 "manufacturer": "HTP",
 "manufacturer_slug": "htp",
 "model": "MODBUS/BACnet Adapter 7350P-636 (BIC-926/928 boilers and water heaters)",
 "model_slug": "modbus-bacnet-adapter-7350p-636",
 "aliases": [
  "7350P-636",
  "64980290",
  "HTP MODBUS/BACnet adapter",
  "LP-548",
  "BIC-928",
  "BIC-926",
  "EnduroTI",
  "Elite Premier",
  "Modcon",
  "Modcon VWH",
  "Pioneer",
  "Versa Flame",
  "Elite VWH",
  "Phoenix"
 ],
 "equipment_type": "Boiler and water heater BACnet adapter",
 "applies_to": "HTP boilers and water heaters with BIC-926 or BIC-928 controls (BIC-928: EnduroTI and Elite Premier boilers; BIC-926: Modcon, Modcon VWH, Pioneer and Versa Flame built from July 2011, and Elite, Elite VWH and Phoenix water heaters built from August 2011) fitted with the 7350P-636 MODBUS/BACnet adapter.",
 "summary": "The HTP 7350P-636 adapter plugs into the appliance's BIC-926/928 control and serves it on BACnet MS/TP (or Modbus RTU). It reports thermostat and safety inputs, pump, gas valve and alarm outputs, outlet, inlet and flue temperatures, firing rates and status/blocking/lockout codes for up to 8 cascaded boilers, and BIC-928 run-hour and fault counters. The BMS writes a configuration word that decides which values it supplies (enable, setpoint or rate, DHW setpoint, outdoor and system temperatures) and then writes those values.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": null,
 "access_inferred": true,
 "notes": [
  "The manual table gives no object names; names here are the 'Heating Appliance' descriptions. Where the water heater meaning differs it is in the description.",
  "The manual header gives part # 64980290; HTP sells the adapter as 7350P-636. The source PDF is scanned (image only); this list was keyed from the page images and checked row by row.",
  "Objects marked BIC-928 only (bold italics in the manual) do not exist on BIC-926 appliances.",
  "Access is not printed per object: AV and BV (holding registers / coils) are taken as writable, AI and BI as read-only.",
  "Temperatures are °F with 0.1 resolution; setpoint objects marked * are only valid during a heating cycle. AI 92-96 counts are in units of 5 hours (x5 resolution).",
  "AV 12 (Pump 5 speed) is referenced in the configuration bits but not printed in the object table."
 ],
 "source": {
  "title": "MODBUS / BACnet Adapter Installation Instructions (Part # 7350P-636)",
  "doc_number": "LP-548 Rev. 000 Rel. 006",
  "revision_date": "2023-10-30",
  "url": "https://htproducts.com/literature/lp-548.pdf"
 },
 "integration": {
  "summary": "Set the adapter for BACnet with its DIP switch, set the address and baud rate in the appliance installer menu, and discover it. Write AV 0 Configuration to say which values the BMS supplies, then write the coils (AV 1) for CH/DHW demand and the setpoint or rate (AV 2) and DHW setpoint (AV 3). Rewrite them at least once a minute, and read outlet temperature, firing rate and the status and lockout codes.",
  "minimum_points": [
   {
    "ref": "AV 0",
    "name": "Configuration",
    "why": "Bits: which values the BMS supplies (1 = from BMS)"
   },
   {
    "ref": "AV 1",
    "name": "Coils",
    "why": "Demand bits: b0 room thermostat (CH), b4 tank (DHW)"
   },
   {
    "ref": "AV 2",
    "name": "0-10 volt / rate / setp",
    "why": "Setpoint or firing-rate command (0-10 V scale)"
   },
   {
    "ref": "AV 3",
    "name": "DHW setpoint",
    "why": "DHW setpoint from the BMS"
   },
   {
    "ref": "AI 8",
    "name": "Outlet Temp. 1",
    "why": "Outlet temperature"
   },
   {
    "ref": "AI 11",
    "name": "Firing Rate 1",
    "why": "Firing rate"
   },
   {
    "ref": "AI 13",
    "name": "Boil. 1 Status Code",
    "why": "Status code"
   },
   {
    "ref": "BI 33",
    "name": "Alarm cont. 1 (EXCEPT Versa Hydro)",
    "why": "Alarm output"
   },
   {
    "ref": "AI 15",
    "name": "Boil. 1 Lockout Code",
    "why": "Lockout code"
   }
  ],
  "enable": "Set configuration bit B0 (boiler enable) or B1 (tank enable) in AV 0, then write the AV 1 Coils bits: b0 room thermostat (CH demand), b4 tank thermostat (DHW demand).",
  "heartbeat": "A 4-minute communication timer returns the appliance to its own controls if no write arrives; each write resets it. Update temperature values at least once a minute but not more than once a second.",
  "remote_sensors": "Setting configuration bits B4-B7 makes the appliance use the BMS-written DHW temperature (AV 4), outdoor temperature (AV 5), system supply (AV 6) and system return (AV 7) instead of its own sensors.",
  "setup": [
   "DIP switch 10 ON selects BACnet (OFF = Modbus); installer menu parameter 37 MODBUS MODE must be ON or AUTO (factory default OFF).",
   "The appliance can also run on its own controls with the BMS only reading values (monitoring only)."
