Modular water-cooled heat pump chiller controller · BACnet points list

ClimaCool SHC onDemand UCH Heat Pump (CoolLogic) BACnet points list

Updated 28 October 2026

Short answer

ClimaCool's CoolLogic master controller runs the whole bank of up to seven modules and exposes one BACnet device; this list comes from the local access display table, which pairs each screen value with its BACnet object name and point location (AV/BV/MSV and instance). Points cover unit mode, cool/heat run commands, BAS enables, chilled, condenser and source water temperatures, setpoints and resets, and per-module compressor data, alarms and resets.

This page lists 530 BACnet objects for the ClimaCool SHC onDemand UCH Heat Pump (CoolLogic) — 332 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from ClimaCool’s own free documentation, linked below.

Manufacturer
ClimaCool
Model
SHC onDemand UCH Heat Pump (CoolLogic)
Equipment
Modular water-cooled heat pump chiller controller
Equipment type
Chillers
BACnet objects
530 (332 writable)
Transport
BACnet MS/TP, BACnet ARC156, BACnet IP
Firmware
UCH.SHC-HP.12b.13
Default device instance
516800
Also known as
SHC-HP, UCH, SHC onDemand, CoolLogic, UCH.SHC-HP.12b.13, simultaneous heating and cooling chiller
Source document
Local Access Display Table - Product Line UCH, Chiller Type SHC-HP · UCH.SHC-HP.12b.13
Download CSV 530 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: ClimaCool SHC onDemand UCH Heat Pump (CoolLogic)

Integration in brief

Set the master controller DIP switches for the BMS port (MS/TP m protocol and baud), keep the device number at 516800, then set Control Source to BAS. Enable cooling and heating through the BAS enable points, write the leaving-water targets, and monitor unit mode, run commands and supply/return temperatures. Keep polling light: the IOM limits it to 50 points at 20-second intervals or slower.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1control_source_1Control source: Dig Input, Keypad or BASWrite
BV 576enable_bas_cool_1Cool enable from the BASWrite
BV 577enable_bas_heat_1Heat enable from the BASWrite
AV 41chw_temp_stp_1Cooling leaving water target (writable)Write
AV 61cw_temp_stp_1Heating leaving water target (writable)Write
MV 16unit_mode_1Unit mode / reason not runningRead
BV 574run_cool_1Chiller cool run command statusRead
BV 575run_heat_1Chiller heat run command statusRead
AV 17chws_stat_1Chilled water supply (leaving) temperatureRead
AV 42cwr_stat_1Heating water leaving temperatureRead

Enable & remote start

Set the master panel LOCAL-OFF-REMOTE switch to Remote and turn Cool/Heat Mode BAS on; the bank then runs on the BAS command. Alternatives are a hard-wired remote enable relay (Digital Input mode) or keypad enable.

Sensors & values from the BMS

Remote cooling/heating targets can come in as analog inputs (input channel types 'Remote Cool Trg' / 'Remote Heat Trg', 4-20 mA or 2-10 VDC); the resulting values show in rem_chw_stp_stat_1 (AV 243) and rem_cw_stp_stat_1 (AV 246).

Network setup

Watch out for

ClimaCool SHC onDemand UCH Heat Pump (CoolLogic) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

