 "manufacturer": "Crompton Instruments",
 "manufacturer_slug": "crompton-instruments",
 "model": "Integra 1221 / 1222 digital metering system, BACnet MS/TP option module",
 "model_slug": "integra-1221-1222-bacnet-mstp",
 "aliases": [
  "Integra 1221",
  "Integra 1222",
  "INT-1221",
  "INT-1222",
  "Integra 12xx",
  "3L57501",
  "Crompton Integra BACnet",
  "TE Connectivity Integra"
 ],
 "equipment_type": "Power meter (multifunction)",
 "applies_to": "Crompton (TE Connectivity) Integra 1221 and 1222 DIN-rail multifunction meters fitted with the plug-on BACnet MS/TP option module.",
 "summary": "The Integra 1221/1222 is a multifunction electricity meter; a plug-on option module adds BACnet MS/TP. All measurements are read-only Analog Inputs (175 objects: per-phase and system voltage, current, power, VA, VAr, power factor, energy, demand, THD, min/max values and vector angles), and 17 Analog Values hold the meter settings such as demand period, CT and VT ratios and baud rate.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": "Application software 001.000.016 (PICS dated June 12th 2012)",
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "In the printed Analog Value table the description column is out of step with the names: the texts for AV 6-10 sit one row low and AV 13's reset text sits on the AV 6 row. The descriptions and access here are paired by content (e.g. the serial-number text goes with Hi Serial, the reset text with Reset Parameter).",
  "AI 32-34 (VAr hours and VA hours) use units the PICS marks as not ASHRAE-defined (enumerations 0xF2 / 0xEF; VA hours is proprietary 257).",
  "AI 110 HRun and AI 111 PFTot are printed with units 'percent'.",
  "AI 159-162 repeat the names VTHDAvg / ATHDAvg for the maximum and minimum values, as printed.",
  "Some Analog Values are protected: write the password to AV 7 first."
 ],
 "source": {
  "title": "Integra INT-1221/1222 BACnet MSTP Communication, Setup and Operation Guide",
  "doc_number": "3L57501 Rev.03",
  "revision_date": null,
  "url": "https://colterlec.com.au/wp-content/uploads/2023/08/3L57501-INT-12xx-BACnet-MSTP-Operating-Manual-_Colterlec.pdf",
  "unofficial": true,
  "host": "Colterlec"
 },
 "integration": {
  "summary": "Set the MS/TP MAC address (1-127) and identity mode on the meter's Comms menu, then read the AI objects. Nothing has to be written for monitoring; settings live in the AV objects.",
  "minimum_points": [
   {
    "ref": "AI 24",
    "name": "PSum",
    "why": "Total active power (sum of phases), W"
   },
   {
    "ref": "AI 30",
    "name": "ImpWh",
    "why": "Import energy, Wh"
   },
   {
    "ref": "AI 35",
    "name": "PSumDmd",
    "why": "Import power demand, W"
   },
   {
    "ref": "AI 21",
    "name": "VLNAvg",
    "why": "Average line-to-neutral voltage"
   },
   {
    "ref": "AI 22",
    "name": "AAvg",
    "why": "Average line current"
   },
   {
    "ref": "AI 27",
    "name": "PFTot",
    "why": "Total system power factor"
   },
   {
    "ref": "AI 29",
    "name": "Frq",
    "why": "Frequency, Hz"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "MS/TP, default 38400 baud, no parity, 1 stop bit; MAC address 1-127, default 001.",
   "The Identity setting picks whether the device instance is the MAC address or a 22-bit instance number.",
   "Baud can also be changed through AV 16; power-cycle the meter to apply."
