- Home
- BACnet points lists
- Hisense
- Hisense VRF BACnet Server (HS-AC-BAC, by Intesis)
VRF BACnet gateway (up to 64 indoor units, H-Link) · BACnet points list
Hisense VRF BACnet Server (HS-AC-BAC, by Intesis) BACnet points list
Updated 6 November 2026
Intesis-made BACnet server for Hisense VRF, published by Hisense Italy. It connects to the H-Link bus at the outdoor unit and serves BACnet IP and BACnet MS/TP: gateway-wide commands, an outdoor-unit block at (OU address x 25) + 1000 and one indoor-unit block per MAPS index at (index x 100) with on/off, mode, setpoint, fan, vane, air and coil temperatures, error code, filter, remote-controller permissions and dehumidification.
This page lists 51 BACnet objects for the Hisense VRF BACnet Server (HS-AC-BAC, by Intesis) — 16 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Hisense’s own free documentation, linked below.
- Manufacturer
- Hisense
- Model
- Hisense VRF BACnet Server (HS-AC-BAC, by Intesis)
- Equipment
- VRF BACnet gateway (up to 64 indoor units, H-Link)
- Equipment type
- VRF & split air conditioners
- BACnet objects
- 51 (16 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 246
- Also known as
- HS-AC-BAC, Hisense VRF BACnet gateway, Hisense H-Link BACnet, Intesis BACnet Server Hisense VRF, HS-AC-BAC-16, HS-AC-BAC-64, INBACHIS016O000, INBACHIS064O000
- Brands covered
- Hisense
Reference only, provided as-is: verify against Hisense’s current documentation and the live device before use. Not official Hisense information. Terms of use.
BMS integration notes: Hisense VRF BACnet Server (HS-AC-BAC, by Intesis)
Wire the H-Link (TB2) terminals of the outdoor unit to Port A (A3/A4, no polarity), configure the units in Intesis MAPS, send the project, then map each indoor unit's _C commands and _S status objects from its (index x 100) block.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 100 | OxxUxxOn/Off_C | Start/stop indoor unit | Command |
| MO 100 | OxxUxxMode_C | Mode command | Command |
| AO 100 | OxxUxxSetpoint_C | Setpoint command | Command |
| MO 101 | OxxUxxFanSpeed_C | Fan speed command (1 = auto) | Command |
| BI 100 | OxxUxxOn/Off_S | Run status | Read |
| AI 100 | OxxUxxSetpoint_S | Setpoint in use | Read |
| AI 102 | OxxUxxInlet Temp. | Return air temperature | Read |
| BI 102 | OxxUxxCommunication Status | Unit present on H-Link | Read |
| AI 106 | OxxUxxUnit Error code | Fault code | Read |
Enable & remote start
No enable point is documented. Remote-controller permissions can be removed per unit with the Allow ... from RC_C objects (BO 102-105).
Network setup
- Default device instance 246; change it in Intesis MAPS.
- BACnet IP: default IP 192.168.100.246, DHCP enabled by default. BACnet MS/TP uses Port B.
- Indoor unit index (xxx) is the unit's index in MAPS, not its H-Link address.
Watch out for
- On/Off, Mode, FanSpeed, Vane and Setpoint at instances 0-2 act on all units at once.
Hisense VRF BACnet Server (HS-AC-BAC, by Intesis) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BO | 0 | On/Off (all units) | Start/stop every unit | Command | 0=Off, 1=On | |
| MO | 0 | Mode (all units) | Mode for every unit | Command | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| MO | 1 | FanSpeed (all units) | Fan speed for every unit | Command | 1=Auto, 2=Low, 3=Mid, 4=High, 5=High+ | |
| MO | 2 | Vane Position swing (all units) | Vane position for every unit | Command | 1=Auto, 2..8=Pos1..Pos7 | |
| AO | 0 | Temperature Setpoint (all units) | Setpoint for every unit (cool 19-30, heat 17-30 °C) | °C | Command | |
| AI | 1025 | OUxx_Outdoor Air Temp. | Outdoor air temperature (-50 to 99 °C) | °C | Read | |
| AI | 1026 | OUXX_Comp.Top Temp. | Compressor top temperature | °C | Read | |
| AI | 1027 | OUXX_Total Real Comp. Freq. | Total real compressor frequency | Hz | Read | |
| AI | 1028 | OUXX_Total Comp. Current | Total compressor current | A | Read | |
| AI | 1029 | OUXX_Out Exp. Valve 1 Open | Outdoor expansion valve 1 opening | % | Read | |
