- TopTronic E BACnet datapoints, use case 7 (heat generator, 3 circuits, hot water, buffer, ventilation)
Boiler / heat generator monitoring (via BACnet gateway) · BACnet points list
Hoval TopTronic E BACnet datapoints, use case 7 (heat generator, 3 circuits, hot water, buffer, ventilation) BACnet points list
Updated 12 November 2026
Hoval's "use case 7" signal file maps 58 read-only analog inputs for monitoring a larger TopTronic E system: heat generator temperatures, modulation, status, hours, cycles, thermal and electrical power, COP, energy totals and heat pump fault code, plus flow, setpoint, mode and pump status per heating circuit, hot water and buffer tank temperatures, and ventilation mode, VOC, temperature and humidity.
This page lists 58 BACnet objects for the Hoval TopTronic E BACnet datapoints, use case 7 (heat generator, 3 circuits, hot water, buffer, ventilation) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Hoval’s own free documentation, linked below.
- Manufacturer
- Hoval
- Model
- TopTronic E BACnet datapoints, use case 7 (heat generator, 3 circuits, hot water, buffer, ventilation)
- Equipment
- Boiler / heat generator monitoring (via BACnet gateway)
- Equipment type
- Boilers & water heaters
- BACnet objects
- 58 (0 writable)
- Transport
- —
- Firmware
- Not stated
- Also known as
- Hoval use case 7, Hoval Anwendungsfall 7, TopTronic E use case 7, TTE BACnet use case 7, Hoval Connect BACnet
Reference only, provided as-is: verify against Hoval’s current documentation and the live device before use. Not official Hoval information. Terms of use.
BMS integration notes: Hoval TopTronic E BACnet datapoints, use case 7 (heat generator, 3 circuits, hot water, buffer, ventilation)
Load the Hoval use-case project into the Intesis BACnet gateway connected to Hoval Connect over Modbus TCP, then trend the heat generator, circuit, hot water, buffer and ventilation values. Nothing is writable in this set.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 20 | Wärmeerzeuger - Status | Heat generator status code | Read |
| AI 16 | Wärmeerzeuger - Vorlauftemperatur-Ist | Heat generator flow temperature | Read |
| AI 17 | Wärmeerzeuger - Rücklauftemperatur | Heat generator return temperature | Read |
| AI 18 | Wärmeerzeuger - Modulation | Heat generator modulation | Read |
| AI 14 | Wärmeerzeuger - Außentemperatur | Outdoor temperature | Read |
| AI 54 | Warmwasser - Isttemperatur Oben (SF / SF1) | Hot water tank temperature, top | Read |
| AI 35 | Heizkreis 1 - Vorlauftemperatur-Ist | Circuit 1 flow temperature | Read |
| AI 33 | Wärmeerzeuger - Fehlercode Wärmepumpe (WFA) | Heat pump fault code | Read |
Enable & remote start
Monitoring only: no writable objects in this set.
Network setup
- Modbus TCP to Hoval Connect (node 0) on the gateway side.
Watch out for
- Ignore the °C unit on non-temperature objects in the gateway project.
