  3. Hoval
  4. TopTronic E BACnet datapoints, use case 7 (heat generator, 3 circuits, hot water, buffer, ventilation)

Boiler / heat generator monitoring (via BACnet gateway) · BACnet points list

Hoval TopTronic E BACnet datapoints, use case 7 (heat generator, 3 circuits, hot water, buffer, ventilation) BACnet points list

Updated 12 November 2026

Short answer

Hoval's "use case 7" signal file maps 58 read-only analog inputs for monitoring a larger TopTronic E system: heat generator temperatures, modulation, status, hours, cycles, thermal and electrical power, COP, energy totals and heat pump fault code, plus flow, setpoint, mode and pump status per heating circuit, hot water and buffer tank temperatures, and ventilation mode, VOC, temperature and humidity.

This page lists 58 BACnet objects for the Hoval TopTronic E BACnet datapoints, use case 7 (heat generator, 3 circuits, hot water, buffer, ventilation) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Hoval’s own free documentation, linked below.

Manufacturer
Hoval
Model
TopTronic E BACnet datapoints, use case 7 (heat generator, 3 circuits, hot water, buffer, ventilation)
Equipment
Boiler / heat generator monitoring (via BACnet gateway)
Equipment type
Boilers & water heaters
BACnet objects
58 (0 writable)
Transport
—
Firmware
Not stated
Also known as
Hoval use case 7, Hoval Anwendungsfall 7, TopTronic E use case 7, TTE BACnet use case 7, Hoval Connect BACnet
Source document
Hoval use case 7 - TTE Modbus BACnet (Intesis MAPS signals file, sheet Signals) · rev. 09/11/2026
Download CSV 58 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Hoval’s current documentation and the live device before use. Not official Hoval information. Terms of use.

BMS integration notes: Hoval TopTronic E BACnet datapoints, use case 7 (heat generator, 3 circuits, hot water, buffer, ventilation)

Integration in brief

Load the Hoval use-case project into the Intesis BACnet gateway connected to Hoval Connect over Modbus TCP, then trend the heat generator, circuit, hot water, buffer and ventilation values. Nothing is writable in this set.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 20Wärmeerzeuger - StatusHeat generator status codeRead
AI 16Wärmeerzeuger - Vorlauftemperatur-IstHeat generator flow temperatureRead
AI 17Wärmeerzeuger - RücklauftemperaturHeat generator return temperatureRead
AI 18Wärmeerzeuger - ModulationHeat generator modulationRead
AI 14Wärmeerzeuger - AußentemperaturOutdoor temperatureRead
AI 54Warmwasser - Isttemperatur Oben (SF / SF1)Hot water tank temperature, topRead
AI 35Heizkreis 1 - Vorlauftemperatur-IstCircuit 1 flow temperatureRead
AI 33Wärmeerzeuger - Fehlercode Wärmepumpe (WFA)Heat pump fault codeRead

Enable & remote start

Monitoring only: no writable objects in this set.

Network setup

Watch out for

Hoval TopTronic E BACnet datapoints, use case 7 (heat generator, 3 circuits, hot water, buffer, ventilation) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

