogBinary
Access
Show
Integra Metering CALEC ST III (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin0AI-0-EnergyEnergy (display E1)energy unit, selectableRead
AI1AI-1 Energy 2/Tariff 1Energy 2 / tariff 1 (E2)energy unit, selectableRead
AImin2AI-2-VolumeVolume (V1)volume unit, selectableRead
AI3AI-3 Volume 2/Tariff 1Volume 2 / tariff 1 (V2)volume unit, selectableRead
AI4AI-4-MassMass (M1); metric tons sent as short tonsmass unit, selectableRead
AI5AI-5-Auxiliary counter 1Auxiliary counter 1 (H1)selectableRead
AI6AI-6-Auxiliary counter 2Auxiliary counter 2 (H2)selectableRead
AImin8AI-8-PowerPower (P1)power unit, selectableRead
AImin9AI-9-Volume flowVolume flow (Qv1)flow unit, selectableRead
AI10AI-10-Mass flowMass flow (Qm1)mass flow unit, selectableRead
AImin11AI-11-Temperature hotHot side temperature (Th)°C, K or °FRead
AImin12AI-12-Temperature coldCold side temperature (Tc)°C, K or °FRead
AImin13AI-13-Temperature differenceTemperature difference (dT)KRead
AI14AI-14-DensityDensity (DEN)kg/m³Read
AI15AI-15 Energy tariff 2Energy tariff 2 (E3)energy unit, selectableRead
AI16AI-16-Power 2Power 2 (P2)power unit, selectableRead
AI17AI-17-Volume flow 2Volume flow 2 (Qv2)selectableRead
AI18AI-18-Energy/Volume tariff R1Energy or volume tariff register R1selectableRead
AI19AI-19-Energy/Volume tariff R2Energy or volume tariff register R2selectableRead
AI20AI-20-Energy/Volume tariff R3Energy or volume tariff register R3selectableRead
AI21AI-21-Energy/Volume tariff R4Energy or volume tariff register R4selectableRead
AI22AI-22-Energy/Volume tariff R5Energy or volume tariff register R5selectableRead
AI23AI-23-Energy/Volume tariff R6Energy or volume tariff register R6selectableRead
AI24AI-24-Energy/Volume tariff R7Energy or volume tariff register R7selectableRead
AI25AI-25-Energy/Volume tariff R8Energy or volume tariff register R8selectableRead
BO0BO-0Relay 1Command
BO1BO-1Relay 2Command
Object ID lookup: Integra Metering CALEC ST III point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CALEC ST III (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Integra Metering CALEC ST III (BACnet MS/TP)

How many BACnet points does the Integra Metering CALEC ST III (BACnet MS/TP) have?

This list has 27 BACnet objects: 25 analog inputs, 2 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Integra Metering CALEC ST III (BACnet MS/TP) BACnet points are writable?

2 of the 27 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Integra Metering CALEC ST III (BACnet MS/TP) BACnet documentation?

Integra Metering does not publish it on its own website. This list comes from CALEC ST III - BACnet MS/TP Protocol Implementation Conformance Statement (PICS-03), revision 2026-09-04, a copy hosted by BACnet International at https://www.bacnetinternational.net/catalog/manu/integra%20metering%20ag/PICS%202026-09-04-CALEC%20ST%20III%20BACNET%20MS-TP%20PICS-03.pdf. Ask Integra Metering or its representative for the current revision.

What are the minimum BACnet points to integrate the Integra Metering CALEC ST III (BACnet MS/TP)?

Start with AI 0 AI-0-Energy (Accumulated energy); AI 8 AI-8-Power (Thermal power); AI 9 AI-9-Volume flow (Volume flow); AI 11 AI-11-Temperature hot (Hot side temperature); AI 12 AI-12-Temperature cold (Cold side temperature); AI 13 AI-13-Temperature difference (Temperature difference, K); AI 2 AI-2-Volume (Accumulated volume).

How do I check these points on the real CALEC ST III (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Integra Metering BACnet points lists

Source: CALEC ST III - BACnet MS/TP Protocol Implementation Conformance Statement · PICS-03 · rev. 2026-09-04. Object names, instances and units are reproduced as published; descriptions are our own.