530 of 530 shown
Type
AnalogBinaryMulti-state
Access
Show
ClimaCool SHC onDemand UCH Heat Pump (CoolLogic) BACnet Points List
DescriptionStates
AV16chwr_stat_1CHWR In Temp StatusRead
AVmin17chws_stat_1CHWS Out Temp StatusRead
AV162num_cool_comp_on_1Num of Cool Comp ON at MgrRead
BVmin574run_cool_1Chiller Cool Run CmdReadOff, On
BVmin575run_heat_1Chiller Heat Run CmdReadOff, On
AV43cws_stat_1CWS In Temp Status°FRead
AV14cw_stp_stat_1Active Htg Setpoint°FRead
AVmin42cwr_stat_1CWR Out StatusRead
AV163num_heat_comp_on_1Num of Heat Comp ON at MgrRead
BV14evap_flow_1Evap Flow SWReadNo, Yes
MVmin16unit_mode_1Unit ModeReadSchedule, No Flo/Ph, CHWR High, CWS Low, Sens Error, No ModAvail, Module Down, Compr Down, NonCrit Alm, Normal Run
BV8cond_flow_1Heat FlReadNo, Yes
BV561source_flow_1Source Flow SWReadNo, Yes
AV538sws_stat_1SWS In Temp StatusRead
AV535swr_stat_1SWR Out Status SETUP, ALARMRead
AV165diff_press_heat_load_1Diff Press Heat LoadpsiRead
AV164diff_press_cool_load_1Diff Press Cool LoadpsiRead
AV129diff_press_source_load_1Diff Press SourceRead
BV352m1_comp1_status_5Module 1 Comp 1 StatusReadOff, On
BV388m5_comp1_status_5Module 5 Comp 1 StatusReadOff, On
BV355m1_comp2_status_5Module 1 Comp 2 StatusReadOff, On
BV392m5_comp2_status_5Module 5 Comp 2 StatusReadOff, On
BV359m2_comp1_status_5Module 2 Comp 1 StatusReadOff, On
BV411m6_comp1_status_5Module 6 Comp 1 StatusReadOff, On
BV362m2_comp2_status_5Module 2 Comp 2 StatusReadOff, On
BV423m6_comp2_status_5Module 6 Comp 2 StatusReadOff, On
BV96m3_comp1_status_5Module 3 Comp 1 StatusReadOff, On
BV715m7_comp1_status_5Module 7 Comp 1 StatusReadOff, On
BV147m3_comp2_status_5Module 3 Comp 2 StatusReadOff, On
BV725m7_comp2_status_5Module 7 Comp 2 StatusReadOff, On
BV378m4_comp1_status_5Module 4 Comp 1 StatusReadOff, On
BV382m4_comp2_status_5Module 4 Comp 2 StatusReadOff, On
AV144stg1_clg_pid_1Stage 1 Cooling PIDRead
AV145stg1_htg_pid_1Stage 1 Heating PIDRead
BV2run_1Chiller Run CmdReadChiller OFF, Chiller ON
AV8step_clgpid_65t_1Clg Step PID Value for 65TRead
AV131step_htgpid_65t_1Htg Step PID Value for 65TRead
AV98m1_size_st_1Mod 1 SizeRead
AV175m1_c1_suc_pres_stat_5Module 1 Comp 1 Suction PressureRead
AV205m1_c1_suc_superheat_5Module 1 Comp 1 Suction SuperheatRead
AV179m1_c1_suct_temp_stat_5Module 1 Comp 1 Suction TempRead
AV87m1_load_temp_stat_5M1 Load Leaving TempRead
AV113m1_c1_disch_pres_stat_5Module 1 Comp 1 Disch PressRead
AV104m1_src_temp_stat_5M1 Source Leaving TempRead
AV194m1_c1_cycles_5Module 1 Comp 1 CyclesRead
BV591m1_c1_min_runtime_5Module 1 Compr 1 Min RunReadOff, On
BV589m1_c1_minimum_off_5Module 1 Comp 1 Min OffReadOff, On
AV362m1_lowest_head_pressure_5Module 1 Lowest Cond Head PressureRead
AV508m1_cdmv_pidout_5Module 1 Cond Vlv PID OutRead
AV509m1_cdmv_scaled_pidout_5Module 1 Cond Vlv Scaled PID OutRead
AV571m1_highest_suct_pressure_5Module 1 Highest Evap Suct PressureRead
AV569m1_evmv_pidout_5Module 1 Evap Vlv PID OutRead
AV570m1_evmv_scaled_pidout_5Module 1 Evap Vlv Scaled PID OutRead
AV211m1_c2_suc_pres_stat_5Module 1 Comp 2 Suction PressureRead
AV212m1_c2_suc_superheat_5Module 1 Comp 2 Suction SuperheatRead
AV213m1_c2_suct_temp_stat_5Module 1 Comp 2 Suction TempRead
AV204m1_c2_disch_pres_stat_5Module 1 Comp 2 Discharge PressureRead
AV207m1_c2_cycles_5Module 1 Comp 2 CyclesRead
BV592m1_c2_min_runtime_5Module 1 Compr 2 Min RunReadOff, On
BV590m1_c2_minimum_off_5Module 1 Comp 2 Min OffReadOff, On
AV269m1_c1_rtime_1Module 1 Comp 1 RuntimeRead
AV270m1_c2_rtime_1Module 1 Comp 2 RuntimeRead
AV275m2_c1_rtime_1Module 2 Comp 1 RuntimeRead
AV276m2_c2_rtime_1Module 2 Comp 2 RuntimeRead
AV277m3_c1_rtime_1Module 3 Comp 1 RuntimeRead
AV278m3_c2_rtime_1Module 3 Comp 2 RuntimeRead
AV279m4_c1_rtime_1Module 4 Comp 1 RuntimeRead
AV280m4_c2_rtime_1Module 4 Comp 2 RuntimeRead
AV281m5_c1_rtime_1Module 5 Comp 1 RuntimeRead
AV282m5_c2_rtime_1Module 5 Comp 2 RuntimeRead
AV283m6_c1_rtime_1Module 6 Comp 1 RuntimeRead
AV284m6_c2_rtime_1Module 6 Comp 2 RuntimeRead
AV285m7_c1_rtime_1Module 7 Comp 1 RuntimeRead
AV286m7_c2_rtime_1Module 7 Comp 2 RuntimeRead
AV462m5_c1_cycles_5Module 5 Comp 1 CyclesRead
AV467m5_c2_cycles_5Module 5 Comp 2 CyclesRead
AV214m2_c1_cycles_5Module 2 Comp 1 CyclesRead
AV472m6_c1_cycles_5Module 6 Comp 1 CyclesRead
AV221m2_c2_cycles_5Module 2 Comp 2 CyclesRead
AV477m6_c2_cycles_5Module 6 Comp 2 CyclesRead
AV103m3_c1_cycles_5Module 3 Comp 1 CyclesRead
AV654m7_c1_cycles_5Module 7 Comp 1 CyclesRead
AV116m3_c2_cycles_5Module 3 Comp 2 CyclesRead
AV661m7_c2_cycles_5Module 7 Comp 2 CyclesRead
AV215m4_c1_cycles_5Module 4 Comp 1 CyclesRead
AV224m4_c2_cycles_5Module 4 Comp 2 CyclesRead
AV99m2_size_st_1Mod 2 SizeRead
AV84m3_size_st_1Mod 3 SizeRead
AV444m4_size_st_1Mod 4 SizeRead
AV445m5_size_st_1Mod 5 SizeRead
AV446m6_size_st_1Mod 6 SizeRead
AV52m7_size_st_1Mod 7 SizeRead
BV160bypass_go_1Use Header Bypass ValvesWriteNo, Yes
AV106hdr_byp_delay_before_close_5Header Bypass Delay Before CloseWrite
