Variable frequency drive · BACnet points list

Fuji Electric FRENIC-Eco OPC-F1-BAC (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The OPC-F1-BAC card gives the FRENIC-Eco a BACnet MS/TP port. It maps the drive's communication command words (S06/S07), status words (M13/M14) and monitor values to fixed objects: BVs for run/reverse/reset commands, drive status bits and the X-terminal link commands, BIs for the final X-terminal states, BOs for the Y and 30 relay outputs, AVs for frequency, current, voltage, temperatures, hour meters and fault history, plus select/value AV pairs that read or write any parameter by group.

This page lists 82 BACnet objects for the Fuji Electric FRENIC-Eco OPC-F1-BAC (BACnet MS/TP) — 41 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Fuji Electric’s own free documentation, linked below.

Manufacturer
Fuji Electric
Model
FRENIC-Eco OPC-F1-BAC (BACnet MS/TP)
Equipment
Variable frequency drive
Equipment type
VFDs & pumps
BACnet objects
82 (41 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
37000 + address DIP switch value (37000-37255)
Also known as
OPC-F1-BAC, FRENIC-Eco, Frenic Eco BACnet, Fuji FRENIC-Eco, FECA-IN-112, FECA-TE-124
Source document
Fuji BACnet (OPC-F1-BAC) Start-Up Guide for the Fuji Electric FRENIC-Eco VFD · FECA-IN-112 (with I/O Map Addendum FECA-TE-124) · rev. 07/2012
Download CSV 82 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Fuji Electric’s current documentation and the live device before use. Not official Fuji Electric information. Terms of use.

BMS integration notes: Fuji Electric FRENIC-Eco OPC-F1-BAC (BACnet MS/TP)

Integration in brief

Fit the card in option port A, set the device instance and baud rate on its DIP switches, set the Y-codes as listed in the guide and set H30 so frequency and run commands come from the link, then restart the drive. Command BV 0 forward run and write the frequency reference to AV 0 (Hz); reset trips with BV 2. Read BV 3, AV 2, AV 30, BV 13 and AV 7.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 0Forward_CommandRun forward command (1 = run)Write
AV 0Frequency_Command_SetptFrequency reference in HzWrite
BV 2Alarm_ResetResets a drive alarmWrite
BV 3Forward_RotationRunning forward statusRead
AV 2Frequency_CommandFrequency command in use, Hz (M05)Read
AV 30Output_Current_RealOutput current in ampsRead
BV 13Alarm_RelayAlarm relay active (drive alarm)Read
AV 7Latest_AlarmLatest alarm codeRead

Enable & remote start

H30 selects where the frequency and run commands come from; the guide's example ('H30=-8') gives both frequency and run command control over BACnet MS/TP. Restart the drive after setting it. BV 14 Communications_Act shows when the link commands are in effect.

Sensors & values from the BMS

AV 1 PID_cmd (S13) takes a PID command from the BMS when the drive's PID is used.

Network setup

Watch out for

Fuji Electric FRENIC-Eco OPC-F1-BAC (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

