 "manufacturer": "ClimaCool",
 "manufacturer_slug": "climacool",
 "model": "SHC onDemand UCH Heat Pump (CoolLogic)",
 "model_slug": "shc-ondemand-uch-heat-pump",
 "aliases": [
  "SHC-HP",
  "UCH",
  "SHC onDemand",
  "CoolLogic",
  "UCH.SHC-HP.12b.13",
  "simultaneous heating and cooling chiller"
 ],
 "equipment_type": "Modular water-cooled heat pump chiller controller",
 "applies_to": "ClimaCool SHC onDemand water-cooled modular simultaneous heating/cooling heat pumps (UCH, SHC-HP) with the CoolLogic master controller.",
 "summary": "ClimaCool's CoolLogic master controller runs the whole bank of up to seven modules and exposes one BACnet device; this list comes from the local access display table, which pairs each screen value with its BACnet object name and point location (AV/BV/MSV and instance). Points cover unit mode, cool/heat run commands, BAS enables, chilled, condenser and source water temperatures, setpoints and resets, and per-module compressor data, alarms and resets.",
 "bacnet_transport": [
  "BACnet MS/TP",
  "BACnet ARC156",
  "BACnet IP"
 ],
 "firmware": "UCH.SHC-HP.12b.13",
 "default_device_instance": 516800,
 "access_inferred": false,
 "notes": [
  "Table is for software UCH.SHC-HP.12b.13; other software versions may number points differently.",
  "About 90 display values (e.g. calibration offsets, bin-load counters, runtime adjust) have no BACnet point location and are not included.",
  "Per-module points (prefix m1_ to m7_) only apply to fitted modules.",
  "Units are taken from the sample default values; many analog values show no unit in the table."
 ],
 "source": {
  "title": "Local Access Display Table - Product Line UCH, Chiller Type SHC-HP",
  "doc_number": "UCH.SHC-HP.12b.13",
  "revision_date": null,
  "url": "https://files.climacoolcorp.com/Display-Tables/Control_Access_Display_Table_SHC-HP.pdf"
 },
 "points": [
  {
   "type": "AV",
   "instance": 16,
   "name": "chwr_stat_1",
   "description": "CHWR In Temp Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "chws_stat_1",
   "description": "CHWS Out Temp Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 162,
   "name": "num_cool_comp_on_1",
   "description": "Num of Cool Comp ON at Mgr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 574,
   "name": "run_cool_1",
   "description": "Chiller Cool Run Cmd",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 575,
   "name": "run_heat_1",
   "description": "Chiller Heat Run Cmd",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "cws_stat_1",
   "description": "CWS In Temp Status",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "cw_stp_stat_1",
   "description": "Active Htg Setpoint",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "cwr_stat_1",
   "description": "CWR Out Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 163,
   "name": "num_heat_comp_on_1",
   "description": "Num of Heat Comp ON at Mgr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 14,
   "name": "evap_flow_1",
   "description": "Evap Flow SW",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "MV",
   "instance": 16,
   "name": "unit_mode_1",
   "description": "Unit Mode",
   "units": "",
   "access": "R",
   "states": "Schedule, No Flo/Ph, CHWR High, CWS Low, Sens Error, No ModAvail, Module Down, Compr Down, NonCrit Alm, Normal Run"
  },
  {
   "type": "BV",
   "instance": 8,
   "name": "cond_flow_1",
   "description": "Heat Fl",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 561,
   "name": "source_flow_1",
   "description": "Source Flow SW",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "AV",
   "instance": 538,
   "name": "sws_stat_1",
   "description": "SWS In Temp Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 535,
   "name": "swr_stat_1",
   "description": "SWR Out Status SETUP, ALARM",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 165,
   "name": "diff_press_heat_load_1",
   "description": "Diff Press Heat Load",
   "units": "psi",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 164,
   "name": "diff_press_cool_load_1",
   "description": "Diff Press Cool Load",
   "units": "psi",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 129,
   "name": "diff_press_source_load_1",
   "description": "Diff Press Source",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 352,
   "name": "m1_comp1_status_5",
   "description": "Module 1 Comp 1 Status",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 388,
   "name": "m5_comp1_status_5",
   "description": "Module 5 Comp 1 Status",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 355,
   "name": "m1_comp2_status_5",
   "description": "Module 1 Comp 2 Status",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 392,
   "name": "m5_comp2_status_5",
   "description": "Module 5 Comp 2 Status",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 359,
   "name": "m2_comp1_status_5",
   "description": "Module 2 Comp 1 Status",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 411,
   "name": "m6_comp1_status_5",
   "description": "Module 6 Comp 1 Status",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 362,
   "name": "m2_comp2_status_5",
   "description": "Module 2 Comp 2 Status",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 423,
   "name": "m6_comp2_status_5",
   "description": "Module 6 Comp 2 Status",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 96,
   "name": "m3_comp1_status_5",
   "description": "Module 3 Comp 1 Status",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 715,
   "name": "m7_comp1_status_5",
   "description": "Module 7 Comp 1 Status",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 147,
   "name": "m3_comp2_status_5",
   "description": "Module 3 Comp 2 Status",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 725,
   "name": "m7_comp2_status_5",
   "description": "Module 7 Comp 2 Status",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 378,
   "name": "m4_comp1_status_5",
   "description": "Module 4 Comp 1 Status",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 382,
   "name": "m4_comp2_status_5",
   "description": "Module 4 Comp 2 Status",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "AV",
   "instance": 144,
   "name": "stg1_clg_pid_1",
   "description": "Stage 1 Cooling PID",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 145,
   "name": "stg1_htg_pid_1",
   "description": "Stage 1 Heating PID",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "run_1",
   "description": "Chiller Run Cmd",
   "units": "",
   "access": "R",
   "states": "Chiller OFF, Chiller ON"
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "step_clgpid_65t_1",
   "description": "Clg Step PID Value for 65T",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 131,
   "name": "step_htgpid_65t_1",
   "description": "Htg Step PID Value for 65T",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 98,
   "name": "m1_size_st_1",
   "description": "Mod 1 Size",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 175,
   "name": "m1_c1_suc_pres_stat_5",
   "description": "Module 1 Comp 1 Suction Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 205,
   "name": "m1_c1_suc_superheat_5",
   "description": "Module 1 Comp 1 Suction Superheat",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 179,
   "name": "m1_c1_suct_temp_stat_5",
   "description": "Module 1 Comp 1 Suction Temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 87,
   "name": "m1_load_temp_stat_5",
   "description": "M1 Load Leaving Temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 113,
   "name": "m1_c1_disch_pres_stat_5",
   "description": "Module 1 Comp 1 Disch Press",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 104,
   "name": "m1_src_temp_stat_5",
   "description": "M1 Source Leaving Temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 194,
   "name": "m1_c1_cycles_5",
   "description": "Module 1 Comp 1 Cycles",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 591,
   "name": "m1_c1_min_runtime_5",
   "description": "Module 1 Compr 1 Min Run",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 589,
   "name": "m1_c1_minimum_off_5",
   "description": "Module 1 Comp 1 Min Off",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "AV",
   "instance": 362,
   "name": "m1_lowest_head_pressure_5",
   "description": "Module 1 Lowest Cond Head Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 508,
   "name": "m1_cdmv_pidout_5",
   "description": "Module 1 Cond Vlv PID Out",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 509,
   "name": "m1_cdmv_scaled_pidout_5",
   "description": "Module 1 Cond Vlv Scaled PID Out",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 571,
   "name": "m1_highest_suct_pressure_5",
   "description": "Module 1 Highest Evap Suct Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 569,
   "name": "m1_evmv_pidout_5",
   "description": "Module 1 Evap Vlv PID Out",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 570,
   "name": "m1_evmv_scaled_pidout_5",
   "description": "Module 1 Evap Vlv Scaled PID Out",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 211,
   "name": "m1_c2_suc_pres_stat_5",
   "description": "Module 1 Comp 2 Suction Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 212,
   "name": "m1_c2_suc_superheat_5",
   "description": "Module 1 Comp 2 Suction Superheat",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 213,
   "name": "m1_c2_suct_temp_stat_5",
   "description": "Module 1 Comp 2 Suction Temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 204,
   "name": "m1_c2_disch_pres_stat_5",
   "description": "Module 1 Comp 2 Discharge Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 207,
   "name": "m1_c2_cycles_5",
   "description": "Module 1 Comp 2 Cycles",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 592,
   "name": "m1_c2_min_runtime_5",
