Power meter (multifunction) · BACnet points list

Crompton Instruments Integra 1221 / 1222 digital metering system, BACnet MS/TP option module BACnet points list

Updated 12 November 2026Unofficial source

Short answer

The Integra 1221/1222 is a multifunction electricity meter; a plug-on option module adds BACnet MS/TP. All measurements are read-only Analog Inputs (175 objects: per-phase and system voltage, current, power, VA, VAr, power factor, energy, demand, THD, min/max values and vector angles), and 17 Analog Values hold the meter settings such as demand period, CT and VT ratios and baud rate.

This page lists 192 BACnet objects for the Crompton Instruments Integra 1221 / 1222 digital metering system, BACnet MS/TP option module — 14 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Crompton Instruments’s documentation hosted by Colterlec, not by Crompton Instruments itself, so treat it as unofficial.

Manufacturer
Crompton Instruments
Model
Integra 1221 / 1222 digital metering system, BACnet MS/TP option module
Equipment
Power meter (multifunction)
Equipment type
Thermostats, sensors & meters
BACnet objects
192 (14 writable)
Transport
BACnet MS/TP
Firmware
Application software 001.000.016 (PICS dated June 12th 2012)
Also known as
Integra 1221, Integra 1222, INT-1221, INT-1222, Integra 12xx, 3L57501, Crompton Integra BACnet, TE Connectivity Integra
Source document
Integra INT-1221/1222 BACnet MSTP Communication, Setup and Operation Guide · 3L57501 Rev.03 (unofficial copy, hosted by Colterlec)
Download CSV 192 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Crompton Instruments’s current documentation and the live device before use. Not official Crompton Instruments information. Terms of use.

BMS integration notes: Crompton Instruments Integra 1221 / 1222 digital metering system, BACnet MS/TP option module

Integration in brief

Set the MS/TP MAC address (1-127) and identity mode on the meter's Comms menu, then read the AI objects. Nothing has to be written for monitoring; settings live in the AV objects.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 24PSumTotal active power (sum of phases), WRead
AI 30ImpWhImport energy, WhRead
AI 35PSumDmdImport power demand, WRead
AI 21VLNAvgAverage line-to-neutral voltageRead
AI 22AAvgAverage line currentRead
AI 27PFTotTotal system power factorRead
AI 29FrqFrequency, HzRead

Network setup

Watch out for

Crompton Instruments Integra 1221 / 1222 digital metering system, BACnet MS/TP option module BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

