- Home
- BACnet points lists
- Devatec
- ElectroVap ERS / RTH resistive steam humidifier (V3 controller)
Resistive steam humidifier · BACnet points list
Devatec ElectroVap ERS / RTH resistive steam humidifier (V3 controller) BACnet points list
Updated 12 November 2026
The ElectroVap ERS and RTH ranges are resistive-element steam humidifiers built around the same V3 main board (an Armstrong motherboard), which speaks Modbus RTU or BACnet MS/TP on RS485. The BACnet map exposes valve, contactor, relay and A1-A10 alarm states as Binary Inputs, a start/stop Binary Output, run data and counters as Analog Inputs, and setpoints, control signal type and PID settings as Analog Values.
This page lists 66 BACnet objects for the Devatec ElectroVap ERS / RTH resistive steam humidifier (V3 controller) — 15 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Devatec’s own free documentation, linked below.
- Manufacturer
- Devatec
- Model
- ElectroVap ERS / RTH resistive steam humidifier (V3 controller)
- Equipment
- Resistive steam humidifier
- Equipment type
- Humidifiers
- BACnet objects
- 66 (15 writable)
- Transport
- BACnet MS/TP
- Firmware
- Application software 1, firmware 1 (PICS)
- Default device instance
- 0x02000000 + vendor ID x 1000 + MS/TP address (settable in the menu)
- Also known as
- ERS, ERS-HC, ERS-LC, RTH-HC, RTH-LC, ElectroVap ERS, ElectroVap RTH, Devatec ERS, Devatec RTH, Armstrong Motherboard
Reference only, provided as-is: verify against Devatec’s current documentation and the live device before use. Not official Devatec information. Terms of use.
BMS integration notes: Devatec ElectroVap ERS / RTH resistive steam humidifier (V3 controller)
Wire RS485 to J2, choose BACnet MS/TP and an address in the controller menu, then start/stop the humidifier with BO 0 and send demand or RH through AV 3 (or use the unit's own setpoint AV 4). Watch run status, steam output and the alarm relay.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 0 | On/Off BMS command | Start/stop (1 = start requested) | Write |
| AV 3 | Digital Rh value or digital demand | Demand or RH from the BMS, 1-100 % | Write |
| AV 4 | Rh set point | Humidity setpoint, %RH | Write |
| AI 4 | Run status | Run status code | Read |
| AI 3 | Steam output | Steam output, 10 x kg/h | Read |
| AI 2 | Demand | Current demand, % | Read |
| BI 6 | Alarm relay | Alarm relay on | Read |
| BI 19 | Rh sensor error | Humidity sensor fault | Read |
Enable & remote start
BO 0 On/Off BMS command starts (1) or stops (0) the unit.
Sensors & values from the BMS
AV 3 takes a digital RH value or digital demand (1-100 %) from the BMS; AV 9 sets whether the control signal is a digital command, a digital sensor or an analog input.
Network setup
- RS485 on connector J2 (1 Data-, 2 Data+, 3 GND); SW1 switches the line termination and bias resistors.
- Baud 2400 to 230400 (9600 default), 8 data bits, no parity; BACnet MS/TP uses 1 stop bit.
- Device instance defaults to 0x02000000 + vendor ID x 1000 + station address and can be set in the menu.
Watch out for
- The adjustment and PID AVs are tuning values; leave them at factory settings unless told otherwise.
- Totals are split into two 16-bit words (MSB/LSB); combine them in the BMS.
- Tank 2 points only apply to two-tank units (AI 26).
Devatec ElectroVap ERS / RTH resistive steam humidifier (V3 controller) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BI | 0 | inlet valve | Fill valve | Read | 0=No filling, 1=Filling | |
| BI | 1 | drain valve | Drain valve | Read | 0=No drain, 1=Drain | |
| BI | 2 | contactor K1 | Heater contactor K1 | Read | 0=Off, 1=On | |
| BI | 3 | contactor K3 | Heater contactor K3 | Read | 0=Off, 1=On | |
| BI | 4 | Blower pack | Blower pack output | Read | 0=Off, 1=On | |
| BI | 5 | Service relay | Service relay | Read | 0=Off, 1=On | |
| BImin | 6 | Alarm relay | Alarm relay | Read | 0=Off, 1=On | |
| BI | 7 | On/off Relay | On/off relay | Read | 0=Off, 1=On | |
| BI | 8 | High limite sw | High limit switch | Read | 0=Not detected, 1=Detected | |
| BI | 9 | Alarm A1 state | Alarm A1 active | Read | 0=Off, 1=On | |
| BI | 10 | Alarm A2 state | Alarm A2 active | Read | 0=Off, 1=On | |
| BI | 11 | Alarm A3 state | Alarm A3 active | Read | 0=Off, 1=On | |