58 of 58 shown
Type
Analog
Show
Hoval TopTronic E BACnet datapoints, use case 7 (heat generator, 3 circuits, hot water, buffer, ventilation) BACnet Points List
DescriptionStates
AImin14Wärmeerzeuger - AußentemperaturHeat generator: Outdoor temperature°CRead
AI15Wärmeerzeuger - Vorlauftemperatur-SollHeat generator: Flow temperature setpoint°CRead
AImin16Wärmeerzeuger - Vorlauftemperatur-IstHeat generator: Flow temperature°CRead
AImin17Wärmeerzeuger - RücklauftemperaturHeat generator: Return temperature°CRead
AImin18Wärmeerzeuger - ModulationHeat generator: Modulation levelRead
AI19Wärmeerzeuger - BetriebsmeldungHeat generator: Operating messageRead
AImin20Wärmeerzeuger - StatusHeat generator: StatusRead
AI21Wärmeerzeuger - BetriebswahlHeat generator: Operating mode selectionRead
AI22Wärmeerzeuger - BetriebsstundenHeat generator: Operating hoursRead
AI23Wärmeerzeuger - SchaltzyklenHeat generator: Switching cyclesRead
AI24Wärmeerzeuger - Aktuelle thermische LeistungHeat generator: Current thermal outputRead
AI25Wärmeerzeuger - Aktuelle elektrische LeistungHeat generator: Current electrical powerRead
AI26Wärmeerzeuger - COP - Coefficient of PerformanceHeat generator: Coefficient of performanceRead
AI27Wärmeerzeuger - JAZ - JahresarbeitszahlHeat generator: Seasonal performance factorRead
AI28Wärmeerzeuger - VolumenstromHeat generator: Volume flowRead
AI29Wärmeerzeuger - Elektrische GesamtenergieHeat generator: Total electrical energyRead
AI30Wärmeerzeuger - Thermische Gesamtenergie HeizenHeat generator: Total thermal energy, heatingRead
AI31Wärmeerzeuger - Thermische Gesamtenergie WarmwasserHeat generator: Total thermal energy, hot waterRead
AI32Wärmeerzeuger - Thermische Gesamtenergie KühlenHeat generator: Total thermal energy, coolingRead
AImin33Wärmeerzeuger - Fehlercode Wärmepumpe (WFA)Heat generator: Heat pump fault codeRead
AI34Wärmeerzeuger - Status (WFA)Heat generator: Heat pump statusRead
AImin35Heizkreis 1 - Vorlauftemperatur-IstHeating circuit 1: Flow temperature°CRead
AI36Heizkreis 1 - Vorlauftemperatur-SollHeating circuit 1: Flow temperature setpoint°CRead
AI37Heizkreis 1 - StatusHeating circuit 1: StatusRead
AI38Heizkreis 1 - BetriebswahlHeating circuit 1: Operating mode selectionRead
AI39Heizkreis 1 - Raum-SollHeating circuit 1: Room temperature setpoint in use°CRead
AI40Heizkreis 1 - Status UmwälzpumpeHeating circuit 1: Circulation pump statusRead
AI41Heizkreis 2 - Vorlauf-IstHeating circuit 2: Flow temperature°CRead
AI42Heizkreis 2 - Vorlauf-SollHeating circuit 2: Flow temperature setpoint°CRead
AI43Heizkreis 2 - StatusHeating circuit 2: StatusRead
AI44Heizkreis 2 - BetriebswahlHeating circuit 2: Operating mode selectionRead
AI45Heizkreis 2 - Raum-SollHeating circuit 2: Room temperature setpoint in use°CRead
AI46Heizkreis 2 - Status UmwälzpumpeHeating circuit 2: Circulation pump statusRead
AI47Heizkreis 3 - Vorlauf-IstHeating circuit 3: Flow temperature°CRead
AI48Heizkreis 3 - Vorlauf-SollHeating circuit 3: Flow temperature setpoint°CRead
AI49Heizkreis 3 - StatusHeating circuit 3: StatusRead
AI50Heizkreis 3 - BetriebswahlHeating circuit 3: Operating mode selectionRead
AI51Heizkreis 3 - Raum-SollHeating circuit 3: Room temperature setpoint in use°CRead
AI52Heizkreis 3 - Status UmwälzpumpeHeating circuit 3: Circulation pump statusRead
AI53Warmwasser - SolltemperaturHot water: Setpoint temperature°CRead
AImin54Warmwasser - Isttemperatur Oben (SF / SF1)Hot water: Tank temperature, top°CRead
AI55Warmwasser - Isttemperatur Unten (SF2)Hot water: Tank temperature, bottom°CRead
AI56Warmwasser - StatusHot water: StatusRead
AI57Warmwasser - BetriebswahlHot water: Operating mode selectionRead
AI58Heiz-,Kühlpufferspeicher - Pufferisttemperatur (WPF)Buffer tank: Buffer tank temperature°CRead
AI59Heiz-,Kühlpufferspeicher - Temperatur Oben (PF/PF1/KPF2)Buffer tank: Buffer temperature, top°CRead
AI60Heiz-,Kühlpufferspeicher - Temperatur Unten (PF2/KPF)Buffer tank: Buffer temperature, bottom°CRead
AI61Heiz-,Kühlpufferspeicher - SolltemperaturBuffer tank: Setpoint temperature°CRead
AI62Heiz-,Kühlpufferspeicher - StatusBuffer tank: StatusRead
AI63Lüftung - BetriebswahlVentilation: Operating mode selectionRead
AI64Lüftung - ModulationVentilation: Modulation levelRead
AI65Lüftung - VOC Abluft RohwertVentilation: Extract air VOC, rawRead
AI66Lüftung - VOC Aussenluft RohwertVentilation: Outdoor air VOC, rawRead
AI67Lüftung - Luftqualität RegulierungVentilation: Air quality controlRead
AI68Lüftung - StatusVentilation: StatusRead
AI69Lüftung - Temperatur AussenluftVentilation: Outdoor air temperature°CRead
AI70Lüftung - Temperatur AbluftVentilation: Extract air temperature°CRead
AI71Lüftung - Feuchtigkeit AbluftVentilation: Extract air humidityRead
Object ID lookup: Hoval TopTronic E BACnet datapoints, use case 7 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TopTronic E BACnet datapoints, use case 7 (heat generator, 3 circuits, hot water, buffer, ventilation) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Hoval TopTronic E BACnet datapoints, use case 7 (heat generator, 3 circuits, hot water, buffer, ventilation)

