Energy meter (multifunction panel meter) · BACnet points list
CET Electric PMC-53A-E multifunction panel meter, BACnet MS/TP BACnet points list
Updated 12 November 2026
The PMC-53A-E is a multifunction panel power meter that acts as a BACnet MS/TP smart actuator (B-SA). Its Analog Inputs carry voltages, currents, power, power factor, energy, demand, THD, K-factor, angles, unbalance and pulse counters, with object instances matching its Modbus register numbers; Analog Values hold PT/CT and wiring setup plus clear commands; four DIs and two DOs are Binary Inputs and Outputs.
This page lists 121 BACnet objects for the CET Electric PMC-53A-E multifunction panel meter, BACnet MS/TP — 22 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CET Electric’s own free documentation, linked below.
- Manufacturer
- CET Electric
- Model
- PMC-53A-E multifunction panel meter, BACnet MS/TP
- Equipment
- Energy meter (multifunction panel meter)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 121 (22 writable)
- Transport
- BACnet MS/TP
- Firmware
- Application V2.00.00, firmware V1.00.00
- Default device instance
- 26001
- Also known as
- PMC-53A-E, PMC53A-E, CET PMC-53A-E
Reference only, provided as-is: verify against CET Electric’s current documentation and the live device before use. Not official CET Electric information. Terms of use.
BMS integration notes: CET Electric PMC-53A-E multifunction panel meter, BACnet MS/TP
Set the PMC-53A-E protocol to BACnet MS/TP with a MAC address and baud rate, then read power, energy, voltages and currents. Set PT/CT ratios and wiring mode first if the BMS manages setup.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 30 | P Total | Total active power, kW | Read |
| AI 500 | kWh Import | Energy imported, kWh | Read |
| AI 502 | kWh Export | Energy exported, kWh | Read |
| AI 14 | ULL Average | Average line-line voltage, V | Read |
| AI 22 | I Average | Average current, A | Read |
| AI 54 | PF Total | Total power factor | Read |
| AI 56 | Freq. | Frequency, Hz | Read |
Network setup
- BACnet MS/TP master at 9600, 19200 or 38400 baud; device instance defaults to 26001.
- Analog Values 6000-6047 hold PT/CT ratios, wiring mode and demand settings.
Watch out for
- Writing 65280 to AV 9601 clears all energy registers.
CET Electric PMC-53A-E multifunction panel meter, BACnet MS/TP BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 0 | Ua | V | Read | ||
| AI | 2 | Ub | V | Read | ||
| AI | 4 | Uc | V | Read | ||
| AI | 6 | ULN Average | V | Read | ||
| AI | 8 | Uab | V | Read | ||
| AI | 10 | Ubc | V | Read | ||
| AI | 12 | Uca | V | Read | ||
| AImin | 14 | ULL Average | V | Read | ||
| AI | 16 | Ia | A | Read | ||
| AI | 18 | Ib | A | Read | ||
| AI | 20 | Ic | A | Read | ||
| AImin | 22 | I Average | A | Read | ||
| AI | 24 | Pa | kW | Read | ||
| AI | 26 | Pb | kW | Read | ||
| AI | 28 | Pc | kW | Read | ||
| AImin | 30 | P Total | kW | Read | ||
| AI | 32 | Qa | kvar | Read | ||
| AI | 34 | Qb | kvar | Read | ||
| AI | 36 | Qc | kvar | Read | ||
| AI | 38 | Q Total | kvar | Read | ||
| AI | 40 | Sa | kVA | Read | ||
| AI | 42 | Sb | kVA | Read | ||
| AI | 44 | Sc | kVA | Read | ||
| AI | 46 | S Total | kVA | Read | ||
| AI | 48 | PFa | Read | |||
| AI | 50 | PFb | Read | |||
| AI | 52 | PFc | Read | |||
| AImin | 54 | PF Total | Read | |||