AV273close_vlv_delay_5Close Mot Vlv DelayWrite
BV831src_hdr_ext_byp_vlv_1Source Header Ext Bypass ValveReadClosed, Open
BV829cl_hdr_ext_byp_vlv_1Cool Header Ext Bypass ValveReadClosed, Open
BV830ht_hdr_ext_byp_vlv_1Heat Header Ext Bypass ValveReadClosed, Open
BV796m1_cool_open_5Module 1 Cool OpenReadClosed, Open
BV797m1_heat_open_5Module 1 Heat OpenReadClosed, Open
BV798m2_cool_open_5Module 2 Cool OpenReadClosed, Open
BV799m2_heat_open_5Module 2 Heat OpenReadClosed, Open
BV800m3_cool_open_5Module 3 Cool OpenReadClosed, Open
BV801m3_heat_open_5Module 3 Heat OpenReadClosed, Open
BV802m4_cool_open_5Module 4 Cool OpenReadClosed, Open
BV803m4_heat_open_5Module 4 Heat OpenReadClosed, Open
BV804m5_cool_open_5Module 5 Cool OpenReadClosed, Open
BV805m5_heat_open_5Module 5 Heat OpenReadClosed, Open
BV806m6_cool_open_5Module 6 Cool OpenReadClosed, Open
BV807m6_heat_open_5Module 6 Heat OpenReadClosed, Open
BV808m7_cool_open_5Module 7 Cool OpenReadClosed, Open
BV809m7_heat_open_5Module 7 Heat OpenReadClosed, Open
BV262m1_ht_closed_5Module 1 Heat MV ClosedReadNo, Yes
BV273m2_ht_closed_5Module 2 Heat MV ClosedReadNo, Yes
BV277m3_ht_closed_5Module 3 Heat MV ClosedReadNo, Yes
BV279m4_ht_closed_5Module 4 Heat MV ClosedReadNo, Yes
BV281m5_ht_closed_5Module 5 Heat MV ClosedReadNo, Yes
BV283m6_ht_closed_5Module 6 Heat MV ClosedReadNo, Yes
BV285m7_ht_closed_5Module 7 Heat MV ClosedReadNo, Yes
BV258m1_cl_closed_5Module 1 Cool MV ClosedReadNo, Yes
BV269m2_cl_closed_5Module 2 Cool MV ClosedReadNo, Yes
BV275m3_cl_closed_5Module 3 Cool MV ClosedReadNo, Yes
BV278m4_cl_closed_5Module 4 Cool MV ClosedReadNo, Yes
BV280m5_cl_closed_5Module 5 Cool MVClosedReadNo, Yes
BV282m6_cl_closed_5Module 6 Cool MV ClosedReadNo, Yes
BV284m7_cl_closed_5Module 7 Cool MVClosedReadNo, Yes
BV323force_archive_1Force ArchiveWriteNo, Yes
MV2control_type_1Control TypeWriteCool Cntrl, Heat Cntrl, Heat Rcvry, Simultaneous
BVmin577enable_bas_heat_1Heat Enable (BAS)WriteOff, On
BVmin576enable_bas_cool_1Cool Enable (BAS)WriteOff, On
MVmin1control_source_1Control SourceWriteDig Input, Keypad, BAS
BV111enable_keypad_1Unit Enable (keypad)WriteOff, On
MV20mod_comp_ref_type_5Module Compr Ref TypeWrite410a, 134a
MV33chiller_model_type_5Chiller Model TypeWriteUCW, UCH, UCR
MV8chiller_model_size_5Chiller Model SizeWriteUC030, UC050, UC070
BV308separate_reversing_vlvs_5Use Separate Reversing Valve OutputsWriteNo, Yes
AV48cool_design_dt_1FULL LD COOL DES TDWrite
AV49heat_design_dt_1FULL LD HEAT DES TDWrite
AV523startup_alarm_delay_1Start-Up Alarm DelaysecWrite
AVmin41chw_temp_stp_1COOL LVG TRG°FWrite
AV96min_chw_temp_stp_1MIN COOL TRG LIM°FWrite
AV89max_chw_temp_stp_1MAX COOL TRG LIM°FWrite
AV243rem_chw_stp_stat_1Remote CHW Setpoint°FRead
AV92max_neg_chw_stp_reset_1MAX NEG DEM LIM COOL RESET°FWrite
AV94max_pos_chw_stp_reset_1MAX POS DEM LIM COOL RESET°FWrite
AV242rem_chw_stp_reset_1Remote CHW Setpoint Reset°FRead
AV13chw_stp_stat_1Active CHW Setpoint°FRead
AV29cl_cntrl_spt_offset_1Cool Control Setpoint OffsetWrite
AVmin61cw_temp_stp_1HEAT LVG TRG°FWrite
AV97min_cw_temp_stp_1MIN HEAT TRG LIM°FWrite
AV91max_cw_temp_stp_1MAX HEAT TRG LIM°FWrite
AV246rem_cw_stp_stat_1Remote CW Setpoint°FRead
AV188max_neg_cw_stp_reset_1MAX NEG DEM LIM HEAT RESET°FWrite
AV190max_pos_cw_stp_reset_1MAX POS DEM LIM HEAT RESET°FWrite
AV247rem_cw_stp_reset_1Remote CW Dem Lim Stpt Reset°FRead
AV34ht_cntrl_spt_offset_1HeatControl Setpoint OffsetWrite
MV23inp_10_point_type_1Input Chnl 10 TypeWriteNone, Remote Heat Trg
MV21an_inp10_typ_1AI10 Type Rem Ht TrgWriteNONE, 4-20 ma, 2-10VDC
MV27inp_6_point_type_1Input Chnl 6 TypeWriteNone, Remote Cool Trg
MV30an_inp6_typ_1AI6 Type Off is 0-10WriteNONE, 4-20 ma, 2-10VDC
AV367source_ht_trg_reset_1SOURCE HT TRG RESETWrite
AV363max_source_htg_trg_reset_1MAX SOURCE HTG TRG RES°FWrite
AV364min_source_htg_trg_reset_1MIN SOURCE HTG TRG RESET°FWrite
AV365source_htg_trg_max_reset_1SOURCE HEAT TRG Max RES°FWrite
AV366source_htg_trg_min_reset_1SOURCE HEAT TRG MIN RES°FWrite
AV690source_cl_trg_reset_1SOURCE CL TRG RESETWrite
AV688max_source_clg_trg_reset_1MAX SOURCE CLG TRG RES°FWrite
AV689min_source_clg_trg_reset_1MIN SOURCE CLG TRG RESET°FWrite
AV691source_clg_trg_max_reset_1SOURCE COOL TRG Max RES°FWrite
AV692source_clg_trg_min_reset_1SOURCE COOL TRG MIN RES°FWrite
BV105reset_oor_1Reset Sensor OOR AlarmWriteOff, On
BV27reset_1LOCK OUT RESETWriteOff, On
BV690m1_reset_all_slave_alarms_5Reset M1 All Slave AlarmsWriteNo, Yes
BV691m2_reset_all_slave_alarms_5Reset M2 All Slave AlarmsWriteNo, Yes
BV692m3_reset_all_slave_alarms_5Reset M3 All Slave AlarmsWriteNo, Yes
BV693m4_reset_all_slave_alarms_5Reset M4 All Slave AlarmsWriteNo, Yes
BV694m5_reset_all_slave_alarms_5Reset M5 All Slave AlarmsWriteNo, Yes
BV695m6_reset_all_slave_alarms_5Reset M6 All Slave AlarmsWriteNo, Yes
BV734m7_reset_all_slave_alarms_5Reset M7 All Slave AlarmsWriteNo, Yes
