Humidifier controller / humidistat (BACnet MS/TP) · BACnet points list

DriSteem TRI2 BACnet humidistat BACnet points list

Updated 4 November 2026

Short answer

The TRI2 is DriSteem's touchscreen humidistat with BACnet MS/TP over RS485. It is built on a general-purpose X2 controller; the manual lists only the objects DriSteem uses (39 here). The BMS can read the humidity inputs and alarms, switch the unit on or off, write the control set point, or take direct control of the dehumidifier output.

This page lists 39 BACnet objects for the DriSteem TRI2 BACnet humidistat — 21 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from DriSteem’s own free documentation, linked below.

Manufacturer
DriSteem
Model
TRI2 BACnet humidistat
Equipment
Humidifier controller / humidistat (BACnet MS/TP)
Equipment type
Humidifiers
BACnet objects
39 (21 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
TRI2, DriSteem TRI2, TCI humidistat, DriSteem BACnet humidistat, X2 controller, AEX-BAC
Source document
DriSteem Humidistats Model TCI-W11-U-H, TCI-W11-U, Model TRI2 with BACnet Humidistat - Installation, Operation, and Maintenance Manual · TCI-IOM-EN-REVF-0125 · rev. 2025-01
Download CSV 39 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against DriSteem’s current documentation and the live device before use. Not official DriSteem information. Terms of use.

BMS integration notes: DriSteem TRI2 BACnet humidistat

Integration in brief

By default the humidistat runs its own control loop: the BMS can switch it on or off with BV 0 and write the set point on AV 211, and read humidity on AI 102 (room) or AI 106 (duct). For BAS control of a dehumidifier, set digital-output parameter 1d 01 to 6 (manual control); the BMS then drives the dehumidifier with BV 412 and the humidistat loop is disabled.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 0OpStOoOn/off; inactive turns the unit offWrite
AV 211LP-01-SSPHumidity set point for the humidistat loopWrite
BV 412DO-01-BIN-OVDehumidifier on/off from BAS (1d 01 = 6)Write
AI 102UI-02Room humidity (room models)Read
AI 106UI-06Duct humidity (duct models)Read
AV 213LP-01-PROPLoop output to the humidifierRead
BV 411DO-01-BINDehumidifier output statusRead
AI 104UI-04Dehumidifier alarm inputRead
MV 602AL-02Duct high limit or dehumidifier error alarmWrite

Enable & remote start

BV 0 (operation state) acts like the power button: inactive turns the controlled unit off, active puts it under the humidistat loop. To let the BAS switch a dehumidifier directly, change parameter 1d 01 from 1 (control loop) to 6 (manual control) and write BV 412.

Sensors & values from the BMS

Humidity comes from the internal sensor (room models) or a remote 0-10 V / 4-20 mA sensor on universal input 6 (duct models); the manual does not describe writing humidity from the BMS.

Network setup

Watch out for

DriSteem TRI2 BACnet humidistat BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

