- Home
- BACnet points lists
- Hoval
- TopTronic E heat generator via Hoval Modbus/BACnet gateway (standard datapoints)
Boiler / heat generator controller (via BACnet gateway) · BACnet points list
Hoval TopTronic E heat generator via Hoval Modbus/BACnet gateway (standard datapoints) BACnet points list
Updated 12 November 2026
Hoval publishes the default signal list for its TopTronic E BACnet gateway: an Intesis BACnet server polling the TopTronic E over Modbus RTU. The standard set has 54 objects: gateway comm-error BIs, outdoor, room, flow and hot water temperatures, heat generator values, writable comfort/eco/manual setpoints for three heating circuits and hot water, and operating-mode selections and status for each circuit.
This page lists 54 BACnet objects for the Hoval TopTronic E heat generator via Hoval Modbus/BACnet gateway (standard datapoints) — 18 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Hoval’s own free documentation, linked below.
- Manufacturer
- Hoval
- Model
- TopTronic E heat generator via Hoval Modbus/BACnet gateway (standard datapoints)
- Equipment
- Boiler / heat generator controller (via BACnet gateway)
- Equipment type
- Boilers & water heaters
- BACnet objects
- 54 (18 writable)
- Transport
- —
- Firmware
- Not stated
- Also known as
- TopTronic E, TTE, Hoval TTE BACnet, Hoval TopTronic E BACnet, Hoval Modbus BACnet gateway, TTE ModBus BACnet Datapoints
Reference only, provided as-is: verify against Hoval’s current documentation and the live device before use. Not official Hoval information. Terms of use.
BMS integration notes: Hoval TopTronic E heat generator via Hoval Modbus/BACnet gateway (standard datapoints)
Install the Hoval BACnet gateway on the TopTronic E Modbus bus and load the Hoval project in Intesis MAPS. Then write the operating mode and room setpoints per heating circuit and the hot water setpoints, and read temperatures and status.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 0 | WEZ 1 - HK 1 - Betriebswahl Heizung | Heating circuit 1 operating mode | Write |
| AV 0 | WEZ 1 - HK 1-Normal-Raumtemperatur Heizbetrieb | Circuit 1 normal room setpoint, °C | Write |
| MV 3 | WEZ 1 - WW - Betriebswahl Warmwasser | Hot water operating mode | Write |
| AV 12 | WEZ 1 - WW - Normal-Warmwassertemperatur | Normal hot water setpoint, °C | Write |
| AI 1 | WEZ 1 - AF1 - Aussenfuehler 1 | Outdoor temperature | Read |
| AI 18 | WEZ-Temperatur | Heat generator temperature | Read |
| AI 11 | WEZ 1 - HK 1 - Vorlauf-Ist | Circuit 1 flow temperature | Read |
| MV 4 | WEZ 1 - HK 1 - Status Heizkreisregelung | Circuit 1 control status | Read |
| BI 0 | Comm Error Device 0 | Gateway lost Modbus link | Read |
Network setup
- Built with Intesis MAPS; the Modbus side is RTU (Port A) to the TopTronic E gateway module.
Watch out for
- State texts for the mode and status MVs are not in the file; get them from the TopTronic E Modbus documentation.
- Only one heat generator (WEZ 1) and three heating circuits are mapped by default.