   "description": "Module 1 Compr 2 Min Run",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 590,
   "name": "m1_c2_minimum_off_5",
   "description": "Module 1 Comp 2 Min Off",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "AV",
   "instance": 269,
   "name": "m1_c1_rtime_1",
   "description": "Module 1 Comp 1 Runtime",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 270,
   "name": "m1_c2_rtime_1",
   "description": "Module 1 Comp 2 Runtime",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 275,
   "name": "m2_c1_rtime_1",
   "description": "Module 2 Comp 1 Runtime",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 276,
   "name": "m2_c2_rtime_1",
   "description": "Module 2 Comp 2 Runtime",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 277,
   "name": "m3_c1_rtime_1",
   "description": "Module 3 Comp 1 Runtime",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 278,
   "name": "m3_c2_rtime_1",
   "description": "Module 3 Comp 2 Runtime",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 279,
   "name": "m4_c1_rtime_1",
   "description": "Module 4 Comp 1 Runtime",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 280,
   "name": "m4_c2_rtime_1",
   "description": "Module 4 Comp 2 Runtime",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 281,
   "name": "m5_c1_rtime_1",
   "description": "Module 5 Comp 1 Runtime",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 282,
   "name": "m5_c2_rtime_1",
   "description": "Module 5 Comp 2 Runtime",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 283,
   "name": "m6_c1_rtime_1",
   "description": "Module 6 Comp 1 Runtime",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 284,
   "name": "m6_c2_rtime_1",
   "description": "Module 6 Comp 2 Runtime",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 285,
   "name": "m7_c1_rtime_1",
   "description": "Module 7 Comp 1 Runtime",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 286,
   "name": "m7_c2_rtime_1",
   "description": "Module 7 Comp 2 Runtime",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 462,
   "name": "m5_c1_cycles_5",
   "description": "Module 5 Comp 1 Cycles",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 467,
   "name": "m5_c2_cycles_5",
   "description": "Module 5 Comp 2 Cycles",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 214,
   "name": "m2_c1_cycles_5",
   "description": "Module 2 Comp 1 Cycles",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 472,
   "name": "m6_c1_cycles_5",
   "description": "Module 6 Comp 1 Cycles",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 221,
   "name": "m2_c2_cycles_5",
   "description": "Module 2 Comp 2 Cycles",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 477,
   "name": "m6_c2_cycles_5",
   "description": "Module 6 Comp 2 Cycles",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 103,
   "name": "m3_c1_cycles_5",
   "description": "Module 3 Comp 1 Cycles",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 654,
   "name": "m7_c1_cycles_5",
   "description": "Module 7 Comp 1 Cycles",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 116,
   "name": "m3_c2_cycles_5",
   "description": "Module 3 Comp 2 Cycles",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 661,
   "name": "m7_c2_cycles_5",
   "description": "Module 7 Comp 2 Cycles",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 215,
   "name": "m4_c1_cycles_5",
   "description": "Module 4 Comp 1 Cycles",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 224,
   "name": "m4_c2_cycles_5",
   "description": "Module 4 Comp 2 Cycles",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 99,
   "name": "m2_size_st_1",
   "description": "Mod 2 Size",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 84,
   "name": "m3_size_st_1",
   "description": "Mod 3 Size",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 444,
   "name": "m4_size_st_1",
   "description": "Mod 4 Size",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 445,
   "name": "m5_size_st_1",
   "description": "Mod 5 Size",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 446,
   "name": "m6_size_st_1",
   "description": "Mod 6 Size",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 52,
   "name": "m7_size_st_1",
   "description": "Mod 7 Size",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 160,
   "name": "bypass_go_1",
   "description": "Use Header Bypass Valves",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "AV",
   "instance": 106,
   "name": "hdr_byp_delay_before_close_5",
   "description": "Header Bypass Delay Before Close",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 273,
   "name": "close_vlv_delay_5",
   "description": "Close Mot Vlv Delay",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 831,
   "name": "src_hdr_ext_byp_vlv_1",
   "description": "Source Header Ext Bypass Valve",
   "units": "",
   "access": "R",
   "states": "Closed, Open"
  },
  {
   "type": "BV",
   "instance": 829,
   "name": "cl_hdr_ext_byp_vlv_1",
   "description": "Cool Header Ext Bypass Valve",
   "units": "",
   "access": "R",
   "states": "Closed, Open"
  },
  {
   "type": "BV",
   "instance": 830,
   "name": "ht_hdr_ext_byp_vlv_1",
   "description": "Heat Header Ext Bypass Valve",
   "units": "",
   "access": "R",
   "states": "Closed, Open"
  },
  {
   "type": "BV",
   "instance": 796,
   "name": "m1_cool_open_5",
   "description": "Module 1 Cool Open",
   "units": "",
   "access": "R",
   "states": "Closed, Open"
  },
  {
   "type": "BV",
   "instance": 797,
   "name": "m1_heat_open_5",
   "description": "Module 1 Heat Open",
   "units": "",
   "access": "R",
   "states": "Closed, Open"
  },
  {
   "type": "BV",
   "instance": 798,
   "name": "m2_cool_open_5",
   "description": "Module 2 Cool Open",
   "units": "",
   "access": "R",
   "states": "Closed, Open"
  },
  {
   "type": "BV",
   "instance": 799,
   "name": "m2_heat_open_5",
   "description": "Module 2 Heat Open",
   "units": "",
   "access": "R",
   "states": "Closed, Open"
  },
  {
   "type": "BV",
   "instance": 800,
   "name": "m3_cool_open_5",
   "description": "Module 3 Cool Open",
   "units": "",
   "access": "R",
   "states": "Closed, Open"
  },
  {
   "type": "BV",
   "instance": 801,
   "name": "m3_heat_open_5",
   "description": "Module 3 Heat Open",
   "units": "",
   "access": "R",
   "states": "Closed, Open"
  },
  {
   "type": "BV",
   "instance": 802,
   "name": "m4_cool_open_5",
   "description": "Module 4 Cool Open",
   "units": "",
   "access": "R",
   "states": "Closed, Open"
  },
  {
   "type": "BV",
   "instance": 803,
   "name": "m4_heat_open_5",
   "description": "Module 4 Heat Open",
   "units": "",
   "access": "R",
   "states": "Closed, Open"
  },
  {
   "type": "BV",
   "instance": 804,
   "name": "m5_cool_open_5",
   "description": "Module 5 Cool Open",
   "units": "",
   "access": "R",
   "states": "Closed, Open"
  },
  {
   "type": "BV",
   "instance": 805,
   "name": "m5_heat_open_5",
   "description": "Module 5 Heat Open",
   "units": "",
   "access": "R",
   "states": "Closed, Open"
  },
  {
   "type": "BV",
   "instance": 806,
   "name": "m6_cool_open_5",
   "description": "Module 6 Cool Open",
   "units": "",
   "access": "R",
   "states": "Closed, Open"
  },
  {
   "type": "BV",
   "instance": 807,
   "name": "m6_heat_open_5",
   "description": "Module 6 Heat Open",
   "units": "",
   "access": "R",
   "states": "Closed, Open"
  },
  {
   "type": "BV",
   "instance": 808,
   "name": "m7_cool_open_5",
   "description": "Module 7 Cool Open",
   "units": "",
   "access": "R",
   "states": "Closed, Open"
  },
  {
   "type": "BV",
   "instance": 809,
   "name": "m7_heat_open_5",
   "description": "Module 7 Heat Open",
   "units": "",
   "access": "R",
   "states": "Closed, Open"
  },
  {
   "type": "BV",
   "instance": 262,
   "name": "m1_ht_closed_5",
   "description": "Module 1 Heat MV Closed",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 273,
   "name": "m2_ht_closed_5",
   "description": "Module 2 Heat MV Closed",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 277,
   "name": "m3_ht_closed_5",
   "description": "Module 3 Heat MV Closed",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 279,
   "name": "m4_ht_closed_5",
   "description": "Module 4 Heat MV Closed",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 281,
   "name": "m5_ht_closed_5",
   "description": "Module 5 Heat MV Closed",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 283,
   "name": "m6_ht_closed_5",
   "description": "Module 6 Heat MV Closed",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 285,
   "name": "m7_ht_closed_5",
   "description": "Module 7 Heat MV Closed",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 258,
   "name": "m1_cl_closed_5",
   "description": "Module 1 Cool MV Closed",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 269,
   "name": "m2_cl_closed_5",
   "description": "Module 2 Cool MV Closed",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 275,
   "name": "m3_cl_closed_5",
   "description": "Module 3 Cool MV Closed",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 278,
   "name": "m4_cl_closed_5",
   "description": "Module 4 Cool MV Closed",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 280,
   "name": "m5_cl_closed_5",
   "description": "Module 5 Cool MVClosed",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 282,
   "name": "m6_cl_closed_5",
   "description": "Module 6 Cool MV Closed",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 284,
   "name": "m7_cl_closed_5",
   "description": "Module 7 Cool MVClosed",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 323,
   "name": "force_archive_1",
   "description": "Force Archive",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "control_type_1",
   "description": "Control Type",
   "units": "",
   "access": "W",