82 of 82 shown
Type
Access
Show
Fuji Electric FRENIC-Eco OPC-F1-BAC (BACnet MS/TP) BACnet Points List
DescriptionStates
BVmin0Forward_CommandRun forward command (S06 bit 0)Write0=Inactive, 1=Forward
BV1Reverse_CommandRun reverse command (S06 bit 1)Write0=Inactive, 1=Reverse
BVmin2Alarm_ResetAlarm reset command (S06 bit 15)Write0=Inactive, 1=Reset
BVmin3Forward_RotationRunning forward (M14 bit 0)Read0=Inactive, 1=Forward
BV4Reverse_CommandRunning in reverse (M14 bit 1)Read0=Inactive, 1=Reverse
BV5DC_Braking/Pre_exitingDC braking or pre-excitation active (M14 bit 2)Read0=Inactive, 1=Braking
BV6Inverter_Shut_DownInverter output shut down (M14 bit 3)Read0=Inactive, 1=Shutdown
BV7BrakingBraking (M14 bit 4)Read0=Inactive, 1=Braking
BV8DC_Voltage_EstDC link voltage established (M14 bit 5)Read0=Inactive, 1=Established
BV9Voltage_LimitingVoltage limiting active (M14 bit 7)Read0=Inactive, 1=Limiting
BV10Current_LimitingCurrent limiting active (M14 bit 8)Read0=Inactive, 1=Limiting
BV11AccelerationAccelerating (M14 bit 9)Read0=Inactive, 1=Accelerating
BV12DecelerationDecelerating (M14 bit 10)Read0=Inactive, 1=Decelerating
BVmin13Alarm_RelayAlarm relay active (M14 bit 11)Read0=Inactive, 1=Alarm
BV14Communications_ActCommunications commands effective (M14 bit 12)Read0=Inactive, 1=Effective
BV15BusyDrive busy (M14 bit 15)Read0=Inactive, 1=Busy
BV16X1_CommunicationsTerminal X1 command via link (S06 bit 2)Write0=Inactive, 1=Active
BV17X2_CommunicationsTerminal X2 command via link (S06 bit 3)Write0=Inactive, 1=Active
BV18X3_CommunicationsTerminal X3 command via link (S06 bit 4)Write0=Inactive, 1=Active
BV19X4_CommunicationsTerminal X4 command via link (S06 bit 5)Write0=Inactive, 1=Active
BV20X5_CommunicationsTerminal X5 command via link (S06 bit 6)Write0=Inactive, 1=Active
BV21XF_CommunicationsTerminal XF command via link (S06 bit 13)Write0=Inactive, 1=Active
BV22XR_CommunicationsTerminal XR command via link (S06 bit 14)Write0=Inactive, 1=Active
BI0X1_FinalTerminal X1 final state (M13 bit 2)Read0=Inactive, 1=Active
BI1X2_FinalTerminal X2 final state (M13 bit 3)Read0=Inactive, 1=Active
BI2X3_FinalTerminal X3 final state (M13 bit 4)Read0=Inactive, 1=Active
BI3X4_FinalTerminal X4 final state (M13 bit 5)Read0=Inactive, 1=Active
BI4X5_FinalTerminal X5 final state (M13 bit 6)Read0=Inactive, 1=Active
BI5XF_FinalTerminal XF final state (M13 bit 13)Read0=Inactive, 1=Active
BI6XR_FinalTerminal XR final state (M13 bit 14)Read0=Inactive, 1=Active
BO0Y1_CommunicationsOutput Y1 command via link (S07 bit 0)Write0=Inactive, 1=Active
BO1Y2_CommunicationsOutput Y2 command via link (S07 bit 1)Write0=Inactive, 1=Active
BO2Y3_CommunicationsOutput Y3 command via link (S07 bit 2)Write0=Inactive, 1=Active
BO3Y5_CommunicationsOutput Y5 command via link (S07 bit 4)Write0=Inactive, 1=Active
BO430_CommunicationsOutput 30 command via link (S07 bit 8)Write0=Inactive, 1=Active
AVmin0Frequency_Command_SetptFrequency reference from BACnet (S05)HzWrite
AV1PID_cmdPID command from BACnet (S13)%Write
AVmin2Frequency_CommandFrequency command in use (M05)HzRead
AV3Output_TorqueOutput torque (M07)%Read
AV4Input_PowerInput power (M10)%Read
AV5Output_CurrentOutput current, % of rated (M11)%Read
AV6Output_VoltageOutput voltage (M12)VRead
AVmin7Latest_AlarmLatest alarm code (M16)Read
AV8Operation_TimeCumulative operation time (M20)hRead
AV9DC_Link_VoltageDC link voltage (M21)VRead
AV10Inverter_Air_TempInverter internal air temperature (M61)°CRead
AV11Inverter_Heat_Sink_TempHeatsink temperature (M62)°CRead
AV12PID_FeedbackPID feedback value (M72)Read
AV13PID_OutputPID output (M73)Read
AV14S_Parameter_SelectParameter number to access in group SWrite
AV15S_Parameter_ValueValue of the selected group S parameterWrite
AV16M_Parameter_SelectParameter number to access in group MWrite
AV17M_Parameter_ValueValue of the selected group M parameterRead
AV18F_Parameter_SelectParameter number to access in group FWrite
AV19F_Parameter_ValueValue of the selected group F parameterWrite
AV20E_Parameter_SelectParameter number to access in group EWrite
AV21E_Parameter_ValueValue of the selected group E parameterWrite
AV22C_Parameter_SelectParameter number to access in group CWrite
AV23C_Parameter_ValueValue of the selected group C parameterWrite
AV24P_Parameter_SelectParameter number to access in group PWrite
AV25P_Parameter_ValueValue of the selected group P parameterWrite
AV26H_Parameter_SelectParameter number to access in group HWrite
AV27H_Parameter_ValueValue of the selected group H parameterWrite
AV28J_Parameter_SelectParameter number to access in group JWrite
AV29J_Parameter_ValueValue of the selected group J parameterWrite
AVmin30Output_Current_RealOutput current in amps (W05)ARead
AV31Y_Parameter_SelectParameter number to access in group YWrite
AV32Y_Parameter_ValueValue of the selected group Y parameterWrite
AV33W_Parameter_SelectParameter number to access in group WWrite
AV34W_Parameter_ValueValue of the selected group W parameterWrite
AV35X_Parameter_SelectParameter number to access in group XWrite
AV36X_Parameter_ValueValue of the selected group X parameterWrite
AV37Z_Parameter_SelectParameter number to access in group ZWrite
AV38Z_Parameter_ValueValue of the selected group Z parameterWrite
AV39Capacitor_LifeCapacitor life (W75)%Read
AV40Cooling_Fan_TimeCooling fan run time (W77)hRead
AV41Motor_Run_TimeMotor run time (W79)hRead
AV42Energy_UsageEnergy usage (W81)Read
AV43Latest_FaultLatest fault code (M17)Read
AV44Second_FaultSecond most recent fault code (M18)Read
AV45Third_FaultThird most recent fault code (M19)Read
AO0Universal_AOUniversal analog output value (S12)Write
Object ID lookup: Fuji Electric FRENIC-Eco OPC-F1-BAC point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the FRENIC-Eco OPC-F1-BAC (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Fuji Electric FRENIC-Eco OPC-F1-BAC (BACnet MS/TP)