How many BACnet points does the Hoval TopTronic E BACnet datapoints, use case 7 (heat generator, 3 circuits, hot water, buffer, ventilation) have?

This list has 58 BACnet objects: 58 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Hoval TopTronic E BACnet datapoints, use case 7 (heat generator, 3 circuits, hot water, buffer, ventilation) BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official Hoval TopTronic E BACnet datapoints, use case 7 (heat generator, 3 circuits, hot water, buffer, ventilation) BACnet documentation?

The source is Hoval use case 7 - TTE Modbus BACnet (Intesis MAPS signals file, sheet Signals), revision 09/11/2026, published free by Hoval at https://cdn.hoval.com/hoval-anwendungsfall-7-tte-modbus-bacnet_hybris_original.xlsx.

What are the minimum BACnet points to integrate the Hoval TopTronic E BACnet datapoints, use case 7 (heat generator, 3 circuits, hot water, buffer, ventilation)?

Start with AI 20 Wärmeerzeuger - Status (Heat generator status code); AI 16 Wärmeerzeuger - Vorlauftemperatur-Ist (Heat generator flow temperature); AI 17 Wärmeerzeuger - Rücklauftemperatur (Heat generator return temperature); AI 18 Wärmeerzeuger - Modulation (Heat generator modulation); AI 14 Wärmeerzeuger - Außentemperatur (Outdoor temperature); AI 54 Warmwasser - Isttemperatur Oben (SF / SF1) (Hot water tank temperature, top); AI 35 Heizkreis 1 - Vorlauftemperatur-Ist (Circuit 1 flow temperature); AI 33 Wärmeerzeuger - Fehlercode Wärmepumpe (WFA) (Heat pump fault code).

How do I enable BMS control of the Hoval TopTronic E BACnet datapoints, use case 7 (heat generator, 3 circuits, hot water, buffer, ventilation)?

Monitoring only: no writable objects in this set.

How do I check these points on the real TopTronic E BACnet datapoints, use case 7 (heat generator, 3 circuits, hot water, buffer, ventilation)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Hoval BACnet points lists

Source: Hoval use case 7 - TTE Modbus BACnet (Intesis MAPS signals file, sheet Signals) · rev. 09/11/2026. Object names, instances and units are reproduced as published; descriptions are our own.