Battery inverter (off-grid / backup) via BACnet gateway · BACnet points list

Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny Island objects BACnet points list

Updated 11 November 2026

Short answer

For an SMA Sunny Island the CAS-2700-24 gateway serves 120 read-only Analog Inputs on BACnet IP, named with SMA's channel codes. They cover battery, generator, external/grid and inverter values for the master and up to three slave units, relay states and Sunny Island Charger PV values.

This page lists 120 BACnet objects for the Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny Island objects — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Chipkin Automation Systems’s own free documentation, linked below.

Manufacturer
Chipkin Automation Systems
Model
CAS-2700-24 SMA Gateway - Sunny Island objects
Equipment
Battery inverter (off-grid / backup) via BACnet gateway
Equipment type
Other equipment
BACnet objects
120 (0 writable)
Transport
BACnet IP
Firmware
Not stated
Default device instance
389001
Also known as
SMA Sunny Island BACnet, Sunny Island battery inverter BACnet, CAS-2700-24, Chipkin SMA gateway
Source document
CAS-2700-24 SMA Gateway Manual (Modbus RTU and TCP / BACnet / HTML Gateway) · CAS-2700-24 · rev. Doc Rev 0, 12 Feb 2014
Download CSV 120 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Chipkin Automation Systems’s current documentation and the live device before use. Not official Chipkin Automation Systems information. Terms of use.

BMS integration notes: Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny Island objects

Integration in brief

Add the WebBox and each SMA device on the gateway's configuration page, then read the Analog Inputs; the gateway is monitoring only.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 82OpSttOperating state (OpStt)Read
AI 6BatSocBattery state of charge (BatSoc)Read
AI 9BatVtgBattery voltageRead
AI 8BatTmpBattery temperatureRead
AI 55GnSttGenerator status (GnStt)Read
AI 18ErrorSunny Island error statusRead

Heartbeat & communication loss

If the gateway loses a device or a value can't be read, the object's Out_Of_Service is set true and the last good value stays in Present_Value.

Network setup

Watch out for

Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny Island objects BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