  ],
  "gotchas": [
   "With the BACnet module fitted no other external protocol is available.",
   "Writing 0 to AV 13 resets the energy readings."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 0,
   "name": "V1",
   "description": "Phase 1 line to neutral voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "V2",
   "description": "Phase 2 line to neutral voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "V3",
   "description": "Phase 3 line to neutral voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "A1",
   "description": "Line 1 current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "A2",
   "description": "Line 2 current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "A3",
   "description": "Line 3 current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "P1",
   "description": "Phase 1 power",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "P2",
   "description": "Phase 2 power",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "P3",
   "description": "Phase 3 power",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "VA1",
   "description": "Phase 1 VA",
   "units": "VA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "VA2",
   "description": "Phase 2 VA",
   "units": "VA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 11,
   "name": "VA3",
   "description": "Phase 3 VA",
   "units": "VA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 12,
   "name": "VAr1",
   "description": "Phase 1 VAr",
   "units": "var",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 13,
   "name": "VAr2",
   "description": "Phase 2 VAr",
   "units": "var",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 14,
   "name": "VAr3",
   "description": "Phase 3 VAr",
   "units": "var",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "PF1",
   "description": "Phase 1 power factor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 16,
   "name": "PF2",
   "description": "Phase 2 power factor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 17,
   "name": "PF3",
   "description": "Phase 3 power factor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 18,
   "name": "PA1",
   "description": "Phase 1 phase angle",
   "units": "°",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 19,
   "name": "PA2",
   "description": "Phase 2 phase angle",
   "units": "°",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 20,
   "name": "PA3",
   "description": "Phase 3 phase angle",
   "units": "°",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 21,
   "name": "VLNAvg",
   "description": "Average line to neutral voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 22,
   "name": "AAvg",
   "description": "Average line current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 23,
   "name": "ASum",
   "description": "Sum of line currents",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 24,
   "name": "PSum",
   "description": "Sum of phase powers",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 25,
   "name": "VASum",
   "description": "Sum of phase VAs",
   "units": "VA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 26,
   "name": "VArSum",
   "description": "Sum of phase VArs",
   "units": "var",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 27,
   "name": "PFTot",
   "description": "Total system power factor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 28,
   "name": "PATot",
   "description": "Total system phase angle",
   "units": "°",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 29,
   "name": "Frq",
   "description": "System frequency",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 30,
   "name": "ImpWh",
   "description": "Import Watt hours",
   "units": "Wh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 31,
   "name": "ExpWh",
   "description": "Export Watt hours",
   "units": "Wh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 32,
   "name": "ImpVArh",
   "description": "Import VAr hours",
   "units": "varh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 33,
   "name": "ExpVArh",
   "description": "Export VAr hours",
   "units": "varh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 34,
   "name": "VAh",
   "description": "VA hours",
   "units": "VAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 35,
   "name": "PSumDmd",
   "description": "Import power sum demand",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 36,
   "name": "PSumDmdMax",
   "description": "Maximum import power sum demand",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 37,
   "name": "VASumDmd",
   "description": "VA sum demand",
   "units": "VA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 38,
   "name": "VASumDmdMax",
   "description": "Maximum VA sum demand",
   "units": "VA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 39,
   "name": "ASumDmd",
   "description": "Current sum demand",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 40,
   "name": "ASumDmdMax",
   "description": "Maximum current sum demand",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 41,
   "name": "V1Max",
   "description": "Maximum phase 1 line to neutral voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 42,
   "name": "V1Min",
   "description": "Minimum phase 1 line to neutral voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 43,
   "name": "V2Max",
   "description": "Maximum phase 2 line to neutral voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 44,
   "name": "V2Min",
   "description": "Minimum phase 2 line to neutral voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 45,
   "name": "V3Max",
   "description": "Maximum phase 3 line to neutral voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 46,
   "name": "V3Min",
   "description": "Minimum phase 3 line to neutral voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 47,
   "name": "A1Max",
   "description": "Maximum line 1 current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 48,
   "name": "A1Min",
   "description": "Minimum line 1 current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 49,
   "name": "A2Max",
   "description": "Maximum line 2 current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 50,
   "name": "A2Min",
   "description": "Minimum line 2 current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 51,