BV351m1_comp1_fail_5Module 1 Comp 1 FailReadNo, Yes
BV38m1reset_c1_alrm_5M1C1 Alarm ResetWriteNo, Yes
BV354m1_comp2_fail_5Module 1 Comp 2 FailReadNo, Yes
BV41m1reset_c2_alrm_5M1C2 Alarm ResetWriteNo, Yes
BV357m2_comp1_fail_5Module 2 Comp 1 FailReadNo, Yes
BV48m2reset_c1_alrm_5M2C1 Alarm ResetWriteNo, Yes
BV360m2_comp2_fail_5Module 2 Comp 2 FailReadNo, Yes
BV42m2reset_c2_alrm_5M2C2 Alarm ResetWriteNo, Yes
BV93m3_comp1_fail_5Module 3 Comp 1 FailReadNo, Yes
BV84m3reset_c1_alrm_5M3C1 Alarm ResetWriteNo, Yes
BV97m3_comp2_fail_5Module 3 Comp 2 FailReadNo, Yes
BV88m3reset_c2_alrm_5M3C2 Alarm ResetWriteNo, Yes
BV375m4_comp1_fail_5Module 4 Comp 1 FailReadNo, Yes
BV266m4reset_c1_alrm_5M4C1 Alarm ResetWriteNo, Yes
BV379m4_comp2_fail_5Module 4 Comp 2 FailReadNo, Yes
BV271m4reset_c2_alrm_5M4C2 Alarm ResetWriteNo, Yes
BV385m5_comp1_fail_5Module 5 Comp 1 FailReadNo, Yes
BV345m5reset_c1_alrm_5M5C1 Alarm ResetWriteNo, Yes
BV389m5_comp2_fail_5Module 5 Comp 2 FailReadNo, Yes
BV349m5reset_c2_alrm_5M5C2 Alarm ResetWriteNo, Yes
BV402m6_comp1_fail_5Module 6 Comp 1 FailReadNo, Yes
BV366m6reset_c1_alrm_5M6C1 Alarm ResetWriteNo, Yes
BV412m6_comp2_fail_5Module 6 Comp 2 FailReadNo, Yes
BV370m6reset_c2_alrm_5M6C2 Alarm ResetWriteNo, Yes
BV711m7_comp1_fail_5Module 7 Comp 1 FailReadNo, Yes
BV697m7reset_c1_alrm_5M7C1 Alarm ResetWriteNo, Yes
BV721m7_comp2_fail_5Module 7 Comp 2 FailReadNo, Yes
BV701m7reset_c2_alrm_5M7C2 Alarm ResetWriteNo, Yes
BV175m1_freeze_alrm_5Module 1 Freeze AlarmReadNo, Yes
BV56m1_reset_freeze_5Reset Mot1 Vlv FailWriteNo, Yes
BV157m1_cwr_alrm_5Module 1 Leaving Cond Water AlarmReadNo, Yes
BV190m2_freeze_alrm_5Module 2 Freeze AlarmReadNo, Yes
BV57m2_reset_freeze_5Reset Mot2 Vlv FailWriteNo, Yes
BV668m2_cwr_alrm_5Module 2 Leaving Cond Water AlarmReadNo, Yes
BV192m3_freeze_alrm_5Module 3 Freeze AlarmReadNo, Yes
BV150m3_reset_freeze_5Reset Mot3 Vlv FailWriteNo, Yes
BV669m3_cwr_alrm_5Module 3 Leaving Cond Water AlarmReadNo, Yes
BV193m4_freeze_alrm_5Module 4 Freeze AlarmReadNo, Yes
BV432m4_reset_freeze_5Reset Mot4 Vlv FailWriteNo, Yes
BV670m4_cwr_alrm_5Module 4 Leaving Cond Water AlarmReadNo, Yes
BV194m5_freeze_alrm_5Module 5 Freeze AlarmReadNo, Yes
BV443m5_reset_freeze_5Reset Mot5 Vlv FailWriteNo, Yes
BV676m5_cwr_alrm_5Module 5 Leaving Cond Water AlarmReadNo, Yes
BV195m6_freeze_alrm_5Module 6 Freeze AlarmReadNo, Yes
BV444m6_reset_freeze_5Reset Mot6 Vlv FailWriteNo, Yes
BV100m6_cwr_alrm_5Module 6 Leaving Cond Water AlarmReadNo, Yes
BV732m7_freeze_alrm_5Module 7 Freeze AlarmReadNo, Yes
BV735m7_reset_freeze_5Reset Mot7 Vlv FailWriteNo, Yes
BV101m7_cwr_alrm_5Module 7 Leaving Cond Water AlarmReadNo, Yes
BV40m1reset_c1_rtim_5M1C1 Runtime ResetWriteNo, Yes
BV45m1c1_cycles_reset_5M1C1 Cycles ResetWriteNo, Yes
BV44m1reset_c2_rtim_5M1C2 Runtime ResetWriteNo, Yes
BV46m1c2_cycles_reset_5M1C2 Cycles ResetWriteNo, Yes
BV51m2reset_c1_rtim_5M2C1 Runtime ResetWriteNo, Yes
BV49m2c1_cycles_reset_5M2C1 Cycles ResetWriteNo, Yes
BV54m2reset_c2_rtim_5M2C2 Runtime ResetWriteNo, Yes
BV52m2c2_cycles_reset_5M2C2 Cycles ResetWriteNo, Yes
BV87m3reset_c1_rtim_5M3C1 Runtime ResetWriteNo, Yes
BV85m3c1_cycles_reset_5M3C1 Cycles ResetWriteNo, Yes
BV91m3reset_c2_rtim_5M3C2 Runtime ResetWriteNo, Yes
BV89m3c2_cycles_reset_5M3C2 Cycles ResetWriteNo, Yes
BV270m4reset_c1_rtim_5M4C1 Runtime ResetWriteNo, Yes
BV267m4c1_cycles_reset_5M4C1 Cycles ResetWriteNo, Yes
BV343m4reset_c2_rtim_5M4C2 Runtime ResetWriteNo, Yes
BV341m4c2_cycles_reset_5M4C2 Cycles ResetWriteNo, Yes
BV348m5reset_c1_rtim_5M5C1 Runtime ResetWriteNo, Yes
BV346m5c1_cycles_reset_5M5C1 Cycles ResetWriteNo, Yes
BV364m5reset_c2_rtim_5M5C2 Runtime ResetWriteNo, Yes
BV350m5c2_cycles_reset_5M5C2 Cycles ResetWriteNo, Yes
BV369m6reset_c1_rtim_5M6C1 Runtime ResetWriteNo, Yes
BV367m6c1_cycles_reset_5M6C1 Cycles ResetWriteNo, Yes
BV373m6reset_c2_rtim_5M6C2 Runtime ResetWriteNo, Yes
BV371m6c2_cycles_reset_5M6C2 Cycles ResetWriteNo, Yes
BV700m7reset_c1_rtim_5M7C1 Runtime ResetWriteNo, Yes
BV698m7c1_cycles_reset_5M7C1 Cycles ResetWriteNo, Yes
BV704m7reset_c2_rtim_5M7C2 Runtime ResetWriteNo, Yes
BV702m7c2_cycles_reset_5M7C2 Cycles ResetWriteNo, Yes
BV605m1_comp1_oor_5Module 1 Comp 1 Sensor OORReadNo, Yes
BV601m1_oorsl_reset_5M1 Sensor OOR ResetWriteNo, Yes
BV606m1_comp2_oor_5Module 1 Comp 2 Sensor OORReadNo, Yes
BV607m2_comp1_oor_5Module 2 Comp 1 Sensor OORReadNo, Yes
BV602m2_oorsl_reset_5M2 Sensor OOR ResetWriteNo, Yes
BV608m2_comp2_oor_5Module 2 Comp 2 Sensor OORReadNo, Yes
BV609m3_comp1_oor_5Module 3 Comp 1 Sensor OORReadNo, Yes
BV603m3_oorsl_reset_5M3 Sensor OOR ResetWriteNo, Yes
BV610m3_comp2_oor_5Module 3 Comp 2 Sensor OORReadNo, Yes
BV611m4_comp1_oor_5Module 4 Comp 1 Sensor OORReadNo, Yes
BV604m4_oorsl_reset_5M4 Sensor OOR ResetWriteNo, Yes
BV612m4_comp2_oor_5Module 4 Comp 2 Sensor OORReadNo, Yes
BV674m5_comp1_oor_5Module 5 Comp 1 Sensor OORReadNo, Yes
BV477m5_oorsl_reset_5M5 Sensor OOR ResetWriteNo, Yes
