Variable frequency drive · BACnet points list
Fuji Electric FRENIC-Eco OPC-F1-BAC (BACnet MS/TP) BACnet points list
Updated 6 November 2026
The OPC-F1-BAC card gives the FRENIC-Eco a BACnet MS/TP port. It maps the drive's communication command words (S06/S07), status words (M13/M14) and monitor values to fixed objects: BVs for run/reverse/reset commands, drive status bits and the X-terminal link commands, BIs for the final X-terminal states, BOs for the Y and 30 relay outputs, AVs for frequency, current, voltage, temperatures, hour meters and fault history, plus select/value AV pairs that read or write any parameter by group.
This page lists 82 BACnet objects for the Fuji Electric FRENIC-Eco OPC-F1-BAC (BACnet MS/TP) — 41 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Fuji Electric’s own free documentation, linked below.
- Manufacturer
- Fuji Electric
- Model
- FRENIC-Eco OPC-F1-BAC (BACnet MS/TP)
- Equipment
- Variable frequency drive
- Equipment type
- VFDs & pumps
- BACnet objects
- 82 (41 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 37000 + address DIP switch value (37000-37255)
- Also known as
- OPC-F1-BAC, FRENIC-Eco, Frenic Eco BACnet, Fuji FRENIC-Eco, FECA-IN-112, FECA-TE-124
Reference only, provided as-is: verify against Fuji Electric’s current documentation and the live device before use. Not official Fuji Electric information. Terms of use.
BMS integration notes: Fuji Electric FRENIC-Eco OPC-F1-BAC (BACnet MS/TP)
Fit the card in option port A, set the device instance and baud rate on its DIP switches, set the Y-codes as listed in the guide and set H30 so frequency and run commands come from the link, then restart the drive. Command BV 0 forward run and write the frequency reference to AV 0 (Hz); reset trips with BV 2. Read BV 3, AV 2, AV 30, BV 13 and AV 7.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 0 | Forward_Command | Run forward command (1 = run) | Write |
| AV 0 | Frequency_Command_Setpt | Frequency reference in Hz | Write |
| BV 2 | Alarm_Reset | Resets a drive alarm | Write |
| BV 3 | Forward_Rotation | Running forward status | Read |
| AV 2 | Frequency_Command | Frequency command in use, Hz (M05) | Read |
| AV 30 | Output_Current_Real | Output current in amps | Read |
| BV 13 | Alarm_Relay | Alarm relay active (drive alarm) | Read |
| AV 7 | Latest_Alarm | Latest alarm code | Read |
Enable & remote start
H30 selects where the frequency and run commands come from; the guide's example ('H30=-8') gives both frequency and run command control over BACnet MS/TP. Restart the drive after setting it. BV 14 Communications_Act shows when the link commands are in effect.
Sensors & values from the BMS
AV 1 PID_cmd (S13) takes a PID command from the BMS when the drive's PID is used.
Network setup
- Device instance: address DIP switches A0-A7 give 37000-37255.
- Baud rate DIP switches B0-B4: 9600, 19200, 38400, 76800 or auto.
- Terminating and bias resistor DIP switches are on the card; turn them on at the end of the line if needed.
- Guide's Y-code settings: Y01 = 1, Y02 = 0, Y03 = 2, Y04 = 4, Y05 = 0, Y06 = 0, Y07 = 1, Y08 = 0, Y09 = 0.01, Y10 = 0; Y11-Y20 the same; Y98 = 0, Y99 = 0.
- The OPC-F1-RS option card may have to be removed to fit the OPC-F1-BAC.
Watch out for
- AV 5 Output_Current is in % of rating; use AV 30 Output_Current_Real for amps.
- Writes through the *_Parameter_Value AVs change drive parameters; don't write them cyclically.
- BV 4 shares its object name with BV 1; tell them apart by instance.
- Use either a link command (BV 16-22) or the terminal for each X input, not both.
