Energy meter (multifunction panel meter) · BACnet points list
CET Electric PMC-53A multifunction panel meter, BACnet MS/TP BACnet points list
Updated 12 November 2026
The PMC-53A is the serial-port multifunction panel meter in CET's PMC-53A family, with BACnet MS/TP from firmware V1.00.03. It uses the same register-number instance scheme as the PMC-53A-E but prints different object names (Uan, Ubn, Ucn ...) and adds DI5-DI6, DO3-DO4 and their counters.
This page lists 128 BACnet objects for the CET Electric PMC-53A multifunction panel meter, BACnet MS/TP — 26 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CET Electric’s own free documentation, linked below.
- Manufacturer
- CET Electric
- Model
- PMC-53A multifunction panel meter, BACnet MS/TP
- Equipment
- Energy meter (multifunction panel meter)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 128 (26 writable)
- Transport
- BACnet MS/TP
- Firmware
- V1.00.03 or later
- Default device instance
- 26001
- Also known as
- PMC-53A, PMC53A, CET PMC-53A
Reference only, provided as-is: verify against CET Electric’s current documentation and the live device before use. Not official CET Electric information. Terms of use.
BMS integration notes: CET Electric PMC-53A multifunction panel meter, BACnet MS/TP
Set the PMC-53A protocol to BACnet MS/TP with a MAC address and baud rate, then read power, energy, voltages and currents. Set PT/CT ratios and wiring mode first if the BMS manages setup.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 30 | P Total | Total active power, kW | Read |
| AI 500 | kWh Import | Energy imported, kWh | Read |
| AI 502 | kWh Export | Energy exported, kWh | Read |
| AI 14 | ULL average | Average line-line voltage, V | Read |
| AI 22 | I average | Average current, A | Read |
| AI 54 | PF Total | Total power factor | Read |
| AI 56 | Frequency | Frequency, Hz | Read |
Network setup
- BACnet MS/TP master at 9600, 19200 or 38400 baud; device instance defaults to 26001.
- Analog Values 6000-6047 hold PT/CT ratios, wiring mode and demand settings.
Watch out for
- Writing 65280 to AV 9601 clears all energy registers.
CET Electric PMC-53A multifunction panel meter, BACnet MS/TP BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 0 | Uan | V | Read | ||
| AI | 2 | Ubn | V | Read | ||
| AI | 4 | Ucn | V | Read | ||
| AI | 6 | ULN average | V | Read | ||
| AI | 8 | Uab | V | Read | ||
| AI | 10 | Ubc | V | Read | ||
| AI | 12 | Uca | V | Read | ||
| AImin | 14 | ULL average | V | Read | ||
| AI | 16 | Ia | A | Read | ||
| AI | 18 | Ib | A | Read | ||
| AI | 20 | Ic | A | Read | ||
| AImin | 22 | I average | A | Read | ||
| AI | 24 | Pa | kW | Read | ||
| AI | 26 | Pb | kW | Read | ||
| AI | 28 | Pc | kW | Read | ||
| AImin | 30 | P Total | kW | Read | ||
| AI | 32 | Qa | kvar | Read | ||
| AI | 34 | Qb | kvar | Read | ||
| AI | 36 | Qc | kvar | Read | ||
| AI | 38 | Q Total | kvar | Read | ||
| AI | 40 | Sa | kVA | Read | ||
| AI | 42 | Sb | kVA | Read | ||
| AI | 44 | Sc | kVA | Read | ||
| AI | 46 | S Total | kVA | Read | ||
| AI | 48 | PFa | Read | |||
| AI | 50 | PFb | Read | |||
| AI | 52 | PFc | Read | |||
| AImin | 54 | PF Total | Read | |||
| AImin | 56 | Frequency | Hz | Read | ||
| AI | 70 | In | A | Read | ||
| AI | 72 | I4 (Optional Measurement) | (optional measurement) | A | Read | |
