Boiler / heat generator controller (via BACnet gateway) · BACnet points list

Hoval TopTronic E heat generator via Hoval Modbus/BACnet gateway (standard datapoints) BACnet points list

Updated 12 November 2026

Short answer

Hoval publishes the default signal list for its TopTronic E BACnet gateway: an Intesis BACnet server polling the TopTronic E over Modbus RTU. The standard set has 54 objects: gateway comm-error BIs, outdoor, room, flow and hot water temperatures, heat generator values, writable comfort/eco/manual setpoints for three heating circuits and hot water, and operating-mode selections and status for each circuit.

This page lists 54 BACnet objects for the Hoval TopTronic E heat generator via Hoval Modbus/BACnet gateway (standard datapoints) — 18 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Hoval’s own free documentation, linked below.

Manufacturer
Hoval
Model
TopTronic E heat generator via Hoval Modbus/BACnet gateway (standard datapoints)
Equipment
Boiler / heat generator controller (via BACnet gateway)
Equipment type
Boilers & water heaters
BACnet objects
54 (18 writable)
Transport
—
Firmware
Not stated
Also known as
TopTronic E, TTE, Hoval TTE BACnet, Hoval TopTronic E BACnet, Hoval Modbus BACnet gateway, TTE ModBus BACnet Datapoints
Source document
TTE ModBus BACnet Datapoints (Intesis MAPS signals file, sheet Signals) · rev. 2025-08-12
Download CSV 54 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Hoval’s current documentation and the live device before use. Not official Hoval information. Terms of use.

BMS integration notes: Hoval TopTronic E heat generator via Hoval Modbus/BACnet gateway (standard datapoints)

Integration in brief

Install the Hoval BACnet gateway on the TopTronic E Modbus bus and load the Hoval project in Intesis MAPS. Then write the operating mode and room setpoints per heating circuit and the hot water setpoints, and read temperatures and status.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 0WEZ 1 - HK 1 - Betriebswahl HeizungHeating circuit 1 operating modeWrite
AV 0WEZ 1 - HK 1-Normal-Raumtemperatur HeizbetriebCircuit 1 normal room setpoint, °CWrite
MV 3WEZ 1 - WW - Betriebswahl WarmwasserHot water operating modeWrite
AV 12WEZ 1 - WW - Normal-WarmwassertemperaturNormal hot water setpoint, °CWrite
AI 1WEZ 1 - AF1 - Aussenfuehler 1Outdoor temperatureRead
AI 18WEZ-TemperaturHeat generator temperatureRead
AI 11WEZ 1 - HK 1 - Vorlauf-IstCircuit 1 flow temperatureRead
MV 4WEZ 1 - HK 1 - Status HeizkreisregelungCircuit 1 control statusRead
BI 0Comm Error Device 0Gateway lost Modbus linkRead

Network setup

Watch out for

Hoval TopTronic E heat generator via Hoval Modbus/BACnet gateway (standard datapoints) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