Fuji Electric FRENIC-Eco OPC-F1-BAC (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BVmin | 0 | Forward_Command | Run forward command (S06 bit 0) | Write | 0=Inactive, 1=Forward | |
| BV | 1 | Reverse_Command | Run reverse command (S06 bit 1) | Write | 0=Inactive, 1=Reverse | |
| BVmin | 2 | Alarm_Reset | Alarm reset command (S06 bit 15) | Write | 0=Inactive, 1=Reset | |
| BVmin | 3 | Forward_Rotation | Running forward (M14 bit 0) | Read | 0=Inactive, 1=Forward | |
| BV | 4 | Reverse_Command | Running in reverse (M14 bit 1) | Read | 0=Inactive, 1=Reverse | |
| BV | 5 | DC_Braking/Pre_exiting | DC braking or pre-excitation active (M14 bit 2) | Read | 0=Inactive, 1=Braking | |
| BV | 6 | Inverter_Shut_Down | Inverter output shut down (M14 bit 3) | Read | 0=Inactive, 1=Shutdown | |
| BV | 7 | Braking | Braking (M14 bit 4) | Read | 0=Inactive, 1=Braking | |
| BV | 8 | DC_Voltage_Est | DC link voltage established (M14 bit 5) | Read | 0=Inactive, 1=Established | |
| BV | 9 | Voltage_Limiting | Voltage limiting active (M14 bit 7) | Read | 0=Inactive, 1=Limiting | |
| BV | 10 | Current_Limiting | Current limiting active (M14 bit 8) | Read | 0=Inactive, 1=Limiting | |
| BV | 11 | Acceleration | Accelerating (M14 bit 9) | Read | 0=Inactive, 1=Accelerating | |
| BV | 12 | Deceleration | Decelerating (M14 bit 10) | Read | 0=Inactive, 1=Decelerating | |
| BVmin | 13 | Alarm_Relay | Alarm relay active (M14 bit 11) | Read | 0=Inactive, 1=Alarm | |
| BV | 14 | Communications_Act | Communications commands effective (M14 bit 12) | Read | 0=Inactive, 1=Effective | |
| BV | 15 | Busy | Drive busy (M14 bit 15) | Read | 0=Inactive, 1=Busy | |
| BV | 16 | X1_Communications | Terminal X1 command via link (S06 bit 2) | Write | 0=Inactive, 1=Active | |
| BV | 17 | X2_Communications | Terminal X2 command via link (S06 bit 3) | Write | 0=Inactive, 1=Active | |
| BV | 18 | X3_Communications | Terminal X3 command via link (S06 bit 4) | Write | 0=Inactive, 1=Active | |
| BV | 19 | X4_Communications | Terminal X4 command via link (S06 bit 5) | Write | 0=Inactive, 1=Active | |
| BV | 20 | X5_Communications | Terminal X5 command via link (S06 bit 6) | Write | 0=Inactive, 1=Active | |
| BV | 21 | XF_Communications | Terminal XF command via link (S06 bit 13) | Write | 0=Inactive, 1=Active | |
| BV | 22 | XR_Communications | Terminal XR command via link (S06 bit 14) | Write | 0=Inactive, 1=Active | |
| BI | 0 | X1_Final | Terminal X1 final state (M13 bit 2) | Read | 0=Inactive, 1=Active | |
| BI | 1 | X2_Final | Terminal X2 final state (M13 bit 3) | Read | 0=Inactive, 1=Active | |
| BI | 2 | X3_Final | Terminal X3 final state (M13 bit 4) | Read | 0=Inactive, 1=Active | |
| BI | 3 | X4_Final | Terminal X4 final state (M13 bit 5) | Read | 0=Inactive, 1=Active | |
| BI | 4 | X5_Final | Terminal X5 final state (M13 bit 6) | Read | 0=Inactive, 1=Active | |
| BI | 5 | XF_Final | Terminal XF final state (M13 bit 13) | Read | 0=Inactive, 1=Active | |
| BI | 6 | XR_Final | Terminal XR final state (M13 bit 14) | Read | 0=Inactive, 1=Active | |
| BO | 0 | Y1_Communications | Output Y1 command via link (S07 bit 0) | Write | 0=Inactive, 1=Active | |
| BO | 1 | Y2_Communications | Output Y2 command via link (S07 bit 1) | Write | 0=Inactive, 1=Active | |
| BO | 2 | Y3_Communications | Output Y3 command via link (S07 bit 2) | Write | 0=Inactive, 1=Active | |
| BO | 3 | Y5_Communications | Output Y5 command via link (S07 bit 4) | Write | 0=Inactive, 1=Active | |
| BO | 4 | 30_Communications | Output 30 command via link (S07 bit 8) | Write | 0=Inactive, 1=Active | |
