- Home
- BACnet points lists
- Chipkin Automation Systems
- CAS-2700-24 SMA Gateway - Sunny Island objects
Battery inverter (off-grid / backup) via BACnet gateway · BACnet points list
Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny Island objects BACnet points list
Updated 11 November 2026
For an SMA Sunny Island the CAS-2700-24 gateway serves 120 read-only Analog Inputs on BACnet IP, named with SMA's channel codes. They cover battery, generator, external/grid and inverter values for the master and up to three slave units, relay states and Sunny Island Charger PV values.
This page lists 120 BACnet objects for the Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny Island objects — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Chipkin Automation Systems’s own free documentation, linked below.
- Manufacturer
- Chipkin Automation Systems
- Model
- CAS-2700-24 SMA Gateway - Sunny Island objects
- Equipment
- Battery inverter (off-grid / backup) via BACnet gateway
- Equipment type
- Other equipment
- BACnet objects
- 120 (0 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Default device instance
- 389001
- Also known as
- SMA Sunny Island BACnet, Sunny Island battery inverter BACnet, CAS-2700-24, Chipkin SMA gateway
Reference only, provided as-is: verify against Chipkin Automation Systems’s current documentation and the live device before use. Not official Chipkin Automation Systems information. Terms of use.
BMS integration notes: Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny Island objects
Add the WebBox and each SMA device on the gateway's configuration page, then read the Analog Inputs; the gateway is monitoring only.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 82 | OpStt | Operating state (OpStt) | Read |
| AI 6 | BatSoc | Battery state of charge (BatSoc) | Read |
| AI 9 | BatVtg | Battery voltage | Read |
| AI 8 | BatTmp | Battery temperature | Read |
| AI 55 | GnStt | Generator status (GnStt) | Read |
| AI 18 | Error | Sunny Island error status | Read |
Heartbeat & communication loss
If the gateway loses a device or a value can't be read, the object's Out_Of_Service is set true and the last good value stays in Present_Value.
Network setup
- Gateway default BACnet device instance 389001, UDP port 47808; give each gateway a unique instance.
- Enter the Sunny WebBox IP address and pick the device type (Invertor, SensorBox or Sunny Island) for each device in the gateway's web page.
- Only one Sunny WebBox per gateway.
Watch out for
- Watch Out_Of_Service rather than the value to spot lost data.
- Names are SMA channel codes; see the SMA documentation for scaling and units.
Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny Island objects BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Adr | Read | |||
| AI | 2 | AptPhs | Read | |||
| AI | 3 | AptTmRmg | Read | |||
| AI | 4 | BatChrgOp | Read | |||
| AI | 5 | BatChrgVtg | Read | |||