   "states": "Cool Cntrl, Heat Cntrl, Heat Rcvry, Simultaneous"
  },
  {
   "type": "BV",
   "instance": 577,
   "name": "enable_bas_heat_1",
   "description": "Heat Enable (BAS)",
   "units": "",
   "access": "W",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 576,
   "name": "enable_bas_cool_1",
   "description": "Cool Enable (BAS)",
   "units": "",
   "access": "W",
   "states": "Off, On"
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "control_source_1",
   "description": "Control Source",
   "units": "",
   "access": "W",
   "states": "Dig Input, Keypad, BAS"
  },
  {
   "type": "BV",
   "instance": 111,
   "name": "enable_keypad_1",
   "description": "Unit Enable (keypad)",
   "units": "",
   "access": "W",
   "states": "Off, On"
  },
  {
   "type": "MV",
   "instance": 20,
   "name": "mod_comp_ref_type_5",
   "description": "Module Compr Ref Type",
   "units": "",
   "access": "W",
   "states": "410a, 134a"
  },
  {
   "type": "MV",
   "instance": 33,
   "name": "chiller_model_type_5",
   "description": "Chiller Model Type",
   "units": "",
   "access": "W",
   "states": "UCW, UCH, UCR"
  },
  {
   "type": "MV",
   "instance": 8,
   "name": "chiller_model_size_5",
   "description": "Chiller Model Size",
   "units": "",
   "access": "W",
   "states": "UC030, UC050, UC070"
  },
  {
   "type": "BV",
   "instance": 308,
   "name": "separate_reversing_vlvs_5",
   "description": "Use Separate Reversing Valve Outputs",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "AV",
   "instance": 48,
   "name": "cool_design_dt_1",
   "description": "FULL LD COOL DES TD",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 49,
   "name": "heat_design_dt_1",
   "description": "FULL LD HEAT DES TD",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 523,
   "name": "startup_alarm_delay_1",
   "description": "Start-Up Alarm Delay",
   "units": "sec",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "chw_temp_stp_1",
   "description": "COOL LVG TRG",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 96,
   "name": "min_chw_temp_stp_1",
   "description": "MIN COOL TRG LIM",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 89,
   "name": "max_chw_temp_stp_1",
   "description": "MAX COOL TRG LIM",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 243,
   "name": "rem_chw_stp_stat_1",
   "description": "Remote CHW Setpoint",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 92,
   "name": "max_neg_chw_stp_reset_1",
   "description": "MAX NEG DEM LIM COOL RESET",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 94,
   "name": "max_pos_chw_stp_reset_1",
   "description": "MAX POS DEM LIM COOL RESET",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 242,
   "name": "rem_chw_stp_reset_1",
   "description": "Remote CHW Setpoint Reset",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "chw_stp_stat_1",
   "description": "Active CHW Setpoint",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "cl_cntrl_spt_offset_1",
   "description": "Cool Control Setpoint Offset",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 61,
   "name": "cw_temp_stp_1",
   "description": "HEAT LVG TRG",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 97,
   "name": "min_cw_temp_stp_1",
   "description": "MIN HEAT TRG LIM",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 91,
   "name": "max_cw_temp_stp_1",
   "description": "MAX HEAT TRG LIM",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 246,
   "name": "rem_cw_stp_stat_1",
   "description": "Remote CW Setpoint",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 188,
   "name": "max_neg_cw_stp_reset_1",
   "description": "MAX NEG DEM LIM HEAT RESET",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 190,
   "name": "max_pos_cw_stp_reset_1",
   "description": "MAX POS DEM LIM HEAT RESET",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 247,
   "name": "rem_cw_stp_reset_1",
   "description": "Remote CW Dem Lim Stpt Reset",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "ht_cntrl_spt_offset_1",
   "description": "HeatControl Setpoint Offset",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 23,
   "name": "inp_10_point_type_1",
   "description": "Input Chnl 10 Type",
   "units": "",
   "access": "W",
   "states": "None, Remote Heat Trg"
  },
  {
   "type": "MV",
   "instance": 21,
   "name": "an_inp10_typ_1",
   "description": "AI10 Type Rem Ht Trg",
   "units": "",
   "access": "W",
   "states": "NONE, 4-20 ma, 2-10VDC"
  },
  {
   "type": "MV",
   "instance": 27,
   "name": "inp_6_point_type_1",
   "description": "Input Chnl 6 Type",
   "units": "",
   "access": "W",
   "states": "None, Remote Cool Trg"
  },
  {
   "type": "MV",
   "instance": 30,
   "name": "an_inp6_typ_1",
   "description": "AI6 Type Off is 0-10",
   "units": "",
   "access": "W",
   "states": "NONE, 4-20 ma, 2-10VDC"
  },
  {
   "type": "AV",
   "instance": 367,
   "name": "source_ht_trg_reset_1",
   "description": "SOURCE HT TRG RESET",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 363,
   "name": "max_source_htg_trg_reset_1",
   "description": "MAX SOURCE HTG TRG RES",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 364,
   "name": "min_source_htg_trg_reset_1",
   "description": "MIN SOURCE HTG TRG RESET",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 365,
   "name": "source_htg_trg_max_reset_1",
   "description": "SOURCE HEAT TRG Max RES",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 366,
   "name": "source_htg_trg_min_reset_1",
   "description": "SOURCE HEAT TRG MIN RES",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 690,
   "name": "source_cl_trg_reset_1",
   "description": "SOURCE CL TRG RESET",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 688,
   "name": "max_source_clg_trg_reset_1",
   "description": "MAX SOURCE CLG TRG RES",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 689,
   "name": "min_source_clg_trg_reset_1",
   "description": "MIN SOURCE CLG TRG RESET",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 691,
   "name": "source_clg_trg_max_reset_1",
   "description": "SOURCE COOL TRG Max RES",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 692,
   "name": "source_clg_trg_min_reset_1",
   "description": "SOURCE COOL TRG MIN RES",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 105,
   "name": "reset_oor_1",
   "description": "Reset Sensor OOR Alarm",
   "units": "",
   "access": "W",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 27,
   "name": "reset_1",
   "description": "LOCK OUT RESET",
   "units": "",
   "access": "W",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 690,
   "name": "m1_reset_all_slave_alarms_5",
   "description": "Reset M1 All Slave Alarms",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 691,
   "name": "m2_reset_all_slave_alarms_5",
   "description": "Reset M2 All Slave Alarms",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 692,
   "name": "m3_reset_all_slave_alarms_5",
   "description": "Reset M3 All Slave Alarms",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 693,
   "name": "m4_reset_all_slave_alarms_5",
   "description": "Reset M4 All Slave Alarms",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 694,
   "name": "m5_reset_all_slave_alarms_5",
   "description": "Reset M5 All Slave Alarms",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 695,
   "name": "m6_reset_all_slave_alarms_5",
   "description": "Reset M6 All Slave Alarms",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 734,
   "name": "m7_reset_all_slave_alarms_5",
   "description": "Reset M7 All Slave Alarms",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 351,
   "name": "m1_comp1_fail_5",
   "description": "Module 1 Comp 1 Fail",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 38,
   "name": "m1reset_c1_alrm_5",
   "description": "M1C1 Alarm Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 354,
   "name": "m1_comp2_fail_5",
   "description": "Module 1 Comp 2 Fail",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 41,
   "name": "m1reset_c2_alrm_5",
   "description": "M1C2 Alarm Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 357,
   "name": "m2_comp1_fail_5",
   "description": "Module 2 Comp 1 Fail",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 48,
   "name": "m2reset_c1_alrm_5",
   "description": "M2C1 Alarm Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 360,
   "name": "m2_comp2_fail_5",
   "description": "Module 2 Comp 2 Fail",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 42,
   "name": "m2reset_c2_alrm_5",
   "description": "M2C2 Alarm Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 93,
   "name": "m3_comp1_fail_5",
   "description": "Module 3 Comp 1 Fail",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 84,
   "name": "m3reset_c1_alrm_5",
   "description": "M3C1 Alarm Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 97,
   "name": "m3_comp2_fail_5",
   "description": "Module 3 Comp 2 Fail",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 88,
   "name": "m3reset_c2_alrm_5",
   "description": "M3C2 Alarm Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 375,
   "name": "m4_comp1_fail_5",
   "description": "Module 4 Comp 1 Fail",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 266,
   "name": "m4reset_c1_alrm_5",
   "description": "M4C1 Alarm Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 379,
   "name": "m4_comp2_fail_5",
   "description": "Module 4 Comp 2 Fail",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 271,
   "name": "m4reset_c2_alrm_5",
   "description": "M4C2 Alarm Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 385,
   "name": "m5_comp1_fail_5",
   "description": "Module 5 Comp 1 Fail",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 345,
   "name": "m5reset_c1_alrm_5",
   "description": "M5C1 Alarm Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 389,