| AVmin | 0 | Frequency_Command_Setpt | Frequency reference from BACnet (S05) | Hz | Write | |
| AV | 1 | PID_cmd | PID command from BACnet (S13) | % | Write | |
| AVmin | 2 | Frequency_Command | Frequency command in use (M05) | Hz | Read | |
| AV | 3 | Output_Torque | Output torque (M07) | % | Read | |
| AV | 4 | Input_Power | Input power (M10) | % | Read | |
| AV | 5 | Output_Current | Output current, % of rated (M11) | % | Read | |
| AV | 6 | Output_Voltage | Output voltage (M12) | V | Read | |
| AVmin | 7 | Latest_Alarm | Latest alarm code (M16) | Read | ||
| AV | 8 | Operation_Time | Cumulative operation time (M20) | h | Read | |
| AV | 9 | DC_Link_Voltage | DC link voltage (M21) | V | Read | |
| AV | 10 | Inverter_Air_Temp | Inverter internal air temperature (M61) | °C | Read | |
| AV | 11 | Inverter_Heat_Sink_Temp | Heatsink temperature (M62) | °C | Read | |
| AV | 12 | PID_Feedback | PID feedback value (M72) | Read | ||
| AV | 13 | PID_Output | PID output (M73) | Read | ||
| AV | 14 | S_Parameter_Select | Parameter number to access in group S | Write | ||
| AV | 15 | S_Parameter_Value | Value of the selected group S parameter | Write | ||
| AV | 16 | M_Parameter_Select | Parameter number to access in group M | Write | ||
| AV | 17 | M_Parameter_Value | Value of the selected group M parameter | Read | ||
| AV | 18 | F_Parameter_Select | Parameter number to access in group F | Write | ||
| AV | 19 | F_Parameter_Value | Value of the selected group F parameter | Write | ||
| AV | 20 | E_Parameter_Select | Parameter number to access in group E | Write | ||
| AV | 21 | E_Parameter_Value | Value of the selected group E parameter | Write | ||
| AV | 22 | C_Parameter_Select | Parameter number to access in group C | Write | ||
| AV | 23 | C_Parameter_Value | Value of the selected group C parameter | Write | ||
| AV | 24 | P_Parameter_Select | Parameter number to access in group P | Write | ||
| AV | 25 | P_Parameter_Value | Value of the selected group P parameter | Write | ||
| AV | 26 | H_Parameter_Select | Parameter number to access in group H | Write | ||
| AV | 27 | H_Parameter_Value | Value of the selected group H parameter | Write | ||
| AV | 28 | J_Parameter_Select | Parameter number to access in group J | Write | ||
| AV | 29 | J_Parameter_Value | Value of the selected group J parameter | Write | ||
| AVmin | 30 | Output_Current_Real | Output current in amps (W05) | A | Read | |
| AV | 31 | Y_Parameter_Select | Parameter number to access in group Y | Write | ||
| AV | 32 | Y_Parameter_Value | Value of the selected group Y parameter | Write | ||
| AV | 33 | W_Parameter_Select | Parameter number to access in group W | Write | ||
| AV | 34 | W_Parameter_Value | Value of the selected group W parameter | Write | ||
| AV | 35 | X_Parameter_Select | Parameter number to access in group X | Write | ||
| AV | 36 | X_Parameter_Value | Value of the selected group X parameter | Write | ||
| AV | 37 | Z_Parameter_Select | Parameter number to access in group Z | Write | ||
| AV | 38 | Z_Parameter_Value | Value of the selected group Z parameter | Write | ||
| AV | 39 | Capacitor_Life | Capacitor life (W75) | % | Read | |
| AV | 40 | Cooling_Fan_Time | Cooling fan run time (W77) | h | Read | |
| AV | 41 | Motor_Run_Time | Motor run time (W79) | h | Read | |
| AV | 42 | Energy_Usage | Energy usage (W81) | Read | ||
| AV | 43 | Latest_Fault | Latest fault code (M17) | Read | ||
| AV | 44 | Second_Fault | Second most recent fault code (M18) | Read | ||
| AV | 45 | Third_Fault | Third most recent fault code (M19) | Read | ||
| AO | 0 | Universal_AO | Universal analog output value (S12) | Write |
No points match these filters.