Hoval TopTronic E heat generator via Hoval Modbus/BACnet gateway (standard datapoints) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BImin | 0 | Comm Error Device 0 | Modbus comm error, gateway/heat generator | Read | 0=No error, 1=Error | |
| BI | 1 | Comm Error Device 1 | Modbus comm error, device | Read | 0=No error, 1=Error | |
| BI | 2 | Comm Error Device 2 | Modbus comm error, device | Read | 0=No error, 1=Error | |
| AImin | 1 | WEZ 1 - AF1 - Aussenfuehler 1 | Outdoor temperature sensor | °C | Read | |
| MVmin | 0 | WEZ 1 - HK 1 - Betriebswahl Heizung | Heating circuit 1: Heating circuit operating mode selection (9 states) | Write | ||
| MV | 1 | WEZ 1 - HK 2- Betriebswahl Heizung | Heating circuit 2: Heating circuit operating mode selection (9 states) | Write | ||
| MV | 2 | WEZ 1 - HK 3- Betriebswahl Heizung | Heating circuit 3: Heating circuit operating mode selection (9 states) | Write | ||
| AVmin | 0 | WEZ 1 - HK 1-Normal-Raumtemperatur Heizbetrieb | Heating circuit 1: Normal room temperature, heating | °C | Write | |
| AV | 1 | WEZ 1 - HK 1 - Spar-Raumtemperatur Heizbetrieb | Heating circuit 1: Eco room temperature, heating | °C | Write | |
| AV | 2 | WEZ 1 - HK 2-Normal-Raumtemperatur Heizbetrieb | Heating circuit 2: Normal room temperature, heating | °C | Write | |
| AV | 3 | WEZ 1 - HK 2 - Spar-Raumtemperatur Heizbetrieb | Heating circuit 2: Eco room temperature, heating | °C | Write | |
| AV | 4 | WEZ 1 - HK 3-Normal-Raumtemperatur Heizbetrieb | Heating circuit 3: Normal room temperature, heating | °C | Write | |
| AV | 5 | WEZ 1 - HK 3 - Spar-Raumtemperatur Heizbetrieb | Heating circuit 3: Eco room temperature, heating | °C | Write | |
| AV | 6 | WEZ 1 - HK 1 - Solltemperatur Handbetrieb | Heating circuit 1: Setpoint for manual mode | °C | Write | |
| AV | 7 | WEZ 1 - HK 2 - Solltemperatur Handbetrieb | Heating circuit 2: Setpoint for manual mode | °C | Write | |
| AV | 8 | WEZ 1 - HK 3 - Solltemperatur Handbetrieb | Heating circuit 3: Setpoint for manual mode | °C | Write | |
| AV | 9 | WEZ 1 - HK 1 - Vorlauf Soll Konstantanf. Heizen | Heating circuit 1: Flow setpoint for constant heating demand | °C | Write | |
| AV | 10 | WEZ 1 - HK 2 - Vorlauf Soll Konstantanf. Heizen | Heating circuit 2: Flow setpoint for constant heating demand | °C | Write | |
| AV | 11 | WEZ 1 - HK 3 - Vorlauf Soll Konstantanf. Heizen | Heating circuit 3: Flow setpoint for constant heating demand | °C | Write | |
| AI | 2 | WEZ 1 - HK 1 - Raum-Soll | Heating circuit 1: Room temperature setpoint in use | °C | Read | |
| AI | 3 | WEZ 1 - HK 2 - Raum-Soll | Heating circuit 2: Room temperature setpoint in use | °C | Read | |
| AI | 4 | WEZ 1 - HK 3 - Raum-Soll | Heating circuit 3: Room temperature setpoint in use | °C | Read | |
| MVmin | 3 | WEZ 1 - WW - Betriebswahl Warmwasser | Hot water: Hot water operating mode selection (7 states) | Write | ||
| AVmin | 12 | WEZ 1 - WW - Normal-Warmwassertemperatur | Hot water: Normal hot water temperature | °C | Write | |
| AV | 13 | WEZ 1 - WW - Spar-Warmwassertemperatur | Hot water: Eco hot water temperature | °C | Write | |
| AI | 5 | WEZ 1 - WW - Warmwasser-Soll | Hot water: Hot water setpoint in use | °C | Read | |
| AI | 6 | WEZ 1 - WW - Warmwasser-Ist SF | Hot water: Hot water temperature (sensor SF) | °C | Read | |
| MVmin | 4 | WEZ 1 - HK 1 - Status Heizkreisregelung | Heating circuit 1: Heating circuit control status (27 states) | Read | ||
| MV | 5 | WEZ 1 - HK 2 - Status Heizkreisregelung | Heating circuit 2: Heating circuit control status (27 states) | Read | ||
