Solar PV inverter via BACnet gateway · BACnet points list

Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny inverter objects BACnet points list

Updated 11 November 2026

Short answer

The Chipkin CAS-2700-24 gateway reads SMA devices through a Sunny WebBox and serves them on BACnet IP. Each Sunny inverter gets 25 read-only Analog Inputs with SMA's own channel names: grid voltage, current and frequency, PV voltage and current, AC power, energy totals, operating hours, mode, error and temperature.

This page lists 25 BACnet objects for the Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny inverter objects — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Chipkin Automation Systems’s own free documentation, linked below.

Manufacturer
Chipkin Automation Systems
Model
CAS-2700-24 SMA Gateway - Sunny inverter objects
Equipment
Solar PV inverter via BACnet gateway
Equipment type
Other equipment
BACnet objects
25 (0 writable)
Transport
BACnet IP
Firmware
Not stated
Default device instance
389001
Also known as
SMA Sunny Boy BACnet, SMA inverter BACnet, Sunny WebBox BACnet gateway, CAS-2700-24, Chipkin SMA gateway
Source document
CAS-2700-24 SMA Gateway Manual (Modbus RTU and TCP / BACnet / HTML Gateway) · CAS-2700-24 · rev. Doc Rev 0, 12 Feb 2014
Download CSV 25 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Chipkin Automation Systems’s current documentation and the live device before use. Not official Chipkin Automation Systems information. Terms of use.

BMS integration notes: Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny inverter objects

Integration in brief

Add the WebBox and each SMA device on the gateway's configuration page, then read the Analog Inputs; the gateway is monitoring only.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 13ModeOperating modeRead
AI 14PacAC output power (Pac)Read
AI 5E-TotalTotal energy yield (E-Total)Read
AI 11IacAC current (Iac)Read
AI 17VacGrid voltage (Vac)Read
AI 4ErrorInverter error statusRead

Heartbeat & communication loss

If the gateway loses a device or a value can't be read, the object's Out_Of_Service is set true and the last good value stays in Present_Value.

Network setup

Watch out for

Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny inverter objects BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

25 of 25 shown
Type
Analog
Show
Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny inverter objects BACnet Points List
DescriptionStates
AI1Backup StateRead
AI2BalancerRead
AI3CO2 savedRead
AImin4ErrorRead
AImin5E-TotalRead
AI6Event-CntRead
AI7FacRead
AI8Grid TypeRead
AI9h-OnRead
AI10h-TotalRead
AImin11IacRead
AI12IpvRead
AImin13ModeRead
AImin14PacRead
AI15Power OnRead
AI16TemperatureRead
AImin17VacRead
AI18VpvRead
AI19Serial NumberRead
AI20VacL1Read
AI21VacL2Read
AI22Vpv-_PERead
AI23Max TemperatureRead
AI24Max VpvRead
AI25VfanRead
Object ID lookup: Chipkin Automation Systems CAS-2700-24 SMA Sunny Inverter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CAS-2700-24 SMA Gateway - Sunny inverter objects and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny inverter objects

How many BACnet points does the Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny inverter objects have?

This list has 25 BACnet objects: 25 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny inverter objects BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny inverter objects BACnet documentation?

The source is CAS-2700-24 SMA Gateway Manual (Modbus RTU and TCP / BACnet / HTML Gateway) (CAS-2700-24), revision Doc Rev 0, 12 Feb 2014, published free by Chipkin Automation Systems at https://cdn.chipkin.com/assets/uploads/2017/mar/09-14-31-59_CAS-2700-24%20-%20SMA%20to%20Modbus_RTU%20and%20TCP_%20BACnet%20and%20HTML%20Gateway%20Manual.pdf.

What are the minimum BACnet points to integrate the Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny inverter objects?

Start with AI 13 Mode (Operating mode); AI 14 Pac (AC output power (Pac)); AI 5 E-Total (Total energy yield (E-Total)); AI 11 Iac (AC current (Iac)); AI 17 Vac (Grid voltage (Vac)); AI 4 Error (Inverter error status).

Does the Chipkin Automation Systems CAS-2700-24 SMA Gateway - Sunny inverter objects need a BACnet heartbeat or have a communication timeout?

If the gateway loses a device or a value can't be read, the object's Out_Of_Service is set true and the last good value stays in Present_Value.

How do I check these points on the real CAS-2700-24 SMA Gateway - Sunny inverter objects?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Chipkin Automation Systems BACnet points lists

Source: CAS-2700-24 SMA Gateway Manual (Modbus RTU and TCP / BACnet / HTML Gateway) · CAS-2700-24 · rev. Doc Rev 0, 12 Feb 2014. Object names, instances and units are reproduced as published; descriptions are our own.