Humidifier controller · BACnet points list

DriSteem Vapor-logic 6 BACnet points list

Updated 28 October 2026

Short answer

Vapor-logic 6 is the DriSteem humidifier control board. Modbus is standard; BACnet MS/TP (terminal P7) or BACnet/IP (Ethernet) is an option enabled with an unlock code matched to the serial number. One shared object table covers all humidifier types, so many objects only apply to a specific product (marked GTS, XT, HPS, LMH, WM, XV or STS in the name).

This page lists 136 BACnet objects for the DriSteem Vapor-logic 6 — 85 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from DriSteem’s own free documentation, linked below.

Manufacturer
DriSteem
Model
Vapor-logic 6
Equipment
Humidifier controller
Equipment type
Humidifiers
BACnet objects
136 (85 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
255
Also known as
Vapor-logic, Vapor-logic version 6, VL6, Vaporlogic, DriSteem humidifier controller
Source document
Vapor-logic Version 6 Installation, Operation, and Maintenance Manual (Table 75-1 Interoperability variable and object names) · VL6-IOM-EN-REVH-0225 · rev. 2025-02 (Rev H)
Download CSV 136 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: DriSteem Vapor-logic 6

Integration in brief

Unlock and enable BACnet on the keypad, set the device instance and MS/TP station or IP settings, and set 'BACnet controlled' to Yes under Control via BACnet if the BMS will send the demand. Then write the demand to AV 9 (percent) or AV 8 (mass), or let the controller run its own PID on SpaceRHSetPoint (AV 5), and use MSV 1 RunMode for auto/standby/drain.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1RunModeRun mode: auto, local/system standby, manual drainWrite
AV 9FieldbusDemandPcntDemand from the BMS in % of capacityWrite
AV 5SpaceRHSetPointSpace RH setpoint when Vapor-logic does the controlWrite
BV 4ClearAllActiveAlarmsWrite 1 to clear all active faultsWrite
AI 1SpaceRHSpace RH measured by the humidifierRead
AV 2SteamOutputPercentEstimated steam output %Read
AI 5SteamDemandPercentDemand the unit is acting on, % of capacityRead
BV 60MainEnableOpenMain enable input open (demand ignored)Write
BV 3ActiveManualClearAlarmsExistA manual-clear alarm existsRead

Enable & remote start

The humidifier must have its Main Enable input (P20) closed or jumpered (J402 shunt), otherwise the demand is ignored (message BV 60). RunMode (MSV 1) switches between Auto, Local standby, System standby and Manual drain; to let BACnet supply the demand, set Setup > Control via BACnet > BACnet controlled = Yes (default No).

Sensors & values from the BMS

No BMS-writable sensor values are listed: space RH, dew point and duct RH are read-only AIs from the controller's own transmitters. The BMS can instead send a demand (AV 8 FieldbusDemandMass or AV 9 FieldbusDemandPcnt, write-only) and setpoints (AV 5 space RH, AV 6 dew point, AV 7 duct high limit).