| AImin | 56 | Freq. | Hz | Read | ||
| AI | 70 | In (Calculated) | A | Read | ||
| AI | 72 | I4 (Optional Measurement) | (optional measurement) | A | Read | |
| AI | 82 | AI (Optional Measurement) | (optional measurement) | Read | ||
| AI | 84 | Ir (Optional Measurement) | (optional measurement) | A | Read | |
| AI | 86 | RTD1 (Optional Measurement) | (optional measurement) | °C | Read | |
| AI | 88 | RTD2 (Optional Measurement) | (optional measurement) | °C | Read | |
| AI | 90 | RTD3 (Optional Measurement) | (optional measurement) | °C | Read | |
| AI | 92 | AO1 (Optional Measurement) | (optional measurement) | Read | ||
| AI | 94 | AO2 (Optional Measurement) | (optional measurement) | Read | ||
| AImin | 500 | kWh Import | kWh | Read | ||
| AImin | 502 | kWh Export | kWh | Read | ||
| AI | 504 | kWh Net | kWh | Read | ||
| AI | 506 | kWh Total | kWh | Read | ||
| AI | 508 | kvarh Import | kvarh | Read | ||
| AI | 510 | kvarh Export | kvarh | Read | ||
| AI | 512 | kvarh Net | kvarh | Read | ||
| AI | 514 | kvarh Total | kvarh | Read | ||
| AI | 516 | kVAh | kVAh | Read | ||
| AI | 3006 | P Demand | kW | Read | ||
| AI | 3008 | Q Demand | kvar | Read | ||
| AI | 3010 | S Demand | kVA | Read | ||
| AI | 3000 | Ia Demand | A | Read | ||
| AI | 3002 | Ib Demand | A | Read | ||
| AI | 3004 | Ic Demand | A | Read | ||
| AI | 3418 | P Max. Demand | kW | Read | ||
| AI | 3424 | Q Max. Demand | kvar | Read | ||
| AI | 3430 | S Max. Demand | kVA | Read | ||
| AI | 3400 | Ia Max. Demand | A | Read | ||
| AI | 3406 | Ib Max. Demand | A | Read | ||
| AI | 3412 | Ic Max. Demand | A | Read | ||
| AI | 1600 | Ua THD | % | Read | ||
| AI | 1602 | UbTHD | % | Read | ||
| AI | 1604 | Uc THD | % | Read | ||
| AI | 1400 | Ia THD | % | Read | ||
| AI | 1402 | Ib THD | % | Read | ||
| AI | 1404 | Ic THD | % | Read | ||
| AI | 1318 | Ia K Factor | Read | |||
| AI | 1320 | Ib K Factor | Read | |||
| AI | 1322 | Ic K Factor | Read | |||
| AI | 1300 | Ia TDD | % | Read | ||
| AI | 1302 | Ib TDD | % | Read | ||
| AI | 1304 | Ic TDD | % | Read | ||
| AI | 1324 | Ia Crest Factor | Read | |||
| AI | 1326 | Ib Crest Factor | Read | |||
| AI | 1328 | Ic Crest Factor | Read | |||
| AI | 1330 | U Unbalance | % | Read | ||
| AI | 1332 | I Unbalance | % | Read | ||
| AI | 74 | dPFa | Read | |||
| AI | 76 | dPFb | Read | |||
| AI | 78 | dPFc | Read | |||
| AI | 58 | Ua Angle | ° | Read | ||
| AI | 60 | Ub Angle | ° | Read | ||
| AI | 62 | Uc Angle | ° | Read | ||
| AI | 64 | Ia Angle | ° | Read | ||
| AI | 66 | Ib Angle | ° | Read | ||
| AI | 68 | Ic Angle | ° | Read | ||
| AI | 104 | Run Hours | h | Read | ||
| AI | 526 | Interval kWh Import | kWh | Read | ||
| AI | 528 | Interval kWh Export | kWh | Read | ||
| AI | 530 | Interval kvarh Import | kvarh | Read | ||
| AI | 532 | Interval kvarh Export | kvarh | Read | ||
| AI | 534 | Interval kVAh | kVAh | Read | ||
| AI | 1200 | DI #1 Counter | Read | |||
| AI | 1202 | DI #2 Counter | Read | |||
| AI | 1204 | DI #3 Counter | Read | |||
| AI | 1206 | DI #4 Counter | Read | |||
| AV | 6000 | PT Primary High # | Range 0 to 1000 kV, default 0* | kV | Write | |
| AV | 6001 | PT Primary Low # | Range 0 to 999 V, default 100* | V | Write | |
| AV | 6002 | PT Secondary# | Range 1 to 690 V, default 100* | V | Write | |