   "name": "A3Max",
   "description": "Maximum line 3 current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 52,
   "name": "A3Min",
   "description": "Minimum line 3 current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 53,
   "name": "VLNAvgMax",
   "description": "Maximum average line to neutral voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 54,
   "name": "VLNAvgMin",
   "description": "Minimum average line to neutral voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 55,
   "name": "AAvgMax",
   "description": "Maximum average line current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 56,
   "name": "AAvgMin",
   "description": "Minimum average line current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 57,
   "name": "ASumMax",
   "description": "Maximum sum of line currents",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 58,
   "name": "ASumMin",
   "description": "Minimum sum of line currents",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 59,
   "name": "P1Max",
   "description": "Maximum phase 1 power",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 60,
   "name": "P1Min",
   "description": "Minimum phase 1 power",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 61,
   "name": "P2Max",
   "description": "Maximum phase 2 power",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 62,
   "name": "P2Min",
   "description": "Minimum phase 2 power",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 63,
   "name": "P3Max",
   "description": "Maximum phase 3 power",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 64,
   "name": "P3Min",
   "description": "Minimum phase 3 power",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65,
   "name": "PSumMax",
   "description": "Maximum sum of phase powers",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 66,
   "name": "PSumMin",
   "description": "Minimum sum of phase powers",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 67,
   "name": "VAr1Max",
   "description": "Maximum phase 1 VArs",
   "units": "var",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 68,
   "name": "VAr1Min",
   "description": "Minimum phase 1 VArs",
   "units": "var",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 69,
   "name": "VAr2Max",
   "description": "Maximum phase 2 VArs",
   "units": "var",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 70,
   "name": "VAr2Min",
   "description": "Minimum phase 2 VArs",
   "units": "var",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 71,
   "name": "VAr3Max",
   "description": "Maximum phase 3 VArs",
   "units": "var",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 72,
   "name": "VAr3Min",
   "description": "Minimum phase 3 VArs",
   "units": "var",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 73,
   "name": "VArSumMax",
   "description": "Maximum sum of phase VArs",
   "units": "var",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 74,
   "name": "VArSumMin",
   "description": "Minimum sum of phase VArs",
   "units": "var",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 75,
   "name": "VA1Max",
   "description": "Maximum phase 1 VAs",
   "units": "VA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 76,
   "name": "VA1Min",
   "description": "Minimum phase 1 VAs",
   "units": "VA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 77,
   "name": "VA2Max",
   "description": "Maximum phase 2 VAs",
   "units": "VA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 78,
   "name": "VA2Min",
   "description": "Minimum phase 2 VAs",
   "units": "VA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 79,
   "name": "VA3Max",
   "description": "Maximum phase 3 VAs",
   "units": "VA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 80,
   "name": "VA3Min",
   "description": "Minimum phase 3 VAs",
   "units": "VA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 81,
   "name": "VASumMax",
   "description": "Maximum sum of phase VAs",
   "units": "VA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 82,
   "name": "VASumMin",
   "description": "Minimum sum of phase VAs",
   "units": "VA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 83,
   "name": "FrqMax",
   "description": "Maximum system voltage frequency",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 84,
   "name": "FrqMin",
   "description": "Minimum system voltage frequency",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 85,
   "name": "V12",
   "description": "Voltage line 1 to line 2",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 86,
   "name": "V23",
   "description": "Voltage line 2 to line 3",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 87,
   "name": "V31",
   "description": "Voltage line 3 to line 1",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 88,
   "name": "VLLAvg",
   "description": "Average line to line voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 89,
   "name": "V12Max",
   "description": "Maximum line 1 to line 2 voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 90,
   "name": "V12Min",
   "description": "Minimum line 1 to line 2 voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 91,
   "name": "V23Max",
   "description": "Maximum line 2 to line 3 voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 92,
   "name": "V23Min",
   "description": "Minimum line 2 to line 3 voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 93,
   "name": "V31Max",
   "description": "Maximum line 3 to line 1 voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 94,
   "name": "V31Min",
   "description": "Minimum line 3 to line 1 voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 95,
   "name": "VLLAvgMax",
   "description": "Maximum average line to line voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 96,
   "name": "VLLAvgMin",
   "description": "Minimum average line to line voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 97,
   "name": "ANeu",
   "description": "Neutral current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 98,
   "name": "ANeuMax",
   "description": "Maximum neutral current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 99,
   "name": "ANeuMin",
