Electrode steam humidifier · BACnet points list

Devatec ElectroVap MC (ELMC) electrode steam humidifier (V3 controller) BACnet points list

Updated 12 November 2026

Short answer

The ElectroVap MC (ELMC) is an electrode-boiler steam humidifier whose V3 controller talks Modbus RTU or BACnet MS/TP on RS485. The BACnet map gives contactor, level, valve and relay states as Binary Inputs, a start/stop Binary Output, current, run status, error code and steam output as Analog Inputs, and setpoint, demand, capacity limit and drain settings as Analog Values.

This page lists 32 BACnet objects for the Devatec ElectroVap MC (ELMC) electrode steam humidifier (V3 controller) — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Devatec’s own free documentation, linked below.

Manufacturer
Devatec
Model
ElectroVap MC (ELMC) electrode steam humidifier (V3 controller)
Equipment
Electrode steam humidifier
Equipment type
Humidifiers
BACnet objects
32 (10 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
ELMC, ElectroVap MC, ElectroVap ELMC, EHU-750, EHU 750, KIT MC, CMC, Steam Bath SB, Devatec ELMC
Source document
ElectroVap ELMC Series Instruction & Operation Manual · DT_ELMC-V3-EN REV B.1
Download CSV 32 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Devatec’s current documentation and the live device before use. Not official Devatec information. Terms of use.

BMS integration notes: Devatec ElectroVap MC (ELMC) electrode steam humidifier (V3 controller)

Integration in brief

Select BACnet MS/TP in the network menu, set a bus address (1-32) and speed, then start/stop the unit with BO 0 and send demand or RH through AV 5 with the control type set to digital control. Watch run status, error code and steam output.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 0On/Off BMS commandStart/stop (1 = start requested)Write
AV 5RH or demand value (digital or digital probe).Demand or RH from the BMS, 1-100 %Write
AV 6RH set pointHumidity setpoint, %RHWrite
AI 3Run statusRun status codeRead
AI 14steam productionSteam output, 10 x kg/hRead
BI 7Alarm returnsAlarm feedbackRead
AI 9Error codeActive error codeRead

Enable & remote start

BO 0 On/Off BMS command starts (1) or stops (0) the unit.

Sensors & values from the BMS

With the control signal type set to digital control in the humidifier menu, the BMS writes RH or demand (1-100 %) to AV 5.

Network setup

Watch out for

Devatec ElectroVap MC (ELMC) electrode steam humidifier (V3 controller) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