Object ID lookup: Fuji Electric FRENIC-Eco OPC-F1-BAC point IDs by name
BV0Forward_CommandBV1Reverse_CommandBV2Alarm_ResetBV3Forward_RotationBV4Reverse_CommandBV5DC_Braking/Pre_exitingBV6Inverter_Shut_DownBV7BrakingBV8DC_Voltage_EstBV9Voltage_LimitingBV10Current_LimitingBV11AccelerationBV12DecelerationBV13Alarm_RelayBV14Communications_ActBV15BusyBV16X1_CommunicationsBV17X2_CommunicationsBV18X3_CommunicationsBV19X4_CommunicationsBV20X5_CommunicationsBV21XF_CommunicationsBV22XR_CommunicationsBI0X1_FinalBI1X2_FinalBI2X3_FinalBI3X4_FinalBI4X5_FinalBI5XF_FinalBI6XR_FinalBO0Y1_CommunicationsBO1Y2_CommunicationsBO2Y3_CommunicationsBO3Y5_CommunicationsBO430_CommunicationsAV0Frequency_Command_SetptAV1PID_cmdAV2Frequency_CommandAV3Output_TorqueAV4Input_PowerAV5Output_CurrentAV6Output_VoltageAV7Latest_AlarmAV8Operation_TimeAV9DC_Link_VoltageAV10Inverter_Air_TempAV11Inverter_Heat_Sink_TempAV12PID_FeedbackAV13PID_OutputAV14S_Parameter_SelectAV15S_Parameter_ValueAV16M_Parameter_SelectAV17M_Parameter_ValueAV18F_Parameter_SelectAV19F_Parameter_ValueAV20E_Parameter_SelectAV21E_Parameter_ValueAV22C_Parameter_SelectAV23C_Parameter_ValueAV24P_Parameter_SelectAV25P_Parameter_ValueAV26H_Parameter_SelectAV27H_Parameter_ValueAV28J_Parameter_SelectAV29J_Parameter_ValueAV30Output_Current_RealAV31Y_Parameter_SelectAV32Y_Parameter_ValueAV33W_Parameter_SelectAV34W_Parameter_ValueAV35X_Parameter_SelectAV36X_Parameter_ValueAV37Z_Parameter_SelectAV38Z_Parameter_ValueAV39Capacitor_LifeAV40Cooling_Fan_TimeAV41Motor_Run_TimeAV42Energy_UsageAV43Latest_FaultAV44Second_FaultAV45Third_FaultAO0Universal_AO
Integration notes
- Object list from the Start-Up Guide FECA-IN-112 (pages 6-9); the linked drive registers in the descriptions and the units come from the I/O Map Addendum FECA-TE-124 (https://americas.fujielectric.com/files/Frenic%20Eco%20Bacnet%20I_O%20Map%20Addendum%20FECA-TE-124.pdf).
- The guide's unit column repeats the object name for the parameter select/value AVs and for AV 42-45; the addendum leaves those units blank, which is used here.
- BV 4 is printed with the same name as BV 1 (Reverse_Command); the addendum links it to the reverse-rotation status bit (M14 bit 1), so it is a read-only status.
- BV 16-22 hold the X1-XR terminal states written through the link (S06); BI 0-6 show the terminal states the drive actually uses (M13). Write BV 16-22 to drive a terminal over BACnet MS/TP.
- Parameter access: write the parameter number to a *_Parameter_Select AV (e.g. AV 14 = 5 for S05), then read or write the matching *_Parameter_Value AV. An unsupported parameter returns 0 with reliability set to fault.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the FRENIC-Eco OPC-F1-BAC (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Fuji Electric FRENIC-Eco OPC-F1-BAC (BACnet MS/TP)
How many BACnet points does the Fuji Electric FRENIC-Eco OPC-F1-BAC (BACnet MS/TP) have?
This list has 82 BACnet objects: 1 analog output, 46 analog values, 7 binary inputs, 5 binary outputs, 23 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Fuji Electric FRENIC-Eco OPC-F1-BAC (BACnet MS/TP) BACnet points are writable?
41 of the 82 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Fuji Electric FRENIC-Eco OPC-F1-BAC (BACnet MS/TP) BACnet documentation?
The source is Fuji BACnet (OPC-F1-BAC) Start-Up Guide for the Fuji Electric FRENIC-Eco VFD (FECA-IN-112 (with I/O Map Addendum FECA-TE-124)), revision 07/2012, published free by Fuji Electric at https://americas.fujielectric.com/files/Fuji_BACnet_Start-Up_Guide%20FECA-IN-112.pdf.
What are the minimum BACnet points to integrate the Fuji Electric FRENIC-Eco OPC-F1-BAC (BACnet MS/TP)?
Start with BV 0 Forward_Command (Run forward command (1 = run)); AV 0 Frequency_Command_Setpt (Frequency reference in Hz); BV 2 Alarm_Reset (Resets a drive alarm); BV 3 Forward_Rotation (Running forward status); AV 2 Frequency_Command (Frequency command in use, Hz (M05)); AV 30 Output_Current_Real (Output current in amps); BV 13 Alarm_Relay (Alarm relay active (drive alarm)); AV 7 Latest_Alarm (Latest alarm code).
How do I enable BMS control of the Fuji Electric FRENIC-Eco OPC-F1-BAC (BACnet MS/TP)?
H30 selects where the frequency and run commands come from; the guide's example ('H30=-8') gives both frequency and run command control over BACnet MS/TP. Restart the drive after setting it. BV 14 Communications_Act shows when the link commands are in effect.
Can the BMS supply sensor values to the Fuji Electric FRENIC-Eco OPC-F1-BAC (BACnet MS/TP)?
AV 1 PID_cmd (S13) takes a PID command from the BMS when the drive's PID is used.
How do I check these points on the real FRENIC-Eco OPC-F1-BAC (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
Source: Fuji BACnet (OPC-F1-BAC) Start-Up Guide for the Fuji Electric FRENIC-Eco VFD · FECA-IN-112 (with I/O Map Addendum FECA-TE-124) · rev. 07/2012. Object names, instances and units are reproduced as published; descriptions are our own.