| AI | 1030 | OUXX_Discharge Pressure | Discharge pressure | MPa | Read | |
| AI | 1031 | OUXX_Suction Pressure | Suction pressure | MPa | Read | |
| BI | 1025 | OUXX_Communication Status | Outdoor unit present on H-Link | Read | 0=Not Exit, 1=Exist | |
| BImin | 100 | OxxUxxOn/Off_S | On/off status | Read | 0=Off, 1=On | |
| BOmin | 100 | OxxUxxOn/Off_C | Start/stop the indoor unit | Command | 0=Off, 1=On | |
| MI | 100 | OxxUxxMode_S | Operating mode in use | Read | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| MOmin | 100 | OxxUxxMode_C | Operating mode command | Command | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| AImin | 100 | OxxUxxSetpoint_S | Setpoint in use (cool 19-30, heat 17-30 °C) | °C | Read | |
| AOmin | 100 | OxxUxxSetpoint_C | Setpoint command (cool 19-30, heat 17-30 °C) | °C | Command | |
| MI | 101 | OxxUxxFanSpeed_S | Fan speed status | Read | 1=Auto, 2=Low, 3=Mid, 4=High, 5=High+ | |
| MOmin | 101 | OxxUxxFanSpeed_C | Fan speed command | Command | 1=Auto, 2=Low, 3=Mid, 4=High, 5=High+ | |
| MI | 102 | OxxUxxVane Position_S | Vane position status | Read | 1=Auto, 2..8=Pos1..Pos7 | |
| MO | 102 | OxxUxxVane Position_C | Vane position command | Command | 1=Auto, 2..8=Pos1..Pos7 | |
| AI | 101 | OxxUxxRemote Sensor Temp. | Remote sensor temperature | °C | Read | |
| AImin | 102 | OxxUxxInlet Temp. | Inlet (return) air temperature | °C | Read | |
| AI | 103 | OxxUxxOutlet Temp. | Outlet (supply) air temperature | °C | Read | |
| AI | 104 | OxxUxxGasPipe Temp. | Gas pipe temperature | °C | Read | |
| AI | 105 | OxxUxxLiquidPipe Temp. | Liquid pipe temperature | °C | Read | |
| AImin | 106 | OxxUxxUnit Error code | Unit error code | Read | ||
| BI | 101 | OxxUxxFilterSign | Filter sign | Read | 0=Normal, 1=Alarm | |
| BO | 101 | OxxUxxFilterReset | Reset the filter sign | Command | 1=Reset | |
| BImin | 102 | OxxUxxCommunication Status | Indoor unit present on H-Link | Read | 0=Not Exit, 1=Exist | |
| BI | 103 | OxxUxxAllow On/Off from RC_S | Remote on/off permission (status) | Read | 0=Allow, 1=Not allow | |
| BO | 102 | OxxUxxAllow On/Off from RC_C | Remote on/off permission (command) | Command | 0=Allow, 1=Not allow | |
| BI | 104 | OxxUxxAllow Mode from RC_S | Remote mode permission (status) | Read | 0=Allow, 1=Not allow | |
| BO | 103 | OxxUxxAllow Mode from RC_C | Remote mode permission (command) | Command | 0=Allow, 1=Not allow | |
| BI | 105 | OxxUxxAllow Setpoint from RC_S | Remote setpoint permission (status) | Read | 0=Allow, 1=Not allow | |
| BO | 104 | OxxUxxAllow Setpoint from RC_C | Remote setpoint permission (command) | Command | 0=Allow, 1=Not allow | |
| BI | 106 | OxxUxxAllow Fan from RC_S | Remote fan permission (status) | Read | 0=Allow, 1=Not allow | |
| BO | 105 | OxxUxxAllow Fan from RC_C | Remote fan permission (command) | Command | 0=Allow, 1=Not allow | |
| MI | 103 | OxxUxxUnit type | Indoor unit type | Read | 1=Not Defined, 2=SS, 3=FC, 4=VRF, 5=IU, 6=ES | |
| AI | 107 | OxxUxxUnit Address | Unit address (1-64) | Read | ||
| AI | 108 | OxxUxxSystem Address | System address (1-64) | Read | ||
| BI | 107 | OxxUxxDehumidification | Dehumidification enabled | Read | 0=Disabled, 1=Enabled | |
| MI | 104 | OxxUxxDehum. Correction_S | Dehumidification correction (status) | Read | 1=0, 2=(-1), 3=(-2) | |
| MO | 103 | OxxUxxDehum. Correction_C | Dehumidification correction (command) | Command | 1=0, 2=(-1), 3=(-2) | |
| AI | 109 | OxxUxxComp. Stop Cause | Compressor stop cause (255 = operation off) | Read | ||
| AI | 110 | OxxUxxExp. Valve Open | Indoor expansion valve opening (0-100) | Read | ||
| MI | 105 | OxxUxxOperat. Condition | Operating condition | Read | 1=Off, 2=Thermo Off, 3=Thermo On, 4=Alarm | |
| AI | 111 | OxxUxxRC SW Temp. | Remote controller sensor temperature | °C | Read | |
| BI | 108 | OxxUxxRC SW Config | Remote controller sensor configuration | Read | 0=With RCS, 1=Without RCS |
No points match these filters.
