  3. HTP
  4. MODBUS/BACnet Adapter 7350P-636 (BIC-926/928 boilers and water heaters)

Boiler and water heater BACnet adapter · BACnet points list

HTP MODBUS/BACnet Adapter 7350P-636 (BIC-926/928 boilers and water heaters) BACnet points list

Updated 7 November 2026

Short answer

The HTP 7350P-636 adapter plugs into the appliance's BIC-926/928 control and serves it on BACnet MS/TP (or Modbus RTU). It reports thermostat and safety inputs, pump, gas valve and alarm outputs, outlet, inlet and flue temperatures, firing rates and status/blocking/lockout codes for up to 8 cascaded boilers, and BIC-928 run-hour and fault counters. The BMS writes a configuration word that decides which values it supplies (enable, setpoint or rate, DHW setpoint, outdoor and system temperatures) and then writes those values.

This page lists 111 BACnet objects for the HTP MODBUS/BACnet Adapter 7350P-636 (BIC-926/928 boilers and water heaters) — 15 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from HTP’s own free documentation, linked below.

Manufacturer
HTP
Model
MODBUS/BACnet Adapter 7350P-636 (BIC-926/928 boilers and water heaters)
Equipment
Boiler and water heater BACnet adapter
Equipment type
Boilers & water heaters
BACnet objects
111 (15 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
7350P-636, 64980290, HTP MODBUS/BACnet adapter, LP-548, BIC-928, BIC-926, EnduroTI, Elite Premier, Modcon, Modcon VWH, Pioneer, Versa Flame, Elite VWH, Phoenix
Source document
MODBUS / BACnet Adapter Installation Instructions (Part # 7350P-636) · LP-548 Rev. 000 Rel. 006 · rev. 2023-10-30
Download CSV 111 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against HTP’s current documentation and the live device before use. Not official HTP information. Terms of use.

BMS integration notes: HTP MODBUS/BACnet Adapter 7350P-636 (BIC-926/928 boilers and water heaters)

Integration in brief

Set the adapter for BACnet with its DIP switch, set the address and baud rate in the appliance installer menu, and discover it. Write AV 0 Configuration to say which values the BMS supplies, then write the coils (AV 1) for CH/DHW demand and the setpoint or rate (AV 2) and DHW setpoint (AV 3). Rewrite them at least once a minute, and read outlet temperature, firing rate and the status and lockout codes.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 0ConfigurationBits: which values the BMS supplies (1 = from BMS)Write
AV 1CoilsDemand bits: b0 room thermostat (CH), b4 tank (DHW)Write
AV 20-10 volt / rate / setpSetpoint or firing-rate command (0-10 V scale)Write
AV 3DHW setpointDHW setpoint from the BMSWrite
AI 8Outlet Temp. 1Outlet temperatureRead
AI 11Firing Rate 1Firing rateRead
AI 13Boil. 1 Status CodeStatus codeRead
BI 33Alarm cont. 1 (EXCEPT Versa Hydro)Alarm outputRead
AI 15Boil. 1 Lockout CodeLockout codeRead

Enable & remote start

Set configuration bit B0 (boiler enable) or B1 (tank enable) in AV 0, then write the AV 1 Coils bits: b0 room thermostat (CH demand), b4 tank thermostat (DHW demand).

Heartbeat & communication loss

A 4-minute communication timer returns the appliance to its own controls if no write arrives; each write resets it. Update temperature values at least once a minute but not more than once a second.

Sensors & values from the BMS

Setting configuration bits B4-B7 makes the appliance use the BMS-written DHW temperature (AV 4), outdoor temperature (AV 5), system supply (AV 6) and system return (AV 7) instead of its own sensors.

Network setup

Watch out for

HTP MODBUS/BACnet Adapter 7350P-636 (BIC-926/928 boilers and water heaters) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