Hoval TopTronic E BACnet datapoints, use case 7 (heat generator, 3 circuits, hot water, buffer, ventilation) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 14 | Wärmeerzeuger - Außentemperatur | Heat generator: Outdoor temperature | °C | Read | |
| AI | 15 | Wärmeerzeuger - Vorlauftemperatur-Soll | Heat generator: Flow temperature setpoint | °C | Read | |
| AImin | 16 | Wärmeerzeuger - Vorlauftemperatur-Ist | Heat generator: Flow temperature | °C | Read | |
| AImin | 17 | Wärmeerzeuger - Rücklauftemperatur | Heat generator: Return temperature | °C | Read | |
| AImin | 18 | Wärmeerzeuger - Modulation | Heat generator: Modulation level | Read | ||
| AI | 19 | Wärmeerzeuger - Betriebsmeldung | Heat generator: Operating message | Read | ||
| AImin | 20 | Wärmeerzeuger - Status | Heat generator: Status | Read | ||
| AI | 21 | Wärmeerzeuger - Betriebswahl | Heat generator: Operating mode selection | Read | ||
| AI | 22 | Wärmeerzeuger - Betriebsstunden | Heat generator: Operating hours | Read | ||
| AI | 23 | Wärmeerzeuger - Schaltzyklen | Heat generator: Switching cycles | Read | ||
| AI | 24 | Wärmeerzeuger - Aktuelle thermische Leistung | Heat generator: Current thermal output | Read | ||
| AI | 25 | Wärmeerzeuger - Aktuelle elektrische Leistung | Heat generator: Current electrical power | Read | ||
| AI | 26 | Wärmeerzeuger - COP - Coefficient of Performance | Heat generator: Coefficient of performance | Read | ||
| AI | 27 | Wärmeerzeuger - JAZ - Jahresarbeitszahl | Heat generator: Seasonal performance factor | Read | ||
| AI | 28 | Wärmeerzeuger - Volumenstrom | Heat generator: Volume flow | Read | ||
| AI | 29 | Wärmeerzeuger - Elektrische Gesamtenergie | Heat generator: Total electrical energy | Read | ||
| AI | 30 | Wärmeerzeuger - Thermische Gesamtenergie Heizen | Heat generator: Total thermal energy, heating | Read | ||
| AI | 31 | Wärmeerzeuger - Thermische Gesamtenergie Warmwasser | Heat generator: Total thermal energy, hot water | Read | ||
| AI | 32 | Wärmeerzeuger - Thermische Gesamtenergie Kühlen | Heat generator: Total thermal energy, cooling | Read | ||
| AImin | 33 | Wärmeerzeuger - Fehlercode Wärmepumpe (WFA) | Heat generator: Heat pump fault code | Read | ||
| AI | 34 | Wärmeerzeuger - Status (WFA) | Heat generator: Heat pump status | Read | ||
| AImin | 35 | Heizkreis 1 - Vorlauftemperatur-Ist | Heating circuit 1: Flow temperature | °C | Read | |
| AI | 36 | Heizkreis 1 - Vorlauftemperatur-Soll | Heating circuit 1: Flow temperature setpoint | °C | Read | |
| AI | 37 | Heizkreis 1 - Status | Heating circuit 1: Status | Read | ||
| AI | 38 | Heizkreis 1 - Betriebswahl | Heating circuit 1: Operating mode selection | Read | ||
| AI | 39 | Heizkreis 1 - Raum-Soll | Heating circuit 1: Room temperature setpoint in use | °C | Read | |
| AI | 40 | Heizkreis 1 - Status Umwälzpumpe | Heating circuit 1: Circulation pump status | Read | ||
| AI | 41 | Heizkreis 2 - Vorlauf-Ist | Heating circuit 2: Flow temperature | °C | Read | |
| AI | 42 | Heizkreis 2 - Vorlauf-Soll | Heating circuit 2: Flow temperature setpoint | °C | Read | |
| AI | 43 | Heizkreis 2 - Status | Heating circuit 2: Status | Read | ||
| AI | 44 | Heizkreis 2 - Betriebswahl | Heating circuit 2: Operating mode selection | Read | ||
| AI | 45 | Heizkreis 2 - Raum-Soll | Heating circuit 2: Room temperature setpoint in use | °C | Read | |
| AI | 46 | Heizkreis 2 - Status Umwälzpumpe | Heating circuit 2: Circulation pump status | Read | ||
| AI | 47 | Heizkreis 3 - Vorlauf-Ist | Heating circuit 3: Flow temperature | °C | Read | |
| AI | 48 | Heizkreis 3 - Vorlauf-Soll | Heating circuit 3: Flow temperature setpoint | °C | Read | |
| AI | 49 | Heizkreis 3 - Status | Heating circuit 3: Status | Read | ||
| AI | 50 | Heizkreis 3 - Betriebswahl | Heating circuit 3: Operating mode selection | Read | ||
| AI | 51 | Heizkreis 3 - Raum-Soll | Heating circuit 3: Room temperature setpoint in use | °C | Read | |
| AI | 52 | Heizkreis 3 - Status Umwälzpumpe | Heating circuit 3: Circulation pump status | Read | ||
| AI | 53 | Warmwasser - Solltemperatur | Hot water: Setpoint temperature | °C | Read | |