192 of 192 shown
Type
Access
Show
Crompton Instruments Integra 1221 / 1222 digital metering system, BACnet MS/TP option module BACnet Points List
DescriptionStates
AI0V1Phase 1 line to neutral voltageVRead
AI1V2Phase 2 line to neutral voltageVRead
AI2V3Phase 3 line to neutral voltageVRead
AI3A1Line 1 currentARead
AI4A2Line 2 currentARead
AI5A3Line 3 currentARead
AI6P1Phase 1 powerWRead
AI7P2Phase 2 powerWRead
AI8P3Phase 3 powerWRead
AI9VA1Phase 1 VAVARead
AI10VA2Phase 2 VAVARead
AI11VA3Phase 3 VAVARead
AI12VAr1Phase 1 VArvarRead
AI13VAr2Phase 2 VArvarRead
AI14VAr3Phase 3 VArvarRead
AI15PF1Phase 1 power factorRead
AI16PF2Phase 2 power factorRead
AI17PF3Phase 3 power factorRead
AI18PA1Phase 1 phase angle°Read
AI19PA2Phase 2 phase angle°Read
AI20PA3Phase 3 phase angle°Read
AImin21VLNAvgAverage line to neutral voltageVRead
AImin22AAvgAverage line currentARead
AI23ASumSum of line currentsARead
AImin24PSumSum of phase powersWRead
AI25VASumSum of phase VAsVARead
AI26VArSumSum of phase VArsvarRead
AImin27PFTotTotal system power factorRead
AI28PATotTotal system phase angle°Read
AImin29FrqSystem frequencyHzRead
AImin30ImpWhImport Watt hoursWhRead
AI31ExpWhExport Watt hoursWhRead
AI32ImpVArhImport VAr hoursvarhRead
AI33ExpVArhExport VAr hoursvarhRead
AI34VAhVA hoursVAhRead
AImin35PSumDmdImport power sum demandWRead
AI36PSumDmdMaxMaximum import power sum demandWRead
AI37VASumDmdVA sum demandVARead
AI38VASumDmdMaxMaximum VA sum demandVARead
AI39ASumDmdCurrent sum demandARead
AI40ASumDmdMaxMaximum current sum demandARead
AI41V1MaxMaximum phase 1 line to neutral voltageVRead
AI42V1MinMinimum phase 1 line to neutral voltageVRead
AI43V2MaxMaximum phase 2 line to neutral voltageVRead
AI44V2MinMinimum phase 2 line to neutral voltageVRead
AI45V3MaxMaximum phase 3 line to neutral voltageVRead
AI46V3MinMinimum phase 3 line to neutral voltageVRead
AI47A1MaxMaximum line 1 currentARead
AI48A1MinMinimum line 1 currentARead
AI49A2MaxMaximum line 2 currentARead
AI50A2MinMinimum line 2 currentARead
AI51A3MaxMaximum line 3 currentARead
AI52A3MinMinimum line 3 currentARead
AI53VLNAvgMaxMaximum average line to neutral voltageVRead
AI54VLNAvgMinMinimum average line to neutral voltageVRead
AI55AAvgMaxMaximum average line currentARead
AI56AAvgMinMinimum average line currentARead
AI57ASumMaxMaximum sum of line currentsARead
AI58ASumMinMinimum sum of line currentsARead
AI59P1MaxMaximum phase 1 powerWRead
AI60P1MinMinimum phase 1 powerWRead
AI61P2MaxMaximum phase 2 powerWRead
AI62P2MinMinimum phase 2 powerWRead
AI63P3MaxMaximum phase 3 powerWRead
AI64P3MinMinimum phase 3 powerWRead
AI65PSumMaxMaximum sum of phase powersWRead
AI66PSumMinMinimum sum of phase powersWRead
AI67VAr1MaxMaximum phase 1 VArsvarRead
AI68VAr1MinMinimum phase 1 VArsvarRead
AI69VAr2MaxMaximum phase 2 VArsvarRead
AI70VAr2MinMinimum phase 2 VArsvarRead
AI71VAr3MaxMaximum phase 3 VArsvarRead
AI72VAr3MinMinimum phase 3 VArsvarRead
AI73VArSumMaxMaximum sum of phase VArsvarRead
AI74VArSumMinMinimum sum of phase VArsvarRead
AI75VA1MaxMaximum phase 1 VAsVARead
AI76VA1MinMinimum phase 1 VAsVARead
AI77VA2MaxMaximum phase 2 VAsVARead
AI78VA2MinMinimum phase 2 VAsVARead
AI79VA3MaxMaximum phase 3 VAsVARead
AI80VA3MinMinimum phase 3 VAsVARead
AI81VASumMaxMaximum sum of phase VAsVARead
AI82VASumMinMinimum sum of phase VAsVARead
AI83FrqMaxMaximum system voltage frequencyHzRead
AI84FrqMinMinimum system voltage frequencyHzRead
AI85V12Voltage line 1 to line 2VRead
AI86V23Voltage line 2 to line 3VRead
AI87V31Voltage line 3 to line 1VRead
AI88VLLAvgAverage line to line voltageVRead
AI89V12MaxMaximum line 1 to line 2 voltageVRead
AI90V12MinMinimum line 1 to line 2 voltageVRead
AI91V23MaxMaximum line 2 to line 3 voltageVRead
AI92V23MinMinimum line 2 to line 3 voltageVRead
AI93V31MaxMaximum line 3 to line 1 voltageVRead
AI94V31MinMinimum line 3 to line 1 voltageVRead
AI95VLLAvgMaxMaximum average line to line voltageVRead
AI96VLLAvgMinMinimum average line to line voltageVRead
AI97ANeuNeutral currentARead
AI98ANeuMaxMaximum neutral currentARead
AI99ANeuMinMinimum neutral currentARead
AI100ANDmdNeutral current demandARead
AI101ANDmdMaxMaximum neutral current demandARead
AI102V1THDPhase 1 line to neutral voltage THD%Read
AI103V2THDPhase 2 line to neutral voltage THD%Read
AI104V3THDPhase 3 line to neutral voltage THD%Read
AI105A1THDLine 1 current THD%Read
AI106A2THDLine 2 current THD%Read
AI107A3THDLine 3 current THD%Read
AI108VTHDAvgAverage line to neutral voltage THD%Read
AI109ATHDAvgAverage line current THD%Read
