Power and energy meter (three-phase submeter) · BACnet points list
DENT Instruments PowerScout 3037 power meter BACnet points list
Updated 6 November 2026
The PowerScout 3037 serves its data as Analog Value objects. Measurements cover system and per-phase power, energy (absolute, net, positive and negative), voltage, current, reactive and apparent power and energy, power factor, demand and frequency. Configuration AVs set CT values and types, multipliers, service type, demand window, serial settings, the pulse output and BBMD registration.
This page lists 119 BACnet objects for the DENT Instruments PowerScout 3037 power meter — 31 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from DENT Instruments’s own free documentation, linked below.
- Manufacturer
- DENT Instruments
- Model
- PowerScout 3037 power meter
- Equipment
- Power and energy meter (three-phase submeter)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 119 (31 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- PICS: firmware 4.33, application 0.5.9
- Default device instance
- From the address switches (PS3037-S) or the Ethernet MAC address (PS3037-E)
- Also known as
- PowerScout 3037, PS3037, PS3037-S, PS3037-E, Power Scout 3037
- Source document
- PowerScout 3037 Operator's Guide (All Things BACnet)
Reference only, provided as-is: verify against DENT Instruments’s current documentation and the live device before use. Not official DENT Instruments information. Terms of use.
BMS integration notes: DENT Instruments PowerScout 3037 power meter
Set the address switches (BACnet MS/TP MAC 1-127), put the meter in BACnet mode (ViewPoint, or write 1833 to Modbus register 44612), set the service type and CT values, then read system kW, kWh, demand, power factor, current, voltage and frequency.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 1030 | kW System | Total real power, kW | Read |
| AV 2000 | kWh System Total | Total real energy, kWh | Read |
| AV 1010 | kW Demand System Now | kW demand, latest window | Read |
| AV 1000 | kW Demand System Maximum | Peak kW demand since reset | Read |
| AV 9030 | Apparent PF System | System power factor | Read |
| AV 4010 | Amps System Average | Average current, A | Read |
| AV 3010 | Volts Line to Neutral Average | Average line-to-neutral voltage, V | Read |
| AV 10000 | Measured Line Frequency | Line frequency, Hz | Read |
Network setup
- BACnet MS/TP defaults: 76800 baud, 8N1; BACnet rates 9600, 19200, 38400, 76800. MS/TP masters use addresses 1-127; 128-254 are for slaves.
- Switch to BACnet in ViewPoint (Comms Setup), or write 1833 to Modbus register 44612; address switches at 00 return the meter to Modbus at 9600.
- Device ID, Max Master and Max Info Frames are writable in the device object or from ViewPoint.
- PS3037-E: register as a foreign device by writing the BBMD IP to AV 14014 (low word) and AV 14015 (high word), network order; TTL 60000 s. Write 0 to both to stop.
Watch out for
- Clear Accumulated Measurements (AV 10140) only acts on the value 1234 and clears every energy total.
- Once a non-factory device ID is written, an ID inside the factory range cannot be written back.
- Set Service Type (AV 12080) to match the wiring: 0 Wye, 1 Delta.
DENT Instruments PowerScout 3037 power meter BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 1000 | kW Demand System Maximum | System Maximum Demand (peak demand) (Unsigned/Absolute) | kW | Read | |
| AVmin | 1010 | kW Demand System Now | Average Power (kW) for most recent demand window | kW | Read | |
| AV | 1020 | kW Demand System Minimum | Min Average power window (kW) (Unsigned/Absolute) | kW | Read | |
| AVmin | 1030 | kW System | System True Power (kW) | kW | Read | |
| AV | 1031 | kW System Net | System Power (kW) Signed net value of (kW L1) + (kW L2) + (kW L3) | kW | Read | |