   "description": "Minimum neutral current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 100,
   "name": "ANDmd",
   "description": "Neutral current demand",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 101,
   "name": "ANDmdMax",
   "description": "Maximum neutral current demand",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 102,
   "name": "V1THD",
   "description": "Phase 1 line to neutral voltage THD",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 103,
   "name": "V2THD",
   "description": "Phase 2 line to neutral voltage THD",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 104,
   "name": "V3THD",
   "description": "Phase 3 line to neutral voltage THD",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 105,
   "name": "A1THD",
   "description": "Line 1 current THD",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 106,
   "name": "A2THD",
   "description": "Line 2 current THD",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 107,
   "name": "A3THD",
   "description": "Line 3 current THD",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 108,
   "name": "VTHDAvg",
   "description": "Average line to neutral voltage THD",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 109,
   "name": "ATHDAvg",
   "description": "Average line current THD",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 110,
   "name": "HRun",
   "description": "Hours run at over minimum load",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 111,
   "name": "PFTot",
   "description": "Total system power factor, times minus one",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 112,
   "name": "A1Dmd",
   "description": "Line 1 current demand",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 113,
   "name": "A2Dmd",
   "description": "Line 2 current demand",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 114,
   "name": "A3Dmd",
   "description": "Line 3 current demand",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 115,
   "name": "A1DmdMax",
   "description": "Maximum line 1 current demand",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 116,
   "name": "A2DmdMax",
   "description": "Maximum line 2 current demand",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 117,
   "name": "A3DmdMax",
   "description": "Maximum line 3 current demand",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 118,
   "name": "PRot",
   "description": "Phase rotation sequence",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 119,
   "name": "VLNBal",
   "description": "Line to neutral voltage out of balance",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 120,
   "name": "ABal",
   "description": "Line current out of balance",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 121,
   "name": "VLNBalMax",
   "description": "Maximum line to neutral voltage out of balance",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 122,
   "name": "VLNBalMin",
   "description": "Minimum line to neutral voltage out of balance",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 123,
   "name": "ABalMax",
   "description": "Maximum line current out of balance",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 124,
   "name": "ABalMin",
   "description": "Minimum line current out of balance",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 125,
   "name": "PF1Max",
   "description": "Maximum phase 1 power factor",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 126,
   "name": "PF1Min",
   "description": "Minimum phase 1 power factor",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 127,
   "name": "PF2Max",
   "description": "Maximum phase 2 power factor",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 128,
   "name": "PF2Min",
   "description": "Minimum phase 2 power factor",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 129,
   "name": "PF3Max",
   "description": "Maximum phase 3 power factor",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 130,
   "name": "PF3Min",
   "description": "Minimum phase 3 power factor",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 131,
   "name": "PFTotMax",
   "description": "Maximum total system power factor",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 132,
   "name": "PFTotMin",
   "description": "Minimum total system power factor",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 133,
   "name": "PATotMax",
   "description": "Maximum total system phase angle",
   "units": "°",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 134,
   "name": "PATotMin",
   "description": "Minimum total system phase angle",
   "units": "°",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 135,
   "name": "V1THDMax",
   "description": "Maximum phase 1 line to neutral voltage THD",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 136,
   "name": "V1THDMin",
   "description": "Minimum phase 1 line to neutral voltage THD",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 137,
   "name": "V2THDMax",
   "description": "Maximum phase 2 line to neutral voltage THD",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 138,
   "name": "V2THDMin",
   "description": "Minimum phase 2 line to neutral voltage THD",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 139,
   "name": "V3THDMax",
   "description": "Maximum phase 3 line to neutral voltage THD",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 140,
   "name": "V3THDMin",
   "description": "Minimum phase 3 line to neutral voltage THD",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 141,
   "name": "A1THDMax",
   "description": "Maximum line 1 current THD",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 142,
   "name": "A1THDMin",
   "description": "Minimum line 1 current THD",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 143,
   "name": "A2THDMax",
   "description": "Maximum line 2 current THD",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 144,
   "name": "A2THDMin",
   "description": "Minimum line 2 current THD",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 145,
   "name": "A3THDMax",
   "description": "Maximum line 3 current THD",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 146,
   "name": "A3THDMin",
   "description": "Minimum line 3 current THD",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 147,
