  4. PowerScout HD (PS12HD / PS24HD / PS48HD) multi-circuit power meter

Multi-circuit power and energy meter (submeter) · BACnet points list

DENT Instruments PowerScout HD (PS12HD / PS24HD / PS48HD) multi-circuit power meter BACnet points list

Updated 6 November 2026

Short answer

The PowerScout HD master register list maps every Modbus register to its BACnet object. System objects cover network settings, reset commands, demand window, snap thresholds, pulse inputs, voltage alarms and the clock. Each metering element (three CT channels) repeats a block of Analog Inputs (current, voltage, power, VA, VAR, power factors, THD, demand, energy by direction and quadrant, phase angles) plus per-CT configuration objects; element A is listed here and each later element adds 10000.

This page lists 187 BACnet objects for the DENT Instruments PowerScout HD (PS12HD / PS24HD / PS48HD) multi-circuit power meter — 77 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from DENT Instruments’s own free documentation, linked below.

Manufacturer
DENT Instruments
Model
PowerScout HD (PS12HD / PS24HD / PS48HD) multi-circuit power meter
Equipment
Multi-circuit power and energy meter (submeter)
Equipment type
Thermostats, sensors & meters
BACnet objects
187 (77 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Also known as
PowerScout HD, PS12HD, PS24HD, PS48HD, PowerScout 12HD, PowerScout 48HD, PSHD
Source document
PowerScout HD Master Register List
Download CSV 187 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against DENT Instruments’s current documentation and the live device before use. Not official DENT Instruments information. Terms of use.

BMS integration notes: DENT Instruments PowerScout HD (PS12HD / PS24HD / PS48HD) multi-circuit power meter

Integration in brief

Set the serial address/baud or IP settings, then configure each element's service type and CT ratings. Read each element's power sum, energy, demand, current and voltage at the element A instance plus 10000 x (element index - 1).

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1167Power Sum ElementElement real power, kW (+10000 per element)Read
AI 1207Imported Energy Sum ElementElement imported energy, kWhRead
AI 2344Energy Net Sum ElementElement net energy, kWhRead
AI 2334Power Demand This Interval ElementElement kW demand, current intervalRead
AI 1191Apparent PF Avg ElementElement apparent power factorRead
AI 1141Current Avg ElementElement average current, ARead
AI 1149Voltage L to N Avg ElementElement average L-N voltage, VRead
AI 1165Line FrequencyLine frequency, HzRead
BV 2451Alarm Output StatusAlarm output stateWrite

Network setup

Watch out for

DENT Instruments PowerScout HD (PS12HD / PS24HD / PS48HD) multi-circuit power meter BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