How many BACnet points does the Fuji Electric FRENIC-Eco OPC-F1-BAC (BACnet MS/TP) have?

This list has 82 BACnet objects: 1 analog output, 46 analog values, 7 binary inputs, 5 binary outputs, 23 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Fuji Electric FRENIC-Eco OPC-F1-BAC (BACnet MS/TP) BACnet points are writable?

41 of the 82 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Fuji Electric FRENIC-Eco OPC-F1-BAC (BACnet MS/TP) BACnet documentation?

The source is Fuji BACnet (OPC-F1-BAC) Start-Up Guide for the Fuji Electric FRENIC-Eco VFD (FECA-IN-112 (with I/O Map Addendum FECA-TE-124)), revision 07/2012, published free by Fuji Electric at https://americas.fujielectric.com/files/Fuji_BACnet_Start-Up_Guide%20FECA-IN-112.pdf.

What are the minimum BACnet points to integrate the Fuji Electric FRENIC-Eco OPC-F1-BAC (BACnet MS/TP)?

Start with BV 0 Forward_Command (Run forward command (1 = run)); AV 0 Frequency_Command_Setpt (Frequency reference in Hz); BV 2 Alarm_Reset (Resets a drive alarm); BV 3 Forward_Rotation (Running forward status); AV 2 Frequency_Command (Frequency command in use, Hz (M05)); AV 30 Output_Current_Real (Output current in amps); BV 13 Alarm_Relay (Alarm relay active (drive alarm)); AV 7 Latest_Alarm (Latest alarm code).

How do I enable BMS control of the Fuji Electric FRENIC-Eco OPC-F1-BAC (BACnet MS/TP)?

H30 selects where the frequency and run commands come from; the guide's example ('H30=-8') gives both frequency and run command control over BACnet MS/TP. Restart the drive after setting it. BV 14 Communications_Act shows when the link commands are in effect.

Can the BMS supply sensor values to the Fuji Electric FRENIC-Eco OPC-F1-BAC (BACnet MS/TP)?

AV 1 PID_cmd (S13) takes a PID command from the BMS when the drive's PID is used.

How do I check these points on the real FRENIC-Eco OPC-F1-BAC (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: Fuji BACnet (OPC-F1-BAC) Start-Up Guide for the Fuji Electric FRENIC-Eco VFD · FECA-IN-112 (with I/O Map Addendum FECA-TE-124) · rev. 07/2012. Object names, instances and units are reproduced as published; descriptions are our own.