Object ID lookup: Hisense Hisense VRF Gateway HS-AC-BAC point IDs by name
BO0On/Off (all units)MO0Mode (all units)MO1FanSpeed (all units)MO2Vane Position swing (all units)AO0Temperature Setpoint (all units)AI1025OUxx_Outdoor Air Temp.AI1026OUXX_Comp.Top Temp.AI1027OUXX_Total Real Comp. Freq.AI1028OUXX_Total Comp. CurrentAI1029OUXX_Out Exp. Valve 1 OpenAI1030OUXX_Discharge PressureAI1031OUXX_Suction PressureBI1025OUXX_Communication StatusBI100OxxUxxOn/Off_SBO100OxxUxxOn/Off_CMI100OxxUxxMode_SMO100OxxUxxMode_CAI100OxxUxxSetpoint_SAO100OxxUxxSetpoint_CMI101OxxUxxFanSpeed_SMO101OxxUxxFanSpeed_CMI102OxxUxxVane Position_SMO102OxxUxxVane Position_CAI101OxxUxxRemote Sensor Temp.AI102OxxUxxInlet Temp.AI103OxxUxxOutlet Temp.AI104OxxUxxGasPipe Temp.AI105OxxUxxLiquidPipe Temp.AI106OxxUxxUnit Error codeBI101OxxUxxFilterSignBO101OxxUxxFilterResetBI102OxxUxxCommunication StatusBI103OxxUxxAllow On/Off from RC_SBO102OxxUxxAllow On/Off from RC_CBI104OxxUxxAllow Mode from RC_SBO103OxxUxxAllow Mode from RC_CBI105OxxUxxAllow Setpoint from RC_SBO104OxxUxxAllow Setpoint from RC_CBI106OxxUxxAllow Fan from RC_SBO105OxxUxxAllow Fan from RC_CMI103OxxUxxUnit typeAI107OxxUxxUnit AddressAI108OxxUxxSystem AddressBI107OxxUxxDehumidificationMI104OxxUxxDehum. Correction_SMO103OxxUxxDehum. Correction_CAI109OxxUxxComp. Stop CauseAI110OxxUxxExp. Valve OpenMI105OxxUxxOperat. ConditionAI111OxxUxxRC SW Temp.BI108OxxUxxRC SW Config
Integration notes
- Indoor unit instance = (xxx x 100) + offset, xxx = unit index in Intesis MAPS; index 1 shown (100-111).
- Outdoor unit instance = (xx x 25) + 1000 + offset, xx = outdoor address 1-64; address 1 shown (1025-1031).
- Made by Intesis (HMS); the object table is the same as the Intesis Hitachi VRF BACnet server INBACHIT016O000/064O000 (listed separately), as Hisense VRF uses the same H-Link bus.
- The member table has no read/write column; access is inferred (outputs commandable, inputs read-only).
- Communication Status states are printed as 0-Not Exit, 1-Exist.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Hisense VRF BACnet Server (HS-AC-BAC, by Intesis) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Hisense VRF BACnet Server (HS-AC-BAC, by Intesis)
How many BACnet points does the Hisense VRF BACnet Server (HS-AC-BAC, by Intesis) have?
This list has 51 BACnet objects: 19 analog inputs, 2 analog outputs, 10 binary inputs, 7 binary outputs, 6 multi-state inputs, 7 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Hisense VRF BACnet Server (HS-AC-BAC, by Intesis) BACnet points are writable?
16 of the 51 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Hisense VRF BACnet Server (HS-AC-BAC, by Intesis) BACnet documentation?
The source is Intesis BACnet Server - Hisense VRF User's Manual (HS-AC-BAC), revision 04/2018 r1.0, published free by Hisense at https://www.hisense.it/wp-content/uploads/2022/08/UM_bacnet-intesis_201804.pdf.
What are the minimum BACnet points to integrate the Hisense VRF BACnet Server (HS-AC-BAC, by Intesis)?
Start with BO 100 OxxUxxOn/Off_C (Start/stop indoor unit); MO 100 OxxUxxMode_C (Mode command); AO 100 OxxUxxSetpoint_C (Setpoint command); MO 101 OxxUxxFanSpeed_C (Fan speed command (1 = auto)); BI 100 OxxUxxOn/Off_S (Run status); AI 100 OxxUxxSetpoint_S (Setpoint in use); AI 102 OxxUxxInlet Temp. (Return air temperature); BI 102 OxxUxxCommunication Status (Unit present on H-Link); AI 106 OxxUxxUnit Error code (Fault code).
How do I enable BMS control of the Hisense VRF BACnet Server (HS-AC-BAC, by Intesis)?
No enable point is documented. Remote-controller permissions can be removed per unit with the Allow ... from RC_C objects (BO 102-105).
How do I check these points on the real Hisense VRF BACnet Server (HS-AC-BAC, by Intesis)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
Source: Intesis BACnet Server - Hisense VRF User's Manual (HS-AC-BAC) · rev. 04/2018 r1.0. Object names, instances and units are reproduced as published; descriptions are our own.