187 of 187 shown
Type
BinaryMulti-state
Access
Show
DENT Instruments PowerScout HD (PS12HD / PS24HD / PS48HD) multi-circuit power meter BACnet Points List
DescriptionStates
PIV1069SERIAL ADDRESSModbus Device AddressWrite
BV1077DHCP/STATIC CONFIGEnum for force IPV4 config method (0=static/1=DHCP)Write0=static, 1=DHCP
CSV1079IP AddressWrite
CSV1087IP NetmaskNetmaskWrite
CSV1095IP GatewayGatewayWrite
PIV1131Serial BaudrateInterface baud rate in bits per secondWrite
AImin1141Current Avg Elementper elementARead
AI1143Current CH1per elementARead
AI1145Current CH2per elementARead
AI1147Current CH3per elementARead
AImin1149Voltage L to N Avg Elementper elementVRead
AI1151Voltage L1 to Nper elementVRead
AI1153Voltage L2 to Nper elementVRead
AI1155Voltage L3 to Nper elementVRead
AI1157Voltage L to L Avg Elementper elementVRead
AI1159Voltage L1 to L2per elementVRead
AI1161Voltage L2 to L3per elementVRead
AI1163Voltage L3 to L1per elementVRead
AImin1165Line Frequencyper elementHzRead
AImin1167Power Sum Elementper elementkWRead
AI1169Power CH1per elementkWRead
AI1171Power CH2per elementkWRead
AI1173Power CH3per elementkWRead
AI1175VA Sum Elementper elementkVARead
AI1177VA CH1per elementkVARead
AI1179VA CH2per elementkVARead
AI1181VA CH3per elementkVARead
AI1183VAR Sum Elementper elementkvarRead
AI1185VAR CH1per elementkvarRead
AI1187VAR CH2per elementkvarRead
AI1189VAR CH3per elementkvarRead
AImin1191Apparent PF Avg Elementper elementRead
AI1193Apparent PF CH1per elementRead
AI1195Apparent PF CH2per elementRead
AI1197Apparent PF CH3per elementRead
AI1199Exported Energy Sum Elementper elementkWhRead
AI1201Exported Energy CH1per elementkWhRead
AI1203Exported Energy CH2per elementkWhRead
AI1205Exported Energy CH3per elementkWhRead
AImin1207Imported Energy Sum Elementper elementkWhRead
AI1209Imported Energy CH1per elementkWhRead
AI1211Imported Energy CH2per elementkWhRead
AI1213Imported Energy CH3per elementkWhRead
AI1215Exported VAh Sum Elementper elementkVAhRead
AI1217Exported VAh CH1per elementkVAhRead
AI1219Exported VAh CH2per elementkVAhRead
AI1221Exported VAh CH3per elementkVAhRead
AI1223Imported VAh Sum Elementper elementkVAhRead
AI1225Imported VAh CH1per elementkVAhRead
AI1227Imported VAh CH2per elementkVAhRead
AI1229Imported VAh CH3per elementkVAhRead
AI1231Imported VARh Q1 Sum Elementper elementkvarhRead
AI1233Imported VARh Q1 CH1per elementkvarhRead
AI1235Imported VARh Q1 CH2per elementkvarhRead
AI1237Imported VARh Q1 CH3per elementkvarhRead
AI1239Imported VARh Q2 Sum Elementper elementkvarhRead
AI1241Imported VARh Q2 CH1per elementkvarhRead
AI1243Imported VARh Q2 CH2per elementkvarhRead
AI1245Imported VARh Q2 CH3per elementkvarhRead
AI1247Exported VARh Q3 Sum Elementper elementkvarhRead
AI1249Exported VARh Q3 CH1per elementkvarhRead
AI1251Exported VARh Q3 CH2per elementkvarhRead
AI1253Exported VARh Q3 CH3per elementkvarhRead
AI1255Exported VARh Q4 Sum Elementper elementkvarhRead
AI1257Exported VARh Q4 CH1per elementkvarhRead
AI1259Exported VARh Q4 CH2per elementkvarhRead
AI1261Exported VARh Q4 CH3per elementkvarhRead
AI1263EventsRead
BV2100Reset ProcessorReset (software) processor; write 1 or 1234Write
BV2101Clear Accumulated Measurements AllClear all accumulated measurements (CAM); write 1 or 1234Write
BV2102Clear Accumulated Measurements ElementWrite 1 or 1234, per elementWrite
BV2103Clear Peak Demand ElementWrite 1 or 1234, per elementWrite
BV2104Clear Peak Demand AllWrite 1 or 1234Write
BV2105Reset to User DefaultsWrite 1 or 1234Write
MV2201Demand Window TypeSliding or FixedRead
PIV2202Demand Window LengthDemand WindowminRead
AV2203Volt Multiplier VINPUT1Write
AV2205Volt Multiplier VINPUT2PS24/48 onlyWrite
MV2207Service Type ElementService Type, per elementWrite
AV2208Millivolt Snap ThresholdSnap MV Threshold%Write
AV2210RoCoil Snap ThresholdSnap Rog Threshold%Write
AV2212Voltage Snap ThresholdSnap Volt ThresholdVWrite
MV2214Communications ModeRead
AV2215RoCoil Millivolt per KiloampWrite
MV2217Voltage InputElement Voltage Input, per element, PS24/48 onlyWrite
AV2218CH1 CT Full Scale RatingCT1 RANGE, per elementAWrite
MV2220CH1 CT Voltage ReferenceVoltage Reference for CT1, per elementWrite
AV2221CH1 CT MultiplierCT1 AMPS MULTIPLIER, per elementWrite
PIV2223CH1 CT TypeCT1 TYPE, per elementWrite
AV2224CH1 CT Phase ShiftCT1 PHASE SHIFT, per element°Write
BV2226CH1 CT FlipperFLIP THE SIGN OF CT 1 READING, per elementWrite
AV2227CH2 CT Full Scale RatingCT2 RANGE, per elementAWrite
MV2229CH2 CT Volts referenceVoltage Reference for CT2, per elementWrite
AV2230CH2 CT MultiplierCT2 AMPS MULTIPLIER, per elementWrite
PIV2232CH2 CT typeCT2 TYPE, per elementWrite
AV2233CH2 CT Phase ShiftCT2 PHASE SHIFT, per element°Write
BV2235CH2 CT FlipperFLIP THE SIGN OF CT 2 READING, per elementWrite