AI110HRunHours run at over minimum load%Read
AI111PFTotTotal system power factor, times minus one%Read
AI112A1DmdLine 1 current demandARead
AI113A2DmdLine 2 current demandARead
AI114A3DmdLine 3 current demandARead
AI115A1DmdMaxMaximum line 1 current demandARead
AI116A2DmdMaxMaximum line 2 current demandARead
AI117A3DmdMaxMaximum line 3 current demandARead
AI118PRotPhase rotation sequence%Read
AI119VLNBalLine to neutral voltage out of balance%Read
AI120ABalLine current out of balance%Read
AI121VLNBalMaxMaximum line to neutral voltage out of balance%Read
AI122VLNBalMinMinimum line to neutral voltage out of balance%Read
AI123ABalMaxMaximum line current out of balance%Read
AI124ABalMinMinimum line current out of balance%Read
AI125PF1MaxMaximum phase 1 power factor%Read
AI126PF1MinMinimum phase 1 power factor%Read
AI127PF2MaxMaximum phase 2 power factor%Read
AI128PF2MinMinimum phase 2 power factor%Read
AI129PF3MaxMaximum phase 3 power factor%Read
AI130PF3MinMinimum phase 3 power factor%Read
AI131PFTotMaxMaximum total system power factor%Read
AI132PFTotMinMinimum total system power factor%Read
AI133PATotMaxMaximum total system phase angle°Read
AI134PATotMinMinimum total system phase angle°Read
AI135V1THDMaxMaximum phase 1 line to neutral voltage THD%Read
AI136V1THDMinMinimum phase 1 line to neutral voltage THD%Read
AI137V2THDMaxMaximum phase 2 line to neutral voltage THD%Read
AI138V2THDMinMinimum phase 2 line to neutral voltage THD%Read
AI139V3THDMaxMaximum phase 3 line to neutral voltage THD%Read
AI140V3THDMinMinimum phase 3 line to neutral voltage THD%Read
AI141A1THDMaxMaximum line 1 current THD%Read
AI142A1THDMinMinimum line 1 current THD%Read
AI143A2THDMaxMaximum line 2 current THD%Read
AI144A2THDMinMinimum line 2 current THD%Read
AI145A3THDMaxMaximum line 3 current THD%Read
AI146A3THDMinMinimum line 3 current THD%Read
AI147P1DmdImport phase 1 power demandWRead
AI148P2DmdImport phase 2 power demandWRead
AI149P3DmdImport phase 3 power demandWRead
AI150P1DmdMaxImport phase 1 power demand maximumWRead
AI151P2DmdMaxImport phase 2 power demand maximumWRead
AI152P3DmdMaxImport phase 3 power demand maximumWRead
AI153VA1DmdPhase 1 VA demandVARead
AI154VA2DmdPhase 2 VA demandVARead
AI155VA3DmdPhase 3 VA demandVARead
AI156VA1DmdMaxPhase 1 VA demand maximumVARead
AI157VA2DmdMaxPhase 2 VA demand maximumVARead
AI158VA3DmdMaxPhase 3 VA demand maximumVARead
AI159VTHDAvgMaximum average line to neutral voltage THD%Read
AI160VTHDAvgMinimum average line to neutral voltage THD%Read
AI161ATHDAvgMaximum average line current THD%Read
AI162ATHDAvgMinimum average line current THD%Read
AI163PA1MaxMaximum phase 1 phase angle°Read
AI164PA2MaxMaximum phase 2 phase angle°Read
AI165PA3MaxMaximum phase 3 phase angle°Read
AI166PA1MinMinimum phase 1 phase angle°Read
AI167PA2MinMinimum phase 2 phase angle°Read
AI168PA3MinMinimum phase 3 phase angle°Read
AI169V1 Vector AngleV1 vector angle°Read
AI170V2 Vector AngleV2 vector angle°Read
AI171V3 Vector AngleV3 vector angle°Read
AI172A1 Vector AngleA1 vector angle°Read
AI173A2 Vector AngleA2 vector angle°Read
AI174A3 Vector AngleA3 vector angle°Read
AV0DmdDemand time; write 0 to reset the demand periodminWrite
AV1Dmd PeriodDemand period: 8, 15, 20, 30 or 60minWrite
AV2Sys VoltsSystem (VT primary) voltage; password protectedVWrite
AV3Sys CurrentCT primary current; password protectedAWrite
AV4SYS TypeSystem type: 1 = 1ph2w, 2 = 3ph3w, 3 = 3ph4w; protectedWrite
AV5Relay Pulse WidthRelay pulse width, multiples of 20 msWrite
AV6Relay Pulse DivisorRelay pulse rate divisorWrite
AV7PasswordPassword to unlock protected settingsWrite
AV8Sys PowerMaximum system power (read only)WRead
AV9Hi SerialSerial number, high partRead
AV10Lo SerialSerial number, low partRead
AV11Selected Energy ParamRelay selected for editing (no relays on MS/TP)Write
AV12Hrs Run VALoad threshold for the hours-run counterWrite
AV13Reset ParameterWrite 0 to reset energy readingsWrite
AV14Secondary VoltsVT secondary voltage; password protectedVWrite
AV15Energy PrefixEnergy units prefix: unit, k, M or GWrite
AV16BACnet Baud RateMS/TP baud: 9600, 19200, 38400; power cycle to applyWrite
Object ID lookup: Crompton Instruments Integra 1221 / 1222 digital metering system, BACnet MS/TP option module point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Integra 1221 / 1222 digital metering system, BACnet MS/TP option module and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Crompton Instruments Integra 1221 / 1222 digital metering system, BACnet MS/TP option module