32 of 32 shown
Type
Access
Show
Devatec ElectroVap MC (ELMC) electrode steam humidifier (V3 controller) BACnet Points List
DescriptionStates
BI0ContactorMain contactor (steam production)Read0=No production, 1=Production
BI1High-level detectionHigh water level reachedRead0=Not reached, 1=Reached
BI2High limit switchHigh limit switchRead0=Closed, 1=Opened
BI3Fill valveFill valveRead0=No filling, 1=Filling
BI4Drain valveDrain valveRead0=No draining, 1=Draining
BI5relay X10 (term. 3-4): Blower pack / remote ON/OFF, service, defaultRelay X10 output (blower, remote on/off, service or fault)Read0=Relay off, 1=Relay on
BI6maintenance returnsMaintenance feedbackRead0=Off, 1=On
BImin7Alarm returnsAlarm feedbackRead0=Off, 1=On
BOmin0On/Off BMS commandStart/stop from the BMSWrite0=Off (stop unit), 1=On (start requested)
BV2option 1 (with SB card 8 relays)Option relay 1, SB 8-relay cardWrite0=Off, 1=On
BV3option 2 (with SB card 8 relays)Option relay 2, SB 8-relay cardWrite0=Off, 1=On
AI0Type unitUnit type codeRead1=Steam Bath, 2=ELMC, 3=CMC, 13=EHU 750
AI1Register versionRegister map versionRead
AI2CurrentElectrode current, value = 10 x AARead
AImin3Run statusOperating statusRead0=Idle, 1=Steam Gen, 2=End of season, 3=Failure, 4=Manual drain, 5=Maintenance
AI4maintenance counterMaintenance counterhRead
AI5timeRun timehRead
AI6time before end-of-season drainingHours before end-of-season drainhRead
AI7Control Signal valueControl signal, 10 x V or 10 x mA or %Read
AI8Temperature (maintenance option or SB)Water temperature (keep-warm option or steam bath)°CRead
AImin9Error codeActive error codeRead0=Normal operating, 1=P1 Error, 2=P2 Error, 3=P3 Error, 4=P4 Error, 5=P5 Error, 6=P6 Error, 7=P7 Error, 8=P8 Error, 9=P9 Error, 10=First inspect., 11=Overdue service
AI10type of waterWater type settingRead1=Tap water, 2=Softened water, 3=Partial DI water, 4=DI water
AI11type of controlControl signal typeRead20=On/Off, 21=Digital Ctrl, 22=Digital Sensor, 23=0-10V CTRL, 24=0-5V CTRL, 25=0-20mA CTRL, 26=0-10V Sensor, 27=0-5V Sensor, 28=4-20mA Sensor, 29=Temp Sensor
AI13ApplicationApplication value%Read
AImin14steam productionSteam output, value = 10 x kg/hkg/hRead
AV3End-of-season (EOS)End-of-season drain delay, 1-168 hhWrite
AV4Steam capacity limitCapacity limit, 20-100 %%Write
AVmin5RH or demand value (digital or digital probe).RH or demand from the BMS, 1-100 %%Write
AVmin6RH set pointRH setpoint 1-100 %; steam bath 25-55 °C%Write
AV9maintenance intervalMaintenance interval, hours/100, 1-200Write
AV10production adjustmentProduction adjustmentWrite1=Draining, 2=Evaporation
AV11anti-foam drain timeAnti-foam drain time, 0-15 ssWrite
Object ID lookup: Devatec ElectroVap MC electrode steam humidifier point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ElectroVap MC (ELMC) electrode steam humidifier (V3 controller) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Devatec ElectroVap MC (ELMC) electrode steam humidifier (V3 controller)

How many BACnet points does the Devatec ElectroVap MC (ELMC) electrode steam humidifier (V3 controller) have?

This list has 32 BACnet objects: 14 analog inputs, 7 analog values, 8 binary inputs, 1 binary output, 2 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Devatec ElectroVap MC (ELMC) electrode steam humidifier (V3 controller) BACnet points are writable?

10 of the 32 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Devatec ElectroVap MC (ELMC) electrode steam humidifier (V3 controller) BACnet documentation?

The source is ElectroVap ELMC Series Instruction & Operation Manual (DT_ELMC-V3-EN REV B.1), published free by Devatec at https://www.devatec.com/wp-content/uploads/2022/01/DT_ELMC-V3-EN_REV-B.1_L.pdf.

What are the minimum BACnet points to integrate the Devatec ElectroVap MC (ELMC) electrode steam humidifier (V3 controller)?

Start with BO 0 On/Off BMS command (Start/stop (1 = start requested)); AV 5 RH or demand value (digital or digital probe). (Demand or RH from the BMS, 1-100 %); AV 6 RH set point (Humidity setpoint, %RH); AI 3 Run status (Run status code); AI 14 steam production (Steam output, 10 x kg/h); BI 7 Alarm returns (Alarm feedback); AI 9 Error code (Active error code).

How do I enable BMS control of the Devatec ElectroVap MC (ELMC) electrode steam humidifier (V3 controller)?

BO 0 On/Off BMS command starts (1) or stops (0) the unit.

Can the BMS supply sensor values to the Devatec ElectroVap MC (ELMC) electrode steam humidifier (V3 controller)?

With the control signal type set to digital control in the humidifier menu, the BMS writes RH or demand (1-100 %) to AV 5.

How do I check these points on the real ElectroVap MC (ELMC) electrode steam humidifier (V3 controller)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Devatec BACnet points lists

Source: ElectroVap ELMC Series Instruction & Operation Manual · DT_ELMC-V3-EN REV B.1. Object names, instances and units are reproduced as published; descriptions are our own.