| BI | 12 | Alarm A4 state | Alarm A4 active | Read | 0=Off, 1=On | |
| BI | 13 | Alarm A5 state | Alarm A5 active | Read | 0=Off, 1=On | |
| BI | 14 | Alarm A6 state | Alarm A6 active | Read | 0=Off, 1=On | |
| BI | 15 | Alarm A7 state | Alarm A7 active | Read | 0=Off, 1=On | |
| BI | 16 | Alarm A8 state | Alarm A8 active | Read | 0=Off, 1=On | |
| BI | 17 | Alarm A9 state | Alarm A9 active | Read | 0=Off, 1=On | |
| BI | 18 | Alarm A10 state | Alarm A10 active | Read | 0=Off, 1=On | |
| BImin | 19 | Rh sensor error | Humidity sensor fault | Read | 0=Off, 1=On | |
| BOmin | 0 | On/Off BMS command | Start/stop from the BMS | Write | 0=Off (device off), 1=On (start required) | |
| BV | 1 | EOS drain statue | End-of-season drain | Write | 0=Off, 1=On | |
| AI | 0 | Type unit | Unit type code | Read | 4=ERS, 5=RTH-LC, 6=ERS-HC, 7=ERS LC | |
| AI | 1 | Reg version | Register map version | Read | ||
| AImin | 2 | Demand | Current demand | % | Read | |
| AImin | 3 | Steam output | Steam output, value = 10 x kg/h | kg/h | Read | |
| AImin | 4 | Run status | Operating status | Read | 1=Idle, 2=Preheat cycle, 3=Steam production, 4=Manual drain, 5=Ready for use, 6=Maintenance due, 7=Fault, 8=Aquastat on | |
| AI | 5 | Estimated time to service | Hours to next service | h | Read | |
| AI | 6 | Production since last service (MSB) | Steam since last service, high word | kg | Read | |
| AI | 7 | Production since last service (LSB) | Steam since last service, low word | kg | Read | |
| AI | 8 | Total production (MSB) | Total steam, high word | kg | Read | |
| AI | 9 | Total production (LSB) | Total steam, low word | kg | Read | |
| AI | 10 | Total run time (MSB) | Total run time, high word | h | Read | |
| AI | 11 | Total run time (LSB) | Total run time, low word | h | Read | |
| AI | 12 | Remaining idle time to EOS drain | Idle hours left before end-of-season drain | h | Read | |
| AI | 13 | Control signal value | Control signal, 10 x V or 10 x mA or % | Read | ||
| AI | 14 | Temperature tank 1 | Tank 1 water temperature | °C | Read | |
| AI | 15 | Temperature tank 2 | Tank 2 water temperature | °C | Read | |
| AI | 16 | Alarm A2 counter | A2 alarm count | Read | ||
| AI | 17 | Alarm A3 counter | A3 alarm count | Read | ||
| AI | 18 | Alarm A6 counter | A6 alarm count | Read | ||
| AI | 19 | Alarm A7 counter | A7 alarm count | Read | ||
| AI | 20 | Alarm A8 counter | A8 alarm count | Read | ||
| AI | 21 | Partial drain timer | Partial drain timer, 10 x s | s | Read | |
| AI | 22 | PWM main supply | PWM trigger value | Read | ||
| AI | 23 | PWM counter | PWM counter | Read | ||
| AI | 25 | Max production capability | Maximum steam capacity | Read | ||
| AI | 26 | Number of tank | Number of tanks, 1 or 2 | Read | ||
| AI | 27 | Unit type ID | Unit type code | Read | ||
| AI | 28 | Unit voltage type | Unit voltage code | Read | ||
| AI | 29 | Water level status | Water level detected, 0-3 | Read | ||
| AI | 30 | Power consumed | Power consumed | kW | Read | |
| AI | 31 | Max power rating | Maximum power rating | kW | Read | |
| AVmin | 3 | Digital Rh value or digital demand | RH or demand from the BMS, 1-100 % | % | Write | |
| AVmin | 4 | Rh set point | Humidity setpoint, 1-100 % | %RH | Write | |
| AV | 5 | EOS drain timer | End-of-season drain delay, 1-120 h | h | Write | |
| AV | 6 | Service counter | Service interval, kg/100, 1-65000 | Write | ||
| AV | 7 | Aquastat status | Tank keep-warm aquastat | Write | 1=Activate, 2=Deactivate | |
| AV | 8 | Aquastat setpoint | Aquastat setpoint, 10-80 °C | °C | Write | |
| AV | 9 | Control signal type | Control signal type | Write | 20=OnOff, 21=digital ctrl, 22=control digital, 23=0-10V ctrl, 24=1-5V ctrl, 25=4-20mA ctrl, 26=0-10V sensor, 27=0-5V sensor | |
| AV | 11 | Control signal adjustment | Control signal trim, raw minus 128 = %, 123-133 | Write | ||
| AV | 13 | Temperature 1 adjustment | Tank 1 temperature trim, raw minus 128, 123-135 | Write | ||
| AV | 14 | Temperature 2 adjustment | Tank 2 temperature trim, raw minus 128, 123-136 | Write | ||
| AV | 15 | Proportional factor of PID | PID P factor, 0-50, typ. 20 | Write | ||
| AV | 16 | Integral factor PID | PID I factor, 0-50 | Write | ||
| AV | 17 | Derivative factor PID | PID D factor, 0-50 | Write |
No points match these filters.