BV675m5_comp2_oor_5Module 5 Comp 2 Sensor OORReadNo, Yes
BV707m6_comp1_oor_5Module 6 Comp 1 Sensor OORReadNo, Yes
BV696m6_oorsl_reset_5M6 Sensor OOR ResetWriteNo, Yes
BV708m6_comp2_oor_5Module 6 Comp 2 Sensor OORReadNo, Yes
BV713m7_comp1_oor_5Module 7 Comp 1 Sensor OORReadNo, Yes
BV706m7_oorsl_reset_5M7 Sensor OOR ResetWriteNo, Yes
BV723m7_comp2_oor_5Module 7 Comp 2 Sensor OORReadNo, Yes
BV199m1_c1_lo_suc_psi_unld_5Module 1 Comp 1 Suct Pressure UnloadReadOff, On
BV203m1_c2_lo_suc_psi_unld_5Module 1 Comp 2 Suct Pressure UnloadReadOff, On
BV650m1_c1_lolo_suc_psi_unld_5Module 1 Comp 1 XLow Suct Pressure UnloadReadOff, On
BV651m1_c2_lolo_suc_psi_unld_5Module 1 Comp 2 XLow Suct Pressure UnloadReadOff, On
BV200m1_c1_lo_suc_tmp_unld_5Module 1 Comp 1 Suct Temp UnloadReadOff, On
BV204m1_c2_lo_suc_tmp_unld_5Module 1 Comp 2 Suct Temp UnloadReadOff, On
BV205m1_freeze_trg_unld_5Module 1 Freeze trg UnloadReadOff, On
BV652m1_cwr_trg_unld_5Module 1 CWR trg UnloadReadOff, On
BV197m1_c1_hi_dis_psi_unld_5Module 1 Comp 1 Dis Pressure UnloadReadOff, On
BV201m1_c2_hi_dis_psi_unld_5Module 1 Comp 2 Dis Pressure UnloadReadOff, On
BV218m1_c1_hi_suc_sh_unld_5Module 1 Comp 1 Dis Temp UnloadReadOff, On
BV276m1_c2_hi_suc_sh_unld_5Module 1 Comp 2 Dis Temp UnloadReadOff, On
BV161m1_c1_no_run_unld_5Module 1 Comp 1 No Run UnloadReadOff, On
BV164m1_c2_no_run_unld_5Module 1 Comp 2 No Run UnloadReadOff, On
BV393mod_disch_psi_avail_5Module DISCH PSI AVAILWriteOff, On
BV396mod_suc_psi_avail_5Module SUC PSI AVAILWriteOff, On
BV397mod_suc_tmp_avail_5Module SUC TMP AVAILWriteOff, On
BV173mod_cwr_avail_5Module CWR AVAILWriteOff, On
BV409mod_cwr_lo_enable_5Module CWR Enable Low LimitWriteOff, On
BV400mod_chs_hi_enable_5Module CWR Enable High LimitWriteOff, On
AV370mod_hi_disch_press_sp_410_ucw_5High Head Press Sp 410a UCWWrite
AV369mod_hi_disch_press_sp_410_uchr_5High Head Press Sp 410a UCH- UCRWrite
AV390mod_hi_disch_press_sp_134_uchr_5High Head Press Sp 134a UCH- UCRWrite
AV421mod_hi_disch_press_sp_5Module Hi Disch Press SetptRead
AV439mod_lo_disch_press_sp_134_5Low Head Press Sp 134aWrite
AV507mod_lo_disch_press_sp_410_5Low Head Press Sp 410aWrite
AV499mod_lo_disch_press_sp_5Module Lo Disch Press SetptRead
AV391mod_high_suct_press_sp_410_5High Suction Press Sp 410aWrite
AV438mod_high_suct_press_sp_134_5High Suction Press Sp 134aWrite
AV581mod_high_suct_press_sp_5Module High Suction Press SetptRead
AV588mod_low_low_press_sp_5Module LO-LO SUC PSI SetpointWrite
AV589mod_lo_suc_psi_delay_5Module LO SUC PSI DelayWrite
AV252mod_heat_lo_suction_tmp_5Module Heat Low Suction TempWrite
AV237mod_cool_lo_suction_tmp_5Module Cool Low Suction TempWrite
AV231mod_heat_lo_suc_press_sp_410_5Heat Low Suction Press Sp 410aWrite
AV95mod_cool_lo_suc_press_sp_410_5Cool Low Suction Press Sp 410aWrite
AV203mod_heat_lo_suc_press_sp_134_5Heat Low Suction Press Sp 134aWrite
AV93mod_cool_lo_suc_press_sp_134_5Cool Low Suction Press Sp 134aWrite
AV245mod_heat_low_press_sp_5Module Heat Low Suction Press SetptRead
AV236mod_cool_low_press_sp_5Module Cool Low Suction Press SetptRead
AV430mod_lo_suc_supht_sp_5Module Low Suct SuperHt SetptWrite
AV585mod_hi_suc_supht_sp_5Module High Suct SuperHt SetptWrite
AV427mod_lo_disc_supht_sp_5Module Low Disch SuperHt SetptWrite
AV413mod_cmpr_min_run_5Module Compr Min Run TimeWrite
AV412mod_cmpr_off_delay_5Module Compr Min Off DelayWrite
AV414mod_comp_stat_alm_delay_5Module Compr Status Alarm DelayWrite
AV232mod_cool_freeze_trg_sp_5Module Cool Freeze Target SetpointWrite
AV234mod_cool_high_evap_lvg_tmp_5Module Cool High Evaporator Leaving TempWrite
AV235mod_cool_low_cond_lvg_tmp_5Module Cool Low Condenser Leaving Temp. @ StartupWrite
AV233mod_cool_cwr_trg_sp_5Module Cool High Cond Leaving Temp at StartupWrite
AV238mod_heat_freeze_trg_sp_5Module Heat Freeze Target SetpointWrite
AV241mod_heat_high_evap_lvg_tmp_5Module Heat High Evaporator Leaving Temp at StartupWrite
AV244mod_heat_low_cond_lvg_tmp_5Module Heat Low Condenser Leaving Temp. @ StartupWrite
AV240mod_heat_cwr_trg_sp_5Module Heat High Cond Leaving Temp at StartupWrite
BV47m1_man_mode_5M1 Manual Mode EnableWriteOff, On
BV39m1c1_man_run_5M1C1 Manual RunWriteOff, On
BV43m1c2_man_run_5M1C2 Manual RunWriteOff, On
BV782m1_mancool_run_5M1 Manual Cool RunWriteOff, On
BV783m1_manheat_run_5M1 Manual Heat RunWriteOff, On
AV356man_mode_time_5Man Mode TimeWrite
BV820m1_forceman_5M1 Force Termination of Manual ModeWriteNo, Yes
AV101m1_load_temp_cp_5M1 Load Temp Calib. PointWrite
AV111m1_src_temp_cp_5M1 SRC Temp Calib. PointWrite
AV392m1c1_disch_pres_cp_5M1C1 DIS Pressure Calib. PointWrite
AV396m1c2_disch_pres_cp_5M1C2 DIS Pressure Calib. PointWrite
AV394m1c1_suc_pres_cp_5M1C1 SUC Pressure Calib. PointWrite
AV398m1c2_suc_pres_cp_5M1C2 SUC Pressure Calib. PointWrite
AV395m1c1_suc_tmp_cp_5M1C1 SUC Temp Calib. PointWrite
AV399m1c2_suc_tmp_cp_5M1C2 SUC Temp Calib. PointWrite
BV309m1c1_disable_comp_5M1C1 Disable ComprWriteNo, Yes
