Power and energy meter (three-phase submeter) · BACnet points list

DENT Instruments PowerScout 3037 power meter BACnet points list

Updated 6 November 2026

Short answer

The PowerScout 3037 serves its data as Analog Value objects. Measurements cover system and per-phase power, energy (absolute, net, positive and negative), voltage, current, reactive and apparent power and energy, power factor, demand and frequency. Configuration AVs set CT values and types, multipliers, service type, demand window, serial settings, the pulse output and BBMD registration.

This page lists 119 BACnet objects for the DENT Instruments PowerScout 3037 power meter — 31 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from DENT Instruments’s own free documentation, linked below.

Manufacturer
DENT Instruments
Model
PowerScout 3037 power meter
Equipment
Power and energy meter (three-phase submeter)
Equipment type
Thermostats, sensors & meters
BACnet objects
119 (31 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
PICS: firmware 4.33, application 0.5.9
Default device instance
From the address switches (PS3037-S) or the Ethernet MAC address (PS3037-E)
Also known as
PowerScout 3037, PS3037, PS3037-S, PS3037-E, Power Scout 3037
Source document
PowerScout 3037 Operator's Guide (All Things BACnet)
Download CSV 119 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against DENT Instruments’s current documentation and the live device before use. Not official DENT Instruments information. Terms of use.

BMS integration notes: DENT Instruments PowerScout 3037 power meter

Integration in brief

Set the address switches (BACnet MS/TP MAC 1-127), put the meter in BACnet mode (ViewPoint, or write 1833 to Modbus register 44612), set the service type and CT values, then read system kW, kWh, demand, power factor, current, voltage and frequency.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 1030kW SystemTotal real power, kWRead
AV 2000kWh System TotalTotal real energy, kWhRead
AV 1010kW Demand System NowkW demand, latest windowRead
AV 1000kW Demand System MaximumPeak kW demand since resetRead
AV 9030Apparent PF SystemSystem power factorRead
AV 4010Amps System AverageAverage current, ARead
AV 3010Volts Line to Neutral AverageAverage line-to-neutral voltage, VRead
AV 10000Measured Line FrequencyLine frequency, HzRead

Network setup

Watch out for

DENT Instruments PowerScout 3037 power meter BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

