Resistive steam humidifier · BACnet points list

Devatec ElectroVap ERS / RTH resistive steam humidifier (V3 controller) BACnet points list

Updated 12 November 2026

Short answer

The ElectroVap ERS and RTH ranges are resistive-element steam humidifiers built around the same V3 main board (an Armstrong motherboard), which speaks Modbus RTU or BACnet MS/TP on RS485. The BACnet map exposes valve, contactor, relay and A1-A10 alarm states as Binary Inputs, a start/stop Binary Output, run data and counters as Analog Inputs, and setpoints, control signal type and PID settings as Analog Values.

This page lists 66 BACnet objects for the Devatec ElectroVap ERS / RTH resistive steam humidifier (V3 controller) — 15 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Devatec’s own free documentation, linked below.

Manufacturer
Devatec
Model
ElectroVap ERS / RTH resistive steam humidifier (V3 controller)
Equipment
Resistive steam humidifier
Equipment type
Humidifiers
BACnet objects
66 (15 writable)
Transport
BACnet MS/TP
Firmware
Application software 1, firmware 1 (PICS)
Default device instance
0x02000000 + vendor ID x 1000 + MS/TP address (settable in the menu)
Also known as
ERS, ERS-HC, ERS-LC, RTH-HC, RTH-LC, ElectroVap ERS, ElectroVap RTH, Devatec ERS, Devatec RTH, Armstrong Motherboard
Source document
ElectroVap ERS Series Instruction & Operation Manual · DT_ERS-V3_EN REV B.3
Download CSV 66 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Devatec’s current documentation and the live device before use. Not official Devatec information. Terms of use.

BMS integration notes: Devatec ElectroVap ERS / RTH resistive steam humidifier (V3 controller)

Integration in brief

Wire RS485 to J2, choose BACnet MS/TP and an address in the controller menu, then start/stop the humidifier with BO 0 and send demand or RH through AV 3 (or use the unit's own setpoint AV 4). Watch run status, steam output and the alarm relay.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 0On/Off BMS commandStart/stop (1 = start requested)Write
AV 3Digital Rh value or digital demandDemand or RH from the BMS, 1-100 %Write
AV 4Rh set pointHumidity setpoint, %RHWrite
AI 4Run statusRun status codeRead
AI 3Steam outputSteam output, 10 x kg/hRead
AI 2DemandCurrent demand, %Read
BI 6Alarm relayAlarm relay onRead
BI 19Rh sensor errorHumidity sensor faultRead

Enable & remote start

BO 0 On/Off BMS command starts (1) or stops (0) the unit.

Sensors & values from the BMS

AV 3 takes a digital RH value or digital demand (1-100 %) from the BMS; AV 9 sets whether the control signal is a digital command, a digital sensor or an analog input.

Network setup

Watch out for

Devatec ElectroVap ERS / RTH resistive steam humidifier (V3 controller) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

