Variable frequency drive (VFD) · BACnet points list

Franklin Electric Cerus X-Drive VFD (embedded BACnet MS/TP) BACnet points list

Updated 12 November 2026

Short answer

The Cerus X-Drive has BACnet MS/TP built into its COM1 RS-485 port. The drive exposes only Analog and Binary Values: commandable AVs for the frequency reference and 16 block-transfer slots, read-only AVs for drive measurements and codes, commandable BVs for run, stop, direction and reset, and status BVs for faults, HOA position and pump modes such as pipe fill, sleep and broken pipe.

This page lists 80 BACnet objects for the Franklin Electric Cerus X-Drive VFD (embedded BACnet MS/TP) — 24 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Franklin Electric’s own free documentation, linked below.

Manufacturer
Franklin Electric
Model
Cerus X-Drive VFD (embedded BACnet MS/TP)
Equipment
Variable frequency drive (VFD)
Equipment type
VFDs & pumps
BACnet objects
80 (24 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
[Comm-27] x 1000 + [Comm-26]
Also known as
Cerus X-Drive, X-Drive, Cerus X Drive, Franklin Cerus VFD, Cerus Industrial X-Drive
Source document
Cerus X-Drive Communications - BACnet Communication
Download CSV 80 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Franklin Electric’s current documentation and the live device before use. Not official Franklin Electric information. Terms of use.

BMS integration notes: Franklin Electric Cerus X-Drive VFD (embedded BACnet MS/TP)

Integration in brief

Set PLC Com Type to BACnet, the MAC, speed and device ID, then point the HOA source, speed references and run commands at RS485 Serial. Run with BV 7, give speed with AV 1 (with BV 0 set to use it), and read output frequency, current, faults and the HOA state.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 7Power Out CMDRun command (1 = run, 0 = coast stop)Command
BV 0Freq Active CMDMust be 1 to use the AV 1 frequency referenceCommand
AV 1FreqRefValueFrequency reference, HzCommand
BV 15ResetFault reset (write 1)Command
AV 31Output FrequencyOutput frequency, HzRead
AV 44Output CurrentMotor current, ARead
BV 33HOA in AutoHOA switch in AutoRead
BV 19Error/FaultAny error/fault activeRead
AV 43Error CodeFault codeRead

Enable & remote start

Set HOA Mode Source [SET-60] to RS485 Serial, Auto Speed Ref [SET-07] and Hand Speed Ref [SET-09] to RS485 Serial, and Auto/Hand Run Cmd [SET-08]/[SET-10] to RS485 Serial so BACnet can run the drive and set its speed.

Network setup

Watch out for

Franklin Electric Cerus X-Drive VFD (embedded BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