| AV | 6004 | CT Primary | Range 1 to 30000 A, default 5* | A | Write | |
| AV | 6006 | CT Secondary | Range 1 to 5/100 A, default 5* | A | Write | |
| AV | 6012 | I4 Primary | Range 1 to 30000 A, default 5* | A | Write | |
| AV | 6014 | I4 Secondary | Range 1 to 5 A, default 5* | A | Write | |
| AV | 6020 | Wiring Mode | Setting, default 3P4W* | Write | 0=DEMO, 1=1P2W L-N, 2=1P2W L-L, 3=1P3W L-L-N, 4=3P3W, 5=3P4W, 6=3x1P | |
| AV | 6021 | PF Convention | Setting, default 0* | Write | 0=IEC, 1=IEEE, 2=-IEEE | |
| AV | 6022 | kVA Calculation | Setting, default 0* | Write | 0=Vector, 1=Scalar | |
| AV | 6028 | THD Calculation | Setting, default 0* | Write | 0=THDf, 1=THDr | |
| AV | 6029 | Demand Period | Range 1~60 mins, default 15* | min | Write | |
| AV | 6030 | Number of Sliding Windows | Range 1 to 15, default 1* | Write | ||
| AV | 6047 | Interval Energy Period | Range 5~60, default 60* | Write | ||
| AV | 9603 | Clear Present Peak Demand | Setting | Write | 65280 (Default=0) | |
| AV | 9601 | Clear Energy | Setting | Write | 65280 (Default = 0) | |
| AV | 9610 | Clear DI #1 Counter | Setting | Write | 65280 (Default = 0) | |
| AV | 9611 | Clear DI #2 Counter | Write 65280 (0xFF00) to clear | Write | ||
| AV | 9612 | Clear DI #3 Counter | Write 65280 (0xFF00) to clear | Write | ||
| AV | 9613 | Clear DI #4 Counter | Write 65280 (0xFF00) to clear | Write | ||
| BI | 0 | DI 1 | Digital input status | Read | 0=Inactive, 1=Active | |
| BI | 1 | DI 2 | Digital input status | Read | 0=Inactive, 1=Active | |
| BI | 2 | DI 3 | Digital input status | Read | 0=Inactive, 1=Active | |
| BI | 3 | DI 4 | Digital input status | Read | 0=Inactive, 1=Active | |
| BO | 0 | DO 1 | Digital output | Write | 0=Inactive, 1=Active | |
| BO | 1 | DO 2 | Digital output | Write | 0=Inactive, 1=Active |
No points match these filters.
Object ID lookup: CET Electric PMC-53A-E multifunction panel meter, BACnet MS/TP point IDs by name
AI0UaAI2UbAI4UcAI6ULN AverageAI8UabAI10UbcAI12UcaAI14ULL AverageAI16IaAI18IbAI20IcAI22I AverageAI24PaAI26PbAI28PcAI30P TotalAI32QaAI34QbAI36QcAI38Q TotalAI40SaAI42SbAI44ScAI46S TotalAI48PFaAI50PFbAI52PFcAI54PF TotalAI56Freq.AI70In (Calculated)AI72I4 (Optional Measurement)AI82AI (Optional Measurement)AI84Ir (Optional Measurement)AI86RTD1 (Optional Measurement)AI88RTD2 (Optional Measurement)AI90RTD3 (Optional Measurement)AI92AO1 (Optional Measurement)AI94AO2 (Optional Measurement)AI500kWh ImportAI502kWh ExportAI504kWh NetAI506kWh TotalAI508kvarh ImportAI510kvarh ExportAI512kvarh NetAI514kvarh TotalAI516kVAhAI3006P DemandAI3008Q DemandAI3010S DemandAI3000Ia DemandAI3002Ib DemandAI3004Ic DemandAI3418P Max. DemandAI3424Q Max. DemandAI3430S Max. DemandAI3400Ia Max. DemandAI3406Ib Max. DemandAI3412Ic Max. DemandAI1600Ua THDAI1602UbTHDAI1604Uc THDAI1400Ia THDAI1402Ib THDAI1404Ic THDAI1318Ia K FactorAI1320Ib K FactorAI1322Ic K FactorAI1300Ia TDDAI1302Ib TDDAI1304Ic TDDAI1324Ia Crest FactorAI1326Ib Crest FactorAI1328Ic Crest FactorAI1330U UnbalanceAI1332I UnbalanceAI74dPFaAI76dPFbAI78dPFcAI58Ua AngleAI60Ub AngleAI62Uc AngleAI64Ia AngleAI66Ib AngleAI68Ic AngleAI104Run HoursAI526Interval kWh ImportAI528Interval kWh ExportAI530Interval kvarh ImportAI532Interval kvarh ExportAI534Interval kVAhAI1200DI #1 CounterAI1202DI #2 CounterAI1204DI #3 CounterAI1206DI #4 CounterAV6000PT Primary High #AV6001PT Primary Low #AV6002PT Secondary#AV6004CT PrimaryAV6006CT SecondaryAV6012I4 PrimaryAV6014I4 SecondaryAV6020Wiring ModeAV6021PF ConventionAV6022kVA CalculationAV6028THD CalculationAV6029Demand PeriodAV6030Number of Sliding WindowsAV6047Interval Energy PeriodAV9603Clear Present Peak DemandAV9601Clear EnergyAV9610Clear DI #1 CounterAV9611Clear DI #2 CounterAV9612Clear DI #3 CounterAV9613Clear DI #4 CounterBI0DI 1BI1DI 2BI2DI 3BI3DI 4BO0DO 1BO1DO 2