54 of 54 shown
Type
BinaryMulti-state
Access
Show
Hoval TopTronic E heat generator via Hoval Modbus/BACnet gateway (standard datapoints) BACnet Points List
DescriptionStates
BImin0Comm Error Device 0Modbus comm error, gateway/heat generatorRead0=No error, 1=Error
BI1Comm Error Device 1Modbus comm error, deviceRead0=No error, 1=Error
BI2Comm Error Device 2Modbus comm error, deviceRead0=No error, 1=Error
AImin1WEZ 1 - AF1 - Aussenfuehler 1Outdoor temperature sensor°CRead
MVmin0WEZ 1 - HK 1 - Betriebswahl HeizungHeating circuit 1: Heating circuit operating mode selection (9 states)Write
MV1WEZ 1 - HK 2- Betriebswahl HeizungHeating circuit 2: Heating circuit operating mode selection (9 states)Write
MV2WEZ 1 - HK 3- Betriebswahl HeizungHeating circuit 3: Heating circuit operating mode selection (9 states)Write
AVmin0WEZ 1 - HK 1-Normal-Raumtemperatur HeizbetriebHeating circuit 1: Normal room temperature, heating°CWrite
AV1WEZ 1 - HK 1 - Spar-Raumtemperatur HeizbetriebHeating circuit 1: Eco room temperature, heating°CWrite
AV2WEZ 1 - HK 2-Normal-Raumtemperatur HeizbetriebHeating circuit 2: Normal room temperature, heating°CWrite
AV3WEZ 1 - HK 2 - Spar-Raumtemperatur HeizbetriebHeating circuit 2: Eco room temperature, heating°CWrite
AV4WEZ 1 - HK 3-Normal-Raumtemperatur HeizbetriebHeating circuit 3: Normal room temperature, heating°CWrite
AV5WEZ 1 - HK 3 - Spar-Raumtemperatur HeizbetriebHeating circuit 3: Eco room temperature, heating°CWrite
AV6WEZ 1 - HK 1 - Solltemperatur HandbetriebHeating circuit 1: Setpoint for manual mode°CWrite
AV7WEZ 1 - HK 2 - Solltemperatur HandbetriebHeating circuit 2: Setpoint for manual mode°CWrite
AV8WEZ 1 - HK 3 - Solltemperatur HandbetriebHeating circuit 3: Setpoint for manual mode°CWrite
AV9WEZ 1 - HK 1 - Vorlauf Soll Konstantanf. HeizenHeating circuit 1: Flow setpoint for constant heating demand°CWrite
AV10WEZ 1 - HK 2 - Vorlauf Soll Konstantanf. HeizenHeating circuit 2: Flow setpoint for constant heating demand°CWrite
AV11WEZ 1 - HK 3 - Vorlauf Soll Konstantanf. HeizenHeating circuit 3: Flow setpoint for constant heating demand°CWrite
AI2WEZ 1 - HK 1 - Raum-SollHeating circuit 1: Room temperature setpoint in use°CRead
AI3WEZ 1 - HK 2 - Raum-SollHeating circuit 2: Room temperature setpoint in use°CRead
AI4WEZ 1 - HK 3 - Raum-SollHeating circuit 3: Room temperature setpoint in use°CRead
MVmin3WEZ 1 - WW - Betriebswahl WarmwasserHot water: Hot water operating mode selection (7 states)Write
AVmin12WEZ 1 - WW - Normal-WarmwassertemperaturHot water: Normal hot water temperature°CWrite
AV13WEZ 1 - WW - Spar-WarmwassertemperaturHot water: Eco hot water temperature°CWrite
AI5WEZ 1 - WW - Warmwasser-SollHot water: Hot water setpoint in use°CRead
AI6WEZ 1 - WW - Warmwasser-Ist SFHot water: Hot water temperature (sensor SF)°CRead
MVmin4WEZ 1 - HK 1 - Status HeizkreisregelungHeating circuit 1: Heating circuit control status (27 states)Read
MV5WEZ 1 - HK 2 - Status HeizkreisregelungHeating circuit 2: Heating circuit control status (27 states)Read
MV6WEZ 1 - HK 3 - Status HeizkreisregelungHeating circuit 3: Heating circuit control status (27 states)Read
MV7WEZ 1 - WW - Status WarmwasserregelungHot water: Hot water control status (14 states)Read
AI7WEZ 1 - HK 1 - Raum-IstHeating circuit 1: Room temperature°CRead
AI8WEZ 1 - HK 2 - Raum-IstHeating circuit 2: Room temperature°CRead
AI9WEZ 1 - HK 3 - Raum-IstHeating circuit 3: Room temperature°CRead
AImin11WEZ 1 - HK 1 - Vorlauf-IstHeating circuit 1: Flow temperature°CRead
AI12WEZ 1 - HK 2 - Vorlauf-IstHeating circuit 2: Flow temperature°CRead
AI13WEZ 1 - HK 3 - Vorlauf-IstHeating circuit 3: Flow temperature°CRead
AI14Sollwert für HeizkreisbetriebHeat generator setpoint, heating circuit mode°CRead
AI15Sollwert für SpeicherbetriebHeat generator setpoint, storage mode°CRead
AI16LeistungsbegrenzungHeat generator output limit%Read
AI17Sollwert für KühlbetriebHeat generator setpoint, cooling°CRead
AImin18WEZ-TemperaturHeat generator temperature°CRead
AI19RücklauftemperaturReturn temperature°CRead
AI20Wasserdruck in BarWater pressurebarRead
AI21Kühlung SollwertCooling setpoint°CRead
AI22WEZ 1 - HK 1 - Vorlauf-SollHeating circuit 1: Flow temperature setpoint°CRead
AI23WEZ 1 - HK 2 - Vorlauf-SollHeating circuit 2: Flow temperature setpoint°CRead
AI24WEZ 1 - HK 3 - Vorlauf-SollHeating circuit 3: Flow temperature setpoint°CRead
AI25WEZ 1 - HK 1 - MischerHeating circuit 1: Mixing valve position%Read
AI26WEZ 1 - HK 2 - MischerHeating circuit 2: Mixing valve position%Read
AI27WEZ 1 - HK 3 - MischerHeating circuit 3: Mixing valve position%Read
AI28WEZ 1 - HK 1 - PumpeHeating circuit 1: Pump output%Read
AI29WEZ 1 - HK 2 - PumpeHeating circuit 2: Pump output%Read
AI30WEZ 1 - HK 3 - PumpeHeating circuit 3: Pump output%Read
Object ID lookup: Hoval TopTronic E heat generator via Hoval Modbus/BACnet gateway point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TopTronic E heat generator via Hoval Modbus/BACnet gateway (standard datapoints) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Hoval TopTronic E heat generator via Hoval Modbus/BACnet gateway (standard datapoints)