AV2236CH3 CT Full Scale RatingCT3 INTEGER, per elementAWrite
MV2238CH3 CT volt referenceVoltage Reference for CT3, per elementWrite
AV2239CH3 CT MultiplierCT3 AMPS MULTIPLIER, per elementWrite
PIV2241CH3 CT typeCT3 TYPE, per elementWrite
AV2242CH3 CT Phase ShiftCT3 PHASE SHIFT, per element°Write
BV2244CH3 CT FlipperFLIP THE SIGN OF CT 3 READING, per elementWrite
MV2248PF Sign ConventionWrite
PIV2250UDP PortBACnet UDP PortWrite
CSV2264BBMD IP AddressWrite
PIV2272LCD/WebApp Read PasswordWrite
PIV2273LCD/WebApp Read/Write PasswordWrite
AV2274Line Frequency ExpectedCustomer Line frequencyWrite
AI2300Displacement PF Avg Elementper elementRead
AI2302Displacement PF CH1per elementRead
AI2304Displacement PF CH2per elementRead
AI2306Displacement PF CH3per elementRead
AI2308Apparent PF Avg ElementAvg Apparent PF Element, per elementRead
AI2310Apparent PF CH1per elementRead
AI2312Apparent PF CH2per elementRead
AI2314Apparent PF CH3per elementRead
AI2316Distortion PF Avg Elementper elementRead
AI2318Distortion PF CH1per elementRead
AI2320Distortion PF CH2per elementRead
AI2322Distortion PF CH3per elementRead
AI2324THD Avg Elementper element%Read
AI2326THD CH1per element%Read
AI2328THD CH2per element%Read
AI2330THD CH3per element%Read
AI2332Power Demand Max Interval Elementper elementkWRead
AImin2334Power Demand This Interval Elementper elementkWRead
AI2336VA Demand Max Interval Elementper elementkVARead
AI2338VA Demand This Interval Elementper elementkVARead
AImin2344Energy Net Sum Elementper elementkWhRead
AI2346Energy Net CH1per elementkWhRead
AI2348Energy Net CH2per elementkWhRead
AI2350Energy Net CH3per elementkWhRead
AI2352Apparent Energy Net Sum Elementper elementkVAhRead
AI2354Apparent Energy Net CH1per elementkVAhRead
AI2356Apparent Energy Net CH2per elementkVAhRead
AI2358Apparent Energy Net CH3per elementkVAhRead
AI2360VARh Net Sum Elementper elementkvarhRead
AI2362VARh Net CH1per elementkvarhRead
AI2364VARh Net CH2per elementkvarhRead
AI2366VARh Net CH3per elementkvarhRead
AI2368Time Since CAMTime Since Reset MSWsRead
AI2371Theta L1CH1 Angle, per element°Read
AI2373Theta L2CH2 Angle, per element°Read
AI2375Theta L3CH3 Angle, per element°Read
Other2377Phase Check System StatusSystem Phase Check Status, BitString ValueRead
Other2378Element Phase Check StatusBitString Value, per elementRead
AI2391Theta ElementElement Angle, per elementRead
BV2400Pulse Input 1 EnablePS12/24/48 onlyWrite
AV2401Pulse Input 1 Scale FactorPS12/24/48 onlyWrite
CSV2403Pulse Input 1 UnitsPS12/24/48 onlyWrite
AI2407Pulse Input 1 AccumulatorPS12/24/48 onlyRead
BV2409Pulse Input 1 Accumulator ClearPS12/24/48 onlyWrite
BV2410Pulse Input 2 EnablePS12/24/48 onlyWrite
AV2411Pulse Input 2 Scale FactorPS12/24/48 onlyWrite
CSV2413Pulse Input 2 UnitsPS12/24/48 onlyWrite
AI2417Pulse Input 2 AccumulatorPS12/24/48 onlyRead
BV2419Pulse Input 2 Accumulator ClearPS12/24/48 onlyWrite
BV2420Pulse Input 3 EnablePS12 onlyWrite
AV2421Pulse Input 3 Scale FactorPS12 onlyWrite
CSV2423Pulse Input 3 UnitsPS12 onlyWrite
AI2427Pulse Input 3 AccumulatorPS12 onlyRead
BV2429Pulse Input 3 Accumulator ClearPS12 onlyWrite
BV2430Pulse Input 4 EnablePS12 onlyWrite
AV2431Pulse Input 4 Scale FactorPS12 onlyWrite
CSV2433Pulse Input 4 UnitsPS12 onlyWrite
AI2437Pulse Input 4 AccumulatorPS12 onlyRead
BV2439Pulse Input 4 Accumulator ClearPS12 onlyWrite
BVmin2451Alarm Output StatusState of AlarmWrite
Other2458Voltage Alarm Vin1 MaskBitfield for all VIN1 and associated phases, BitString ValueWrite
Other2459Voltage Alarm Vin2 MaskBitfield for all VIN2 (PS48) and associated phases, BitString ValueWrite
PIV2460Voltage Alarm Range Vin1 L1N UnderVWrite
PIV2462Voltage Alarm Range Vin1 L2N UnderVWrite
PIV2464Voltage Alarm Range Vin1 L3N UnderVWrite
PIV2466Voltage Alarm Range Vin1 L1L2 UnderVWrite
PIV2468Voltage Alarm Range Vin1 L2L3 UnderVWrite
PIV2470Voltage Alarm Range Vin1 L3L1 UnderVWrite
PIV2472Voltage Alarm Range Vin2 L1N UnderPS24/48 onlyVWrite
PIV2474Voltage Alarm Range Vin2 L2N UnderPS24/48 onlyVWrite
PIV2476Voltage Alarm Range Vin2 L3N UnderPS24/48 onlyVWrite
PIV2478Voltage Alarm Range Vin2 L1L2 UnderPS24/48 onlyVWrite
PIV2480Voltage Alarm Range Vin2 L2L3 UnderPS24/48 onlyVWrite
PIV2482Voltage Alarm Range Vin2 L3L1 UnderPS24/48 onlyVWrite
PIV2484Voltage Alarm PersistencesWrite
Other2485Voltage Vin1 Alarm Status UnderBitString ValueRead
Other2487Voltage Vin2 Alarm Status UnderBitString Value, PS24/48 onlyRead
PIV2489RTC CLOCKReal Time Clock MSWWrite
Object ID lookup: DENT Instruments PowerScout HD multi-circuit power meter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PowerScout HD (PS12HD / PS24HD / PS48HD) multi-circuit power meter and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the DENT Instruments PowerScout HD (PS12HD / PS24HD / PS48HD) multi-circuit power meter