| AI | 82 | AI | Read | |||
| AI | 86 | RTD1 | °C | Read | ||
| AI | 88 | RTD2 | °C | Read | ||
| AI | 90 | AO1 | Read | |||
| AI | 92 | AO2 | Read | |||
| AI | 174 | Ir | A | Read | ||
| AImin | 500 | kWh Import | kWh | Read | ||
| AImin | 502 | kWh Export | kWh | Read | ||
| AI | 504 | kWh Net | kWh | Read | ||
| AI | 506 | kWh Total | kWh | Read | ||
| AI | 508 | kvarh Import | kvarh | Read | ||
| AI | 510 | kvarh Export | kvarh | Read | ||
| AI | 512 | kvarh Net | kvarh | Read | ||
| AI | 514 | kvarh Total | kvarh | Read | ||
| AI | 516 | kVAh | kVAh | Read | ||
| AI | 3006 | P Total Demand | kW | Read | ||
| AI | 3008 | Q Total Demand | kvar | Read | ||
| AI | 3010 | S Total Demand | kVA | Read | ||
| AI | 3000 | Ia Demand | A | Read | ||
| AI | 3002 | Ib Demand | A | Read | ||
| AI | 3004 | Ic Demand | A | Read | ||
| AI | 3418 | P Total Max. Demand | kW | Read | ||
| AI | 3424 | Q Total Max. Demand | kvar | Read | ||
| AI | 3430 | S Total Max. Demand | kVA | Read | ||
| AI | 3400 | Ia Max. Demand | A | Read | ||
| AI | 3406 | Ib Max. Demand | A | Read | ||
| AI | 3412 | Ic Max. Demand | A | Read | ||
| AI | 1600 | Uan THD | % | Read | ||
| AI | 1602 | Ubn THD | % | Read | ||
| AI | 1604 | Ucn THD | % | Read | ||
| AI | 1400 | Ia THD | % | Read | ||
| AI | 1402 | Ib THD | % | Read | ||
| AI | 1404 | Ic THD | % | Read | ||
| AI | 1318 | Ia K-Factor | Read | |||
| AI | 1320 | Ib K-Factor | Read | |||
| AI | 1322 | Ic K-Factor | Read | |||
| AI | 1300 | Ia TDD | % | Read | ||
| AI | 1302 | Ib TDD | % | Read | ||
| AI | 1304 | Ic TDD | % | Read | ||
| AI | 1324 | Ia Crest Factor | Read | |||
| AI | 1326 | Ib Crest Factor | Read | |||
| AI | 1328 | Ic Crest Factor | Read | |||
| AI | 1330 | U Unbalance | % | Read | ||
| AI | 1332 | I Unbalance | % | Read | ||
| AI | 74 | dPFa | Read | |||
| AI | 76 | dPFb | Read | |||
| AI | 78 | dPFc | Read | |||
| AI | 58 | Uan Angle | ° | Read | ||
| AI | 60 | Ubn Angle | ° | Read | ||
| AI | 62 | Ucn Angle | ° | Read | ||
| AI | 64 | Ia Angle | ° | Read | ||
| AI | 66 | Ib Angle | ° | Read | ||
| AI | 68 | Ic Angle | ° | Read | ||
| AI | 104 | Operating Time | h | Read | ||
| AI | 526 | Interval kWh Import | kWh | Read | ||
| AI | 528 | Interval kWh Export | kWh | Read | ||
| AI | 530 | Interval kvarh Import | kvarh | Read | ||
| AI | 532 | Interval kvarh Export | kvarh | Read | ||
| AI | 534 | Interval kVAh | kVAh | Read | ||
| AI | 1200 | DI1 Counter | Read | |||
| AI | 1202 | DI2 Counter | Read | |||
| AI | 1204 | DI3 Counter | Read | |||
| AI | 1206 | DI4 Counter | Read | |||
| AI | 1208 | DI5 Counter | Read | |||
| AI | 1210 | DI6 Counter | Read | |||
| AV | 6000 | PT Primary High# | Range 0 to 1000 kV, default 0 | kV | Write | |
| AV | 6001 | PT Primary Low# | Range 1 to 999 V, default 100 | V | Write | |
| AV | 6002 | PT Secondary# | Range 1 to 690, default 100 | Write | ||
| AV | 6004 | CT Primary | Range 1 to 30000, default 5 | Write | ||
| AV | 6006 | CT Secondary | Range 1 to 5, default 5 | Write | ||
| AV | 6012 | I4 Primary | Range 1 to 30000, default 5 | Write | ||
| AV | 6014 | I4 Secondary | Range 1 to 5, default 5 | Write | ||
| AV | 6020 | Wiring Mode | Setting, default 5 | Write | 0=DEMO, 1=1P2W L-N, 2=1P2W L-L, 3=1P3W L-L-N, 4=3P3W, 5=3P4W | |
| AV | 6021 | PF Convention | Setting, default 0 | Write | 0=IEC, 1=IEEE, 2=-IEEE | |
