Energy meter (multifunction panel meter) · BACnet points list

CET Electric PMC-53A-E multifunction panel meter, BACnet MS/TP BACnet points list

Updated 12 November 2026

Short answer

The PMC-53A-E is a multifunction panel power meter that acts as a BACnet MS/TP smart actuator (B-SA). Its Analog Inputs carry voltages, currents, power, power factor, energy, demand, THD, K-factor, angles, unbalance and pulse counters, with object instances matching its Modbus register numbers; Analog Values hold PT/CT and wiring setup plus clear commands; four DIs and two DOs are Binary Inputs and Outputs.

This page lists 121 BACnet objects for the CET Electric PMC-53A-E multifunction panel meter, BACnet MS/TP — 22 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CET Electric’s own free documentation, linked below.

Manufacturer
CET Electric
Model
PMC-53A-E multifunction panel meter, BACnet MS/TP
Equipment
Energy meter (multifunction panel meter)
Equipment type
Thermostats, sensors & meters
BACnet objects
121 (22 writable)
Transport
BACnet MS/TP
Firmware
Application V2.00.00, firmware V1.00.00
Default device instance
26001
Also known as
PMC-53A-E, PMC53A-E, CET PMC-53A-E
Source document
PMC-53A-E User Manual, Appendix C BACnet MS/TP Implementation · V2.2 · rev. 2026-04-01
Download CSV 121 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CET Electric’s current documentation and the live device before use. Not official CET Electric information. Terms of use.

BMS integration notes: CET Electric PMC-53A-E multifunction panel meter, BACnet MS/TP

Integration in brief

Set the PMC-53A-E protocol to BACnet MS/TP with a MAC address and baud rate, then read power, energy, voltages and currents. Set PT/CT ratios and wiring mode first if the BMS manages setup.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 30P TotalTotal active power, kWRead
AI 500kWh ImportEnergy imported, kWhRead
AI 502kWh ExportEnergy exported, kWhRead
AI 14ULL AverageAverage line-line voltage, VRead
AI 22I AverageAverage current, ARead
AI 54PF TotalTotal power factorRead
AI 56Freq.Frequency, HzRead

Network setup

Watch out for

CET Electric PMC-53A-E multifunction panel meter, BACnet MS/TP BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