Network setup

Watch out for

DriSteem Vapor-logic 6 BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

136 of 136 shown
Type
Multi-state
Access
Show
DriSteem Vapor-logic 6 BACnet Points List
DescriptionStates
AImin1SpaceRHRelative humidity content of the air in the space being humidified%Read
AI2SpaceDewPointDew point of the air in the space being humidified°F or °CRead
AI3DuctRHRelative humidity content of air in the duct%Read
AI4SteamDemandMassSteam demand in pounds or kilograms per hourlbs/hr or kg/hRead
AImin5SteamDemandPercentSteam demand as a percentage of the humidifier’s total capacity%Read
AI6AuxTempTemperature of auxiliary temperature sensor°F or °CRead
AI7TankTemperature / WaterTemperature (HPS)Temperature of the water in the humidifier’s evaporating chamber°F or °CRead
AV1SteamOutputMassEstimated amount of steam the humidifier is producing in pounds or kilograms...lbs/hr or kg/hRead
AVmin2SteamOutputPercentEstimated amount of steam the humidifier is producing as a percentage of...%Read
AV3WaterUntilADSPounds or kilograms of water remaining to be converted to steam before...lbs or kgWrite
AV4WaterUntilServicePounds or kilograms of water remaining to be converted to steam before...lbs or kgWrite
AI8MTSteamDemandMassMT steam demand masslbs/hr or kg/hRead
AI9MTSteamDemandPercentMT steam demand percent%Read
AI10XTBottle1Current (XT)XT operating currentARead
AI11XTBottle2Current (XT)XT operating current, right cylinderARead
AI12InPressure (HPS)Input (supply) pressurepsi or barRead
AI13OutPressure (HPS)Output pressurepsi or barRead
AI14CurrentTankCOC (WM)Current tank COCRead
AI15SupplyWaterConductivity (WM)Supply water conductivity in µSµSRead
AI16Stage1Temperature (WM)Stage 1 temperature°F or °CRead
AI17Stage2Temperature (WM)Stage 2 temperature°F or °CRead
AI18WM: Stage3Temperature / GTS: FlueTemperatureStage 3 temperature (WM) Temperature of the LX flue box (GTS)°F or °CRead
AI19WM: SupplyAirTemperature / GTS: DrainTemperatureSupply air temperature (WM) Temperature of the water in the drain block...°F or °CRead
AI20Stage1MediaEffectiveness (WM)Stage 1 media effectiveness%Read
AI21Stage2MediaEffectiveness (WM)Stage 2 media effectiveness%Read
AI22Stage3MediaEffectiveness (WM)Stage 3 media effectiveness%Read
AI23OutputTemperature (WM)Output temperature°F or °CRead
AI24WetbulbTemperature (WM)Wetbulb temperature°F or °CRead
AI25StoragePressure (LMH)Storage pressurepsi or barRead
AI26PumpRuntimeHours (HPS, LMH)Pump runtime hourshoursRead
AI27TDS (LMH)TDSRead
AI28HPASActivePumpStationNumber (HPS)Active pump station numberRead
MVmin1RunModeMode of the unit or systemWrite1=Auto, 2=Local standby, 3=System standby, 4=Manual drain, 5=Test outputs, 6=Test run
MV2MTRunModeMT run modeWrite1=System standby, 2=System auto
AVmin5SpaceRHSetPointHumidity set point for the space being humidified%Write
AV6SpaceDewPointSetPointDew point set point for the space being humidified°F or °CWrite
AV7DuctHighLimitSetPointDuct high limit set point%Write
AV8FieldbusDemandMassSteam output (as demanded via fieldbus) in pounds or kilograms per hourlbs/hr or kg/hWrite
AVmin9FieldbusDemandPcntSteam output (as demanded via the fieldbus) as a percentage of the...%Write
AV10PIDBandPID band%Write
AV11PIDKpPID-Kp (proportional gain) factorWrite
AV12PIDKiPID-Ki (integral gain) factorWrite
AV13PIDKdPID-Kp (derivative gain) factorWrite
AV14MTSteamOutputReqMassMT fieldbus request for steam in pounds or kilograms per hourlbs/hr or kg/hWrite
AV15MTSteamOutputReqPcntMT fieldbus request for steam in percentage of system capacity%Write
AV16Pumps1RuntimeHours (HPS, LMH)Number of hours pump 1 has run since resethoursWrite
AV17Pump2RuntimeHours (HPS)Number of hours pump 2 has run since resethoursWrite
AV18TargetCOC (WM)Desired cycles at concentrationWrite
AV19HPASPumpSelected (HPS)Selected pump (HPS systems only)Write0=Pump 1, 1=Pump 2
BI1AirflowProvingSwitchRead0=Open, 1=Closed
BI2DuctHLSwitchRead0=Open, 1=Closed
BI3SafetyInterlockRead0=Open, 1=Closed
BI4GTS: CombustionAirDamper / HPS: Stage1ActiveRead0=Damper Closed, 1=Damper Open
BI5GTS: FluePressureSwitch / HPS: Stage2Active / LMH: InletPressureSwitchReadGTS/LMH: 0=Open, 1=Closed; HPS: 0=Closed, 1=Open
BI6GTS: PowerVentSwitch / HPS: Stage3Active / STS: XVHeaderEmptyOrExternalDemandReadGTS: 0=Off, 1=On; HPS: 0=Closed, 1=Open; STS: 0=Not ready, 1=Ready
BI7LowWaterSensorOrOvertempLoop (GTS)Read0=No Water, 1=Water
BI8MTActiveFaultInSystemRead0=No, 1=Yes
BI9MTActiveMessageInSystemRead0=No, 1=Yes
BI10HighWaterSensor (XT)Read0=No Water, 1=Water
BI11HighWaterSensor2 (XT)Read0=No Water, 1=Water
BI12HPASVFDDriveFault (HPS)Read0=No Fault, 1=Fault
BI13XV2PositionValveEndSwitch (XV)Read0=Open, 1=Closed
BI14XVFloatSwitch (XV)Read0=Empty, 1=Full
BV1ProgOutput1StatusNO-1Programmable dry contact 1 statusRead0=Open, 1=Closed
BV2ProgOutput2StatusNO-2Programmable dry contact 2 statusRead0=Open, 1=Closed
BVmin3ActiveManualClearAlarmsExistFlag that a manual clear alarm exists in the systemRead
BVmin4ClearAllActiveAlarmsWhen set will clear all active faultsWrite
BV5TankTempSensorFailed / WaterTempSensorFailed (HPS)Alarm flag (see Alarms menu table)Write
BV6TankOvertemp-UnitRebootRequiredAlarm flag (see Alarms menu table)Write
