Fan drive (VFD) via BACnet gateway · BACnet points list

Hunter Fans Fan with Mitsubishi inverter (ProtoNode FPC-N64 profile) BACnet points list

Updated 7 November 2026Unofficial source

Short answer

Hunter's ProtoNode FPC-N64 profile for fans with a Mitsubishi inverter exposes 57 BACnet objects per fan: inverter reset and parameter clear commands, the inverter status bits (run, direction, fault and terminal states), operation mode and running frequency, output frequency, current, voltage and power, energy and load data, PID values and eight fault history entries.

This page lists 57 BACnet objects for the Hunter Fans Fan with Mitsubishi inverter (ProtoNode FPC-N64 profile) — 21 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Hunter Fans’s documentation hosted by W.W. Cannon (manufacturer's rep), not by Hunter Fans itself, so treat it as unofficial.

Manufacturer
Hunter Fans
Model
Fan with Mitsubishi inverter (ProtoNode FPC-N64 profile)
Equipment
Fan drive (VFD) via BACnet gateway
Equipment type
VFDs & pumps
BACnet objects
57 (21 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
50000 + Node-ID
Also known as
Hunter Fans ProtoNode, FPC-N64, Hunter Mitsubishi fan BACnet
Source document
ProtoNode FPC-N64 Start-up Guide For Interfacing Hunter Fans Products · rev. Document Revision 2.B (unofficial copy, hosted by W.W. Cannon (manufacturer's rep))
Download CSV 57 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Hunter Fans’s current documentation and the live device before use. Not official Hunter Fans information. Terms of use.

BMS integration notes: Hunter Fans Fan with Mitsubishi inverter (ProtoNode FPC-N64 profile)

Integration in brief

Set the running frequency for each fan and read the run status bit, output frequency, current and power, plus the fault bit and fault history.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 19InvXXX Op Mode/Inverter SetOperation mode / inverter settingWrite
AV 20InvXXX Running Freq (RAM Value)Running frequency (RAM, not EEPROM)Write
BV 6InvXXX Inverter Status Run/StopInverter status: runningWrite
AI 22InvXXX Output Frequency/SpeedOutput frequencyRead
AI 23InvXXX Output CurrentOutput currentRead
AI 33InvXXX Output PowerOutput powerRead
BI 57InvXXX Inverter Status Fault OccurFault occurredRead
AI 49InvXXX Fault History 1Latest fault (history 1)Read

Network setup

Watch out for

Hunter Fans Fan with Mitsubishi inverter (ProtoNode FPC-N64 profile) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