121 of 121 shown
Type
Access
Show
CET Electric PMC-53A-E multifunction panel meter, BACnet MS/TP BACnet Points List
DescriptionStates
AI0UaVRead
AI2UbVRead
AI4UcVRead
AI6ULN AverageVRead
AI8UabVRead
AI10UbcVRead
AI12UcaVRead
AImin14ULL AverageVRead
AI16IaARead
AI18IbARead
AI20IcARead
AImin22I AverageARead
AI24PakWRead
AI26PbkWRead
AI28PckWRead
AImin30P TotalkWRead
AI32QakvarRead
AI34QbkvarRead
AI36QckvarRead
AI38Q TotalkvarRead
AI40SakVARead
AI42SbkVARead
AI44SckVARead
AI46S TotalkVARead
AI48PFaRead
AI50PFbRead
AI52PFcRead
AImin54PF TotalRead
AImin56Freq.HzRead
AI70In (Calculated)ARead
AI72I4 (Optional Measurement)(optional measurement)ARead
AI82AI (Optional Measurement)(optional measurement)Read
AI84Ir (Optional Measurement)(optional measurement)ARead
AI86RTD1 (Optional Measurement)(optional measurement)°CRead
AI88RTD2 (Optional Measurement)(optional measurement)°CRead
AI90RTD3 (Optional Measurement)(optional measurement)°CRead
AI92AO1 (Optional Measurement)(optional measurement)Read
AI94AO2 (Optional Measurement)(optional measurement)Read
AImin500kWh ImportkWhRead
AImin502kWh ExportkWhRead
AI504kWh NetkWhRead
AI506kWh TotalkWhRead
AI508kvarh ImportkvarhRead
AI510kvarh ExportkvarhRead
AI512kvarh NetkvarhRead
AI514kvarh TotalkvarhRead
AI516kVAhkVAhRead
AI3006P DemandkWRead
AI3008Q DemandkvarRead
AI3010S DemandkVARead
AI3000Ia DemandARead
AI3002Ib DemandARead
AI3004Ic DemandARead
AI3418P Max. DemandkWRead
AI3424Q Max. DemandkvarRead
AI3430S Max. DemandkVARead
AI3400Ia Max. DemandARead
AI3406Ib Max. DemandARead
AI3412Ic Max. DemandARead
AI1600Ua THD%Read
AI1602UbTHD%Read
AI1604Uc THD%Read
AI1400Ia THD%Read
AI1402Ib THD%Read
AI1404Ic THD%Read
AI1318Ia K FactorRead
AI1320Ib K FactorRead
AI1322Ic K FactorRead
AI1300Ia TDD%Read
AI1302Ib TDD%Read
AI1304Ic TDD%Read
AI1324Ia Crest FactorRead
AI1326Ib Crest FactorRead
AI1328Ic Crest FactorRead
AI1330U Unbalance%Read
AI1332I Unbalance%Read
AI74dPFaRead
AI76dPFbRead
AI78dPFcRead
AI58Ua Angle°Read
AI60Ub Angle°Read
AI62Uc Angle°Read
AI64Ia Angle°Read
AI66Ib Angle°Read
AI68Ic Angle°Read
AI104Run HourshRead
AI526Interval kWh ImportkWhRead
AI528Interval kWh ExportkWhRead
AI530Interval kvarh ImportkvarhRead
AI532Interval kvarh ExportkvarhRead
AI534Interval kVAhkVAhRead
AI1200DI #1 CounterRead
AI1202DI #2 CounterRead
AI1204DI #3 CounterRead
AI1206DI #4 CounterRead
AV6000PT Primary High #Range 0 to 1000 kV, default 0*kVWrite
AV6001PT Primary Low #Range 0 to 999 V, default 100*VWrite
AV6002PT Secondary#Range 1 to 690 V, default 100*VWrite
AV6004CT PrimaryRange 1 to 30000 A, default 5*AWrite
AV6006CT SecondaryRange 1 to 5/100 A, default 5*AWrite
AV6012I4 PrimaryRange 1 to 30000 A, default 5*AWrite
AV6014I4 SecondaryRange 1 to 5 A, default 5*AWrite
AV6020Wiring ModeSetting, default 3P4W*Write0=DEMO, 1=1P2W L-N, 2=1P2W L-L, 3=1P3W L-L-N, 4=3P3W, 5=3P4W, 6=3x1P
AV6021PF ConventionSetting, default 0*Write0=IEC, 1=IEEE, 2=-IEEE
AV6022kVA CalculationSetting, default 0*Write0=Vector, 1=Scalar
AV6028THD CalculationSetting, default 0*Write0=THDf, 1=THDr
AV6029Demand PeriodRange 1~60 mins, default 15*minWrite
AV6030Number of Sliding WindowsRange 1 to 15, default 1*Write
AV6047Interval Energy PeriodRange 5~60, default 60*Write
AV9603Clear Present Peak DemandSettingWrite65280 (Default=0)
AV9601Clear EnergySettingWrite65280 (Default = 0)
AV9610Clear DI #1 CounterSettingWrite65280 (Default = 0)
AV9611Clear DI #2 CounterWrite 65280 (0xFF00) to clearWrite
AV9612Clear DI #3 CounterWrite 65280 (0xFF00) to clearWrite
AV9613Clear DI #4 CounterWrite 65280 (0xFF00) to clearWrite
BI0DI 1Digital input statusRead0=Inactive, 1=Active
BI1DI 2Digital input statusRead0=Inactive, 1=Active
BI2DI 3Digital input statusRead0=Inactive, 1=Active
BI3DI 4Digital input statusRead0=Inactive, 1=Active
BO0DO 1Digital outputWrite0=Inactive, 1=Active
BO1DO 2Digital outputWrite0=Inactive, 1=Active
Object ID lookup: CET Electric PMC-53A-E multifunction panel meter, BACnet MS/TP point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PMC-53A-E multifunction panel meter, BACnet MS/TP and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CET Electric PMC-53A-E multifunction panel meter, BACnet MS/TP

How many BACnet points does the CET Electric PMC-53A-E multifunction panel meter, BACnet MS/TP have?

This list has 121 BACnet objects: 95 analog inputs, 20 analog values, 4 binary inputs, 2 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CET Electric PMC-53A-E multifunction panel meter, BACnet MS/TP BACnet points are writable?

22 of the 121 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official CET Electric PMC-53A-E multifunction panel meter, BACnet MS/TP BACnet documentation?

The source is PMC-53A-E User Manual, Appendix C BACnet MS/TP Implementation (V2.2), revision 2026-04-01, published free by CET Electric at https://www.cet-global.com/uploadfiles/2026/04/PMC-53A-E%20User%20Manual%20V2.2%20(20260401).pdf.

What are the minimum BACnet points to integrate the CET Electric PMC-53A-E multifunction panel meter, BACnet MS/TP?

Start with AI 30 P Total (Total active power, kW); AI 500 kWh Import (Energy imported, kWh); AI 502 kWh Export (Energy exported, kWh); AI 14 ULL Average (Average line-line voltage, V); AI 22 I Average (Average current, A); AI 54 PF Total (Total power factor); AI 56 Freq. (Frequency, Hz).

How do I check these points on the real PMC-53A-E multifunction panel meter, BACnet MS/TP?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More CET Electric BACnet points lists

Source: PMC-53A-E User Manual, Appendix C BACnet MS/TP Implementation · V2.2 · rev. 2026-04-01. Object names, instances and units are reproduced as published; descriptions are our own.