119 of 119 shown
Type
Analog
Access
Show
DENT Instruments PowerScout 3037 power meter BACnet Points List
DescriptionStates
AVmin1000kW Demand System MaximumSystem Maximum Demand (peak demand) (Unsigned/Absolute)kWRead
AVmin1010kW Demand System NowAverage Power (kW) for most recent demand windowkWRead
AV1020kW Demand System MinimumMin Average power window (kW) (Unsigned/Absolute)kWRead
AVmin1030kW SystemSystem True Power (kW)kWRead
AV1031kW System NetSystem Power (kW) Signed net value of (kW L1) + (kW L2) + (kW L3)kWRead
AV1060kW System AverageEquals kWh System / (Time Since Reset /3600 seconds/Hr)kWRead
AV1080kW System Average PositiveEquals kWh System Positive / (Time Since Reset /3600 seconds/Hr)kWRead
AV1090kW System Average NegativeEquals kWh System Negative / (Time Since Reset /3600 seconds/Hr)kWRead
AV1100kW System MaximumSystem Highest Instantaneous Draw Since Reset (kW)kWRead
AV1110kW System Maximum PositiveSystem Highest Instantaneous Positive Draw Since Reset (kW)kWRead
AV1120kW System Maximum NegativeSystem Highest Instantaneous Negative Draw Since Reset (kW)kWRead
AV1130kW System MinimumSystem Lowest Instantaneous Draw Since Reset (kW, resettable)kWRead
AV1140kW System Minimum PositiveSystem Lowest Instantaneous Positive Draw Since Reset (kW,kWRead
AV1150kW System Minimum NegativeSystem Lowest Instantaneous Negative Draw Since Reset (kW,kWRead
AV1160kW L1Individual Phase True Power (kW) (Signed)kWRead
AV1190kW L2Individual Phase True Power (kW) (Signed)kWRead
AV1220kW L3Individual Phase True Power (kW) (Signed)kWRead
AVmin2000kWh System TotalSystem True Energy (kWh) (Unsigned/Absolute)kWhRead
AV2010kWh System Total PositiveSystem True Energy (kWh) Positive (Signed Net)kWhRead
AV2020kWh System Total NegativeSystem True Energy (kWh) Negative (Signed Net)kWhRead
AV2021kWh System Total NetSystem True Energy (kWh) (Net)kWhRead
AV2040kWh L1 PositivekWhRead
AV2050kWh L1 NegativeIndividual Phase True Energy (kWh) (Signed)kWhRead
AV2051kWh L1 NetIndividual Phase True Energy (kWh) (Net)kWhRead
AV2070kWh L2 PositiveSystem True Energy (kWh) Positive (Signed Net)kWhRead
AV2080kWh L2 NegativeIndividual Phase True Energy (kWh) (Signed)kWhRead
AV2081kWh L2 NetIndividual Phase True Energy (kWh) (Net)kWhRead
AV2100kWh L3 PositiveSystem True Energy (kWh) Positive (Signed Net)kWhRead
AV2110kWh L3 NegativeIndividual Phase True Energy (kWh) (Signed)kWhRead
AV2111kWh L3 NetIndividual Phase True Energy (kWh) (Net)kWhRead
AV3000Volts Line to Line AverageVoltage Line to line AverageVRead
AVmin3010Volts Line to Neutral AverageVoltage Line to neutral AverageVRead
AV3020Volts L1 to L2Individual Phase to Phase VoltagesVRead
AV3030Volts L2 to L3Individual Phase to Phase VoltagesVRead
AV3040Volts L1 to L3Individual Phase to Phase VoltagesVRead
AV3050Volts L1 to NeutralIndividual Phase to Neutral Voltages (V)VRead
AV3060Volts L2 to NeutralIndividual Phase to Neutral Voltages (V)VRead
AV3070Volts L3 to NeutralIndividual Phase to Neutral Voltages (V)VRead
AVmin4010Amps System AverageAverage of all phasesARead
AV4020Amps L1Individual Phase Currents (A)ARead
AV4030Amps L2Individual Phase Currents (A)ARead
AV4040Amps L3Individual Phase Currents (A)ARead
AV5000kVAR SystemSystem Total Reactive Power (kVAR)kvarRead
AV5001kVAR System NetSystem Total Reactive Power (kVAR)kvarRead
AV5030kVAR L1Individual Phase Reactive Energy LSW (kVARh) (Signed)kvarRead
AV5060kVAR L2Individual Phase Reactive Energy LSW (kVARh) (Signed)kvarRead
AV5090kVAR L3Individual Phase Reactive Energy LSW (kVARh) (Signed)kvarRead
AV5120kVAR Demand System MaxSystem Maximum Instantaneous kVAR Demand (kVA, resettable)kvarRead
AV5130kVAR Demand System NowAverage kVAR demand for most recent window (resettable)kvarRead
AV6010kVARh SystemSystem Total Reactive Energy (Unsigned/Absolute)kvarhRead
AV6020kVARh System Total PositivekvarhRead
AV6030kVARh Sys NegativeSystem Total Reactive Energy (Signed Net)kvarhRead
AV6050kVARh L1 PositivekvarhRead
AV6060kVARh L1 NegativeIndividual Phase Reactive Energy (kVARh) (Signed)kvarhRead
AV6080kVARh L2 PositiveSystem Total Reactive Energy (Signed Net)kvarhRead
AV6090kVARh L2 NegativeIndividual Phase Reactive Energy (kVARh) (Signed)kvarhRead
AV6110kVARh L3 PositiveSystem Total Reactive Energy (Signed Net)kvarhRead
AV6120kVARh L3 NegativeIndividual Phase Reactive Energy (kVARh) (Signed)kvarhRead
AV7000kVAh System TotalSystem Total Apparent Energy (Unsigned/Absolute)kVAhRead
AV7001kVAh System Total PositiveSystem Total Positive Apparent Energy (kVAh) (Signed Net)kVAhRead
AV7002kVAh System Total NegativeSystem Total Negative Apparent Energy (Signed Net)kVAhRead
AV7020kVAh L1 PositiveIndividual Phase Apparent Energy (kVAh) (Signed)kVAhRead
AV7030kVAh L1 NegativeIndividual Phase Apparent Energy (kVAh) (Signed)kVAhRead
AV7050kVAh L2 PositiveIndividual Phase Apparent Energy (kVAh) (Signed)kVAhRead
AV7060kVAh L2 NegativeIndividual Phase Apparent Energy (kVAh) (Signed)kVAhRead
AV7080kVAh L3 PositiveIndividual Phase Apparent Energy (kVAh) (Signed)kVAhRead