111 of 111 shown
Type
Access
Show
HTP MODBUS/BACnet Adapter 7350P-636 (BIC-926/928 boilers and water heaters) BACnet Points List
DescriptionStates
BV0En / Room Th1 / Stg 1Write0=Off, 1=On
BV4Tank thermostatWrite0=Off, 1=On
BI0MHRLwater heater: High temp safety switch / High flue temp switchRead0=Off, 1=On
BI1Flow switchRead0=Off, 1=On
BI2Gas Press. SwitchBIC-928 onlyRead0=Off, 1=On
BI4Air Press SwitchRead0=Off, 1=On
BI5Blocked drainwater heater: Blocked vent pressure switchRead0=Off, 1=On
BI6ARHLwater heater: High temp safety switch / High flue temp switchRead0=Off, 1=On
BI7Flame 1water heater: Flame rectification probeRead0=Off, 1=On
BI8Enable / STG1Read0=Off, 1=On
BI9Tank thRead0=Off, 1=On
BI10STG2 / APSRead0=Off, 1=On
BI32Run-time cont. 1Read0=Off, 1=On
BImin33Alarm cont. 1 (EXCEPT Versa Hydro)water heater: Alarm outputRead0=Off, 1=On
BI34CH pump 1Read0=Off, 1=On
BI35DHW pump 1Read0=Off, 1=On
BI37Gas valve 1water heater: Gas valveRead0=Off, 1=On
BI38Sys pumpRead0=Off, 1=On
BI48Boiler 1 Run (same as 11118)water heater: Run statusRead0=Off, 1=On
BI49Boiler 2 Run (same as 10023)Read0=Off, 1=On
BI50Boiler 3 RunRead0=Off, 1=On
BI51Boiler 4 RunRead0=Off, 1=On
BI52Boiler 5 RunRead0=Off, 1=On
BI53Boiler 6 RunRead0=Off, 1=On
BI54Boiler 7 RunRead0=Off, 1=On
BI55Boiler 8 RunRead0=Off, 1=On
BI56Lockout 1 (same as 10034)water heater: Lockout StatusRead0=Off, 1=On
BI57Lockout 2 (same as 10042)Read0=Off, 1=On
BI58Lockout 3Read0=Off, 1=On
BI59Lockout 4Read0=Off, 1=On
BI60Lockout 5Read0=Off, 1=On
BI61Lockout 6Read0=Off, 1=On
BI62Lockout 7Read0=Off, 1=On
BI63Lockout 8Read0=Off, 1=On
BI64Alarm relais ecs (Versa Hydro ONLY)Read0=Off, 1=On
AI0Discrete Inputs 1-16Packed discrete inputs 1-16Read
AI1Discrete Inputs 17-32Packed discrete inputs 17-32Read
AI2Discrete Inputs 33-48Packed discrete inputs 33-48Read
AI3*System / Cascade Setp.System / cascade setpoint (valid while heating)°FRead
AI4System Pump 4 speed%Read
AI5Cascade Total Power%Read
AI6Cascade Current Power%Read
AI7*Outlet Setp. 1Boiler 1 outlet setpoint (valid while heating)°FRead
AImin8Outlet Temp. 1water heater: Upper Temp Sensor°FRead
AI9Inlet Temp. 1water heater: Lower Temp Sensor°FRead
AI10Flue Temp. 1°FRead
AImin11Firing Rate 1%Read
AI12Boil. 1 Pump speed 5%Read
AImin13Boil. 1 Status Codewater heater: Status Code 1Read
AI14Boil. 1 Blocking Codewater heater: Blocking Code 1Read
AImin15Boil. 1 Lockout Codewater heater: Lockout Code 1Read
AI17Outlet Temp 2°FRead
AI20Firing Rate 2%Read
AI21Boil. 2 Pump 4 speed%Read
AI22Boil. 2 Status CodeRead
AI23Boil. 2 Blocking CodeRead
AI24Boil. 2 Lockout CodeRead
AI25Boiler Outlet 3°FRead
AI26Boiler 3 Firing Rate%Read
AI27Boiler 3 StatusRead
AI28Boiler 3 LockoutRead
AI29Boiler Outlet 4°FRead
AI30Boiler 4 Firing Rate%Read
AI31Boiler 4 StatusRead
AI32Boiler 4 LockoutRead
AI33Boiler Outlet 5°FRead
AI34Boiler 5 Firing Rate%Read
AI35Boiler 5 StatusRead
AI36Boiler 5 LockoutRead
AI37Boiler Outlet 6°FRead
AI38Boiler 6 Firing Rate%Read
AI39Boiler 6 StatusRead
AI40Boiler 6 LockoutRead
AI41Boiler Outlet 7°FRead
AI42Boiler 7 Firing Rate%Read
AI43Boiler 7 StatusRead
AI44Boiler 7 LockoutRead
AI45Boiler Outlet 8°FRead
AI46Boiler 8 Firing Rate%Read
AI47Boiler 8 StatusRead
AI48Boiler 8 LockoutRead
AI49Discrete Inputs 49 - 64Packed discrete inputs 49-64Read
AI50NTC 6 temperature°FRead
AI51NTC 7 temperature°FRead
AI52NTC 9 temperature°FRead
AI53Vortex 1 flowL/minRead
AI54Vortex 1 temp°FRead
AI55Vortex 2 flowL/minRead
AI56Vortex 2 temp°FRead
AI90Total FaultsBIC-928 onlyRead
AI91Total Last FaultsBIC-928 onlyRead
AI92Run Hours CHBIC-928 onlyhRead
AI93Run Hours DHWBIC-928 onlyhRead
AI94Run Hours Cas CHBIC-928 onlyhRead
AI95Run Hours Cas DHWBIC-928 onlyhRead
AI96Power HoursBIC-928 onlyhRead
AI98Start CounterBIC-928 onlyRead
AI99Start CounterBIC-928 onlyRead
AVmin0ConfigurationConfiguration bits: which inputs come from the BMSWrite
AVmin1CoilsCoil bits: boiler enable (b0), tank enable (b4)Write
AVmin20-10 volt / rate / setpRate / setpoint command via 0-10 V scale; water heater: 0-10 volt / rate / setVWrite
AVmin3DHW setpointDHW setpoint from the BMS; water heater: DHW set°FWrite
AV4DHW temperaturDHW tank temperature from the BMS; water heater: DHW temp°FWrite
AV5Outdoor temp.Outdoor temperature from the BMS; water heater: Outdoor Sensor°FWrite
AV6Sys supply temp.System supply temperature from the BMS°FWrite
AV7Sys rtn temp.System return temperature from the BMS°FWrite
AV8I4 for directI4 offset°FWrite
AV9CH post purgeCH post-purge timesWrite
AV10DHW post purgeDHW post-purge timesWrite
AV11Pump 4 SpeedPump 4 speed%Write
AV13Extra out ECSExtra 0-10 V output%Write
Object ID lookup: HTP MODBUS/BACnet Adapter 7350P-636 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MODBUS/BACnet Adapter 7350P-636 (BIC-926/928 boilers and water heaters) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the HTP MODBUS/BACnet Adapter 7350P-636 (BIC-926/928 boilers and water heaters)