BV7SignalAtRHInputOutOfRangeAlarm flag (see Alarms menu table)Write
BV8DuctRHSignalOutOfRangeAlarm flag (see Alarms menu table)Write
BV9AuxTempSenseOutOfRangeAlarm flag (see Alarms menu table)Write
BV10WaterProbeMiswiredAlarm flag (see Alarms menu table)Write
BV11FaultyWaterProbe / VFDFault (HPS)Alarm flag (see Alarms menu table)Write
BV12ExcessiveFillTimeAlarm flag (see Alarms menu table)Write
BV13ExcessiveRefillTimeAlarm flag (see Alarms menu table)Write
BV14TankNotDraining / CheckHumidifierFloats (LMH)Alarm flag (see Alarms menu table)Write
BV15ExcessiveBoilTime-UnitRebootRequiredAlarm flag (see Alarms menu table)Write
BV16NoSDUAirflowAlarm flag (see Alarms menu table)Write
BV17GTS: NoPowerVentAirflow / STS: XVHeaderFloodedAlarm flag (see Alarms menu table)Write
BV18NoCombustionAirflow (GTS)Alarm flag (see Alarms menu table)Write
BV19BlockedFlue (GTS)Alarm flag (see Alarms menu table)Write
BV20Burner1Fault (GTS)Alarm flag (see Alarms menu table)Write
BV21Burner2Fault (GTS)Alarm flag (see Alarms menu table)Write
BV22Burner3Fault (GTS)Alarm flag (see Alarms menu table)Write
BV23Burner4Fault (GTS)Alarm flag (see Alarms menu table)Write
BV24GTS: IgnitionModule1Fault / WM: Stage1EfficiencyBelow50PercentAlarm flag (see Alarms menu table)Write
BV25GTS: IgnitionModule2Fault / WM: Stage2EfficiencyBelow50PercentAlarm flag (see Alarms menu table)Write
BV26GTS: IgnitionModule3Fault / WM: Stage3EfficiencyBelow50PercentAlarm flag (see Alarms menu table)Write
BV27IgnitionModule4Fault (GTS)Alarm flag (see Alarms menu table)Write
BV28GTS: Blower1Fault / WM: TempSensorStage1FaultAlarm flag (see Alarms menu table)Write
BV29GTS: Blower2Fault / WM: TempSensorStage2FaultAlarm flag (see Alarms menu table)Write
BV30GTS: Blower3Fault / WM: TempSensorStage3FaultAlarm flag (see Alarms menu table)Write
BV31GTS: Blower4Fault / WM: TempSensorFaultAlarm flag (see Alarms menu table)Write
BV32GasValve1Fault (GTS)Alarm flag (see Alarms menu table)Write
BV33GasValve2Fault (GTS)Alarm flag (see Alarms menu table)Write
BV34GasValve3Fault (GTS)Alarm flag (see Alarms menu table)Write
BV35GasValve4Fault (GTS)Alarm flag (see Alarms menu table)Write
BV36GTS: LowWaterOrOvertemp / Electric/LMH: OvertempCutoutUnitRebootRequiredAlarm flag (see Alarms menu table)Write
BV37XT: ExcessiveFoaming2 / HPS/LMH: LowInletPressure / GTS: ReplaceIgnitorsNow!Alarm flag (see Alarms menu table)Write
BV51CurrentSensorOutOfRange (XT)Alarm flag (see Alarms menu table)Write
BV52XT: CurrentSensorOutOfRange (XT) / HPS: ROSensorOutOfRangeAlarm flag (see Alarms menu table)Write
BV53XT: Overcurrent / HPS: HighInletPressureAlarm flag (see Alarms menu table)Write
BV54XT: SupplyWaterFailure / HPS: LowInletWaterTempAlarm flag (see Alarms menu table)Write
BV55XT: ExcessiveFoaming / HPS: HighPumpPressure / GTS: FoamingFaultAlarm flag (see Alarms menu table)Write
BV57XT: Overcurrent2 / HPS: HighInletWaterTempAlarm flag (see Alarms menu table)Write
BV58XT: SupplyWater2Failure / HPS: LowPumpPressureAlarm flag (see Alarms menu table)Write
BV61LowInletPressure (LMH)Alarm flag (see Alarms menu table)Write
BV62HighOutletPressure (LMH)Alarm flag (see Alarms menu table)Write
BV63HPS: InletSensorOutOfRange / LMH: StorageSensorOutOfRange / GTS: FlueSensorOutOfRangeAlarm flag (see Alarms menu table)Write
BV64ExcessiveTDSAlarm (LMH)Alarm flag (see Alarms menu table)Write
BV66PumpStationCannonRun (HPS)HPS redundant system cannot runWrite
BV68XVCondensateClearingFailure (XV)XV has failed to clear the header of condensateWrite
BV69XV2PositionValveFailure (XV)XV 2 position valve end switch failed to close while the valve...Write
BV70HPS: PumpSensorOutOfRange / LMH: InletSensorOutOfRange / GTS: DrainSensorOutOfRangeAlarm flag (see Alarms menu table)Write
BV38GTS: ReplaceIgnitorsSoon / Electric/LMH: ReplaceContactors / WM: ReplaceUV LampMessage flag (see Diagnostics menu table)Write
BV39ServiceUnitMessage flag (see Diagnostics menu table)Write
BV40DrainPendingMessage flag (see Diagnostics menu table)Write
BV41NoAirflowMessage flag (see Diagnostics menu table)Write
BV42InterlockOpenMessage flag (see Diagnostics menu table)Write
BV43FreezeDrainMessage flag (see Diagnostics menu table)Write
BV44EndOfSeasonDrainActiveMessage flag (see Diagnostics menu table)Write
BV45TempCompOnMessage flag (see Diagnostics menu table)Write
BV46CleanProbesMessage flag (see Diagnostics menu table)Write
BV47DuctHLTripMessage flag (see Diagnostics menu table)Write
BV48DuctHLSpanMessage flag (see Diagnostics menu table)Write
BV49InsufficientWaterFlowMessage flag (see Diagnostics menu table)Write
BV50BoilingTempCalibratedMessage flag (see Diagnostics menu table)Write
BV56XT: CheckCylinderEndOfLife / HPS: LowInletWaterTempMessageMessage flag (see Diagnostics menu table)Write
BV59CheckCylinder2EndOfLife (XT)Message flag (see Diagnostics menu table)Write
BVmin60MainEnableOpenMessage flag (see Diagnostics menu table)Write
BV65ExcessiveTDSDuringFill (LMH)Message flag (see Diagnostics menu table)Write
BV67XVClearingCondensate (XV)XV is attempting to clear condensate out of the headerRead
BV101FillValveRead0=Closed, 1=Open
BV102DrainValveRead0=Not Draining, 1=Draining
BV103XV: 2 position shutoff valveRead0=Valve not powered, 1=Valve powered