   "name": "m5_comp2_fail_5",
   "description": "Module 5 Comp 2 Fail",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 349,
   "name": "m5reset_c2_alrm_5",
   "description": "M5C2 Alarm Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 402,
   "name": "m6_comp1_fail_5",
   "description": "Module 6 Comp 1 Fail",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 366,
   "name": "m6reset_c1_alrm_5",
   "description": "M6C1 Alarm Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 412,
   "name": "m6_comp2_fail_5",
   "description": "Module 6 Comp 2 Fail",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 370,
   "name": "m6reset_c2_alrm_5",
   "description": "M6C2 Alarm Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 711,
   "name": "m7_comp1_fail_5",
   "description": "Module 7 Comp 1 Fail",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 697,
   "name": "m7reset_c1_alrm_5",
   "description": "M7C1 Alarm Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 721,
   "name": "m7_comp2_fail_5",
   "description": "Module 7 Comp 2 Fail",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 701,
   "name": "m7reset_c2_alrm_5",
   "description": "M7C2 Alarm Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 175,
   "name": "m1_freeze_alrm_5",
   "description": "Module 1 Freeze Alarm",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 56,
   "name": "m1_reset_freeze_5",
   "description": "Reset Mot1 Vlv Fail",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 157,
   "name": "m1_cwr_alrm_5",
   "description": "Module 1 Leaving Cond Water Alarm",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 190,
   "name": "m2_freeze_alrm_5",
   "description": "Module 2 Freeze Alarm",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 57,
   "name": "m2_reset_freeze_5",
   "description": "Reset Mot2 Vlv Fail",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 668,
   "name": "m2_cwr_alrm_5",
   "description": "Module 2 Leaving Cond Water Alarm",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 192,
   "name": "m3_freeze_alrm_5",
   "description": "Module 3 Freeze Alarm",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 150,
   "name": "m3_reset_freeze_5",
   "description": "Reset Mot3 Vlv Fail",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 669,
   "name": "m3_cwr_alrm_5",
   "description": "Module 3 Leaving Cond Water Alarm",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 193,
   "name": "m4_freeze_alrm_5",
   "description": "Module 4 Freeze Alarm",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 432,
   "name": "m4_reset_freeze_5",
   "description": "Reset Mot4 Vlv Fail",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 670,
   "name": "m4_cwr_alrm_5",
   "description": "Module 4 Leaving Cond Water Alarm",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 194,
   "name": "m5_freeze_alrm_5",
   "description": "Module 5 Freeze Alarm",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 443,
   "name": "m5_reset_freeze_5",
   "description": "Reset Mot5 Vlv Fail",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 676,
   "name": "m5_cwr_alrm_5",
   "description": "Module 5 Leaving Cond Water Alarm",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 195,
   "name": "m6_freeze_alrm_5",
   "description": "Module 6 Freeze Alarm",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 444,
   "name": "m6_reset_freeze_5",
   "description": "Reset Mot6 Vlv Fail",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 100,
   "name": "m6_cwr_alrm_5",
   "description": "Module 6 Leaving Cond Water Alarm",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 732,
   "name": "m7_freeze_alrm_5",
   "description": "Module 7 Freeze Alarm",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 735,
   "name": "m7_reset_freeze_5",
   "description": "Reset Mot7 Vlv Fail",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 101,
   "name": "m7_cwr_alrm_5",
   "description": "Module 7 Leaving Cond Water Alarm",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 40,
   "name": "m1reset_c1_rtim_5",
   "description": "M1C1 Runtime Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 45,
   "name": "m1c1_cycles_reset_5",
   "description": "M1C1 Cycles Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 44,
   "name": "m1reset_c2_rtim_5",
   "description": "M1C2 Runtime Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 46,
   "name": "m1c2_cycles_reset_5",
   "description": "M1C2 Cycles Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 51,
   "name": "m2reset_c1_rtim_5",
   "description": "M2C1 Runtime Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 49,
   "name": "m2c1_cycles_reset_5",
   "description": "M2C1 Cycles Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 54,
   "name": "m2reset_c2_rtim_5",
   "description": "M2C2 Runtime Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 52,
   "name": "m2c2_cycles_reset_5",
   "description": "M2C2 Cycles Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 87,
   "name": "m3reset_c1_rtim_5",
   "description": "M3C1 Runtime Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 85,
   "name": "m3c1_cycles_reset_5",
   "description": "M3C1 Cycles Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 91,
   "name": "m3reset_c2_rtim_5",
   "description": "M3C2 Runtime Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 89,
   "name": "m3c2_cycles_reset_5",
   "description": "M3C2 Cycles Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 270,
   "name": "m4reset_c1_rtim_5",
   "description": "M4C1 Runtime Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 267,
   "name": "m4c1_cycles_reset_5",
   "description": "M4C1 Cycles Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 343,
   "name": "m4reset_c2_rtim_5",
   "description": "M4C2 Runtime Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 341,
   "name": "m4c2_cycles_reset_5",
   "description": "M4C2 Cycles Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 348,
   "name": "m5reset_c1_rtim_5",
   "description": "M5C1 Runtime Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 346,
   "name": "m5c1_cycles_reset_5",
   "description": "M5C1 Cycles Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 364,
   "name": "m5reset_c2_rtim_5",
   "description": "M5C2 Runtime Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 350,
   "name": "m5c2_cycles_reset_5",
   "description": "M5C2 Cycles Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 369,
   "name": "m6reset_c1_rtim_5",
   "description": "M6C1 Runtime Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 367,
   "name": "m6c1_cycles_reset_5",
   "description": "M6C1 Cycles Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 373,
   "name": "m6reset_c2_rtim_5",
   "description": "M6C2 Runtime Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 371,
   "name": "m6c2_cycles_reset_5",
   "description": "M6C2 Cycles Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 700,
   "name": "m7reset_c1_rtim_5",
   "description": "M7C1 Runtime Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 698,
   "name": "m7c1_cycles_reset_5",
   "description": "M7C1 Cycles Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 704,
   "name": "m7reset_c2_rtim_5",
   "description": "M7C2 Runtime Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 702,
   "name": "m7c2_cycles_reset_5",
   "description": "M7C2 Cycles Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 605,
   "name": "m1_comp1_oor_5",
   "description": "Module 1 Comp 1 Sensor OOR",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 601,
   "name": "m1_oorsl_reset_5",
   "description": "M1 Sensor OOR Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 606,
   "name": "m1_comp2_oor_5",
   "description": "Module 1 Comp 2 Sensor OOR",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 607,
   "name": "m2_comp1_oor_5",
   "description": "Module 2 Comp 1 Sensor OOR",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 602,
   "name": "m2_oorsl_reset_5",
   "description": "M2 Sensor OOR Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 608,
   "name": "m2_comp2_oor_5",
   "description": "Module 2 Comp 2 Sensor OOR",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 609,
   "name": "m3_comp1_oor_5",
   "description": "Module 3 Comp 1 Sensor OOR",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 603,
   "name": "m3_oorsl_reset_5",
   "description": "M3 Sensor OOR Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 610,
   "name": "m3_comp2_oor_5",
   "description": "Module 3 Comp 2 Sensor OOR",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 611,
   "name": "m4_comp1_oor_5",
   "description": "Module 4 Comp 1 Sensor OOR",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 604,
   "name": "m4_oorsl_reset_5",
   "description": "M4 Sensor OOR Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 612,
   "name": "m4_comp2_oor_5",
   "description": "Module 4 Comp 2 Sensor OOR",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 674,
   "name": "m5_comp1_oor_5",
   "description": "Module 5 Comp 1 Sensor OOR",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 477,
   "name": "m5_oorsl_reset_5",
   "description": "M5 Sensor OOR Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 675,
   "name": "m5_comp2_oor_5",
   "description": "Module 5 Comp 2 Sensor OOR",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 707,
   "name": "m6_comp1_oor_5",
   "description": "Module 6 Comp 1 Sensor OOR",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 696,
   "name": "m6_oorsl_reset_5",
   "description": "M6 Sensor OOR Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 708,
   "name": "m6_comp2_oor_5",
   "description": "Module 6 Comp 2 Sensor OOR",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 713,
   "name": "m7_comp1_oor_5",