| AV | 1060 | kW System Average | Equals kWh System / (Time Since Reset /3600 seconds/Hr) | kW | Read | |
| AV | 1080 | kW System Average Positive | Equals kWh System Positive / (Time Since Reset /3600 seconds/Hr) | kW | Read | |
| AV | 1090 | kW System Average Negative | Equals kWh System Negative / (Time Since Reset /3600 seconds/Hr) | kW | Read | |
| AV | 1100 | kW System Maximum | System Highest Instantaneous Draw Since Reset (kW) | kW | Read | |
| AV | 1110 | kW System Maximum Positive | System Highest Instantaneous Positive Draw Since Reset (kW) | kW | Read | |
| AV | 1120 | kW System Maximum Negative | System Highest Instantaneous Negative Draw Since Reset (kW) | kW | Read | |
| AV | 1130 | kW System Minimum | System Lowest Instantaneous Draw Since Reset (kW, resettable) | kW | Read | |
| AV | 1140 | kW System Minimum Positive | System Lowest Instantaneous Positive Draw Since Reset (kW, | kW | Read | |
| AV | 1150 | kW System Minimum Negative | System Lowest Instantaneous Negative Draw Since Reset (kW, | kW | Read | |
| AV | 1160 | kW L1 | Individual Phase True Power (kW) (Signed) | kW | Read | |
| AV | 1190 | kW L2 | Individual Phase True Power (kW) (Signed) | kW | Read | |
| AV | 1220 | kW L3 | Individual Phase True Power (kW) (Signed) | kW | Read | |
| AVmin | 2000 | kWh System Total | System True Energy (kWh) (Unsigned/Absolute) | kWh | Read | |
| AV | 2010 | kWh System Total Positive | System True Energy (kWh) Positive (Signed Net) | kWh | Read | |
| AV | 2020 | kWh System Total Negative | System True Energy (kWh) Negative (Signed Net) | kWh | Read | |
| AV | 2021 | kWh System Total Net | System True Energy (kWh) (Net) | kWh | Read | |
| AV | 2040 | kWh L1 Positive | kWh | Read | ||
| AV | 2050 | kWh L1 Negative | Individual Phase True Energy (kWh) (Signed) | kWh | Read | |
| AV | 2051 | kWh L1 Net | Individual Phase True Energy (kWh) (Net) | kWh | Read | |
| AV | 2070 | kWh L2 Positive | System True Energy (kWh) Positive (Signed Net) | kWh | Read | |
| AV | 2080 | kWh L2 Negative | Individual Phase True Energy (kWh) (Signed) | kWh | Read | |
| AV | 2081 | kWh L2 Net | Individual Phase True Energy (kWh) (Net) | kWh | Read | |
| AV | 2100 | kWh L3 Positive | System True Energy (kWh) Positive (Signed Net) | kWh | Read | |
| AV | 2110 | kWh L3 Negative | Individual Phase True Energy (kWh) (Signed) | kWh | Read | |
| AV | 2111 | kWh L3 Net | Individual Phase True Energy (kWh) (Net) | kWh | Read | |
| AV | 3000 | Volts Line to Line Average | Voltage Line to line Average | V | Read | |
| AVmin | 3010 | Volts Line to Neutral Average | Voltage Line to neutral Average | V | Read | |
| AV | 3020 | Volts L1 to L2 | Individual Phase to Phase Voltages | V | Read | |
| AV | 3030 | Volts L2 to L3 | Individual Phase to Phase Voltages | V | Read | |
| AV | 3040 | Volts L1 to L3 | Individual Phase to Phase Voltages | V | Read | |
| AV | 3050 | Volts L1 to Neutral | Individual Phase to Neutral Voltages (V) | V | Read | |
| AV | 3060 | Volts L2 to Neutral | Individual Phase to Neutral Voltages (V) | V | Read | |
| AV | 3070 | Volts L3 to Neutral | Individual Phase to Neutral Voltages (V) | V | Read | |
| AVmin | 4010 | Amps System Average | Average of all phases | A | Read | |
| AV | 4020 | Amps L1 | Individual Phase Currents (A) | A | Read | |
| AV | 4030 | Amps L2 | Individual Phase Currents (A) | A | Read | |
| AV | 4040 | Amps L3 | Individual Phase Currents (A) | A | Read | |
| AV | 5000 | kVAR System | System Total Reactive Power (kVAR) | kvar | Read | |
| AV | 5001 | kVAR System Net | System Total Reactive Power (kVAR) | kvar | Read | |
| AV | 5030 | kVAR L1 | Individual Phase Reactive Energy LSW (kVARh) (Signed) | kvar | Read | |
| AV | 5060 | kVAR L2 | Individual Phase Reactive Energy LSW (kVARh) (Signed) | kvar | Read | |
| AV | 5090 | kVAR L3 | Individual Phase Reactive Energy LSW (kVARh) (Signed) | kvar | Read | |