How many BACnet points does the Crompton Instruments Integra 1221 / 1222 digital metering system, BACnet MS/TP option module have?

This list has 192 BACnet objects: 175 analog inputs, 17 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Crompton Instruments Integra 1221 / 1222 digital metering system, BACnet MS/TP option module BACnet points are writable?

14 of the 192 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Crompton Instruments Integra 1221 / 1222 digital metering system, BACnet MS/TP option module BACnet documentation?

Crompton Instruments does not publish it on its own website. This list comes from Integra INT-1221/1222 BACnet MSTP Communication, Setup and Operation Guide (3L57501 Rev.03), a copy hosted by Colterlec at https://colterlec.com.au/wp-content/uploads/2023/08/3L57501-INT-12xx-BACnet-MSTP-Operating-Manual-_Colterlec.pdf. Ask Crompton Instruments or its representative for the current revision.

What are the minimum BACnet points to integrate the Crompton Instruments Integra 1221 / 1222 digital metering system, BACnet MS/TP option module?

Start with AI 24 PSum (Total active power (sum of phases), W); AI 30 ImpWh (Import energy, Wh); AI 35 PSumDmd (Import power demand, W); AI 21 VLNAvg (Average line-to-neutral voltage); AI 22 AAvg (Average line current); AI 27 PFTot (Total system power factor); AI 29 Frq (Frequency, Hz).

How do I check these points on the real Integra 1221 / 1222 digital metering system, BACnet MS/TP option module?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: Integra INT-1221/1222 BACnet MSTP Communication, Setup and Operation Guide · 3L57501 Rev.03. Object names, instances and units are reproduced as published; descriptions are our own.