Object ID lookup: Devatec ElectroVap ERS / RTH resistive steam humidifier point IDs by name
BI0inlet valveBI1drain valveBI2contactor K1BI3contactor K3BI4Blower packBI5Service relayBI6Alarm relayBI7On/off RelayBI8High limite swBI9Alarm A1 stateBI10Alarm A2 stateBI11Alarm A3 stateBI12Alarm A4 stateBI13Alarm A5 stateBI14Alarm A6 stateBI15Alarm A7 stateBI16Alarm A8 stateBI17Alarm A9 stateBI18Alarm A10 stateBI19Rh sensor errorBO0On/Off BMS commandBV1EOS drain statueAI0Type unitAI1Reg versionAI2DemandAI3Steam outputAI4Run statusAI5Estimated time to serviceAI6Production since last service (MSB)AI7Production since last service (LSB)AI8Total production (MSB)AI9Total production (LSB)AI10Total run time (MSB)AI11Total run time (LSB)AI12Remaining idle time to EOS drainAI13Control signal valueAI14Temperature tank 1AI15Temperature tank 2AI16Alarm A2 counterAI17Alarm A3 counterAI18Alarm A6 counterAI19Alarm A7 counterAI20Alarm A8 counterAI21Partial drain timerAI22PWM main supplyAI23PWM counterAI25Max production capabilityAI26Number of tankAI27Unit type IDAI28Unit voltage typeAI29Water level statusAI30Power consumedAI31Max power ratingAV3Digital Rh value or digital demandAV4Rh set pointAV5EOS drain timerAV6Service counterAV7Aquastat statusAV8Aquastat setpointAV9Control signal typeAV11Control signal adjustmentAV13Temperature 1 adjustmentAV14Temperature 2 adjustmentAV15Proportional factor of PIDAV16Integral factor PIDAV17Derivative factor PID
Integration notes
- The manual's table has no read/write column; access is inferred from the Modbus register area (coils and holding registers writable).
- The table gives each object's class, instance, hex ID and a description; the description is used as the object name.
- AV 3 is printed with class "A0" and ID 00000003; its Modbus holding register (40004) and place in the AV block point to Analog Value 3. Check with a scan.
- Several values are scaled: steam output and partial drain timer are 10x, totals are split into MSB/LSB words, and the adjustment AVs are raw minus 128 = %.
- The ERS-LC, RTH-HC and RTH-LC manuals (rev B.2) print the same objects and IDs with older wording (Fill valve, Contactor 1, Contactor 2, Onoff Relay); this list follows the newer ERS rev B.3.
- AI 24 is not printed.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ElectroVap ERS / RTH resistive steam humidifier (V3 controller) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Devatec ElectroVap ERS / RTH resistive steam humidifier (V3 controller)
How many BACnet points does the Devatec ElectroVap ERS / RTH resistive steam humidifier (V3 controller) have?
This list has 66 BACnet objects: 31 analog inputs, 13 analog values, 20 binary inputs, 1 binary output, 1 binary value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Devatec ElectroVap ERS / RTH resistive steam humidifier (V3 controller) BACnet points are writable?
15 of the 66 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Devatec ElectroVap ERS / RTH resistive steam humidifier (V3 controller) BACnet documentation?
The source is ElectroVap ERS Series Instruction & Operation Manual (DT_ERS-V3_EN REV B.3), published free by Devatec at https://www.devatec.com/wp-content/uploads/2024/12/DT_ERS-V3_EN_REV-B.3_L-2.pdf.
What are the minimum BACnet points to integrate the Devatec ElectroVap ERS / RTH resistive steam humidifier (V3 controller)?
Start with BO 0 On/Off BMS command (Start/stop (1 = start requested)); AV 3 Digital Rh value or digital demand (Demand or RH from the BMS, 1-100 %); AV 4 Rh set point (Humidity setpoint, %RH); AI 4 Run status (Run status code); AI 3 Steam output (Steam output, 10 x kg/h); AI 2 Demand (Current demand, %); BI 6 Alarm relay (Alarm relay on); BI 19 Rh sensor error (Humidity sensor fault).
How do I enable BMS control of the Devatec ElectroVap ERS / RTH resistive steam humidifier (V3 controller)?
BO 0 On/Off BMS command starts (1) or stops (0) the unit.
Can the BMS supply sensor values to the Devatec ElectroVap ERS / RTH resistive steam humidifier (V3 controller)?
AV 3 takes a digital RH value or digital demand (1-100 %) from the BMS; AV 9 sets whether the control signal is a digital command, a digital sensor or an analog input.
How do I check these points on the real ElectroVap ERS / RTH resistive steam humidifier (V3 controller)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Devatec BACnet points lists
Source: ElectroVap ERS Series Instruction & Operation Manual · DT_ERS-V3_EN REV B.3. Object names, instances and units are reproduced as published; descriptions are our own.