| AV | 6022 | kVA Calculation | Setting, default 0 | Write | 0=Vector, 1=Scalar | |
| AV | 6028 | THD Calculation | Setting, default 0 | Write | 0=THDf, 1=THDr | |
| AV | 6029 | Demand Period | Range 1 to 60 min, default 15 | min | Write | |
| AV | 6030 | Number of Sliding Windows | Range 1 to 15, default 1 | Write | ||
| AV | 6047 | Interval Energy Period | Range 5 to 60 min, default 60 | min | Write | |
| AV | 9603 | Clear Present Max. Demand | Write 65280 (0xFF00) to clear | Write | ||
| AV | 9601 | Clear Energy | Write 65280 (0xFF00) to clear | Write | ||
| AV | 9610 | Clear DI1 Counter | Write 65280 (0xFF00) to clear | Write | ||
| AV | 9611 | Clear DI2 Counter | Write 65280 (0xFF00) to clear | Write | ||
| AV | 9612 | Clear DI3 Counter | Write 65280 (0xFF00) to clear | Write | ||
| AV | 9613 | Clear DI4 Counter | Write 65280 (0xFF00) to clear | Write | ||
| AV | 9614 | Clear DI5 Counter | Write 65280 (0xFF00) to clear | Write | ||
| AV | 9615 | Clear DI6 Counter | Write 65280 (0xFF00) to clear | Write | ||
| BI | 0 | DI1 | Digital input status | Read | 0=Inactive, 1=Active | |
| BI | 1 | DI2 | Digital input status | Read | 0=Inactive, 1=Active | |
| BI | 2 | DI3 | Digital input status | Read | 0=Inactive, 1=Active | |
| BI | 3 | DI4 | Digital input status | Read | 0=Inactive, 1=Active | |
| BI | 4 | DI5 | Digital input status | Read | 0=Inactive, 1=Active | |
| BI | 5 | DI6 | Digital input status | Read | 0=Inactive, 1=Active | |
| BO | 0 | DO1 | Digital output | Write | 0=Inactive, 1=Active | |
| BO | 1 | DO2 | Digital output | Write | 0=Inactive, 1=Active | |
| BO | 2 | DO3 | Digital output | Write | 0=Inactive, 1=Active | |
| BO | 3 | DO4 | Digital output | Write | 0=Inactive, 1=Active |
No points match these filters.
Object ID lookup: CET Electric PMC-53A multifunction panel meter, BACnet MS/TP point IDs by name
AI0UanAI2UbnAI4UcnAI6ULN averageAI8UabAI10UbcAI12UcaAI14ULL averageAI16IaAI18IbAI20IcAI22I averageAI24PaAI26PbAI28PcAI30P TotalAI32QaAI34QbAI36QcAI38Q TotalAI40SaAI42SbAI44ScAI46S TotalAI48PFaAI50PFbAI52PFcAI54PF TotalAI56FrequencyAI70InAI72I4 (Optional Measurement)AI82AIAI86RTD1AI88RTD2AI90AO1AI92AO2AI174IrAI500kWh ImportAI502kWh ExportAI504kWh NetAI506kWh TotalAI508kvarh ImportAI510kvarh ExportAI512kvarh NetAI514kvarh TotalAI516kVAhAI3006P Total DemandAI3008Q Total DemandAI3010S Total DemandAI3000Ia DemandAI3002Ib DemandAI3004Ic DemandAI3418P Total Max. DemandAI3424Q Total Max. DemandAI3430S Total Max. DemandAI3400Ia Max. DemandAI3406Ib Max. DemandAI3412Ic Max. DemandAI1600Uan THDAI1602Ubn THDAI1604Ucn THDAI1400Ia THDAI1402Ib THDAI1404Ic THDAI1318Ia K-FactorAI1320Ib K-FactorAI1322Ic K-FactorAI1300Ia TDDAI1302Ib TDDAI1304Ic TDDAI1324Ia Crest FactorAI1326Ib Crest FactorAI1328Ic Crest FactorAI1330U UnbalanceAI1332I UnbalanceAI74dPFaAI76dPFbAI78dPFcAI58Uan AngleAI60Ubn AngleAI62Ucn AngleAI64Ia AngleAI66Ib AngleAI68Ic AngleAI104Operating TimeAI526Interval kWh ImportAI528Interval kWh ExportAI530Interval kvarh ImportAI532Interval kvarh ExportAI534Interval kVAhAI1200DI1 CounterAI1202DI2 CounterAI1204DI3 CounterAI1206DI4 CounterAI1208DI5 CounterAI1210DI6 CounterAV6000PT Primary High#AV6001PT Primary Low#AV6002PT Secondary#AV6004CT PrimaryAV6006CT SecondaryAV6012I4 PrimaryAV6014I4 SecondaryAV6020Wiring ModeAV6021PF ConventionAV6022kVA CalculationAV6028THD CalculationAV6029Demand PeriodAV6030Number of Sliding WindowsAV6047Interval Energy PeriodAV9603Clear Present Max. DemandAV9601Clear EnergyAV9610Clear DI1 CounterAV9611Clear DI2 CounterAV9612Clear DI3 CounterAV9613Clear DI4 CounterAV9614Clear DI5 CounterAV9615Clear DI6 CounterBI0DI1BI1DI2BI2DI3BI3DI4BI4DI5BI5DI6BO0DO1BO1DO2BO2DO3BO3DO4