AV7090kVAh L3 NegativeIndividual Phase Apparent Energy (kVAh) (Signed)kVAhRead
AV8000kVA SystemSystem Total Apparent Power (kVA)kVARead
AV8001kVA System NetSystem Net Apparent Power (kVA)kVARead
AV8010kVA L1Individual Phase Apparent Powers (kVA) (signed)kVARead
AV8020kVA L2Individual Phase Apparent Powers (kVA) (signed)kVARead
AV8030kVA L3Individual Phase Apparent Powers (kVA) (signed)kVARead
AV8040kVA Demand System MaxSystem Maximum Instantaneous kVA Demand (kVA, resettable)kVARead
AV8050kVA Demand System NowAverage kVA for most recent demand window (resettable)kVARead
AV9000Displacement PF SystemSystem Total Power Factor (PF) (Signed)Read
AVmin9030Apparent PF SystemSystem Total Power Factor (PF) (Signed)Read
AV9060Displacement PF L1Individual Phase displacement Power Factor (PF)Read
AV9090Displacement PF L2Individual Phase displacement Power Factor (PF)Read
AV9120Displacement PF L3Individual Phase displacement Power Factor (PF)Read
AV9150Apparent PF L1Individual Phase apparent Power Factors (PF)Read
AV9180Apparent PF L2Individual Phase apparent Power Factors (PF)Read
AV9210Apparent PF L3Individual Phase apparent Power Factors (PF)Read
AVmin10000Measured Line FrequencyLine Frequency (Hz)HzRead
AV10010Time Since ResetSeconds since accumulators were resetsRead
AV10020Data Acquisition TickSample count, cleared every minuteRead
AV10080Hardware IDHardware revisionsRead
AV10090FeaturesNew featuresRead
AV10140Clear Accumulated MeasurementsWrite 1234 to reset all energy accumulatorsWrite
AV10150PowerScout Element IDElement index x 256 + number of elementsRead
AV10190Communications protocolSwitches between BACnet and ModbusWrite
AV12001CT1 Phase ShiftCT1 phase shift (degrees)°Write
AV12002CT2 Phase ShiftCT2 phase shift (degrees)°Write
AV12003CT3 Phase ShiftCT3 phase shift (degrees)°Write
AV12011CT1 ValueCT1 ValueWrite
AV12012CT2 ValueCT2 ValueWrite
AV12013CT3 ValueCT3 ValueWrite
AV12030CT Pulse ScalarChanges the scaling of the output pulsesWrite
AV12040Demand WindowDemand window, minutes (default 15)minWrite
AV12050Volts MultiplierMultiply volts values by this scalarVWrite
AV12061CT1 Amps MultiplierMultiply CT1 amps values by this scalarWrite
AV12062CT2 Amps MultiplierMultiply CT2 amps values by this scalarWrite
AV12063CT3 Amps MultiplierMultiply CT3 amps values by this scalarWrite
AV12070Com SettingsSerial settings code, e.g. 901 = 9600 8N1Write
AV12080Service TypeService type: 0 = Wye, 1 = DeltaWrite
AV12090Line FrequencyLine frequency: 50 or 60Write
AV12110Snap Rog Threshold“Snap to Zero” threshold Rogowski CTsWrite
AV12120Snap Volt Threshold“Snap to Zero” threshold for voltageWrite
AV12130CT Type AllWrites same type for all CTs: 1=MilliVolt, 2=RogowskiWrite
AV12131CT1 Type1=MilliVolt, 2=RogowskiWrite
AV12132CT2 Type1=MilliVolt, 2=RogowskiWrite
AV12133CT3 Type1=MilliVolt, 2=RogowskiWrite
AV12134CT1 Voltage SourceIndividual Phase Voltage SourceWrite
AV12135CT2 Voltage SourceIndividual Phase Voltage SourceWrite
AV12136CT3 Voltage SourceIndividual Phase Voltage SourceWrite
AV13020Port 1 output control when used as an on/off—open/closed switchPort 1 switch output: 0 low/closed, 1 high/openWrite
AV13100Digital Port 1 ConfigurationPort 1 pulses: 0 off, 44001 kWh, 44008 kVARh, 44011 kVAhWrite
AV13110Port 1 pulse output relay type0 = normally open, 1 = normally closedWrite
AV14014BBMD IP AddressBBMD IP address, low word (network order)Write
AV14015BBMD IP AddressBBMD IP address, high word (network order)Write
Object ID lookup: DENT Instruments PowerScout 3037 power meter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PowerScout 3037 power meter and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the DENT Instruments PowerScout 3037 power meter

How many BACnet points does the DENT Instruments PowerScout 3037 power meter have?

This list has 119 BACnet objects: 119 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which DENT Instruments PowerScout 3037 power meter BACnet points are writable?

31 of the 119 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official DENT Instruments PowerScout 3037 power meter BACnet documentation?

The source is PowerScout 3037 Operator's Guide (All Things BACnet), published free by DENT Instruments at https://www.dentinstruments.com/wp-content/uploads/2022/04/PS3037_Manual.pdf.

What are the minimum BACnet points to integrate the DENT Instruments PowerScout 3037 power meter?

Start with AV 1030 kW System (Total real power, kW); AV 2000 kWh System Total (Total real energy, kWh); AV 1010 kW Demand System Now (kW demand, latest window); AV 1000 kW Demand System Maximum (Peak kW demand since reset); AV 9030 Apparent PF System (System power factor); AV 4010 Amps System Average (Average current, A); AV 3010 Volts Line to Neutral Average (Average line-to-neutral voltage, V); AV 10000 Measured Line Frequency (Line frequency, Hz).

How do I check these points on the real PowerScout 3037 power meter?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.