How many BACnet points does the Hoval TopTronic E heat generator via Hoval Modbus/BACnet gateway (standard datapoints) have?

This list has 54 BACnet objects: 29 analog inputs, 14 analog values, 3 binary inputs, 8 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Hoval TopTronic E heat generator via Hoval Modbus/BACnet gateway (standard datapoints) BACnet points are writable?

18 of the 54 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Hoval TopTronic E heat generator via Hoval Modbus/BACnet gateway (standard datapoints) BACnet documentation?

The source is TTE ModBus BACnet Datapoints (Intesis MAPS signals file, sheet Signals), revision 2025-08-12, published free by Hoval at https://cdn.hoval.com/tte-modbus-bacnet-datapoints-hybris-original.xlsx.

What are the minimum BACnet points to integrate the Hoval TopTronic E heat generator via Hoval Modbus/BACnet gateway (standard datapoints)?

Start with MV 0 WEZ 1 - HK 1 - Betriebswahl Heizung (Heating circuit 1 operating mode); AV 0 WEZ 1 - HK 1-Normal-Raumtemperatur Heizbetrieb (Circuit 1 normal room setpoint, °C); MV 3 WEZ 1 - WW - Betriebswahl Warmwasser (Hot water operating mode); AV 12 WEZ 1 - WW - Normal-Warmwassertemperatur (Normal hot water setpoint, °C); AI 1 WEZ 1 - AF1 - Aussenfuehler 1 (Outdoor temperature); AI 18 WEZ-Temperatur (Heat generator temperature); AI 11 WEZ 1 - HK 1 - Vorlauf-Ist (Circuit 1 flow temperature); MV 4 WEZ 1 - HK 1 - Status Heizkreisregelung (Circuit 1 control status); BI 0 Comm Error Device 0 (Gateway lost Modbus link).

How do I check these points on the real TopTronic E heat generator via Hoval Modbus/BACnet gateway (standard datapoints)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Hoval BACnet points lists

Source: TTE ModBus BACnet Datapoints (Intesis MAPS signals file, sheet Signals) · rev. 2025-08-12. Object names, instances and units are reproduced as published; descriptions are our own.