   "description": "Module 7 Comp 1 Sensor OOR",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 706,
   "name": "m7_oorsl_reset_5",
   "description": "M7 Sensor OOR Reset",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 723,
   "name": "m7_comp2_oor_5",
   "description": "Module 7 Comp 2 Sensor OOR",
   "units": "",
   "access": "R",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 199,
   "name": "m1_c1_lo_suc_psi_unld_5",
   "description": "Module 1 Comp 1 Suct Pressure Unload",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 203,
   "name": "m1_c2_lo_suc_psi_unld_5",
   "description": "Module 1 Comp 2 Suct Pressure Unload",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 650,
   "name": "m1_c1_lolo_suc_psi_unld_5",
   "description": "Module 1 Comp 1 XLow Suct Pressure Unload",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 651,
   "name": "m1_c2_lolo_suc_psi_unld_5",
   "description": "Module 1 Comp 2 XLow Suct Pressure Unload",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 200,
   "name": "m1_c1_lo_suc_tmp_unld_5",
   "description": "Module 1 Comp 1 Suct Temp Unload",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 204,
   "name": "m1_c2_lo_suc_tmp_unld_5",
   "description": "Module 1 Comp 2 Suct Temp Unload",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 205,
   "name": "m1_freeze_trg_unld_5",
   "description": "Module 1 Freeze trg Unload",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 652,
   "name": "m1_cwr_trg_unld_5",
   "description": "Module 1 CWR trg Unload",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 197,
   "name": "m1_c1_hi_dis_psi_unld_5",
   "description": "Module 1 Comp 1 Dis Pressure Unload",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 201,
   "name": "m1_c2_hi_dis_psi_unld_5",
   "description": "Module 1 Comp 2 Dis Pressure Unload",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 218,
   "name": "m1_c1_hi_suc_sh_unld_5",
   "description": "Module 1 Comp 1 Dis Temp Unload",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 276,
   "name": "m1_c2_hi_suc_sh_unld_5",
   "description": "Module 1 Comp 2 Dis Temp Unload",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 161,
   "name": "m1_c1_no_run_unld_5",
   "description": "Module 1 Comp 1 No Run Unload",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 164,
   "name": "m1_c2_no_run_unld_5",
   "description": "Module 1 Comp 2 No Run Unload",
   "units": "",
   "access": "R",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 393,
   "name": "mod_disch_psi_avail_5",
   "description": "Module DISCH PSI AVAIL",
   "units": "",
   "access": "W",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 396,
   "name": "mod_suc_psi_avail_5",
   "description": "Module SUC PSI AVAIL",
   "units": "",
   "access": "W",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 397,
   "name": "mod_suc_tmp_avail_5",
   "description": "Module SUC TMP AVAIL",
   "units": "",
   "access": "W",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 173,
   "name": "mod_cwr_avail_5",
   "description": "Module CWR AVAIL",
   "units": "",
   "access": "W",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 409,
   "name": "mod_cwr_lo_enable_5",
   "description": "Module CWR Enable Low Limit",
   "units": "",
   "access": "W",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 400,
   "name": "mod_chs_hi_enable_5",
   "description": "Module CWR Enable High Limit",
   "units": "",
   "access": "W",
   "states": "Off, On"
  },
  {
   "type": "AV",
   "instance": 370,
   "name": "mod_hi_disch_press_sp_410_ucw_5",
   "description": "High Head Press Sp 410a UCW",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 369,
   "name": "mod_hi_disch_press_sp_410_uchr_5",
   "description": "High Head Press Sp 410a UCH- UCR",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 390,
   "name": "mod_hi_disch_press_sp_134_uchr_5",
   "description": "High Head Press Sp 134a UCH- UCR",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 421,
   "name": "mod_hi_disch_press_sp_5",
   "description": "Module Hi Disch Press Setpt",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 439,
   "name": "mod_lo_disch_press_sp_134_5",
   "description": "Low Head Press Sp 134a",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 507,
   "name": "mod_lo_disch_press_sp_410_5",
   "description": "Low Head Press Sp 410a",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 499,
   "name": "mod_lo_disch_press_sp_5",
   "description": "Module Lo Disch Press Setpt",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 391,
   "name": "mod_high_suct_press_sp_410_5",
   "description": "High Suction Press Sp 410a",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 438,
   "name": "mod_high_suct_press_sp_134_5",
   "description": "High Suction Press Sp 134a",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 581,
   "name": "mod_high_suct_press_sp_5",
   "description": "Module High Suction Press Setpt",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 588,
   "name": "mod_low_low_press_sp_5",
   "description": "Module LO-LO SUC PSI Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 589,
   "name": "mod_lo_suc_psi_delay_5",
   "description": "Module LO SUC PSI Delay",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 252,
   "name": "mod_heat_lo_suction_tmp_5",
   "description": "Module Heat Low Suction Temp",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 237,
   "name": "mod_cool_lo_suction_tmp_5",
   "description": "Module Cool Low Suction Temp",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 231,
   "name": "mod_heat_lo_suc_press_sp_410_5",
   "description": "Heat Low Suction Press Sp 410a",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 95,
   "name": "mod_cool_lo_suc_press_sp_410_5",
   "description": "Cool Low Suction Press Sp 410a",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 203,
   "name": "mod_heat_lo_suc_press_sp_134_5",
   "description": "Heat Low Suction Press Sp 134a",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 93,
   "name": "mod_cool_lo_suc_press_sp_134_5",
   "description": "Cool Low Suction Press Sp 134a",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 245,
   "name": "mod_heat_low_press_sp_5",
   "description": "Module Heat Low Suction Press Setpt",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 236,
   "name": "mod_cool_low_press_sp_5",
   "description": "Module Cool Low Suction Press Setpt",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 430,
   "name": "mod_lo_suc_supht_sp_5",
   "description": "Module Low Suct SuperHt Setpt",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 585,
   "name": "mod_hi_suc_supht_sp_5",
   "description": "Module High Suct SuperHt Setpt",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 427,
   "name": "mod_lo_disc_supht_sp_5",
   "description": "Module Low Disch SuperHt Setpt",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 413,
   "name": "mod_cmpr_min_run_5",
   "description": "Module Compr Min Run Time",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 412,
   "name": "mod_cmpr_off_delay_5",
   "description": "Module Compr Min Off Delay",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 414,
   "name": "mod_comp_stat_alm_delay_5",
   "description": "Module Compr Status Alarm Delay",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 232,
   "name": "mod_cool_freeze_trg_sp_5",
   "description": "Module Cool Freeze Target Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 234,
   "name": "mod_cool_high_evap_lvg_tmp_5",
   "description": "Module Cool High Evaporator Leaving Temp",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 235,
   "name": "mod_cool_low_cond_lvg_tmp_5",
   "description": "Module Cool Low Condenser Leaving Temp. @ Startup",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 233,
   "name": "mod_cool_cwr_trg_sp_5",
   "description": "Module Cool High Cond Leaving Temp at Startup",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 238,
   "name": "mod_heat_freeze_trg_sp_5",
   "description": "Module Heat Freeze Target Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 241,
   "name": "mod_heat_high_evap_lvg_tmp_5",
   "description": "Module Heat High Evaporator Leaving Temp at Startup",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 244,
   "name": "mod_heat_low_cond_lvg_tmp_5",
   "description": "Module Heat Low Condenser Leaving Temp. @ Startup",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 240,
   "name": "mod_heat_cwr_trg_sp_5",
   "description": "Module Heat High Cond Leaving Temp at Startup",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 47,
   "name": "m1_man_mode_5",
   "description": "M1 Manual Mode Enable",
   "units": "",
   "access": "W",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 39,
   "name": "m1c1_man_run_5",
   "description": "M1C1 Manual Run",
   "units": "",
   "access": "W",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 43,
   "name": "m1c2_man_run_5",
   "description": "M1C2 Manual Run",
   "units": "",
   "access": "W",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 782,
   "name": "m1_mancool_run_5",
   "description": "M1 Manual Cool Run",
   "units": "",
   "access": "W",
   "states": "Off, On"
  },
  {
   "type": "BV",
   "instance": 783,
   "name": "m1_manheat_run_5",
   "description": "M1 Manual Heat Run",
   "units": "",
   "access": "W",
   "states": "Off, On"
  },
  {
   "type": "AV",
   "instance": 356,
   "name": "man_mode_time_5",
   "description": "Man Mode Time",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 820,
   "name": "m1_forceman_5",
   "description": "M1 Force Termination of Manual Mode",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "AV",
   "instance": 101,
   "name": "m1_load_temp_cp_5",
   "description": "M1 Load Temp Calib. Point",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 111,