57 of 57 shown
Type
Access
Show
Hunter Fans Fan with Mitsubishi inverter (ProtoNode FPC-N64 profile) BACnet Points List
DescriptionStates
AV1InvXXX Inverter ResetModbus register 40002Write
AV2InvXXX Parameter ClearModbus register 40003Write
AV3InvXXX All Parameter ClearModbus register 40004Write
AV4InvXXX Parameter ClearModbus register 40006Write
AV5InvXXX All Parameter ClearModbus register 40007Write
BVmin6InvXXX Inverter Status Run/StopModbus register 40009.0Write
BV7InvXXX Inverter Status Forward RotModbus register 40009.1Write
BV8InvXXX Inverter Status Reverse RotModbus register 40009.2Write
BV9InvXXX Inverter Status SL/RHModbus register 40009.3Write
BV10InvXXX Inverter Status OL/RMModbus register 40009.4Write
BV11InvXXX Inverter Status IPF/RLModbus register 40009.5Write
BV12InvXXX Inverter Status FU/JOGModbus register 40009.6Write
BV13InvXXX Inverter Status ABC1/RTModbus register 40009.7Write
BV14InvXXX Inverter Status ABC2/AUModbus register 40009.8Write
BV15InvXXX Inverter Status CSModbus register 40009.9Write
BV16InvXXX Inverter Status MRSModbus register 40009.10Write
BV17InvXXX Inverter Status STOPModbus register 40009.11Write
BV18InvXXX Inverter Status RESModbus register 40009.12Write
AVmin19InvXXX Op Mode/Inverter SetModbus register 40010Write
AVmin20InvXXX Running Freq (RAM Value)Modbus register 40014Write
AV21InvXXX Running Freq (EEPROM Value)Modbus register 40015Write
AImin22InvXXX Output Frequency/SpeedModbus register 40201Read
AImin23InvXXX Output CurrentModbus register 40202Read
AI24InvXXX Output VoltageModbus register 40203Read
AI25InvXXX Freq Setting Value/Spd SetModbus register 40205Read
AI26InvXXX Running SpeedModbus register 40206Read
AI27InvXXX Converter Output VoltageModbus register 40208Read
AI28InvXXX Regenerative Brake DutyModbus register 40209Read
AI29InvXXX Elec Thrm Rel Func Load FacModbus register 40210Read
AI30InvXXX Output Current Peak ValueModbus register 40211Read
AI31InvXXX Conv Output Volt Peak ValueModbus register 40212Read
AI32InvXXX Input PowerModbus register 40213Read
AImin33InvXXX Output PowerModbus register 40214Read
AI34InvXXX Input Terminal StatusModbus register 40215Read
AI35InvXXX Output Terminal StatusModbus register 40216Read
AI36InvXXX Load MeterModbus register 40217Read
AI37InvXXX Cum energization TimeModbus register 40220Read
AI38InvXXX Actual Operation TimeModbus register 40223Read
AI39InvXXX Motor Load FactorModbus register 40224Read
AI40InvXXX Cumulative PowerModbus register 40225Read
AI41InvXXX Power Saving EffectModbus register 40250Read
AI42InvXXX Cumulative Saving PowerModbus register 40251Read
AI43InvXXX PID SetpointModbus register 40252Read
AI44InvXXX PID Measured ValueModbus register 40253Read
AI45InvXXX PID DeviationModbus register 40254Read
AI46InvXXX PTC Thermistor ResistanceModbus register 40264Read
AI47InvXXX Cumulative Power U32Modbus register 40277/40278Read
AI48InvXXX Cumulative Power FltModbus register 40279/40280Read
AImin49InvXXX Fault History 1Modbus register 40501Read
AI50InvXXX Fault History 2Modbus register 40502Read
AI51InvXXX Fault History 3Modbus register 40503Read
AI52InvXXX Fault History 4Modbus register 40504Read
AI53InvXXX Fault History 5Modbus register 40505Read
AI54InvXXX Fault History 6Modbus register 40506Read
AI55InvXXX Fault History 7Modbus register 40507Read
AI56InvXXX Fault History 8Modbus register 40508Read
BImin57InvXXX Inverter Status Fault OccurModbus register 40009.15Read
Object ID lookup: Hunter Fans Fan with Mitsubishi inverter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Fan with Mitsubishi inverter (ProtoNode FPC-N64 profile) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Hunter Fans Fan with Mitsubishi inverter (ProtoNode FPC-N64 profile)

How many BACnet points does the Hunter Fans Fan with Mitsubishi inverter (ProtoNode FPC-N64 profile) have?

This list has 57 BACnet objects: 35 analog inputs, 8 analog values, 1 binary input, 13 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Hunter Fans Fan with Mitsubishi inverter (ProtoNode FPC-N64 profile) BACnet points are writable?

21 of the 57 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Hunter Fans Fan with Mitsubishi inverter (ProtoNode FPC-N64 profile) BACnet documentation?

Hunter Fans does not publish it on its own website. This list comes from ProtoNode FPC-N64 Start-up Guide For Interfacing Hunter Fans Products, revision Document Revision 2.B, a copy hosted by W.W. Cannon (manufacturer's rep) at https://wwcannon.com/wp-content/uploads/2024/11/Hunter-ProtoNode-BMS-Secure-Gateway-Interface-Products.pdf. Ask Hunter Fans or its representative for the current revision.

What are the minimum BACnet points to integrate the Hunter Fans Fan with Mitsubishi inverter (ProtoNode FPC-N64 profile)?

Start with AV 19 InvXXX Op Mode/Inverter Set (Operation mode / inverter setting); AV 20 InvXXX Running Freq (RAM Value) (Running frequency (RAM, not EEPROM)); BV 6 InvXXX Inverter Status Run/Stop (Inverter status: running); AI 22 InvXXX Output Frequency/Speed (Output frequency); AI 23 InvXXX Output Current (Output current); AI 33 InvXXX Output Power (Output power); BI 57 InvXXX Inverter Status Fault Occur (Fault occurred); AI 49 InvXXX Fault History 1 (Latest fault (history 1)).

How do I check these points on the real Fan with Mitsubishi inverter (ProtoNode FPC-N64 profile)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Hunter Fans BACnet points lists