BV310m1c2_disable_comp_5M1C2 Disable ComprWriteNo, Yes
BV311m2c1_disable_comp_5M2C1 Disable ComprWriteNo, Yes
BV312m2c2_disable_comp_5M2C2 Disable ComprWriteNo, Yes
BV313m3c1_disable_comp_5M3C1 Disable ComprWriteNo, Yes
BV314m3c2_disable_comp_5M3C2 Disable ComprWriteNo, Yes
BV315m4c1_disable_comp_5M4C1 Disable ComprWriteNo, Yes
BV316m4c2_disable_comp_5M4C2 Disable ComprWriteNo, Yes
BV317m5c1_disable_comp_5M5C1 Disable ComprWriteNo, Yes
BV318m5c2_disable_comp_5M5C2 Disable ComprWriteNo, Yes
BV319m6c1_disable_comp_5M6C1 Disable ComprWriteNo, Yes
BV320m6c2_disable_comp_5M6C2 Disable ComprWriteNo, Yes
BV321m7c1_disable_comp_5M7C1 Disable ComprWriteNo, Yes
BV322m7c2_disable_comp_5M7C2 Disable ComprWriteNo, Yes
AV423mod_hi_dis_psi_retry_5Module HI DIS PSI RETRYWrite
AV425mod_lo_suc_psi_retry_5Module LO SUC PSI RETRYWrite
AV418mod_freeze_trg_retry_5Module FREEZE TRG RETRYWrite
AV582mod_cwr_trg_retry_5Module CWR TRG RETRYWrite
AV426mod_lo_suc_tmp_retry_5Module LO SUC TMP RETRYWrite
AV268mod_compr_norun_retry_5Module Compressor No-Run RETRYWrite
BV599mod1_unused_1Module 1 UnusedWriteNo, Yes
BV600mod2_unused_1Module 2 UnusedWriteNo, Yes
BV672mod3_unused_1Module 3 UnusedWriteNo, Yes
BV736mod4_unused_1Module 4 UnusedWriteNo, Yes
BV743mod5_unused_1Module 5 UnusedWriteNo, Yes
BV755mod6_unused_1Module 6 UnusedWriteNo, Yes
BV779mod7_unused_1Module 7 UnusedWriteNo, Yes
AV695m1_mod_number_5M1 Module NumberWrite
AV696m2_mod_number_5M2 Module NumberWrite
AV697m3_mod_number_5M3 Module NumberWrite
AV698m4_mod_number_5M4 Module NumberWrite
AV699m5_mod_number_5M5 Module NumberWrite
AV700m6_mod_number_5M6 Module NumberWrite
AV701m7_mod_number_5M7 Module NumberWrite
BV117fix_module1_cool_1Fix Mod1 as CoolWriteNo, Yes
BV9fix_module1_heat_1Fix Mod1 as HeatWriteNo, Yes
BV152never_close_mod1_1Never Close Module #1WriteNo, Yes
BV12fix_module2_cool_1Fix Mod2 as CoolWriteNo, Yes
BV460fix_module2_heat_1Fix Mod2 as HeatWriteNo, Yes
BV156never_close_mod2_1Never Close Module #2WriteNo, Yes
BV552fix_module3_cool_1Fix Mod3 as CoolWriteNo, Yes
BV553fix_module3_heat_1Fix Mod3 as HeatWriteNo, Yes
BV158never_close_mod3_1Never Close Module #3WriteNo, Yes
BV555fix_module4_cool_1Fix Mod4 as CoolWriteNo, Yes
BV556fix_module4_heat_1Fix Mod4 as HeatWriteNo, Yes
BV159never_close_mod4_1Never Close Module #4WriteNo, Yes
BV568fix_module5_cool_1Fix Mod5 as CoolWriteNo, Yes
BV569fix_module5_heat_1Fix Mod5 as HeatWriteNo, Yes
BV162never_close_mod5_1Never Close Module #5WriteNo, Yes
BV571fix_module6_cool_1Fix Mod6 as CoolWriteNo, Yes
BV572fix_module6_heat_1Fix Mod6 as HeatWriteNo, Yes
BV253never_close_mod6_1Never Close Module #6WriteNo, Yes
BV573fix_module7_cool_1Fix Mod7 as CoolWriteNo, Yes
BV118fix_module7_heat_1Fix Mod7 as HeatWriteNo, Yes
BV163never_close_mod7_1Never Close Module #7WriteNo, Yes
BV293use_ht_cl_mod_fract_1Use Heat/Cool Module FractionsWriteNo, Yes
AV274fract_cool_mods_1Fraction of Cool Mods vs Total ModsWrite
AV253fract_heat_mods_1Fraction of Heat Mods vs Total ModsWrite
AV124fract_cool_cmpr_overshoot_1Fraction of Cool Compressor PID OvershootWrite
AV181fract_heat_cmpr_overshoot_1Fraction of Heat Compressor PID OvershootWrite
MV28inp_7_point_type_1Input Chnl 7 TypeWriteNone, Demand Lim Cl TrgRst, Demand Lim Max #Cmp
MV31an_inp7_typ_1AI7 Type Rem Cl Trg or Dem LimWriteNONE, 4-20 ma, 2-10VDC
BV827man_sel_clg_dem_lim_1Manual Select Cool Demand LimitingWriteOff, On
AV693voltin_clg_comp_dem_lim_1Volts In for Cool Comp Demand Limiting°FWrite
MV5inp_1_5_point_type_1Input Chnl 1-5 TypeWriteNone, Demand Lim Ht TrgRst, Demand Lim Max #Cmp
MV4an_inp1_5_typ_1AI1-3 Type Rem Cl Trg or Dem LimWriteNONE, 4-20 ma, 2-10VDC
BV828man_sel_htg_dem_lim_1Manual Select Heat Demand LimitingWriteOff, On
AV694voltin_htg_comp_dem_lim_1Volts In for Heat Comp Demand Limiting°FWrite
AV25clg_interval_1Clg PID IntervalsecWrite
BV75use_calc_prop_integ_1Use Calculated P and IWriteNo, Yes
AV26clg_p_gain_1Clg PID P-gainWrite
AV24clg_i_gain_1Clg PID I-gainWrite
AV138clg_rise_1Clg PID RisesecWrite
AV135clg_fall_1Clg PID FallWrite
BV843use_double_rise_1Use Rise DoublerWriteNo, Yes
AV55clg_dblrise_1Clg PID Double Rise AmountsecWrite
AV3max_cool_ramp_rate_1MAX COOL RAMP RATEWrite
AV132clg_db1_1Clg PID DB1Write
AV617pid_diff_fact_1PID Differential FactorWrite
BV306use_auto_pid_reset_1Use Automatic PID Reset FeatureWriteNo, Yes
AV287delay_before_auto_pid_reset_1Delay Before Auto PID ResetsecWrite
BV305use_auto_pid_reset_alm_1Use Automatic PID Reset AlarmWriteNo, Yes
AV68htg_interval_1Htg PID IntervalsecWrite
AV69htg_p_gain_1Htg PID P-gainWrite
AV67htg_i_gain_1Htg PID I-gainWrite
AV182htg_rise_1Htg PID RisesecWrite
AV178htg_fall_1Htg PID FallWrite
AV56htg_dblrise_1Htg PID Double Rise AmountsecWrite
AV9max_heat_ramp_rate_1MAX HEAT RAMP RATEWrite
AV174htg_db1_1Htg PID DB1Write
MV34mot_vlv_opt_5Motorized Valve OptionsWriteNo Mot Vlvs, Evap Mot Vlvs Only, Cond&Evap Mot Vlvs