  ],
  "gotchas": [
   "While the BMS writes tank temperature and tank enable, the appliance ignores its internal DHW limit.",
   "A bit set in AV 0 tells the appliance to ignore its own value and wait for the BMS one; leave bits clear for values it should measure itself."
  ]
 },
 "points": [
  {
   "type": "BV",
   "instance": 0,
   "name": "En / Room Th1 / Stg 1",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "Tank thermostat",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 0,
   "name": "MHRL",
   "description": "water heater: High temp safety switch / High flue temp switch",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "Flow switch",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "Gas Press. Switch",
   "description": "BIC-928 only",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "Air Press Switch",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 5,
   "name": "Blocked drain",
   "description": "water heater: Blocked vent pressure switch",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 6,
   "name": "ARHL",
   "description": "water heater: High temp safety switch / High flue temp switch",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 7,
   "name": "Flame 1",
   "description": "water heater: Flame rectification probe",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 8,
   "name": "Enable / STG1",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 9,
   "name": "Tank th",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 10,
   "name": "STG2 / APS",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 32,
   "name": "Run-time cont. 1",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 33,
   "name": "Alarm cont. 1 (EXCEPT Versa Hydro)",
   "description": "water heater: Alarm output",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 34,
   "name": "CH pump 1",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 35,
   "name": "DHW pump 1",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 37,
   "name": "Gas valve 1",
   "description": "water heater: Gas valve",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 38,
   "name": "Sys pump",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 48,
   "name": "Boiler 1 Run (same as 11118)",
   "description": "water heater: Run status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 49,
   "name": "Boiler 2 Run (same as 10023)",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 50,
   "name": "Boiler 3 Run",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 51,
   "name": "Boiler 4 Run",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 52,
   "name": "Boiler 5 Run",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 53,
   "name": "Boiler 6 Run",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 54,
   "name": "Boiler 7 Run",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 55,
   "name": "Boiler 8 Run",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 56,
   "name": "Lockout 1 (same as 10034)",
   "description": "water heater: Lockout Status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 57,
   "name": "Lockout 2 (same as 10042)",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 58,
   "name": "Lockout 3",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 59,
   "name": "Lockout 4",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 60,
   "name": "Lockout 5",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 61,
   "name": "Lockout 6",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 62,
   "name": "Lockout 7",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 63,
   "name": "Lockout 8",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 64,
   "name": "Alarm relais ecs (Versa Hydro ONLY)",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AI",
   "instance": 0,
   "name": "Discrete Inputs 1-16",
   "description": "Packed discrete inputs 1-16",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "Discrete Inputs 17-32",
   "description": "Packed discrete inputs 17-32",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "Discrete Inputs 33-48",
   "description": "Packed discrete inputs 33-48",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "*System / Cascade Setp.",
   "description": "System / cascade setpoint (valid while heating)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "System Pump 4 speed",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "Cascade Total Power",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "Cascade Current Power",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "*Outlet Setp. 1",
   "description": "Boiler 1 outlet setpoint (valid while heating)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "Outlet Temp. 1",
   "description": "water heater: Upper Temp Sensor",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "Inlet Temp. 1",
   "description": "water heater: Lower Temp Sensor",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "Flue Temp. 1",
   "description": "",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 11,
   "name": "Firing Rate 1",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 12,
   "name": "Boil. 1 Pump speed 5",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 13,
   "name": "Boil. 1 Status Code",
   "description": "water heater: Status Code 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 14,
   "name": "Boil. 1 Blocking Code",
   "description": "water heater: Blocking Code 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "Boil. 1 Lockout Code",
   "description": "water heater: Lockout Code 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 17,
   "name": "Outlet Temp 2",
   "description": "",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 20,
   "name": "Firing Rate 2",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 21,
   "name": "Boil. 2 Pump 4 speed",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 22,
   "name": "Boil. 2 Status Code",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 23,
   "name": "Boil. 2 Blocking Code",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 24,
   "name": "Boil. 2 Lockout Code",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 25,