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Vapor-logic 6 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the DriSteem Vapor-logic 6

How many BACnet points does the DriSteem Vapor-logic 6 have?

This list has 136 BACnet objects: 28 analog inputs, 19 analog values, 14 binary inputs, 73 binary values, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which DriSteem Vapor-logic 6 BACnet points are writable?

85 of the 136 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official DriSteem Vapor-logic 6 BACnet documentation?

The source is Vapor-logic Version 6 Installation, Operation, and Maintenance Manual (Table 75-1 Interoperability variable and object names) (VL6-IOM-EN-REVH-0225), revision 2025-02 (Rev H), published free by DriSteem at https://d2tsmyh31fn7w8.cloudfront.net/public-documents/docs/iom/vapor-logic/VL6-IOM-EN.pdf.

What are the minimum BACnet points to integrate the DriSteem Vapor-logic 6?

Start with MV 1 RunMode (Run mode: auto, local/system standby, manual drain); AV 9 FieldbusDemandPcnt (Demand from the BMS in % of capacity); AV 5 SpaceRHSetPoint (Space RH setpoint when Vapor-logic does the control); BV 4 ClearAllActiveAlarms (Write 1 to clear all active faults); AI 1 SpaceRH (Space RH measured by the humidifier); AV 2 SteamOutputPercent (Estimated steam output %); AI 5 SteamDemandPercent (Demand the unit is acting on, % of capacity); BV 60 MainEnableOpen (Main enable input open (demand ignored)); BV 3 ActiveManualClearAlarmsExist (A manual-clear alarm exists).

How do I enable BMS control of the DriSteem Vapor-logic 6?

The humidifier must have its Main Enable input (P20) closed or jumpered (J402 shunt), otherwise the demand is ignored (message BV 60). RunMode (MSV 1) switches between Auto, Local standby, System standby and Manual drain; to let BACnet supply the demand, set Setup > Control via BACnet > BACnet controlled = Yes (default No).

Can the BMS supply sensor values to the DriSteem Vapor-logic 6?

No BMS-writable sensor values are listed: space RH, dew point and duct RH are read-only AIs from the controller's own transmitters. The BMS can instead send a demand (AV 8 FieldbusDemandMass or AV 9 FieldbusDemandPcnt, write-only) and setpoints (AV 5 space RH, AV 6 dew point, AV 7 duct high limit).

How do I check these points on the real Vapor-logic 6?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: Vapor-logic Version 6 Installation, Operation, and Maintenance Manual (Table 75-1 Interoperability variable and object names) · VL6-IOM-EN-REVH-0225 · rev. 2025-02 (Rev H). Object names, instances and units are reproduced as published; descriptions are our own.