39 of 39 shown
Type
BinaryMulti-state
Access
Show
DriSteem TRI2 BACnet humidistat BACnet Points List
DescriptionStates
AV0#CtrLpNumber of control loopsRead
AV2#ulnNumber of universal inputsRead
AV4#BinOutNumber of binary outputs (not used by humidifiers)Read
AV5#aOutNumber of analog outputs (not used by dehumidifiers)Read
AV8#AlarmNumber of alarmsRead
BVmin0OpStOoOperation state on/offWriteInactive, Active
BV4AccSpEnable access to set pointsWrite
MV2DegreeDisplay unitsWrite1=Celsius, 2=Fahrenheit
MV3OpStOPMSMaster/slave modeWriteMaster, Slave
MV4OpStWinkWink functionWriteWinkON, WinkOFF
AI101UI-01Universal input 1, temperatureRead
AV101UI-01-OSUniversal input 1 offset (calibration), temperatureWrite
AImin102UI-02Universal input 2, internal humidity (room models)Read
AV102UI-02-OSUniversal input 2 offset, internal humidity (room models)Write
AImin104UI-04Universal input 4 (dehumidifier alarm input)Read
AV104UI-04-OSUniversal input 4 offsetWrite
AI105UI-05Universal input 5 (not used for dehumidifiers)Read
AV105UI-05-OSUniversal input 5 offset (not used for dehumidifiers)Write
AImin106UI-06Universal input 6, remote humidity (duct models)Read
AV106UI-06-OSUniversal input 6 offset, remote humidity (duct models)Write
MV601AL-01Alarm 1: humidity out of range (duct models)WriteNot Active, Active, Need confirmation
MVmin602AL-02Alarm 2: duct high limit or dehumidifier errorsWriteNot Active, Active, Need confirmation
MV603AL-03Alarm 3: air flow or temperature switch (humidifiers)WriteNot Active, Active, Need confirmation
MV604AL-04Alarm 4WriteNot Active, Active, Need confirmation
MV605AL-05Alarm 5WriteNot Active, Active, Need confirmation
MV606AL-06Alarm 6WriteNot Active, Active, Need confirmation
MV607AL-07Alarm 7WriteNot Active, Active, Need confirmation
MV608AL-08Alarm 8WriteNot Active, Active, Need confirmation
AVmin211LP-01-SSPControl loop 1 saved set pointWrite
AVmin213LP-01-PROPControl loop 1 proportional outputRead
MV212LP-01-DOControl loop 1 binary output stageReadStage OFF, Stage 1, Stage 2, ...
MV311AO-01-STAnalog output 1 state (humidifiers only)Read
AV311AO-01-VALAnalog output 1 value (humidifiers only)Read
AV312AO-01-OVAnalog output 1 override value (humidifiers only)Write
BVmin411DO-01-BINDigital output 1 state (dehumidifiers only)Read
BVmin412DO-01-BIN-OVDigital output 1 override value (BAS control)Write
AV511DO-01-RTDigital output 1 run time totalizerRead
BV511DO-01-ALADigital output 1 run time limit exceededRead
MV411DO-01-STDigital output 1 stateReadNORMAL, OVERRIDE
Object ID lookup: DriSteem TRI2 BACnet humidistat point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TRI2 BACnet humidistat and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the DriSteem TRI2 BACnet humidistat

How many BACnet points does the DriSteem TRI2 BACnet humidistat have?

This list has 39 BACnet objects: 5 analog inputs, 15 analog values, 5 binary values, 14 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which DriSteem TRI2 BACnet humidistat BACnet points are writable?

21 of the 39 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official DriSteem TRI2 BACnet humidistat BACnet documentation?

The source is DriSteem Humidistats Model TCI-W11-U-H, TCI-W11-U, Model TRI2 with BACnet Humidistat - Installation, Operation, and Maintenance Manual (TCI-IOM-EN-REVF-0125), revision 2025-01, published free by DriSteem at https://d2tsmyh31fn7w8.cloudfront.net/public-documents/docs/iom/humidistat/TCI-IOM-EN.pdf.

What are the minimum BACnet points to integrate the DriSteem TRI2 BACnet humidistat?

Start with BV 0 OpStOo (On/off; inactive turns the unit off); AV 211 LP-01-SSP (Humidity set point for the humidistat loop); BV 412 DO-01-BIN-OV (Dehumidifier on/off from BAS (1d 01 = 6)); AI 102 UI-02 (Room humidity (room models)); AI 106 UI-06 (Duct humidity (duct models)); AV 213 LP-01-PROP (Loop output to the humidifier); BV 411 DO-01-BIN (Dehumidifier output status); AI 104 UI-04 (Dehumidifier alarm input); MV 602 AL-02 (Duct high limit or dehumidifier error alarm).

How do I enable BMS control of the DriSteem TRI2 BACnet humidistat?

BV 0 (operation state) acts like the power button: inactive turns the controlled unit off, active puts it under the humidistat loop. To let the BAS switch a dehumidifier directly, change parameter 1d 01 from 1 (control loop) to 6 (manual control) and write BV 412.

Can the BMS supply sensor values to the DriSteem TRI2 BACnet humidistat?

Humidity comes from the internal sensor (room models) or a remote 0-10 V / 4-20 mA sensor on universal input 6 (duct models); the manual does not describe writing humidity from the BMS.

How do I check these points on the real TRI2 BACnet humidistat?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More DriSteem BACnet points lists

Source: DriSteem Humidistats Model TCI-W11-U-H, TCI-W11-U, Model TRI2 with BACnet Humidistat - Installation, Operation, and Maintenance Manual · TCI-IOM-EN-REVF-0125 · rev. 2025-01. Object names, instances and units are reproduced as published; descriptions are our own.