   "name": "m1_src_temp_cp_5",
   "description": "M1 SRC Temp Calib. Point",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 392,
   "name": "m1c1_disch_pres_cp_5",
   "description": "M1C1 DIS Pressure Calib. Point",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 396,
   "name": "m1c2_disch_pres_cp_5",
   "description": "M1C2 DIS Pressure Calib. Point",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 394,
   "name": "m1c1_suc_pres_cp_5",
   "description": "M1C1 SUC Pressure Calib. Point",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 398,
   "name": "m1c2_suc_pres_cp_5",
   "description": "M1C2 SUC Pressure Calib. Point",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 395,
   "name": "m1c1_suc_tmp_cp_5",
   "description": "M1C1 SUC Temp Calib. Point",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 399,
   "name": "m1c2_suc_tmp_cp_5",
   "description": "M1C2 SUC Temp Calib. Point",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 309,
   "name": "m1c1_disable_comp_5",
   "description": "M1C1 Disable Compr",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 310,
   "name": "m1c2_disable_comp_5",
   "description": "M1C2 Disable Compr",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 311,
   "name": "m2c1_disable_comp_5",
   "description": "M2C1 Disable Compr",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 312,
   "name": "m2c2_disable_comp_5",
   "description": "M2C2 Disable Compr",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 313,
   "name": "m3c1_disable_comp_5",
   "description": "M3C1 Disable Compr",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 314,
   "name": "m3c2_disable_comp_5",
   "description": "M3C2 Disable Compr",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 315,
   "name": "m4c1_disable_comp_5",
   "description": "M4C1 Disable Compr",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 316,
   "name": "m4c2_disable_comp_5",
   "description": "M4C2 Disable Compr",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 317,
   "name": "m5c1_disable_comp_5",
   "description": "M5C1 Disable Compr",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 318,
   "name": "m5c2_disable_comp_5",
   "description": "M5C2 Disable Compr",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 319,
   "name": "m6c1_disable_comp_5",
   "description": "M6C1 Disable Compr",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 320,
   "name": "m6c2_disable_comp_5",
   "description": "M6C2 Disable Compr",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 321,
   "name": "m7c1_disable_comp_5",
   "description": "M7C1 Disable Compr",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 322,
   "name": "m7c2_disable_comp_5",
   "description": "M7C2 Disable Compr",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "AV",
   "instance": 423,
   "name": "mod_hi_dis_psi_retry_5",
   "description": "Module HI DIS PSI RETRY",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 425,
   "name": "mod_lo_suc_psi_retry_5",
   "description": "Module LO SUC PSI RETRY",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 418,
   "name": "mod_freeze_trg_retry_5",
   "description": "Module FREEZE TRG RETRY",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 582,
   "name": "mod_cwr_trg_retry_5",
   "description": "Module CWR TRG RETRY",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 426,
   "name": "mod_lo_suc_tmp_retry_5",
   "description": "Module LO SUC TMP RETRY",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 268,
   "name": "mod_compr_norun_retry_5",
   "description": "Module Compressor No-Run RETRY",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 599,
   "name": "mod1_unused_1",
   "description": "Module 1 Unused",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 600,
   "name": "mod2_unused_1",
   "description": "Module 2 Unused",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 672,
   "name": "mod3_unused_1",
   "description": "Module 3 Unused",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 736,
   "name": "mod4_unused_1",
   "description": "Module 4 Unused",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 743,
   "name": "mod5_unused_1",
   "description": "Module 5 Unused",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 755,
   "name": "mod6_unused_1",
   "description": "Module 6 Unused",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 779,
   "name": "mod7_unused_1",
   "description": "Module 7 Unused",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "AV",
   "instance": 695,
   "name": "m1_mod_number_5",
   "description": "M1 Module Number",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 696,
   "name": "m2_mod_number_5",
   "description": "M2 Module Number",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 697,
   "name": "m3_mod_number_5",
   "description": "M3 Module Number",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 698,
   "name": "m4_mod_number_5",
   "description": "M4 Module Number",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 699,
   "name": "m5_mod_number_5",
   "description": "M5 Module Number",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 700,
   "name": "m6_mod_number_5",
   "description": "M6 Module Number",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 701,
   "name": "m7_mod_number_5",
   "description": "M7 Module Number",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 117,
   "name": "fix_module1_cool_1",
   "description": "Fix Mod1 as Cool",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 9,
   "name": "fix_module1_heat_1",
   "description": "Fix Mod1 as Heat",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 152,
   "name": "never_close_mod1_1",
   "description": "Never Close Module #1",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 12,
   "name": "fix_module2_cool_1",
   "description": "Fix Mod2 as Cool",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 460,
   "name": "fix_module2_heat_1",
   "description": "Fix Mod2 as Heat",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 156,
   "name": "never_close_mod2_1",
   "description": "Never Close Module #2",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 552,
   "name": "fix_module3_cool_1",
   "description": "Fix Mod3 as Cool",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 553,
   "name": "fix_module3_heat_1",
   "description": "Fix Mod3 as Heat",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 158,
   "name": "never_close_mod3_1",
   "description": "Never Close Module #3",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 555,
   "name": "fix_module4_cool_1",
   "description": "Fix Mod4 as Cool",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 556,
   "name": "fix_module4_heat_1",
   "description": "Fix Mod4 as Heat",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 159,
   "name": "never_close_mod4_1",
   "description": "Never Close Module #4",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 568,
   "name": "fix_module5_cool_1",
   "description": "Fix Mod5 as Cool",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 569,
   "name": "fix_module5_heat_1",
   "description": "Fix Mod5 as Heat",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 162,
   "name": "never_close_mod5_1",
   "description": "Never Close Module #5",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 571,
   "name": "fix_module6_cool_1",
   "description": "Fix Mod6 as Cool",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 572,
   "name": "fix_module6_heat_1",
   "description": "Fix Mod6 as Heat",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 253,
   "name": "never_close_mod6_1",
   "description": "Never Close Module #6",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 573,
   "name": "fix_module7_cool_1",
   "description": "Fix Mod7 as Cool",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 118,
   "name": "fix_module7_heat_1",
   "description": "Fix Mod7 as Heat",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 163,
   "name": "never_close_mod7_1",
   "description": "Never Close Module #7",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 293,
   "name": "use_ht_cl_mod_fract_1",
   "description": "Use Heat/Cool Module Fractions",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "AV",
   "instance": 274,
   "name": "fract_cool_mods_1",
   "description": "Fraction of Cool Mods vs Total Mods",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 253,
   "name": "fract_heat_mods_1",
   "description": "Fraction of Heat Mods vs Total Mods",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 124,
   "name": "fract_cool_cmpr_overshoot_1",
   "description": "Fraction of Cool Compressor PID Overshoot",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 181,
   "name": "fract_heat_cmpr_overshoot_1",
   "description": "Fraction of Heat Compressor PID Overshoot",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 28,
   "name": "inp_7_point_type_1",
   "description": "Input Chnl 7 Type",
   "units": "",
   "access": "W",
   "states": "None, Demand Lim Cl TrgRst, Demand Lim Max #Cmp"
  },
  {
   "type": "MV",
   "instance": 31,
   "name": "an_inp7_typ_1",
   "description": "AI7 Type Rem Cl Trg or Dem Lim",
   "units": "",
   "access": "W",
   "states": "NONE, 4-20 ma, 2-10VDC"
  },
  {
   "type": "BV",
   "instance": 827,
   "name": "man_sel_clg_dem_lim_1",
   "description": "Manual Select Cool Demand Limiting",
   "units": "",
   "access": "W",
   "states": "Off, On"
  },
  {
   "type": "AV",
   "instance": 693,
   "name": "voltin_clg_comp_dem_lim_1",
   "description": "Volts In for Cool Comp Demand Limiting",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 5,
   "name": "inp_1_5_point_type_1",
   "description": "Input Chnl 1-5 Type",
   "units": "",