| AV | 5120 | kVAR Demand System Max | System Maximum Instantaneous kVAR Demand (kVA, resettable) | kvar | Read | |
| AV | 5130 | kVAR Demand System Now | Average kVAR demand for most recent window (resettable) | kvar | Read | |
| AV | 6010 | kVARh System | System Total Reactive Energy (Unsigned/Absolute) | kvarh | Read | |
| AV | 6020 | kVARh System Total Positive | kvarh | Read | ||
| AV | 6030 | kVARh Sys Negative | System Total Reactive Energy (Signed Net) | kvarh | Read | |
| AV | 6050 | kVARh L1 Positive | kvarh | Read | ||
| AV | 6060 | kVARh L1 Negative | Individual Phase Reactive Energy (kVARh) (Signed) | kvarh | Read | |
| AV | 6080 | kVARh L2 Positive | System Total Reactive Energy (Signed Net) | kvarh | Read | |
| AV | 6090 | kVARh L2 Negative | Individual Phase Reactive Energy (kVARh) (Signed) | kvarh | Read | |
| AV | 6110 | kVARh L3 Positive | System Total Reactive Energy (Signed Net) | kvarh | Read | |
| AV | 6120 | kVARh L3 Negative | Individual Phase Reactive Energy (kVARh) (Signed) | kvarh | Read | |
| AV | 7000 | kVAh System Total | System Total Apparent Energy (Unsigned/Absolute) | kVAh | Read | |
| AV | 7001 | kVAh System Total Positive | System Total Positive Apparent Energy (kVAh) (Signed Net) | kVAh | Read | |
| AV | 7002 | kVAh System Total Negative | System Total Negative Apparent Energy (Signed Net) | kVAh | Read | |
| AV | 7020 | kVAh L1 Positive | Individual Phase Apparent Energy (kVAh) (Signed) | kVAh | Read | |
| AV | 7030 | kVAh L1 Negative | Individual Phase Apparent Energy (kVAh) (Signed) | kVAh | Read | |
| AV | 7050 | kVAh L2 Positive | Individual Phase Apparent Energy (kVAh) (Signed) | kVAh | Read | |
| AV | 7060 | kVAh L2 Negative | Individual Phase Apparent Energy (kVAh) (Signed) | kVAh | Read | |
| AV | 7080 | kVAh L3 Positive | Individual Phase Apparent Energy (kVAh) (Signed) | kVAh | Read | |
| AV | 7090 | kVAh L3 Negative | Individual Phase Apparent Energy (kVAh) (Signed) | kVAh | Read | |
| AV | 8000 | kVA System | System Total Apparent Power (kVA) | kVA | Read | |
| AV | 8001 | kVA System Net | System Net Apparent Power (kVA) | kVA | Read | |
| AV | 8010 | kVA L1 | Individual Phase Apparent Powers (kVA) (signed) | kVA | Read | |
| AV | 8020 | kVA L2 | Individual Phase Apparent Powers (kVA) (signed) | kVA | Read | |
| AV | 8030 | kVA L3 | Individual Phase Apparent Powers (kVA) (signed) | kVA | Read | |
| AV | 8040 | kVA Demand System Max | System Maximum Instantaneous kVA Demand (kVA, resettable) | kVA | Read | |
| AV | 8050 | kVA Demand System Now | Average kVA for most recent demand window (resettable) | kVA | Read | |
| AV | 9000 | Displacement PF System | System Total Power Factor (PF) (Signed) | Read | ||
| AVmin | 9030 | Apparent PF System | System Total Power Factor (PF) (Signed) | Read | ||
| AV | 9060 | Displacement PF L1 | Individual Phase displacement Power Factor (PF) | Read | ||
| AV | 9090 | Displacement PF L2 | Individual Phase displacement Power Factor (PF) | Read | ||
| AV | 9120 | Displacement PF L3 | Individual Phase displacement Power Factor (PF) | Read | ||
| AV | 9150 | Apparent PF L1 | Individual Phase apparent Power Factors (PF) | Read | ||
| AV | 9180 | Apparent PF L2 | Individual Phase apparent Power Factors (PF) | Read | ||
| AV | 9210 | Apparent PF L3 | Individual Phase apparent Power Factors (PF) | Read | ||
| AVmin | 10000 | Measured Line Frequency | Line Frequency (Hz) | Hz | Read | |
| AV | 10010 | Time Since Reset | Seconds since accumulators were reset | s | Read | |
| AV | 10020 | Data Acquisition Tick | Sample count, cleared every minute | Read | ||
| AV | 10080 | Hardware ID | Hardware revisions | Read | ||
| AV | 10090 | Features | New features | Read | ||
| AV | 10140 | Clear Accumulated Measurements | Write 1234 to reset all energy accumulators | Write | ||
| AV | 10150 | PowerScout Element ID | Element index x 256 + number of elements | Read | ||