AV415mod_cond_vlv_alm_delay_5Module COND VLV ALM DELAYWrite
AV416mod_evap_vlv_alm_delay_5Module EVAP VLV ALM DELAYWrite
AV503cdmv_interval_5CDMV PID IntervalsecWrite
AV505cdmv_p_gain_5CDMV PID P-gainWrite
AV502cdmv_i_gain_5CDMV PID I-gainWrite
AV500cdmv_pid_db_5CDMV PID DeadbandWrite
AV506cdmv_pid_ramp_5CDMV PID RAMPWrite
AV386evmv_interval_5EVMV PID IntervalsecWrite
AV388evmv_p_gain_5EVMV PID P-gainWrite
AV385evmv_i_gain_5EVMV PID I-gainWrite
AV383evmv_pid_db_5EVMV PID DeadbandWrite
AV389evmv_pid_ramp_5EVMV PID RAMPWrite
AV387evmv_pid_mnpct_5EVMV PID Minimum PercentWrite
BV845use_hi_sh_cutout_5Use Hi Superheat for Compr CutoutWriteNo, Yes
AV592mod_hp_pos_adj_5Module Head Pressure Positive AdjWrite
AV594mod_sp_neg_adj_5Module Suction Pressure Negative AdjWrite
AV81mod_min_cdmv_adj_heat_5Module Minimum MV Adjustment HeatWrite
AV79cdmv_pid_mnpct_heat_5CDMV PID Minimum Percent HeatRead
AV80mod_min_cdmv_adj_cool_5Module Minimum MV Adjustment CoolWrite
AV78cdmv_pid_mnpct_cool_5CDMV PID Minimum Percent CoolRead
BV844use_hi_hp_comp_5Use Hi Head Pressure Compr for Low HP CtrlWriteNo, Yes
AV371mod_defaulthp410_usehihp_5Default HP R-410A Using High Head PressureWrite
AV372mod_defaulthp410_uselowhp_5Default HP R-410A Using Low Head PressureWrite
AV239mod_defaulthp134_usehihp_5Default HP R-134a Using High Head PressureWrite
AV368mod_defaulthp134_uselowhp_5Default HP R-134a Using Low Head PressureWrite
AV590mod_default_hp_5Module Default Head PressureRead
AV441mod_default_sp_410_5Module Default Suction Press 410aWrite
AV440mod_default_sp_134_5Module Default Suction Press 134aWrite
BV583use_diff_pr_flow_sens_1Use Diff Press Flow SensorsWriteNo, Yes
AV227max_delta_temp_ld_ht_5Max Delta Temp- Load HeatWrite
AV218max_delta_temp_ld_cl_5Max Delta Temp- Load CoolWrite
AV254max_delta_temp_src_5Max Delta Temp- SourceWrite
AV90diff_pr_trip_mult_5Diff Pressure Trip MultiplierWrite
BV874use_pre_calc_dif_pr_setpt_1Use Pre-Calc Diff Pr CutoutWriteNo, Yes
AV622lo_ld_cool_diff_pr_1Lo LD Cool Diff PressureWrite
AV623lo_ld_heat_diff_pr_1Lo LD Heat Diff PressureWrite
AV139lo_src_diff_pr_1LO SRC Diff PressWrite
AV130act_lo_diff_press_ld_cl_1Actual Low Diff Press Trip Load CoolRead
AV134act_lo_diff_press_ld_ht_1Actual Low Diff Press Trip Load HeatRead
AV586act_lo_diff_press_src_1Actual Low Diff Press Trip SourceRead
AV206est_watts_5Estimated Watts°FRead
AV161est_tons_5Estimated Tons°FRead
AV115est_kw_per_ton_5Estimated Kw Per Ton°FRead
MV9an_inp11_typ_1AI11 TypeWrite4-20 ma, 0-10VDC, 0-5 VDC
AV86min_scale_src_diff_pr_1Min Source Diff Press Scale @ 0Write
AV57max_scale_src_diff_pr_1Max Source Diff Press ScaleWrite
MV6an_inp8_typ_1AI8 TypeWrite4-20 ma, 0-10VDC, 0-5 VDC
AV70min_scale_cool_diff_pr_1Min Cool Diff Press Scale @ 0Write
AV53max_scale_cool_diff_pr_1Max Cool Diff Press ScaleWrite
MV3an_inp1-13_typ_1AI1-13 TypeWrite4-20 ma, 0-10VDC, 0-5 VDC
AV85min_scale_heat_diff_pr_1Min Heat Diff Press Scale @ 0Write
AV54max_scale_heat_diff_pr_1Max Heat Diff Press ScaleWrite
AV303min_dp_oor_offset_1Min DP Scale Offset for OOR°FWrite
AV302max_dp_oor_offset_1Max DP Scale Offset for OOR°FWrite
AV18chwr_lo_lim_1CHWR Enable Lo LimitWrite
AV19chwr_hi_lim_1CHWR Enable Hi LimitWrite
AV73chws_low_lim_1LO EVAP LVG TMPWrite
AV64chws_hi_lim_1HI EVAP LVG TMPWrite
AV200cws_low_lim_1LO CND LVG TMPWrite
AV199cws_hi_lim_1HI COND LVG TMPWrite
AV66cwr_lo_lim_1CWR Enable Lo LimitWrite
AV63cwr_hi_lim_1CWR Enable Hi LimitWrite
AV71lo_ambient_tmp_1LO AMBIENT TMP°FWrite
AV62hi_ambient_tmp_1HI AMBIENT TMP°FWrite
AV537sws_lo_lim_1SWS Enable Lo LimitWrite
AV536sws_hi_lim_1SWS Enable Hi LimitWrite
AV530swr_lo_lim_1SWR Enable Lo LimitWrite
AV529swr_hi_lim_1SWR Enable Hi LimitWrite
AV146off_delay_time_1OFF MODE DELAY TIMEWrite
AV75mod_open_vlv_on_delay_5Module Open VLV ON DELAYWrite
AV587mod_heat_vlv_on_delay_5Module Heat VLV ON DELAYWrite
AV30mod_cool_vlv_on_delay_5Module Cool VLV ON DELAYWrite
AV150o562_1Start-Up DelaysecWrite
AV149n003_1Stage Up DelaysecWrite
AV148n006_1Stage Down DelaysecWrite
AV51cmprlead_refr_runtime_1Compr Lead Refresh on RuntimeWrite
AV74runtime_refresh_1Runtime RefreshWrite
AV250safety_ind_delay2_5SAFETY INDEX 2 DELAY STG DWNsecWrite
AV249safety_ind_delay1_5SAFETY INDEX 1 DELAYsecWrite
BV137m01trimcool_5Module 1 Trim CoolWriteNo, Yes
BV172m02trimcool_5Module 2 Trim CoolWriteNo, Yes
BV188m03trimcool_5Module 3 Trim CoolWriteNo, Yes
BV198m04trimcool_5Module 4 Trim CoolWriteNo, Yes
BV207m05trimcool_5Module 5 Trim CoolWriteNo, Yes
BV217m06trimcool_5Module 6 Trim CoolWriteNo, Yes
BV221m07trimcool_5Module 7 Trim CoolWriteNo, Yes
BV139m01trimheat_5Module 1 Trim HeatWriteNo, Yes
BV174m02trimheat_5Module 2 Trim HeatWriteNo, Yes
BV191m03trimheat_5Module 3 Trim HeatWriteNo, Yes
BV202m04trimheat_5Module 4 Trim HeatWriteNo, Yes
BV212m05trimheat_5Module 5 Trim HeatWriteNo, Yes
BV219m06trimheat_5Module 6 Trim HeatWriteNo, Yes
BV225m07trimheat_5Module 7 Trim HeatWriteNo, Yes