   "name": "P1Dmd",
   "description": "Import phase 1 power demand",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 148,
   "name": "P2Dmd",
   "description": "Import phase 2 power demand",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 149,
   "name": "P3Dmd",
   "description": "Import phase 3 power demand",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 150,
   "name": "P1DmdMax",
   "description": "Import phase 1 power demand maximum",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 151,
   "name": "P2DmdMax",
   "description": "Import phase 2 power demand maximum",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 152,
   "name": "P3DmdMax",
   "description": "Import phase 3 power demand maximum",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 153,
   "name": "VA1Dmd",
   "description": "Phase 1 VA demand",
   "units": "VA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 154,
   "name": "VA2Dmd",
   "description": "Phase 2 VA demand",
   "units": "VA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 155,
   "name": "VA3Dmd",
   "description": "Phase 3 VA demand",
   "units": "VA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 156,
   "name": "VA1DmdMax",
   "description": "Phase 1 VA demand maximum",
   "units": "VA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 157,
   "name": "VA2DmdMax",
   "description": "Phase 2 VA demand maximum",
   "units": "VA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 158,
   "name": "VA3DmdMax",
   "description": "Phase 3 VA demand maximum",
   "units": "VA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 159,
   "name": "VTHDAvg",
   "description": "Maximum average line to neutral voltage THD",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 160,
   "name": "VTHDAvg",
   "description": "Minimum average line to neutral voltage THD",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 161,
   "name": "ATHDAvg",
   "description": "Maximum average line current THD",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 162,
   "name": "ATHDAvg",
   "description": "Minimum average line current THD",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 163,
   "name": "PA1Max",
   "description": "Maximum phase 1 phase angle",
   "units": "°",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 164,
   "name": "PA2Max",
   "description": "Maximum phase 2 phase angle",
   "units": "°",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 165,
   "name": "PA3Max",
   "description": "Maximum phase 3 phase angle",
   "units": "°",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 166,
   "name": "PA1Min",
   "description": "Minimum phase 1 phase angle",
   "units": "°",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 167,
   "name": "PA2Min",
   "description": "Minimum phase 2 phase angle",
   "units": "°",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 168,
   "name": "PA3Min",
   "description": "Minimum phase 3 phase angle",
   "units": "°",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 169,
   "name": "V1 Vector Angle",
   "description": "V1 vector angle",
   "units": "°",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 170,
   "name": "V2 Vector Angle",
   "description": "V2 vector angle",
   "units": "°",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 171,
   "name": "V3 Vector Angle",
   "description": "V3 vector angle",
   "units": "°",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 172,
   "name": "A1 Vector Angle",
   "description": "A1 vector angle",
   "units": "°",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 173,
   "name": "A2 Vector Angle",
   "description": "A2 vector angle",
   "units": "°",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 174,
   "name": "A3 Vector Angle",
   "description": "A3 vector angle",
   "units": "°",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 0,
   "name": "Dmd",
   "description": "Demand time; write 0 to reset the demand period",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "Dmd Period",
   "description": "Demand period: 8, 15, 20, 30 or 60",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "Sys Volts",
   "description": "System (VT primary) voltage; password protected",
   "units": "V",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "Sys Current",
   "description": "CT primary current; password protected",
   "units": "A",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "SYS Type",
   "description": "System type: 1 = 1ph2w, 2 = 3ph3w, 3 = 3ph4w; protected",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "Relay Pulse Width",
   "description": "Relay pulse width, multiples of 20 ms",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "Relay Pulse Divisor",
   "description": "Relay pulse rate divisor",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "Password",
   "description": "Password to unlock protected settings",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "Sys Power",
   "description": "Maximum system power (read only)",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "Hi Serial",
   "description": "Serial number, high part",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "Lo Serial",
   "description": "Serial number, low part",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "Selected Energy Param",
   "description": "Relay selected for editing (no relays on MS/TP)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "Hrs Run VA",
   "description": "Load threshold for the hours-run counter",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "Reset Parameter",
   "description": "Write 0 to reset energy readings",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "Secondary Volts",
   "description": "VT secondary voltage; password protected",
   "units": "V",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "Energy Prefix",
   "description": "Energy units prefix: unit, k, M or G",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "BACnet Baud Rate",
   "description": "MS/TP baud: 9600, 19200, 38400; power cycle to apply",
   "units": "",
   "access": "W",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/crompton-instruments/integra-1221-1222-bacnet-mstp",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}