| AImin | 54 | Warmwasser - Isttemperatur Oben (SF / SF1) | Hot water: Tank temperature, top | °C | Read | |
| AI | 55 | Warmwasser - Isttemperatur Unten (SF2) | Hot water: Tank temperature, bottom | °C | Read | |
| AI | 56 | Warmwasser - Status | Hot water: Status | Read | ||
| AI | 57 | Warmwasser - Betriebswahl | Hot water: Operating mode selection | Read | ||
| AI | 58 | Heiz-,Kühlpufferspeicher - Pufferisttemperatur (WPF) | Buffer tank: Buffer tank temperature | °C | Read | |
| AI | 59 | Heiz-,Kühlpufferspeicher - Temperatur Oben (PF/PF1/KPF2) | Buffer tank: Buffer temperature, top | °C | Read | |
| AI | 60 | Heiz-,Kühlpufferspeicher - Temperatur Unten (PF2/KPF) | Buffer tank: Buffer temperature, bottom | °C | Read | |
| AI | 61 | Heiz-,Kühlpufferspeicher - Solltemperatur | Buffer tank: Setpoint temperature | °C | Read | |
| AI | 62 | Heiz-,Kühlpufferspeicher - Status | Buffer tank: Status | Read | ||
| AI | 63 | Lüftung - Betriebswahl | Ventilation: Operating mode selection | Read | ||
| AI | 64 | Lüftung - Modulation | Ventilation: Modulation level | Read | ||
| AI | 65 | Lüftung - VOC Abluft Rohwert | Ventilation: Extract air VOC, raw | Read | ||
| AI | 66 | Lüftung - VOC Aussenluft Rohwert | Ventilation: Outdoor air VOC, raw | Read | ||
| AI | 67 | Lüftung - Luftqualität Regulierung | Ventilation: Air quality control | Read | ||
| AI | 68 | Lüftung - Status | Ventilation: Status | Read | ||
| AI | 69 | Lüftung - Temperatur Aussenluft | Ventilation: Outdoor air temperature | °C | Read | |
| AI | 70 | Lüftung - Temperatur Abluft | Ventilation: Extract air temperature | °C | Read | |
| AI | 71 | Lüftung - Feuchtigkeit Abluft | Ventilation: Extract air humidity | Read |
No points match these filters.
Object ID lookup: Hoval TopTronic E BACnet datapoints, use case 7 point IDs by name
AI14Wärmeerzeuger - AußentemperaturAI15Wärmeerzeuger - Vorlauftemperatur-SollAI16Wärmeerzeuger - Vorlauftemperatur-IstAI17Wärmeerzeuger - RücklauftemperaturAI18Wärmeerzeuger - ModulationAI19Wärmeerzeuger - BetriebsmeldungAI20Wärmeerzeuger - StatusAI21Wärmeerzeuger - BetriebswahlAI22Wärmeerzeuger - BetriebsstundenAI23Wärmeerzeuger - SchaltzyklenAI24Wärmeerzeuger - Aktuelle thermische LeistungAI25Wärmeerzeuger - Aktuelle elektrische LeistungAI26Wärmeerzeuger - COP - Coefficient of PerformanceAI27Wärmeerzeuger - JAZ - JahresarbeitszahlAI28Wärmeerzeuger - VolumenstromAI29Wärmeerzeuger - Elektrische GesamtenergieAI30Wärmeerzeuger - Thermische Gesamtenergie HeizenAI31Wärmeerzeuger - Thermische Gesamtenergie WarmwasserAI32Wärmeerzeuger - Thermische Gesamtenergie KühlenAI33Wärmeerzeuger - Fehlercode Wärmepumpe (WFA)AI34Wärmeerzeuger - Status (WFA)AI35Heizkreis 1 - Vorlauftemperatur-IstAI36Heizkreis 1 - Vorlauftemperatur-SollAI37Heizkreis 1 - StatusAI38Heizkreis 1 - BetriebswahlAI39Heizkreis 1 - Raum-SollAI40Heizkreis 1 - Status UmwälzpumpeAI41Heizkreis 2 - Vorlauf-IstAI42Heizkreis 2 - Vorlauf-SollAI43Heizkreis 2 - StatusAI44Heizkreis 2 - BetriebswahlAI45Heizkreis 2 - Raum-SollAI46Heizkreis 2 - Status UmwälzpumpeAI47Heizkreis 3 - Vorlauf-IstAI48Heizkreis 3 - Vorlauf-SollAI49Heizkreis 3 - StatusAI50Heizkreis 3 - BetriebswahlAI51Heizkreis 3 - Raum-SollAI52Heizkreis 3 - Status UmwälzpumpeAI53Warmwasser - SolltemperaturAI54Warmwasser - Isttemperatur Oben (SF / SF1)AI55Warmwasser - Isttemperatur Unten (SF2)AI56Warmwasser - StatusAI57Warmwasser - BetriebswahlAI58Heiz-,Kühlpufferspeicher - Pufferisttemperatur (WPF)AI59Heiz-,Kühlpufferspeicher - Temperatur Oben (PF/PF1/KPF2)AI60Heiz-,Kühlpufferspeicher - Temperatur Unten (PF2/KPF)AI61Heiz-,Kühlpufferspeicher - SolltemperaturAI62Heiz-,Kühlpufferspeicher - StatusAI63Lüftung - BetriebswahlAI64Lüftung - ModulationAI65Lüftung - VOC Abluft RohwertAI66Lüftung - VOC Aussenluft RohwertAI67Lüftung - Luftqualität RegulierungAI68Lüftung - StatusAI69Lüftung - Temperatur AussenluftAI70Lüftung - Temperatur AbluftAI71Lüftung - Feuchtigkeit Abluft
Integration notes
- The file is an Intesis MAPS signals export (Modbus master to BACnet server) that Hoval publishes for its BACnet gateway; the mapping can be edited on site, so treat this as the factory default.