| AImin | 6 | BatSoc | Read | |||
| AI | 7 | BatSocErr | Read | |||
| AImin | 8 | BatTmp | Read | |||
| AImin | 9 | BatVtg | Read | |||
| AI | 10 | CardStt | Read | |||
| AI | 11 | ChpPwrAt | Read | |||
| AI | 12 | ChpRmgTm | Read | |||
| AI | 13 | ChpStrRmgTm | Read | |||
| AI | 14 | ChpStt | Read | |||
| AI | 15 | EgyCntIn | Read | |||
| AI | 16 | EgyCntOut | Read | |||
| AI | 17 | EgyCntTm | Read | |||
| AImin | 18 | Error | Read | |||
| AI | 19 | E-Total | Read | |||
| AI | 20 | E-Total-In | Read | |||
| AI | 21 | ExtCur | Read | |||
| AI | 22 | ExtCurSlv1 | Read | |||
| AI | 23 | ExtCurSlv2 | Read | |||
| AI | 24 | ExtCurSlv3 | Read | |||
| AI | 25 | ExtFrq | Read | |||
| AI | 26 | ExtPwrAt | Read | |||
| AI | 27 | ExtPwrAtSlv1 | Read | |||
| AI | 28 | ExtPwrAtSlv2 | Read | |||
| AI | 29 | ExtPwrAtSlv3 | Read | |||
| AI | 30 | ExtPwrRt | Read | |||
| AI | 31 | ExtPwrRtSlv1 | Read | |||
| AI | 32 | ExtPwrRtSlv2 | Read | |||
| AI | 33 | ExtPwrRtSlv3 | Read | |||
| AI | 34 | ExtVtg | Read | |||
| AI | 35 | ExtVtgSlv1 | Read | |||
| AI | 36 | ExtVtgSlv2 | Read | |||
| AI | 37 | ExtVtgSlv3 | Read | |||
| AI | 38 | Fac | Read | |||
| AI | 39 | Firmware | Read | |||
| AI | 40 | FwVer | Read | |||
| AI | 41 | FwVer2 | Read | |||
| AI | 42 | GdCtcCnt | Read | |||
| AI | 43 | GdEgyCntIn | Read | |||
| AI | 44 | GdEgyCntOut | Read | |||
| AI | 45 | GdEgyTmh | Read | |||
| AI | 46 | GdOpTmh | Read | |||
| AI | 47 | GdRmgTm | Read | |||
| AI | 48 | GnDmdSrc | Read | |||
| AI | 49 | GnEgyCnt | Read | |||
| AI | 50 | GnEgyTm | Read | |||
| AI | 51 | GnOpTmh | Read | |||
| AI | 52 | GnRmgTm | Read | |||
| AI | 53 | GnRnStt | Read | |||
| AI | 54 | GnStrCnt | Read | |||
| AImin | 55 | GnStt | Read | |||
| AI | 56 | h-On | Read | |||
| AI | 57 | Iac | Read | |||
| AI | 58 | InvCur | Read | |||
| AI | 59 | InvCurSlv1 | Read | |||
| AI | 60 | InvCurSlv2 | Read | |||
| AI | 61 | InvCurSlv3 | Read | |||
| AI | 62 | InvFrq | Read | |||
| AI | 63 | InvOpStt | Read | |||
| AI | 64 | InvOpSttSlv1 | Read | |||
| AI | 65 | InvOpSttSlv2 | Read | |||
| AI | 66 | InvOpSttSlv3 | Read | |||
| AI | 67 | InvPwrAt | Read | |||
| AI | 68 | InvPwrAtSlv1 | Read | |||
| AI | 69 | InvPwrAtSlv2 | Read | |||
| AI | 70 | InvPwrAtSlv3 | Read | |||
| AI | 71 | InvPwrRt | Read | |||
| AI | 72 | InvPwrRtSlv1 | Read | |||
| AI | 73 | InvPwrRtSlv2 | Read | |||
| AI | 74 | InvPwrRtSlv3 | Read | |||
| AI | 75 | InvVtg | Read | |||
| AI | 76 | InvVtgSlv1 | Read | |||
| AI | 77 | InvVtgSlv2 | Read | |||
| AI | 78 | InvVtgSlv3 | Read | |||
| AI | 79 | Mode | Read | |||
| AI | 80 | Msg | Read | |||
| AI | 81 | OnTmh | Read | |||
| AImin | 82 | OpStt | Read | |||
| AI | 83 | OpSttSlv1 | Read | |||
| AI | 84 | OpSttSlv2 | Read | |||
| AI | 85 | OpSttSlv3 | Read | |||
| AI | 86 | Pac | Read | |||
| AI | 87 | Prio | Read | |||
| AI | 88 | Rly1Stt | Read | |||
| AI | 89 | Rly2Stt | Read | |||