   "access": "W",
   "states": "None, Demand Lim Ht TrgRst, Demand Lim Max #Cmp"
  },
  {
   "type": "MV",
   "instance": 4,
   "name": "an_inp1_5_typ_1",
   "description": "AI1-3 Type Rem Cl Trg or Dem Lim",
   "units": "",
   "access": "W",
   "states": "NONE, 4-20 ma, 2-10VDC"
  },
  {
   "type": "BV",
   "instance": 828,
   "name": "man_sel_htg_dem_lim_1",
   "description": "Manual Select Heat Demand Limiting",
   "units": "",
   "access": "W",
   "states": "Off, On"
  },
  {
   "type": "AV",
   "instance": 694,
   "name": "voltin_htg_comp_dem_lim_1",
   "description": "Volts In for Heat Comp Demand Limiting",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "clg_interval_1",
   "description": "Clg PID Interval",
   "units": "sec",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 75,
   "name": "use_calc_prop_integ_1",
   "description": "Use Calculated P and I",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "clg_p_gain_1",
   "description": "Clg PID P-gain",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "clg_i_gain_1",
   "description": "Clg PID I-gain",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 138,
   "name": "clg_rise_1",
   "description": "Clg PID Rise",
   "units": "sec",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 135,
   "name": "clg_fall_1",
   "description": "Clg PID Fall",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 843,
   "name": "use_double_rise_1",
   "description": "Use Rise Doubler",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "AV",
   "instance": 55,
   "name": "clg_dblrise_1",
   "description": "Clg PID Double Rise Amount",
   "units": "sec",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "max_cool_ramp_rate_1",
   "description": "MAX COOL RAMP RATE",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 132,
   "name": "clg_db1_1",
   "description": "Clg PID DB1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 617,
   "name": "pid_diff_fact_1",
   "description": "PID Differential Factor",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 306,
   "name": "use_auto_pid_reset_1",
   "description": "Use Automatic PID Reset Feature",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "AV",
   "instance": 287,
   "name": "delay_before_auto_pid_reset_1",
   "description": "Delay Before Auto PID Reset",
   "units": "sec",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 305,
   "name": "use_auto_pid_reset_alm_1",
   "description": "Use Automatic PID Reset Alarm",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "AV",
   "instance": 68,
   "name": "htg_interval_1",
   "description": "Htg PID Interval",
   "units": "sec",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 69,
   "name": "htg_p_gain_1",
   "description": "Htg PID P-gain",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 67,
   "name": "htg_i_gain_1",
   "description": "Htg PID I-gain",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 182,
   "name": "htg_rise_1",
   "description": "Htg PID Rise",
   "units": "sec",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 178,
   "name": "htg_fall_1",
   "description": "Htg PID Fall",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56,
   "name": "htg_dblrise_1",
   "description": "Htg PID Double Rise Amount",
   "units": "sec",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "max_heat_ramp_rate_1",
   "description": "MAX HEAT RAMP RATE",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 174,
   "name": "htg_db1_1",
   "description": "Htg PID DB1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 34,
   "name": "mot_vlv_opt_5",
   "description": "Motorized Valve Options",
   "units": "",
   "access": "W",
   "states": "No Mot Vlvs, Evap Mot Vlvs Only, Cond&Evap Mot Vlvs"
  },
  {
   "type": "AV",
   "instance": 415,
   "name": "mod_cond_vlv_alm_delay_5",
   "description": "Module COND VLV ALM DELAY",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 416,
   "name": "mod_evap_vlv_alm_delay_5",
   "description": "Module EVAP VLV ALM DELAY",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 503,
   "name": "cdmv_interval_5",
   "description": "CDMV PID Interval",
   "units": "sec",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 505,
   "name": "cdmv_p_gain_5",
   "description": "CDMV PID P-gain",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 502,
   "name": "cdmv_i_gain_5",
   "description": "CDMV PID I-gain",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 500,
   "name": "cdmv_pid_db_5",
   "description": "CDMV PID Deadband",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 506,
   "name": "cdmv_pid_ramp_5",
   "description": "CDMV PID RAMP",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 386,
   "name": "evmv_interval_5",
   "description": "EVMV PID Interval",
   "units": "sec",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 388,
   "name": "evmv_p_gain_5",
   "description": "EVMV PID P-gain",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 385,
   "name": "evmv_i_gain_5",
   "description": "EVMV PID I-gain",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 383,
   "name": "evmv_pid_db_5",
   "description": "EVMV PID Deadband",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 389,
   "name": "evmv_pid_ramp_5",
   "description": "EVMV PID RAMP",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 387,
   "name": "evmv_pid_mnpct_5",
   "description": "EVMV PID Minimum Percent",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 845,
   "name": "use_hi_sh_cutout_5",
   "description": "Use Hi Superheat for Compr Cutout",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "AV",
   "instance": 592,
   "name": "mod_hp_pos_adj_5",
   "description": "Module Head Pressure Positive Adj",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 594,
   "name": "mod_sp_neg_adj_5",
   "description": "Module Suction Pressure Negative Adj",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 81,
   "name": "mod_min_cdmv_adj_heat_5",
   "description": "Module Minimum MV Adjustment Heat",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 79,
   "name": "cdmv_pid_mnpct_heat_5",
   "description": "CDMV PID Minimum Percent Heat",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 80,
   "name": "mod_min_cdmv_adj_cool_5",
   "description": "Module Minimum MV Adjustment Cool",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 78,
   "name": "cdmv_pid_mnpct_cool_5",
   "description": "CDMV PID Minimum Percent Cool",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 844,
   "name": "use_hi_hp_comp_5",
   "description": "Use Hi Head Pressure Compr for Low HP Ctrl",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "AV",
   "instance": 371,
   "name": "mod_defaulthp410_usehihp_5",
   "description": "Default HP R-410A Using High Head Pressure",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 372,
   "name": "mod_defaulthp410_uselowhp_5",
   "description": "Default HP R-410A Using Low Head Pressure",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 239,
   "name": "mod_defaulthp134_usehihp_5",
   "description": "Default HP R-134a Using High Head Pressure",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 368,
   "name": "mod_defaulthp134_uselowhp_5",
   "description": "Default HP R-134a Using Low Head Pressure",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 590,
   "name": "mod_default_hp_5",
   "description": "Module Default Head Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 441,
   "name": "mod_default_sp_410_5",
   "description": "Module Default Suction Press 410a",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 440,
   "name": "mod_default_sp_134_5",
   "description": "Module Default Suction Press 134a",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 583,
   "name": "use_diff_pr_flow_sens_1",
   "description": "Use Diff Press Flow Sensors",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "AV",
   "instance": 227,
   "name": "max_delta_temp_ld_ht_5",
   "description": "Max Delta Temp- Load Heat",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 218,
   "name": "max_delta_temp_ld_cl_5",
   "description": "Max Delta Temp- Load Cool",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 254,
   "name": "max_delta_temp_src_5",
   "description": "Max Delta Temp- Source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 90,
   "name": "diff_pr_trip_mult_5",
   "description": "Diff Pressure Trip Multiplier",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 874,
   "name": "use_pre_calc_dif_pr_setpt_1",
   "description": "Use Pre-Calc Diff Pr Cutout",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "AV",
   "instance": 622,
   "name": "lo_ld_cool_diff_pr_1",
   "description": "Lo LD Cool Diff Pressure",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 623,
   "name": "lo_ld_heat_diff_pr_1",
   "description": "Lo LD Heat Diff Pressure",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 139,
   "name": "lo_src_diff_pr_1",
   "description": "LO SRC Diff Press",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 130,
   "name": "act_lo_diff_press_ld_cl_1",
   "description": "Actual Low Diff Press Trip Load Cool",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 134,
   "name": "act_lo_diff_press_ld_ht_1",
   "description": "Actual Low Diff Press Trip Load Heat",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 586,
   "name": "act_lo_diff_press_src_1",
   "description": "Actual Low Diff Press Trip Source",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 206,
   "name": "est_watts_5",
   "description": "Estimated Watts",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 161,
   "name": "est_tons_5",
   "description": "Estimated Tons",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 115,
   "name": "est_kw_per_ton_5",
   "description": "Estimated Kw Per Ton",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 9,