Integration notes
- Object instances equal the meter's Modbus register numbers, so they are not consecutive.
- Units are taken from the table where printed; rows that share a merged units cell were filled from the measurement type. BACnet has no kvarh/kVAh units, so those registers report in kWh units per the manual.
- The Clear AVs take 65280 (0xFF00) to run the action.
- Optional measurement objects (I4, AI, Ir, RTD1-3, AO1-2) only report when the matching option is fitted.
- The printed table gives AI 40 (Sa) the unit kvar; it is listed as kVA here like Sb and Sc.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PMC-53A-E multifunction panel meter, BACnet MS/TP and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the CET Electric PMC-53A-E multifunction panel meter, BACnet MS/TP
How many BACnet points does the CET Electric PMC-53A-E multifunction panel meter, BACnet MS/TP have?
This list has 121 BACnet objects: 95 analog inputs, 20 analog values, 4 binary inputs, 2 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which CET Electric PMC-53A-E multifunction panel meter, BACnet MS/TP BACnet points are writable?
22 of the 121 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official CET Electric PMC-53A-E multifunction panel meter, BACnet MS/TP BACnet documentation?
The source is PMC-53A-E User Manual, Appendix C BACnet MS/TP Implementation (V2.2), revision 2026-04-01, published free by CET Electric at https://www.cet-global.com/uploadfiles/2026/04/PMC-53A-E%20User%20Manual%20V2.2%20(20260401).pdf.
What are the minimum BACnet points to integrate the CET Electric PMC-53A-E multifunction panel meter, BACnet MS/TP?
Start with AI 30 P Total (Total active power, kW); AI 500 kWh Import (Energy imported, kWh); AI 502 kWh Export (Energy exported, kWh); AI 14 ULL Average (Average line-line voltage, V); AI 22 I Average (Average current, A); AI 54 PF Total (Total power factor); AI 56 Freq. (Frequency, Hz).
How do I check these points on the real PMC-53A-E multifunction panel meter, BACnet MS/TP?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More CET Electric BACnet points lists
- Energy meter (power quality monitor)
CET Electric iMeter 6 advanced power quality monitor, BACnet IP
CET Electric Technology iMeter 6 advanced power quality monitors with BACnet IP (firmware V3.01.01, application V3.50.00).
Also known as: iMeter 6, iMeter6, CET iMeter 6, iMeter 6 BACnet/IP - Energy meter (multifunction panel meter)
CET Electric PMC-53A multifunction panel meter, BACnet MS/TP
CET Electric Technology PMC-53A multifunction panel meters (serial model) with BACnet MS/TP from firmware V1.00.03.
Also known as: PMC-53A, PMC53A, CET PMC-53A
Source: PMC-53A-E User Manual, Appendix C BACnet MS/TP Implementation · V2.2 · rev. 2026-04-01. Object names, instances and units are reproduced as published; descriptions are our own.