| MV | 6 | WEZ 1 - HK 3 - Status Heizkreisregelung | Heating circuit 3: Heating circuit control status (27 states) | Read | ||
| MV | 7 | WEZ 1 - WW - Status Warmwasserregelung | Hot water: Hot water control status (14 states) | Read | ||
| AI | 7 | WEZ 1 - HK 1 - Raum-Ist | Heating circuit 1: Room temperature | °C | Read | |
| AI | 8 | WEZ 1 - HK 2 - Raum-Ist | Heating circuit 2: Room temperature | °C | Read | |
| AI | 9 | WEZ 1 - HK 3 - Raum-Ist | Heating circuit 3: Room temperature | °C | Read | |
| AImin | 11 | WEZ 1 - HK 1 - Vorlauf-Ist | Heating circuit 1: Flow temperature | °C | Read | |
| AI | 12 | WEZ 1 - HK 2 - Vorlauf-Ist | Heating circuit 2: Flow temperature | °C | Read | |
| AI | 13 | WEZ 1 - HK 3 - Vorlauf-Ist | Heating circuit 3: Flow temperature | °C | Read | |
| AI | 14 | Sollwert für Heizkreisbetrieb | Heat generator setpoint, heating circuit mode | °C | Read | |
| AI | 15 | Sollwert für Speicherbetrieb | Heat generator setpoint, storage mode | °C | Read | |
| AI | 16 | Leistungsbegrenzung | Heat generator output limit | % | Read | |
| AI | 17 | Sollwert für Kühlbetrieb | Heat generator setpoint, cooling | °C | Read | |
| AImin | 18 | WEZ-Temperatur | Heat generator temperature | °C | Read | |
| AI | 19 | Rücklauftemperatur | Return temperature | °C | Read | |
| AI | 20 | Wasserdruck in Bar | Water pressure | bar | Read | |
| AI | 21 | Kühlung Sollwert | Cooling setpoint | °C | Read | |
| AI | 22 | WEZ 1 - HK 1 - Vorlauf-Soll | Heating circuit 1: Flow temperature setpoint | °C | Read | |
| AI | 23 | WEZ 1 - HK 2 - Vorlauf-Soll | Heating circuit 2: Flow temperature setpoint | °C | Read | |
| AI | 24 | WEZ 1 - HK 3 - Vorlauf-Soll | Heating circuit 3: Flow temperature setpoint | °C | Read | |
| AI | 25 | WEZ 1 - HK 1 - Mischer | Heating circuit 1: Mixing valve position | % | Read | |
| AI | 26 | WEZ 1 - HK 2 - Mischer | Heating circuit 2: Mixing valve position | % | Read | |
| AI | 27 | WEZ 1 - HK 3 - Mischer | Heating circuit 3: Mixing valve position | % | Read | |
| AI | 28 | WEZ 1 - HK 1 - Pumpe | Heating circuit 1: Pump output | % | Read | |
| AI | 29 | WEZ 1 - HK 2 - Pumpe | Heating circuit 2: Pump output | % | Read | |
| AI | 30 | WEZ 1 - HK 3 - Pumpe | Heating circuit 3: Pump output | % | Read |
No points match these filters.
Object ID lookup: Hoval TopTronic E heat generator via Hoval Modbus/BACnet gateway point IDs by name
BI0Comm Error Device 0BI1Comm Error Device 1BI2Comm Error Device 2AI1WEZ 1 - AF1 - Aussenfuehler 1MV0WEZ 1 - HK 1 - Betriebswahl HeizungMV1WEZ 1 - HK 2- Betriebswahl HeizungMV2WEZ 1 - HK 3- Betriebswahl HeizungAV0WEZ 1 - HK 1-Normal-Raumtemperatur HeizbetriebAV1WEZ 1 - HK 1 - Spar-Raumtemperatur HeizbetriebAV2WEZ 1 - HK 2-Normal-Raumtemperatur HeizbetriebAV3WEZ 1 - HK 2 - Spar-Raumtemperatur HeizbetriebAV4WEZ 1 - HK 3-Normal-Raumtemperatur HeizbetriebAV5WEZ 1 - HK 3 - Spar-Raumtemperatur HeizbetriebAV6WEZ 1 - HK 1 - Solltemperatur HandbetriebAV7WEZ 1 - HK 2 - Solltemperatur HandbetriebAV8WEZ 1 - HK 3 - Solltemperatur HandbetriebAV9WEZ 1 - HK 1 - Vorlauf Soll Konstantanf. HeizenAV10WEZ 1 - HK 2 - Vorlauf Soll Konstantanf. HeizenAV11WEZ 1 - HK 3 - Vorlauf Soll Konstantanf. HeizenAI2WEZ 1 - HK 1 - Raum-SollAI3WEZ 1 - HK 2 - Raum-SollAI4WEZ 1 - HK 3 - Raum-SollMV3WEZ 1 - WW - Betriebswahl WarmwasserAV12WEZ 1 - WW - Normal-WarmwassertemperaturAV13WEZ 1 - WW - Spar-WarmwassertemperaturAI5WEZ 1 - WW - Warmwasser-SollAI6WEZ 1 - WW - Warmwasser-Ist SFMV4WEZ 1 - HK 1 - Status HeizkreisregelungMV5WEZ 1 - HK 2 - Status HeizkreisregelungMV6WEZ 1 - HK 3 - Status