| AI | 90 | RmgTmEqu | Read | |||
| AI | 91 | RmgTmFul | Read | |||
| AI | 92 | Serial Number | Read | |||
| AI | 93 | Sic1EgyCntIn | Read | |||
| AI | 94 | Sic1PvPwr | Read | |||
| AI | 95 | Sic1TdyEgyCntIn | Read | |||
| AI | 96 | Sic2EgyCntIn | Read | |||
| AI | 97 | Sic2PvPwr | Read | |||
| AI | 98 | Sic2TdyEgyCntIn | Read | |||
| AI | 99 | Sic3EgyCntIn | Read | |||
| AI | 100 | Sic3PvPwr | Read | |||
| AI | 101 | Sic3TdyEgyCntIn | Read | |||
| AI | 102 | Sic4EgyCntIn | Read | |||
| AI | 103 | Sic4PvPwr | Read | |||
| AI | 104 | Sic4TdyEgyCntIn | Read | |||
| AI | 105 | Soh | Read | |||
| AI | 106 | TotBatCur | Read | |||
| AI | 107 | TotExtCur | Read | |||
| AI | 108 | TotExtPwrAt | Read | |||
| AI | 109 | TotExtPwrRt | Read | |||
| AI | 110 | TotInvCur | Read | |||
| AI | 111 | TotInvPwrAt | Read | |||
| AI | 112 | TotInvPwrRt | Read | |||
| AI | 113 | TotLodPwr | Read | |||
| AI | 114 | TotMccLodPwr | Read | |||
| AI | 115 | TotSicBatCur | Read | |||
| AI | 116 | TotSicDyEgyCntI | Read | |||
| AI | 117 | TotSicEgyCntIn | Read | |||
| AI | 118 | TotSicPvPwr | Read | |||
| AI | 119 | TotTmh | Read | |||
| AI | 120 | Vac | Read |
No points match these filters.
Object ID lookup: Chipkin Automation Systems CAS-2700-24 SMA Sunny Island point IDs by name
AI1AdrAI2AptPhsAI3AptTmRmgAI4BatChrgOpAI5BatChrgVtgAI6BatSocAI7BatSocErrAI8BatTmpAI9BatVtgAI10CardSttAI11ChpPwrAtAI12ChpRmgTmAI13ChpStrRmgTmAI14ChpSttAI15EgyCntInAI16EgyCntOutAI17EgyCntTmAI18ErrorAI19E-TotalAI20E-Total-InAI21ExtCurAI22ExtCurSlv1AI23ExtCurSlv2AI24ExtCurSlv3AI25ExtFrqAI26ExtPwrAtAI27ExtPwrAtSlv1AI28ExtPwrAtSlv2AI29ExtPwrAtSlv3AI30ExtPwrRtAI31ExtPwrRtSlv1AI32ExtPwrRtSlv2AI33ExtPwrRtSlv3AI34ExtVtgAI35ExtVtgSlv1AI36ExtVtgSlv2AI37ExtVtgSlv3AI38FacAI39FirmwareAI40FwVerAI41FwVer2AI42GdCtcCntAI43GdEgyCntInAI44GdEgyCntOutAI45GdEgyTmhAI46GdOpTmhAI47GdRmgTmAI48GnDmdSrcAI49GnEgyCntAI50GnEgyTmAI51GnOpTmhAI52GnRmgTmAI53GnRnSttAI54GnStrCntAI55GnSttAI56h-OnAI57IacAI58InvCurAI59InvCurSlv1AI60InvCurSlv2AI61InvCurSlv3AI62InvFrqAI63InvOpSttAI64InvOpSttSlv1AI65InvOpSttSlv2AI66InvOpSttSlv3AI67InvPwrAtAI68InvPwrAtSlv1AI69InvPwrAtSlv2AI70InvPwrAtSlv3AI71InvPwrRtAI72InvPwrRtSlv1AI73InvPwrRtSlv2AI74InvPwrRtSlv3AI75InvVtgAI76InvVtgSlv1AI77InvVtgSlv2AI78InvVtgSlv3AI79ModeAI80MsgAI81OnTmhAI82OpSttAI83OpSttSlv1AI84OpSttSlv2AI85OpSttSlv3AI86PacAI87PrioAI88Rly1SttAI89Rly2SttAI90RmgTmEquAI91RmgTmFulAI92Serial NumberAI93Sic1EgyCntInAI94Sic1PvPwrAI95Sic1TdyEgyCntInAI96Sic2EgyCntInAI97Sic2PvPwrAI98Sic2TdyEgyCntInAI99Sic3EgyCntInAI100Sic3PvPwrAI101Sic3TdyEgyCntInAI102Sic4EgyCntInAI103Sic4PvPwrAI104Sic4TdyEgyCntInAI105SohAI106TotBatCurAI107TotExtCurAI108TotExtPwrAtAI109TotExtPwrRtAI110TotInvCurAI111TotInvPwrAtAI112TotInvPwrRtAI113TotLodPwrAI114TotMccLodPwrAI115TotSicBatCurAI116TotSicDyEgyCntIAI117TotSicEgyCntInAI118TotSicPvPwrAI119TotTmhAI120Vac
Integration notes
- All objects are Analog Inputs; the manual gives names only, with no units or descriptions.