| AV | 10190 | Communications protocol | Switches between BACnet and Modbus | Write | ||
| AV | 12001 | CT1 Phase Shift | CT1 phase shift (degrees) | ° | Write | |
| AV | 12002 | CT2 Phase Shift | CT2 phase shift (degrees) | ° | Write | |
| AV | 12003 | CT3 Phase Shift | CT3 phase shift (degrees) | ° | Write | |
| AV | 12011 | CT1 Value | CT1 Value | Write | ||
| AV | 12012 | CT2 Value | CT2 Value | Write | ||
| AV | 12013 | CT3 Value | CT3 Value | Write | ||
| AV | 12030 | CT Pulse Scalar | Changes the scaling of the output pulses | Write | ||
| AV | 12040 | Demand Window | Demand window, minutes (default 15) | min | Write | |
| AV | 12050 | Volts Multiplier | Multiply volts values by this scalar | V | Write | |
| AV | 12061 | CT1 Amps Multiplier | Multiply CT1 amps values by this scalar | Write | ||
| AV | 12062 | CT2 Amps Multiplier | Multiply CT2 amps values by this scalar | Write | ||
| AV | 12063 | CT3 Amps Multiplier | Multiply CT3 amps values by this scalar | Write | ||
| AV | 12070 | Com Settings | Serial settings code, e.g. 901 = 9600 8N1 | Write | ||
| AV | 12080 | Service Type | Service type: 0 = Wye, 1 = Delta | Write | ||
| AV | 12090 | Line Frequency | Line frequency: 50 or 60 | Write | ||
| AV | 12110 | Snap Rog Threshold | “Snap to Zero” threshold Rogowski CTs | Write | ||
| AV | 12120 | Snap Volt Threshold | “Snap to Zero” threshold for voltage | Write | ||
| AV | 12130 | CT Type All | Writes same type for all CTs: 1=MilliVolt, 2=Rogowski | Write | ||
| AV | 12131 | CT1 Type | 1=MilliVolt, 2=Rogowski | Write | ||
| AV | 12132 | CT2 Type | 1=MilliVolt, 2=Rogowski | Write | ||
| AV | 12133 | CT3 Type | 1=MilliVolt, 2=Rogowski | Write | ||
| AV | 12134 | CT1 Voltage Source | Individual Phase Voltage Source | Write | ||
| AV | 12135 | CT2 Voltage Source | Individual Phase Voltage Source | Write | ||
| AV | 12136 | CT3 Voltage Source | Individual Phase Voltage Source | Write | ||
| AV | 13020 | Port 1 output control when used as an on/off—open/closed switch | Port 1 switch output: 0 low/closed, 1 high/open | Write | ||
| AV | 13100 | Digital Port 1 Configuration | Port 1 pulses: 0 off, 44001 kWh, 44008 kVARh, 44011 kVAh | Write | ||
| AV | 13110 | Port 1 pulse output relay type | 0 = normally open, 1 = normally closed | Write | ||
| AV | 14014 | BBMD IP Address | BBMD IP address, low word (network order) | Write | ||
| AV | 14015 | BBMD IP Address | BBMD IP address, high word (network order) | Write |
No points match these filters.
Object ID lookup: DENT Instruments PowerScout 3037 power meter point IDs by name
AV1000kW Demand System MaximumAV1010kW Demand System NowAV1020kW Demand System MinimumAV1030kW SystemAV1031kW System NetAV1060kW System AverageAV1080kW System Average PositiveAV1090kW System Average NegativeAV1100kW System MaximumAV1110kW System Maximum PositiveAV1120kW System Maximum NegativeAV1130kW System MinimumAV1140kW System Minimum PositiveAV1150kW System Minimum NegativeAV1160kW L1AV1190kW L2AV1220kW L3AV2000kWh System TotalAV2010kWh System Total PositiveAV2020kWh System Total NegativeAV2021kWh System Total NetAV2040kWh L1 PositiveAV2050kWh L1 NegativeAV2051kWh L1 NetAV2070kWh L2 PositiveAV2080kWh L2 NegativeAV2081kWh L2 NetAV2100kWh L3 PositiveAV2110kWh L3 NegativeAV2111kWh L3 NetAV3000Volts Line to Line AverageAV3010Volts Line to Neutral AverageAV3020Volts L1 to L2AV3030Volts L2 to L3AV3040Volts L1 to L3AV3050Volts L1 to NeutralAV3060Volts L2 to NeutralAV3070Volts L3 to NeutralAV4010Amps System AverageAV4020Amps L1AV4030Amps L2AV4040Amps L3AV5000kVAR SystemAV5001kVAR System NetAV5030kVAR L1AV5060kVAR L2AV5090kVAR L3AV5120kVAR Demand System MaxAV5130kVAR Demand System NowAV6010kVARh SystemAV6020kVARh System Total PositiveAV6030kVARh Sys NegativeAV6050kVARh L1 PositiveAV6060kVARh L1 NegativeAV6080kVARh L2 PositiveAV6090kVARh L2 