How many BACnet points does the DENT Instruments PowerScout HD (PS12HD / PS24HD / PS48HD) multi-circuit power meter have?

This list has 187 BACnet objects: 103 analog inputs, 20 analog values, 19 binary values, 8 multi-state values, 8 characterstring values, 23 positive integer values, 6 others. The exact set on a given unit depends on its firmware, installed options and configuration.

Which DENT Instruments PowerScout HD (PS12HD / PS24HD / PS48HD) multi-circuit power meter BACnet points are writable?

77 of the 187 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official DENT Instruments PowerScout HD (PS12HD / PS24HD / PS48HD) multi-circuit power meter BACnet documentation?

The source is PowerScout HD Master Register List, published free by DENT Instruments at https://www.dentinstruments.com/wp-content/uploads/2022/04/PSHD_MASTER_REGISTER_LIST_current-1.xlsx.

What are the minimum BACnet points to integrate the DENT Instruments PowerScout HD (PS12HD / PS24HD / PS48HD) multi-circuit power meter?

Start with AI 1167 Power Sum Element (Element real power, kW (+10000 per element)); AI 1207 Imported Energy Sum Element (Element imported energy, kWh); AI 2344 Energy Net Sum Element (Element net energy, kWh); AI 2334 Power Demand This Interval Element (Element kW demand, current interval); AI 1191 Apparent PF Avg Element (Element apparent power factor); AI 1141 Current Avg Element (Element average current, A); AI 1149 Voltage L to N Avg Element (Element average L-N voltage, V); AI 1165 Line Frequency (Line frequency, Hz); BV 2451 Alarm Output Status (Alarm output state).

How do I check these points on the real PowerScout HD (PS12HD / PS24HD / PS48HD) multi-circuit power meter?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.