   "name": "an_inp11_typ_1",
   "description": "AI11 Type",
   "units": "",
   "access": "W",
   "states": "4-20 ma, 0-10VDC, 0-5 VDC"
  },
  {
   "type": "AV",
   "instance": 86,
   "name": "min_scale_src_diff_pr_1",
   "description": "Min Source Diff Press Scale @ 0",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 57,
   "name": "max_scale_src_diff_pr_1",
   "description": "Max Source Diff Press Scale",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 6,
   "name": "an_inp8_typ_1",
   "description": "AI8 Type",
   "units": "",
   "access": "W",
   "states": "4-20 ma, 0-10VDC, 0-5 VDC"
  },
  {
   "type": "AV",
   "instance": 70,
   "name": "min_scale_cool_diff_pr_1",
   "description": "Min Cool Diff Press Scale @ 0",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 53,
   "name": "max_scale_cool_diff_pr_1",
   "description": "Max Cool Diff Press Scale",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "an_inp1-13_typ_1",
   "description": "AI1-13 Type",
   "units": "",
   "access": "W",
   "states": "4-20 ma, 0-10VDC, 0-5 VDC"
  },
  {
   "type": "AV",
   "instance": 85,
   "name": "min_scale_heat_diff_pr_1",
   "description": "Min Heat Diff Press Scale @ 0",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 54,
   "name": "max_scale_heat_diff_pr_1",
   "description": "Max Heat Diff Press Scale",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 303,
   "name": "min_dp_oor_offset_1",
   "description": "Min DP Scale Offset for OOR",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 302,
   "name": "max_dp_oor_offset_1",
   "description": "Max DP Scale Offset for OOR",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "chwr_lo_lim_1",
   "description": "CHWR Enable Lo Limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "chwr_hi_lim_1",
   "description": "CHWR Enable Hi Limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 73,
   "name": "chws_low_lim_1",
   "description": "LO EVAP LVG TMP",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 64,
   "name": "chws_hi_lim_1",
   "description": "HI EVAP LVG TMP",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 200,
   "name": "cws_low_lim_1",
   "description": "LO CND LVG TMP",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 199,
   "name": "cws_hi_lim_1",
   "description": "HI COND LVG TMP",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 66,
   "name": "cwr_lo_lim_1",
   "description": "CWR Enable Lo Limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 63,
   "name": "cwr_hi_lim_1",
   "description": "CWR Enable Hi Limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 71,
   "name": "lo_ambient_tmp_1",
   "description": "LO AMBIENT TMP",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 62,
   "name": "hi_ambient_tmp_1",
   "description": "HI AMBIENT TMP",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 537,
   "name": "sws_lo_lim_1",
   "description": "SWS Enable Lo Limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 536,
   "name": "sws_hi_lim_1",
   "description": "SWS Enable Hi Limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 530,
   "name": "swr_lo_lim_1",
   "description": "SWR Enable Lo Limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 529,
   "name": "swr_hi_lim_1",
   "description": "SWR Enable Hi Limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 146,
   "name": "off_delay_time_1",
   "description": "OFF MODE DELAY TIME",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 75,
   "name": "mod_open_vlv_on_delay_5",
   "description": "Module Open VLV ON DELAY",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 587,
   "name": "mod_heat_vlv_on_delay_5",
   "description": "Module Heat VLV ON DELAY",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "mod_cool_vlv_on_delay_5",
   "description": "Module Cool VLV ON DELAY",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 150,
   "name": "o562_1",
   "description": "Start-Up Delay",
   "units": "sec",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 149,
   "name": "n003_1",
   "description": "Stage Up Delay",
   "units": "sec",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 148,
   "name": "n006_1",
   "description": "Stage Down Delay",
   "units": "sec",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 51,
   "name": "cmprlead_refr_runtime_1",
   "description": "Compr Lead Refresh on Runtime",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 74,
   "name": "runtime_refresh_1",
   "description": "Runtime Refresh",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 250,
   "name": "safety_ind_delay2_5",
   "description": "SAFETY INDEX 2 DELAY STG DWN",
   "units": "sec",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 249,
   "name": "safety_ind_delay1_5",
   "description": "SAFETY INDEX 1 DELAY",
   "units": "sec",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 137,
   "name": "m01trimcool_5",
   "description": "Module 1 Trim Cool",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 172,
   "name": "m02trimcool_5",
   "description": "Module 2 Trim Cool",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 188,
   "name": "m03trimcool_5",
   "description": "Module 3 Trim Cool",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 198,
   "name": "m04trimcool_5",
   "description": "Module 4 Trim Cool",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 207,
   "name": "m05trimcool_5",
   "description": "Module 5 Trim Cool",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 217,
   "name": "m06trimcool_5",
   "description": "Module 6 Trim Cool",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 221,
   "name": "m07trimcool_5",
   "description": "Module 7 Trim Cool",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 139,
   "name": "m01trimheat_5",
   "description": "Module 1 Trim Heat",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 174,
   "name": "m02trimheat_5",
   "description": "Module 2 Trim Heat",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 191,
   "name": "m03trimheat_5",
   "description": "Module 3 Trim Heat",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 202,
   "name": "m04trimheat_5",
   "description": "Module 4 Trim Heat",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 212,
   "name": "m05trimheat_5",
   "description": "Module 5 Trim Heat",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 219,
   "name": "m06trimheat_5",
   "description": "Module 6 Trim Heat",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  },
  {
   "type": "BV",
   "instance": 225,
   "name": "m07trimheat_5",
   "description": "Module 7 Trim Heat",
   "units": "",
   "access": "W",
   "states": "No, Yes"
  }
 ],
 "integration": {
  "summary": "Set the master controller DIP switches for the BMS port (MS/TP m protocol and baud), keep the device number at 516800, then set Control Source to BAS. Enable cooling and heating through the BAS enable points, write the leaving-water targets, and monitor unit mode, run commands and supply/return temperatures. Keep polling light: the IOM limits it to 50 points at 20-second intervals or slower.",
  "minimum_points": [
   {
    "ref": "MV 1",
    "name": "control_source_1",
    "why": "Control source: Dig Input, Keypad or BAS"
   },
   {
    "ref": "BV 576",
    "name": "enable_bas_cool_1",
    "why": "Cool enable from the BAS"
   },
   {
    "ref": "BV 577",
    "name": "enable_bas_heat_1",
    "why": "Heat enable from the BAS"
   },
   {
    "ref": "AV 41",
    "name": "chw_temp_stp_1",
    "why": "Cooling leaving water target (writable)"
   },
   {
    "ref": "AV 61",
    "name": "cw_temp_stp_1",
    "why": "Heating leaving water target (writable)"
   },
   {
    "ref": "MV 16",
    "name": "unit_mode_1",
    "why": "Unit mode / reason not running"
   },
   {
    "ref": "BV 574",
    "name": "run_cool_1",
    "why": "Chiller cool run command status"
   },
   {
    "ref": "BV 575",
    "name": "run_heat_1",
    "why": "Chiller heat run command status"
   },
   {
    "ref": "AV 17",
    "name": "chws_stat_1",
    "why": "Chilled water supply (leaving) temperature"
   },
   {
    "ref": "AV 42",
    "name": "cwr_stat_1",
    "why": "Heating water leaving temperature"
   }
  ],
  "enable": "Set the master panel LOCAL-OFF-REMOTE switch to Remote and turn Cool/Heat Mode BAS on; the bank then runs on the BAS command. Alternatives are a hard-wired remote enable relay (Digital Input mode) or keypad enable.",
  "heartbeat": null,
  "remote_sensors": "Remote cooling/heating targets can come in as analog inputs (input channel types 'Remote Cool Trg' / 'Remote Heat Trg', 4-20 mA or 2-10 VDC); the resulting values show in rem_chw_stp_stat_1 (AV 243) and rem_cw_stp_stat_1 (AV 246).",
  "setup": [
   "Default master board device number is 516800; ClimaCool says other numbers need custom programming.",
   "Port 1 is BACnet over ARC156 (Port 1 Mode jumper to ARC156); the BMS uses Port 2 with DIP 'BMS Port' ON and 'Enhanced Port 2a' OFF.",
   "DIP switches 4-5 set the BMS baud rate and 6-8 the protocol; use 'MS/TP m' for BACnet MS/TP.",
   "For BACnet IP set the IP-address DIP switch ON and configure the address in BACview under FN0 > IP; newer CoolLogic Touch panels use the Gig-E port for BACnet/IP."
  ],
  "gotchas": [
   "Poll no more than 50 points, no faster than every 20 seconds.",
   "When re-powering, the CoolLogic master must be the last device powered after the modules to restore communication.",
   "Many writable points are configuration values (limits, delays, PID settings); limit BMS writes to enables and setpoints."
  ]
 },
 "page": "https://easybacnet.com/bacnet-points-lists/climacool/shc-ondemand-uch-heat-pump",
 "note": "Re-typed from the manufacturer's public documentation (see source). Point availability varies by firmware and options; verify against the live device."
}