80 of 80 shown
Type
AnalogBinary
Access
Show
Franklin Electric Cerus X-Drive VFD (embedded BACnet MS/TP) BACnet Points List
DescriptionStates
AVmin1FreqRefValueFrequency referenceHzCommand
AV11Block TransferBlock transfer mapping 1Command
AV12Block TransferBlock transfer mapping 2Command
AV13Block TransferBlock transfer mapping 3Command
AV14Block TransferBlock transfer mapping 4Command
AV15Block TransferBlock transfer mapping 5Command
AV16Block TransferBlock transfer mapping 6Command
AV17Block TransferBlock transfer mapping 7Command
AV18Block TransferBlock transfer mapping 8Command
AV19Block TransferBlock transfer mapping 9Command
AV20Block TransferBlock transfer mapping 10Command
AV21Block TransferBlock transfer mapping 11Command
AV22Block TransferBlock transfer mapping 12Command
AV23Block TransferBlock transfer mapping 13Command
AV24Block TransferBlock transfer mapping 14Command
AV25Block TransferBlock transfer mapping 15Command
AV26Block TransferBlock transfer mapping 16Command
AVmin31Output FrequencyOutput frequencyHzRead
AV35Output TorqueOutput torque%Read
AV39Status WordDrive status word (BV 16-31 packed)Read
AV41Drive Type CodeDrive type codeRead
AV42Warning CodeWarning/alarm codeRead
AVmin43Error CodeError/fault codeRead
AVmin44Output CurrentOutput/motor currentARead
AV45DC Bus VoltageDC bus voltageVRead
AV46Output VoltageOutput voltageVRead
AV47Count ValueAccumulated TRG DI counterRead
AV48Power FactorOutput power factorRead
AV49Output PowerOutput powerkWRead
AV50IGBT TemperatureIGBT temperature°CRead
AV51Caps TemperatureDC bus capacitor temperature°CRead
AV52Carrier FrequencyActual carrier frequencykHzRead
AV53PID F/B ValuePID feedback value%Read
AV54Overload RateOverload value%Read
AV55GND Fault LevelGround fault trip level%Read
AV56DC Bus RipplesDC bus ripple amplitudeVRead
AV57Fan SpeedDrive cooling fan speed%Read
AV58Motor SpeedActual motor speedrpmRead
AV59kWhEnergy (printed as kilowatts per hour)kWhRead
AV60Step FrequencyStep frequency ID numberRead
AV61AVI1 Input ValueAVI1 analog input reading%Read
AV62ACI Input ValueACI analog input reading%Read
AV63AVI2 Input ValueAVI2 analog input reading%Read
AV64Digital IN StatusDigital inputs status [IO-46]Read
AV65Digital OUT StatusDigital outputs status [IO-58]Read
AV66CPU DI Pin StatusCPU pins from digital inputsRead
AV67CPU DO Pin StatusCPU pins to digital outputsRead
AV68PLC D1043 StatusPLC register D1043Read
AV70ULD Recover CounterUnder-load recover counter [SET-46]Read
AV71HLD Recover CounterHigh-load recover counter [SET-52]Read
BVmin0Freq Active CMDUse frequency referenceCommand0=Frq CMD=0Hz, 1=Frq CMD=FreqRefValue
BV1FWD/REV CMDDirection commandCommand0=Forward, 1=Reverse
BV3Stop CMDStop (decelerate to 0 Hz)Command0=None, 1=Stop
BV4Hold SPDHold current frequencyCommand0=None, 1=Stay at current frequency
BV6Q-Stop CMDQuick stopCommand0=None, 1=Quick stop
BVmin7Power Out CMDRun command (power to motor)Command0=Power OFF (coast to stop), 1=Power ON (run)
BVmin15ResetFault resetCommand0=None, 1=Reset fault
BV16At CMD FreqOutput at commanded frequencyRead0=Out Frq not at CMD, 1=Out Frq = CMD Frq
BV17DirectionRunning directionRead0=Forward, 1=Reverse
BV18WarningWarning activeRead0=None, 1=Warning active
BVmin19Error/FaultError/fault activeRead0=None, 1=Error/fault active
BV20ULD FaultUnder-load faultRead0=No fault, 1=Under load triggered (ULD)
BV21HLD FaultHigh-load faultRead0=No fault, 1=High load triggered (HLD)
BV22Q-Stop ModeQuick stop activeRead0=None, 1=Q-Stop active
BV23Power OUTPower output on (running)Read0=Power OUT off, 1=Power OUT on (run)
BV22Broken PipeBroken pipe fault (printed as BV 022 a second time)Read0=No fault, 1=Broken pipe fault
BV23Pipe LeakPipe leak fault (printed as BV 023 a second time)Read0=No fault, 1=Pipe leak fault
BV24Signal LossSignal loss faultRead0=No fault, 1=Signal loss fault
BV25OverpressureOverpressure faultRead0=No fault, 1=Overpressure fault
BV26Damper FaultDamper faultRead0=No fault, 1=Damper fault
BV27No-Flow FaultNo-flow faultRead0=No fault, 1=No-flow fault
BV28Fireman's OverrideFireman's override modeRead0=Normal mode, 1=Fireman's override mode
BV29Shutdown ModeShutdown modeRead0=Normal mode, 1=Shutdown mode
BV30Pipe Fill ModePipe fill modeRead0=Normal mode, 1=Pipe fill mode
BV31Sleep ModeSleep modeRead0=Normal mode, 1=Sleep mode
BV32HOA in OFFHOA switch in OffRead0=HOA not in OFF, 1=HOA is in OFF
BVmin33HOA in AutoHOA switch in AutoRead0=HOA not in Auto, 1=HOA is in Auto
BV34HOA in HandHOA switch in HandRead0=HOA not in Hand, 1=HOA is in Hand
BV35Stopped by AI LevelStopped by analog input levelRead0=Normal control, 1=Stopped by analog input level
BV36Frequency Limit by AIFrequency limited by analog input levelRead0=Normal freq. limit, 1=Freq. limit by analog input level
Object ID lookup: Franklin Electric Cerus X-Drive VFD point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Cerus X-Drive VFD (embedded BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Franklin Electric Cerus X-Drive VFD (embedded BACnet MS/TP)

How many BACnet points does the Franklin Electric Cerus X-Drive VFD (embedded BACnet MS/TP) have?

This list has 80 BACnet objects: 50 analog values, 30 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Franklin Electric Cerus X-Drive VFD (embedded BACnet MS/TP) BACnet points are writable?

24 of the 80 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Franklin Electric Cerus X-Drive VFD (embedded BACnet MS/TP) BACnet documentation?

The source is Cerus X-Drive Communications - BACnet Communication, published free by Franklin Electric at https://fele.widen.net/content/nfq71r6s8h/pdf/BACnet_Communications.pdf?u=bt7ctv.

What are the minimum BACnet points to integrate the Franklin Electric Cerus X-Drive VFD (embedded BACnet MS/TP)?

Start with BV 7 Power Out CMD (Run command (1 = run, 0 = coast stop)); BV 0 Freq Active CMD (Must be 1 to use the AV 1 frequency reference); AV 1 FreqRefValue (Frequency reference, Hz); BV 15 Reset (Fault reset (write 1)); AV 31 Output Frequency (Output frequency, Hz); AV 44 Output Current (Motor current, A); BV 33 HOA in Auto (HOA switch in Auto); BV 19 Error/Fault (Any error/fault active); AV 43 Error Code (Fault code).

How do I enable BMS control of the Franklin Electric Cerus X-Drive VFD (embedded BACnet MS/TP)?

Set HOA Mode Source [SET-60] to RS485 Serial, Auto Speed Ref [SET-07] and Hand Speed Ref [SET-09] to RS485 Serial, and Auto/Hand Run Cmd [SET-08]/[SET-10] to RS485 Serial so BACnet can run the drive and set its speed.

How do I check these points on the real Cerus X-Drive VFD (embedded BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: Cerus X-Drive Communications - BACnet Communication. Object names, instances and units are reproduced as published; descriptions are our own.