How many BACnet points does the HTP MODBUS/BACnet Adapter 7350P-636 (BIC-926/928 boilers and water heaters) have?

This list has 111 BACnet objects: 63 analog inputs, 13 analog values, 33 binary inputs, 2 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which HTP MODBUS/BACnet Adapter 7350P-636 (BIC-926/928 boilers and water heaters) BACnet points are writable?

15 of the 111 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official HTP MODBUS/BACnet Adapter 7350P-636 (BIC-926/928 boilers and water heaters) BACnet documentation?

The source is MODBUS / BACnet Adapter Installation Instructions (Part # 7350P-636) (LP-548 Rev. 000 Rel. 006), revision 2023-10-30, published free by HTP at https://htproducts.com/literature/lp-548.pdf.

What are the minimum BACnet points to integrate the HTP MODBUS/BACnet Adapter 7350P-636 (BIC-926/928 boilers and water heaters)?

Start with AV 0 Configuration (Bits: which values the BMS supplies (1 = from BMS)); AV 1 Coils (Demand bits: b0 room thermostat (CH), b4 tank (DHW)); AV 2 0-10 volt / rate / setp (Setpoint or firing-rate command (0-10 V scale)); AV 3 DHW setpoint (DHW setpoint from the BMS); AI 8 Outlet Temp. 1 (Outlet temperature); AI 11 Firing Rate 1 (Firing rate); AI 13 Boil. 1 Status Code (Status code); BI 33 Alarm cont. 1 (EXCEPT Versa Hydro) (Alarm output); AI 15 Boil. 1 Lockout Code (Lockout code).

How do I enable BMS control of the HTP MODBUS/BACnet Adapter 7350P-636 (BIC-926/928 boilers and water heaters)?

Set configuration bit B0 (boiler enable) or B1 (tank enable) in AV 0, then write the AV 1 Coils bits: b0 room thermostat (CH demand), b4 tank thermostat (DHW demand).

Does the HTP MODBUS/BACnet Adapter 7350P-636 (BIC-926/928 boilers and water heaters) need a BACnet heartbeat or have a communication timeout?

A 4-minute communication timer returns the appliance to its own controls if no write arrives; each write resets it. Update temperature values at least once a minute but not more than once a second.

Can the BMS supply sensor values to the HTP MODBUS/BACnet Adapter 7350P-636 (BIC-926/928 boilers and water heaters)?

Setting configuration bits B4-B7 makes the appliance use the BMS-written DHW temperature (AV 4), outdoor temperature (AV 5), system supply (AV 6) and system return (AV 7) instead of its own sensors.

How do I check these points on the real MODBUS/BACnet Adapter 7350P-636 (BIC-926/928 boilers and water heaters)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: MODBUS / BACnet Adapter Installation Instructions (Part # 7350P-636) · LP-548 Rev. 000 Rel. 006 · rev. 2023-10-30. Object names, instances and units are reproduced as published; descriptions are our own.