Integration notes
- Object instances equal the meter's Modbus register numbers, so they are not consecutive.
- Units are taken from the table where printed; rows that share a merged units cell were filled from the measurement type. BACnet has no kvarh/kVAh units, so those registers report in kWh units per the manual.
- The Clear AVs take 65280 (0xFF00) to run the action.
- Superscript note markers printed after some names (1, 2, 3 for 3P3W behaviour, * for kvarh/kVAh units) are dropped from the names.
- In 3P3W wiring the per-phase line-to-neutral values have no meaning, and Uan/Ubn/Ucn THD and angle report the line-to-line values.
- The table lists AO1 and AO2 at AI 90 and AI 92; RTD3 is not printed.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PMC-53A multifunction panel meter, BACnet MS/TP and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the CET Electric PMC-53A multifunction panel meter, BACnet MS/TP
How many BACnet points does the CET Electric PMC-53A multifunction panel meter, BACnet MS/TP have?
This list has 128 BACnet objects: 96 analog inputs, 22 analog values, 6 binary inputs, 4 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which CET Electric PMC-53A multifunction panel meter, BACnet MS/TP BACnet points are writable?
26 of the 128 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official CET Electric PMC-53A multifunction panel meter, BACnet MS/TP BACnet documentation?
The source is PMC-53A User Manual, Appendix C BACnet MS/TP Implementation (V2.2), revision 2026-02-04, published free by CET Electric at https://www.cet-global.com/uploadfiles/2026/02/PMC-53A%20User%20Manual%20V2.2%20(20260204).pdf.
What are the minimum BACnet points to integrate the CET Electric PMC-53A multifunction panel meter, BACnet MS/TP?
Start with AI 30 P Total (Total active power, kW); AI 500 kWh Import (Energy imported, kWh); AI 502 kWh Export (Energy exported, kWh); AI 14 ULL average (Average line-line voltage, V); AI 22 I average (Average current, A); AI 54 PF Total (Total power factor); AI 56 Frequency (Frequency, Hz).
How do I check these points on the real PMC-53A multifunction panel meter, BACnet MS/TP?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More CET Electric BACnet points lists
- Energy meter (power quality monitor)
CET Electric iMeter 6 advanced power quality monitor, BACnet IP
CET Electric Technology iMeter 6 advanced power quality monitors with BACnet IP (firmware V3.01.01, application V3.50.00).
Also known as: iMeter 6, iMeter6, CET iMeter 6, iMeter 6 BACnet/IP - Energy meter (multifunction panel meter)
CET Electric PMC-53A-E multifunction panel meter, BACnet MS/TP
CET Electric Technology PMC-53A-E multifunction panel meters (application V2.00.00, firmware V1.00.00) on BACnet MS/TP.
Also known as: PMC-53A-E, PMC53A-E, CET PMC-53A-E
Source: PMC-53A User Manual, Appendix C BACnet MS/TP Implementation · V2.2 · rev. 2026-02-04. Object names, instances and units are reproduced as published; descriptions are our own.