120 of 120 shown
Type
Analog
Show
Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny Island objects BACnet Points List
DescriptionStates
AI1AdrRead
AI2AptPhsRead
AI3AptTmRmgRead
AI4BatChrgOpRead
AI5BatChrgVtgRead
AImin6BatSocRead
AI7BatSocErrRead
AImin8BatTmpRead
AImin9BatVtgRead
AI10CardSttRead
AI11ChpPwrAtRead
AI12ChpRmgTmRead
AI13ChpStrRmgTmRead
AI14ChpSttRead
AI15EgyCntInRead
AI16EgyCntOutRead
AI17EgyCntTmRead
AImin18ErrorRead
AI19E-TotalRead
AI20E-Total-InRead
AI21ExtCurRead
AI22ExtCurSlv1Read
AI23ExtCurSlv2Read
AI24ExtCurSlv3Read
AI25ExtFrqRead
AI26ExtPwrAtRead
AI27ExtPwrAtSlv1Read
AI28ExtPwrAtSlv2Read
AI29ExtPwrAtSlv3Read
AI30ExtPwrRtRead
AI31ExtPwrRtSlv1Read
AI32ExtPwrRtSlv2Read
AI33ExtPwrRtSlv3Read
AI34ExtVtgRead
AI35ExtVtgSlv1Read
AI36ExtVtgSlv2Read
AI37ExtVtgSlv3Read
AI38FacRead
AI39FirmwareRead
AI40FwVerRead
AI41FwVer2Read
AI42GdCtcCntRead
AI43GdEgyCntInRead
AI44GdEgyCntOutRead
AI45GdEgyTmhRead
AI46GdOpTmhRead
AI47GdRmgTmRead
AI48GnDmdSrcRead
AI49GnEgyCntRead
AI50GnEgyTmRead
AI51GnOpTmhRead
AI52GnRmgTmRead
AI53GnRnSttRead
AI54GnStrCntRead
AImin55GnSttRead
AI56h-OnRead
AI57IacRead
AI58InvCurRead
AI59InvCurSlv1Read
AI60InvCurSlv2Read
AI61InvCurSlv3Read
AI62InvFrqRead
AI63InvOpSttRead
AI64InvOpSttSlv1Read
AI65InvOpSttSlv2Read
AI66InvOpSttSlv3Read
AI67InvPwrAtRead
AI68InvPwrAtSlv1Read
AI69InvPwrAtSlv2Read
AI70InvPwrAtSlv3Read
AI71InvPwrRtRead
AI72InvPwrRtSlv1Read
AI73InvPwrRtSlv2Read
AI74InvPwrRtSlv3Read
AI75InvVtgRead
AI76InvVtgSlv1Read
AI77InvVtgSlv2Read
AI78InvVtgSlv3Read
AI79ModeRead
AI80MsgRead
AI81OnTmhRead
AImin82OpSttRead
AI83OpSttSlv1Read
AI84OpSttSlv2Read
AI85OpSttSlv3Read
AI86PacRead
AI87PrioRead
AI88Rly1SttRead
AI89Rly2SttRead
AI90RmgTmEquRead
AI91RmgTmFulRead
AI92Serial NumberRead
AI93Sic1EgyCntInRead
AI94Sic1PvPwrRead
AI95Sic1TdyEgyCntInRead
AI96Sic2EgyCntInRead
AI97Sic2PvPwrRead
AI98Sic2TdyEgyCntInRead
AI99Sic3EgyCntInRead
AI100Sic3PvPwrRead
AI101Sic3TdyEgyCntInRead
AI102Sic4EgyCntInRead
AI103Sic4PvPwrRead
AI104Sic4TdyEgyCntInRead
AI105SohRead
AI106TotBatCurRead
AI107TotExtCurRead
AI108TotExtPwrAtRead
AI109TotExtPwrRtRead
AI110TotInvCurRead
AI111TotInvPwrAtRead
AI112TotInvPwrRtRead
AI113TotLodPwrRead
AI114TotMccLodPwrRead
AI115TotSicBatCurRead
AI116TotSicDyEgyCntIRead
AI117TotSicEgyCntInRead
AI118TotSicPvPwrRead
AI119TotTmhRead
AI120VacRead
Object ID lookup: Chipkin Automation Systems CAS-2700-24 SMA Sunny Island point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CAS-2700-24 SMA Gateway - Sunny Island objects and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny Island objects

How many BACnet points does the Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny Island objects have?

This list has 120 BACnet objects: 120 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny Island objects BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny Island objects BACnet documentation?

The source is CAS-2700-24 SMA Gateway Manual (Modbus RTU and TCP / BACnet / HTML Gateway) (CAS-2700-24), revision Doc Rev 0, 12 Feb 2014, published free by Chipkin Automation Systems at https://cdn.chipkin.com/assets/uploads/2017/mar/09-14-31-59_CAS-2700-24%20-%20SMA%20to%20Modbus_RTU%20and%20TCP_%20BACnet%20and%20HTML%20Gateway%20Manual.pdf.

What are the minimum BACnet points to integrate the Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny Island objects?

Start with AI 82 OpStt (Operating state (OpStt)); AI 6 BatSoc (Battery state of charge (BatSoc)); AI 9 BatVtg (Battery voltage); AI 8 BatTmp (Battery temperature); AI 55 GnStt (Generator status (GnStt)); AI 18 Error (Sunny Island error status).

Does the Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny Island objects need a BACnet heartbeat or have a communication timeout?

If the gateway loses a device or a value can't be read, the object's Out_Of_Service is set true and the last good value stays in Present_Value.

How do I check these points on the real CAS-2700-24 SMA Gateway - Sunny Island objects?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Chipkin Automation Systems BACnet points lists

Source: CAS-2700-24 SMA Gateway Manual (Modbus RTU and TCP / BACnet / HTML Gateway) · CAS-2700-24 · rev. Doc Rev 0, 12 Feb 2014. Object names, instances and units are reproduced as published; descriptions are our own.