66 of 66 shown
Type
Access
Show
Devatec ElectroVap ERS / RTH resistive steam humidifier (V3 controller) BACnet Points List
DescriptionStates
BI0inlet valveFill valveRead0=No filling, 1=Filling
BI1drain valveDrain valveRead0=No drain, 1=Drain
BI2contactor K1Heater contactor K1Read0=Off, 1=On
BI3contactor K3Heater contactor K3Read0=Off, 1=On
BI4Blower packBlower pack outputRead0=Off, 1=On
BI5Service relayService relayRead0=Off, 1=On
BImin6Alarm relayAlarm relayRead0=Off, 1=On
BI7On/off RelayOn/off relayRead0=Off, 1=On
BI8High limite swHigh limit switchRead0=Not detected, 1=Detected
BI9Alarm A1 stateAlarm A1 activeRead0=Off, 1=On
BI10Alarm A2 stateAlarm A2 activeRead0=Off, 1=On
BI11Alarm A3 stateAlarm A3 activeRead0=Off, 1=On
BI12Alarm A4 stateAlarm A4 activeRead0=Off, 1=On
BI13Alarm A5 stateAlarm A5 activeRead0=Off, 1=On
BI14Alarm A6 stateAlarm A6 activeRead0=Off, 1=On
BI15Alarm A7 stateAlarm A7 activeRead0=Off, 1=On
BI16Alarm A8 stateAlarm A8 activeRead0=Off, 1=On
BI17Alarm A9 stateAlarm A9 activeRead0=Off, 1=On
BI18Alarm A10 stateAlarm A10 activeRead0=Off, 1=On
BImin19Rh sensor errorHumidity sensor faultRead0=Off, 1=On
BOmin0On/Off BMS commandStart/stop from the BMSWrite0=Off (device off), 1=On (start required)
BV1EOS drain statueEnd-of-season drainWrite0=Off, 1=On
AI0Type unitUnit type codeRead4=ERS, 5=RTH-LC, 6=ERS-HC, 7=ERS LC
AI1Reg versionRegister map versionRead
AImin2DemandCurrent demand%Read
AImin3Steam outputSteam output, value = 10 x kg/hkg/hRead
AImin4Run statusOperating statusRead1=Idle, 2=Preheat cycle, 3=Steam production, 4=Manual drain, 5=Ready for use, 6=Maintenance due, 7=Fault, 8=Aquastat on
AI5Estimated time to serviceHours to next servicehRead
AI6Production since last service (MSB)Steam since last service, high wordkgRead
AI7Production since last service (LSB)Steam since last service, low wordkgRead
AI8Total production (MSB)Total steam, high wordkgRead
AI9Total production (LSB)Total steam, low wordkgRead
AI10Total run time (MSB)Total run time, high wordhRead
AI11Total run time (LSB)Total run time, low wordhRead
AI12Remaining idle time to EOS drainIdle hours left before end-of-season drainhRead
AI13Control signal valueControl signal, 10 x V or 10 x mA or %Read
AI14Temperature tank 1Tank 1 water temperature°CRead
AI15Temperature tank 2Tank 2 water temperature°CRead
AI16Alarm A2 counterA2 alarm countRead
AI17Alarm A3 counterA3 alarm countRead
AI18Alarm A6 counterA6 alarm countRead
AI19Alarm A7 counterA7 alarm countRead
AI20Alarm A8 counterA8 alarm countRead
AI21Partial drain timerPartial drain timer, 10 x ssRead
AI22PWM main supplyPWM trigger valueRead
AI23PWM counterPWM counterRead
AI25Max production capabilityMaximum steam capacityRead
AI26Number of tankNumber of tanks, 1 or 2Read
AI27Unit type IDUnit type codeRead
AI28Unit voltage typeUnit voltage codeRead
AI29Water level statusWater level detected, 0-3Read
AI30Power consumedPower consumedkWRead
AI31Max power ratingMaximum power ratingkWRead
AVmin3Digital Rh value or digital demandRH or demand from the BMS, 1-100 %%Write
AVmin4Rh set pointHumidity setpoint, 1-100 %%RHWrite
AV5EOS drain timerEnd-of-season drain delay, 1-120 hhWrite
AV6Service counterService interval, kg/100, 1-65000Write
AV7Aquastat statusTank keep-warm aquastatWrite1=Activate, 2=Deactivate
AV8Aquastat setpointAquastat setpoint, 10-80 °C°CWrite
AV9Control signal typeControl signal typeWrite20=OnOff, 21=digital ctrl, 22=control digital, 23=0-10V ctrl, 24=1-5V ctrl, 25=4-20mA ctrl, 26=0-10V sensor, 27=0-5V sensor
AV11Control signal adjustmentControl signal trim, raw minus 128 = %, 123-133Write
AV13Temperature 1 adjustmentTank 1 temperature trim, raw minus 128, 123-135Write
AV14Temperature 2 adjustmentTank 2 temperature trim, raw minus 128, 123-136Write
AV15Proportional factor of PIDPID P factor, 0-50, typ. 20Write
AV16Integral factor PIDPID I factor, 0-50Write
AV17Derivative factor PIDPID D factor, 0-50Write
Object ID lookup: Devatec ElectroVap ERS / RTH resistive steam humidifier point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ElectroVap ERS / RTH resistive steam humidifier (V3 controller) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Devatec ElectroVap ERS / RTH resistive steam humidifier (V3 controller)

How many BACnet points does the Devatec ElectroVap ERS / RTH resistive steam humidifier (V3 controller) have?

This list has 66 BACnet objects: 31 analog inputs, 13 analog values, 20 binary inputs, 1 binary output, 1 binary value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Devatec ElectroVap ERS / RTH resistive steam humidifier (V3 controller) BACnet points are writable?

15 of the 66 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Devatec ElectroVap ERS / RTH resistive steam humidifier (V3 controller) BACnet documentation?

The source is ElectroVap ERS Series Instruction & Operation Manual (DT_ERS-V3_EN REV B.3), published free by Devatec at https://www.devatec.com/wp-content/uploads/2024/12/DT_ERS-V3_EN_REV-B.3_L-2.pdf.

What are the minimum BACnet points to integrate the Devatec ElectroVap ERS / RTH resistive steam humidifier (V3 controller)?

Start with BO 0 On/Off BMS command (Start/stop (1 = start requested)); AV 3 Digital Rh value or digital demand (Demand or RH from the BMS, 1-100 %); AV 4 Rh set point (Humidity setpoint, %RH); AI 4 Run status (Run status code); AI 3 Steam output (Steam output, 10 x kg/h); AI 2 Demand (Current demand, %); BI 6 Alarm relay (Alarm relay on); BI 19 Rh sensor error (Humidity sensor fault).

How do I enable BMS control of the Devatec ElectroVap ERS / RTH resistive steam humidifier (V3 controller)?

BO 0 On/Off BMS command starts (1) or stops (0) the unit.

Can the BMS supply sensor values to the Devatec ElectroVap ERS / RTH resistive steam humidifier (V3 controller)?

AV 3 takes a digital RH value or digital demand (1-100 %) from the BMS; AV 9 sets whether the control signal is a digital command, a digital sensor or an analog input.

How do I check these points on the real ElectroVap ERS / RTH resistive steam humidifier (V3 controller)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Devatec BACnet points lists

Source: ElectroVap ERS Series Instruction & Operation Manual · DT_ERS-V3_EN REV B.3. Object names, instances and units are reproduced as published; descriptions are our own.