HeizkreisregelungMV7WEZ 1 - WW - Status WarmwasserregelungAI7WEZ 1 - HK 1 - Raum-IstAI8WEZ 1 - HK 2 - Raum-IstAI9WEZ 1 - HK 3 - Raum-IstAI11WEZ 1 - HK 1 - Vorlauf-IstAI12WEZ 1 - HK 2 - Vorlauf-IstAI13WEZ 1 - HK 3 - Vorlauf-IstAI14Sollwert für HeizkreisbetriebAI15Sollwert für SpeicherbetriebAI16LeistungsbegrenzungAI17Sollwert für KühlbetriebAI18WEZ-TemperaturAI19RücklauftemperaturAI20Wasserdruck in BarAI21Kühlung SollwertAI22WEZ 1 - HK 1 - Vorlauf-SollAI23WEZ 1 - HK 2 - Vorlauf-SollAI24WEZ 1 - HK 3 - Vorlauf-SollAI25WEZ 1 - HK 1 - MischerAI26WEZ 1 - HK 2 - MischerAI27WEZ 1 - HK 3 - MischerAI28WEZ 1 - HK 1 - PumpeAI29WEZ 1 - HK 2 - PumpeAI30WEZ 1 - HK 3 - Pumpe
Integration notes
- The file is an Intesis MAPS signals export (Modbus master to BACnet server) that Hoval publishes for its BACnet gateway; the mapping can be edited on site, so treat this as the factory default.
- Object names are the Name column (German); descriptions here are English translations. WEZ = heat generator, HK = heating circuit, WW = domestic hot water.
- Multistate objects have no state texts in the file, only the number of states.
- Access: objects with a Modbus write function in the file are listed as W, the rest R.
- Signal file exported with Intesis MAPS 1.2.25.0, timestamp 2025-08-12.
- The file does not say whether the gateway serves BACnet IP or BACnet MS/TP; check the gateway configuration.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TopTronic E heat generator via Hoval Modbus/BACnet gateway (standard datapoints) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Hoval TopTronic E heat generator via Hoval Modbus/BACnet gateway (standard datapoints)
How many BACnet points does the Hoval TopTronic E heat generator via Hoval Modbus/BACnet gateway (standard datapoints) have?
This list has 54 BACnet objects: 29 analog inputs, 14 analog values, 3 binary inputs, 8 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Hoval TopTronic E heat generator via Hoval Modbus/BACnet gateway (standard datapoints) BACnet points are writable?
18 of the 54 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Hoval TopTronic E heat generator via Hoval Modbus/BACnet gateway (standard datapoints) BACnet documentation?
The source is TTE ModBus BACnet Datapoints (Intesis MAPS signals file, sheet Signals), revision 2025-08-12, published free by Hoval at https://cdn.hoval.com/tte-modbus-bacnet-datapoints-hybris-original.xlsx.
What are the minimum BACnet points to integrate the Hoval TopTronic E heat generator via Hoval Modbus/BACnet gateway (standard datapoints)?
Start with MV 0 WEZ 1 - HK 1 - Betriebswahl Heizung (Heating circuit 1 operating mode); AV 0 WEZ 1 - HK 1-Normal-Raumtemperatur Heizbetrieb (Circuit 1 normal room setpoint, °C); MV 3 WEZ 1 - WW - Betriebswahl Warmwasser (Hot water operating mode); AV 12 WEZ 1 - WW - Normal-Warmwassertemperatur (Normal hot water setpoint, °C); AI 1 WEZ 1 - AF1 - Aussenfuehler 1 (Outdoor temperature); AI 18 WEZ-Temperatur (Heat generator temperature); AI 11 WEZ 1 - HK 1 - Vorlauf-Ist (Circuit 1 flow temperature); MV 4 WEZ 1 - HK 1 - Status Heizkreisregelung (Circuit 1 control status); BI 0 Comm Error Device 0 (Gateway lost Modbus link).
How do I check these points on the real TopTronic E heat generator via Hoval Modbus/BACnet gateway (standard datapoints)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Hoval BACnet points lists
Source: TTE ModBus BACnet Datapoints (Intesis MAPS signals file, sheet Signals) · rev. 2025-08-12. Object names, instances and units are reproduced as published; descriptions are our own.