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SHC onDemand UCH Heat Pump (CoolLogic) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the ClimaCool SHC onDemand UCH Heat Pump (CoolLogic)

How many BACnet points does the ClimaCool SHC onDemand UCH Heat Pump (CoolLogic) have?

This list has 530 BACnet objects: 251 analog values, 261 binary values, 18 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which ClimaCool SHC onDemand UCH Heat Pump (CoolLogic) BACnet points are writable?

332 of the 530 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official ClimaCool SHC onDemand UCH Heat Pump (CoolLogic) BACnet documentation?

The source is Local Access Display Table - Product Line UCH, Chiller Type SHC-HP (UCH.SHC-HP.12b.13), published free by ClimaCool at https://files.climacoolcorp.com/Display-Tables/Control_Access_Display_Table_SHC-HP.pdf.

What are the minimum BACnet points to integrate the ClimaCool SHC onDemand UCH Heat Pump (CoolLogic)?

Start with MV 1 control_source_1 (Control source: Dig Input, Keypad or BAS); BV 576 enable_bas_cool_1 (Cool enable from the BAS); BV 577 enable_bas_heat_1 (Heat enable from the BAS); AV 41 chw_temp_stp_1 (Cooling leaving water target (writable)); AV 61 cw_temp_stp_1 (Heating leaving water target (writable)); MV 16 unit_mode_1 (Unit mode / reason not running); BV 574 run_cool_1 (Chiller cool run command status); BV 575 run_heat_1 (Chiller heat run command status); AV 17 chws_stat_1 (Chilled water supply (leaving) temperature); AV 42 cwr_stat_1 (Heating water leaving temperature).

How do I enable BMS control of the ClimaCool SHC onDemand UCH Heat Pump (CoolLogic)?

Set the master panel LOCAL-OFF-REMOTE switch to Remote and turn Cool/Heat Mode BAS on; the bank then runs on the BAS command. Alternatives are a hard-wired remote enable relay (Digital Input mode) or keypad enable.

Can the BMS supply sensor values to the ClimaCool SHC onDemand UCH Heat Pump (CoolLogic)?

Remote cooling/heating targets can come in as analog inputs (input channel types 'Remote Cool Trg' / 'Remote Heat Trg', 4-20 mA or 2-10 VDC); the resulting values show in rem_chw_stp_stat_1 (AV 243) and rem_cw_stp_stat_1 (AV 246).

How do I check these points on the real SHC onDemand UCH Heat Pump (CoolLogic)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: Local Access Display Table - Product Line UCH, Chiller Type SHC-HP · UCH.SHC-HP.12b.13. Object names, instances and units are reproduced as published; descriptions are our own.