- Each further SMA device added to the gateway is offset by 100 (second device starts at AI 101, third at AI 201).
- The list is what the gateway exposes with its default configuration; the gateway polls the devices through one SMA Sunny WebBox.
- Access is inferred: Analog Inputs are read-only.
- This list runs to AI 120 but the guide offsets each further device by only 100, so a second device would overlap; check instances on site.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CAS-2700-24 SMA Gateway - Sunny Island objects and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny Island objects
How many BACnet points does the Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny Island objects have?
This list has 120 BACnet objects: 120 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny Island objects BACnet points are writable?
None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.
Where is the official Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny Island objects BACnet documentation?
The source is CAS-2700-24 SMA Gateway Manual (Modbus RTU and TCP / BACnet / HTML Gateway) (CAS-2700-24), revision Doc Rev 0, 12 Feb 2014, published free by Chipkin Automation Systems at https://cdn.chipkin.com/assets/uploads/2017/mar/09-14-31-59_CAS-2700-24%20-%20SMA%20to%20Modbus_RTU%20and%20TCP_%20BACnet%20and%20HTML%20Gateway%20Manual.pdf.
What are the minimum BACnet points to integrate the Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny Island objects?
Start with AI 82 OpStt (Operating state (OpStt)); AI 6 BatSoc (Battery state of charge (BatSoc)); AI 9 BatVtg (Battery voltage); AI 8 BatTmp (Battery temperature); AI 55 GnStt (Generator status (GnStt)); AI 18 Error (Sunny Island error status).
Does the Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny Island objects need a BACnet heartbeat or have a communication timeout?
If the gateway loses a device or a value can't be read, the object's Out_Of_Service is set true and the last good value stays in Present_Value.
How do I check these points on the real CAS-2700-24 SMA Gateway - Sunny Island objects?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Chipkin Automation Systems BACnet points lists
- Solar irradiance and weather sensor via BACnet gateway
Chipkin Automation Systems CAS-2700-24 SMA Gateway - SensorBox objects
SMA Sunny SensorBox weather/irradiance stations connected to a Sunny WebBox polled by the Chipkin CAS-2700-24 gateway.
Also known as: SMA SensorBox BACnet, Sunny SensorBox BACnet, CAS-2700-24, Chipkin SMA gateway - Solar PV inverter via BACnet gateway
Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny inverter objects
SMA Sunny inverters connected to a Sunny WebBox that the Chipkin CAS-2700-24 gateway polls.
Also known as: SMA Sunny Boy BACnet, SMA inverter BACnet, Sunny WebBox BACnet gateway, CAS-2700-24, Chipkin SMA gateway
Source: CAS-2700-24 SMA Gateway Manual (Modbus RTU and TCP / BACnet / HTML Gateway) · CAS-2700-24 · rev. Doc Rev 0, 12 Feb 2014. Object names, instances and units are reproduced as published; descriptions are our own.