- Object names are the Name column (German); descriptions here are English translations. WEZ = heat generator, HK = heating circuit, WW = domestic hot water.
- All objects are AIs with no write function (monitoring only). Status, mode and fault values are numeric codes.
- The file sets units code 62 (°C) on every object, including hours, counts, power and COP; units are kept here only on temperature objects.
- Project name in the file: IN-BAC-MBM_Testanlage (a test installation), Intesis MAPS 1.2.33.0. The "use case 3 and 4" file only has 3 objects and is not listed.
- The file does not say whether the gateway serves BACnet IP or BACnet MS/TP; check the gateway configuration.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TopTronic E BACnet datapoints, use case 7 (heat generator, 3 circuits, hot water, buffer, ventilation) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Hoval TopTronic E BACnet datapoints, use case 7 (heat generator, 3 circuits, hot water, buffer, ventilation)
How many BACnet points does the Hoval TopTronic E BACnet datapoints, use case 7 (heat generator, 3 circuits, hot water, buffer, ventilation) have?
This list has 58 BACnet objects: 58 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Hoval TopTronic E BACnet datapoints, use case 7 (heat generator, 3 circuits, hot water, buffer, ventilation) BACnet points are writable?
None of the listed objects are marked writable in the source documentation.
Where is the official Hoval TopTronic E BACnet datapoints, use case 7 (heat generator, 3 circuits, hot water, buffer, ventilation) BACnet documentation?
The source is Hoval use case 7 - TTE Modbus BACnet (Intesis MAPS signals file, sheet Signals), revision 09/11/2026, published free by Hoval at https://cdn.hoval.com/hoval-anwendungsfall-7-tte-modbus-bacnet_hybris_original.xlsx.
What are the minimum BACnet points to integrate the Hoval TopTronic E BACnet datapoints, use case 7 (heat generator, 3 circuits, hot water, buffer, ventilation)?
Start with AI 20 Wärmeerzeuger - Status (Heat generator status code); AI 16 Wärmeerzeuger - Vorlauftemperatur-Ist (Heat generator flow temperature); AI 17 Wärmeerzeuger - Rücklauftemperatur (Heat generator return temperature); AI 18 Wärmeerzeuger - Modulation (Heat generator modulation); AI 14 Wärmeerzeuger - Außentemperatur (Outdoor temperature); AI 54 Warmwasser - Isttemperatur Oben (SF / SF1) (Hot water tank temperature, top); AI 35 Heizkreis 1 - Vorlauftemperatur-Ist (Circuit 1 flow temperature); AI 33 Wärmeerzeuger - Fehlercode Wärmepumpe (WFA) (Heat pump fault code).
How do I enable BMS control of the Hoval TopTronic E BACnet datapoints, use case 7 (heat generator, 3 circuits, hot water, buffer, ventilation)?
Monitoring only: no writable objects in this set.
How do I check these points on the real TopTronic E BACnet datapoints, use case 7 (heat generator, 3 circuits, hot water, buffer, ventilation)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Hoval BACnet points lists
Source: Hoval use case 7 - TTE Modbus BACnet (Intesis MAPS signals file, sheet Signals) · rev. 09/11/2026. Object names, instances and units are reproduced as published; descriptions are our own.