   "name": "Boiler Outlet 3",
   "description": "",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 26,
   "name": "Boiler 3 Firing Rate",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 27,
   "name": "Boiler 3 Status",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 28,
   "name": "Boiler 3 Lockout",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 29,
   "name": "Boiler Outlet 4",
   "description": "",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 30,
   "name": "Boiler 4 Firing Rate",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 31,
   "name": "Boiler 4 Status",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 32,
   "name": "Boiler 4 Lockout",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 33,
   "name": "Boiler Outlet 5",
   "description": "",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 34,
   "name": "Boiler 5 Firing Rate",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 35,
   "name": "Boiler 5 Status",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 36,
   "name": "Boiler 5 Lockout",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 37,
   "name": "Boiler Outlet 6",
   "description": "",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 38,
   "name": "Boiler 6 Firing Rate",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 39,
   "name": "Boiler 6 Status",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 40,
   "name": "Boiler 6 Lockout",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 41,
   "name": "Boiler Outlet 7",
   "description": "",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 42,
   "name": "Boiler 7 Firing Rate",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 43,
   "name": "Boiler 7 Status",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 44,
   "name": "Boiler 7 Lockout",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 45,
   "name": "Boiler Outlet 8",
   "description": "",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 46,
   "name": "Boiler 8 Firing Rate",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 47,
   "name": "Boiler 8 Status",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 48,
   "name": "Boiler 8 Lockout",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 49,
   "name": "Discrete Inputs 49 - 64",
   "description": "Packed discrete inputs 49-64",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 50,
   "name": "NTC 6 temperature",
   "description": "",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 51,
   "name": "NTC 7 temperature",
   "description": "",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 52,
   "name": "NTC 9 temperature",
   "description": "",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 53,
   "name": "Vortex 1 flow",
   "description": "",
   "units": "L/min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 54,
   "name": "Vortex 1 temp",
   "description": "",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 55,
   "name": "Vortex 2 flow",
   "description": "",
   "units": "L/min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 56,
   "name": "Vortex 2 temp",
   "description": "",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 90,
   "name": "Total Faults",
   "description": "BIC-928 only",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 91,
   "name": "Total Last Faults",
   "description": "BIC-928 only",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 92,
   "name": "Run Hours CH",
   "description": "BIC-928 only",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 93,
   "name": "Run Hours DHW",
   "description": "BIC-928 only",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 94,
   "name": "Run Hours Cas CH",
   "description": "BIC-928 only",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 95,
   "name": "Run Hours Cas DHW",
   "description": "BIC-928 only",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 96,
   "name": "Power Hours",
   "description": "BIC-928 only",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 98,
   "name": "Start Counter",
   "description": "BIC-928 only",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 99,
   "name": "Start Counter",
   "description": "BIC-928 only",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 0,
   "name": "Configuration",
   "description": "Configuration bits: which inputs come from the BMS",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "Coils",
   "description": "Coil bits: boiler enable (b0), tank enable (b4)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "0-10 volt / rate / setp",
   "description": "Rate / setpoint command via 0-10 V scale; water heater: 0-10 volt / rate / set",
   "units": "V",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "DHW setpoint",
   "description": "DHW setpoint from the BMS; water heater: DHW set",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "DHW temperatur",
   "description": "DHW tank temperature from the BMS; water heater: DHW temp",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "Outdoor temp.",
   "description": "Outdoor temperature from the BMS; water heater: Outdoor Sensor",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "Sys supply temp.",
   "description": "System supply temperature from the BMS",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "Sys rtn temp.",
   "description": "System return temperature from the BMS",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "I4 for direct",
   "description": "I4 offset",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "CH post purge",
   "description": "CH post-purge time",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "DHW post purge",
   "description": "DHW post-purge time",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "Pump 4 Speed",
   "description": "Pump 4 speed",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "Extra out ECS",
   "description": "Extra 0-10 V output",
   "units": "%",
   "access": "W",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/htp/modbus-bacnet-adapter-7350p-636",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}