NegativeAV6110kVARh L3 PositiveAV6120kVARh L3 NegativeAV7000kVAh System TotalAV7001kVAh System Total PositiveAV7002kVAh System Total NegativeAV7020kVAh L1 PositiveAV7030kVAh L1 NegativeAV7050kVAh L2 PositiveAV7060kVAh L2 NegativeAV7080kVAh L3 PositiveAV7090kVAh L3 NegativeAV8000kVA SystemAV8001kVA System NetAV8010kVA L1AV8020kVA L2AV8030kVA L3AV8040kVA Demand System MaxAV8050kVA Demand System NowAV9000Displacement PF SystemAV9030Apparent PF SystemAV9060Displacement PF L1AV9090Displacement PF L2AV9120Displacement PF L3AV9150Apparent PF L1AV9180Apparent PF L2AV9210Apparent PF L3AV10000Measured Line FrequencyAV10010Time Since ResetAV10020Data Acquisition TickAV10080Hardware IDAV10090FeaturesAV10140Clear Accumulated MeasurementsAV10150PowerScout Element IDAV10190Communications protocolAV12001CT1 Phase ShiftAV12002CT2 Phase ShiftAV12003CT3 Phase ShiftAV12011CT1 ValueAV12012CT2 ValueAV12013CT3 ValueAV12030CT Pulse ScalarAV12040Demand WindowAV12050Volts MultiplierAV12061CT1 Amps MultiplierAV12062CT2 Amps MultiplierAV12063CT3 Amps MultiplierAV12070Com SettingsAV12080Service TypeAV12090Line FrequencyAV12110Snap Rog ThresholdAV12120Snap Volt ThresholdAV12130CT Type AllAV12131CT1 TypeAV12132CT2 TypeAV12133CT3 TypeAV12134CT1 Voltage SourceAV12135CT2 Voltage SourceAV12136CT3 Voltage SourceAV13020Port 1 output control when used as an on/off—open/closed switchAV13100Digital Port 1 ConfigurationAV13110Port 1 pulse output relay typeAV14014BBMD IP AddressAV14015BBMD IP Address
Integration notes
- The manual's object tables give the identifier, name and description only. Types are Analog Value: the manual's glossary says PowerScout measurements are Analog Values and DENT's PowerScout series PICS lists only the Device and Analog Value object types.
- Access is not in the table. The PICS lists Present_Value as writable for Analog Values; configuration objects (10140 and 12xxx-14xxx) are marked W here and measurements R.
- Object 6010 is printed twice: 'kVARh System' in the absolute table and again, signed net, in the positive table. It is listed once.
- BACnet IP is on the Ethernet model (PS3037-E) only.
- Source: PS3037 manual, 'All Things BACnet' chapter; object type from the PowerScout series PICS (August 28, 2014).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PowerScout 3037 power meter and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the DENT Instruments PowerScout 3037 power meter
How many BACnet points does the DENT Instruments PowerScout 3037 power meter have?
This list has 119 BACnet objects: 119 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which DENT Instruments PowerScout 3037 power meter BACnet points are writable?
31 of the 119 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official DENT Instruments PowerScout 3037 power meter BACnet documentation?
The source is PowerScout 3037 Operator's Guide (All Things BACnet), published free by DENT Instruments at https://www.dentinstruments.com/wp-content/uploads/2022/04/PS3037_Manual.pdf.
What are the minimum BACnet points to integrate the DENT Instruments PowerScout 3037 power meter?
Start with AV 1030 kW System (Total real power, kW); AV 2000 kWh System Total (Total real energy, kWh); AV 1010 kW Demand System Now (kW demand, latest window); AV 1000 kW Demand System Maximum (Peak kW demand since reset); AV 9030 Apparent PF System (System power factor); AV 4010 Amps System Average (Average current, A); AV 3010 Volts Line to Neutral Average (Average line-to-neutral voltage, V); AV 10000 Measured Line Frequency (Line frequency, Hz).
How do I check these points on the real PowerScout 3037 power meter?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More DENT Instruments BACnet points lists
Source: PowerScout 3037 Operator's Guide (All Things BACnet). Object names, instances and units are reproduced as published; descriptions are our own.