Medical gas source plant controller (monitoring only) · BACnet points list

BeaconMedaes TotalAlert 360 (TA360-S) controller - scroll medical air systems BACnet points list

Updated 12 November 2026Unofficial source

Short answer

The TA360 source controller runs BeaconMedaes medical air and vacuum source plants and serves BACnet IP as a BACnet Smart Sensor. For scroll air systems the map has 103 read-only objects: system pressure, ambient temperature, dew point and CO, running hours per unit (up to 6) and per dryer, dryer cycles, system and per-unit alarm/service/shutdown flags, individual alarms, and running, sequence and operation modes for units and dryers.

This page lists 103 BACnet objects for the BeaconMedaes TotalAlert 360 (TA360-S) controller - scroll medical air systems — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of BeaconMedaes’s documentation hosted by BACnet International, not by BeaconMedaes itself, so treat it as unofficial.

Manufacturer
BeaconMedaes
Model
TotalAlert 360 (TA360-S) controller - scroll medical air systems
Equipment
Medical gas source plant controller (monitoring only)
Equipment type
Other equipment
BACnet objects
103 (0 writable)
Transport
BACnet IP
Firmware
4107600055 Rev07 and above
Also known as
TA360, TotalAlert 360, TA360-S, TA360 Source Controller, BeaconMedaes TA360, Beacon Medaes
Source document
BACnet Protocol Implementation Conformance Statement - TA360 Systems (Object Mapping for TA360 Systems) · 4107 9010 48 Rev02 · rev. 2025-07-16 (unofficial copy, hosted by BACnet International)
Download CSV 103 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against BeaconMedaes’s current documentation and the live device before use. Not official BeaconMedaes information. Terms of use.

BMS integration notes: BeaconMedaes TotalAlert 360 (TA360-S) controller - scroll medical air systems

Integration in brief

Discover the TA360 controller over BACnet IP and read its Object_List to see which objects apply to the installed plant. Map the system alarm, shutdown and service flags and the main pressure or vacuum value first; the BMS cannot command the plant.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 0Any System AlarmsAny system alarmRead
BV 2Any System ShutdownsAny shutdown activeRead
BV 1Any System ServiceService dueRead
AV 0System PressurePlant outlet pressureRead
AV 4Dew PointMedical air dew pointRead
AV 6CO LevelCO level, ppmRead
MV 0Unit 1 Running ModeUnit 1 running stateRead
BV 200Unit 1 AlarmsUnit 1 alarmRead

Enable & remote start

Monitoring only: the PICS lists no writable objects.

Network setup

Watch out for

BeaconMedaes TotalAlert 360 (TA360-S) controller - scroll medical air systems BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

103 of 103 shown
Type
AnalogBinaryMulti-stateOther
Show
BeaconMedaes TotalAlert 360 (TA360-S) controller - scroll medical air systems BACnet Points List
DescriptionStates
AVmin0System PressurePSI/kPa/bar/inHg/mmHgRead
AV3Ambient Temperature°FRead
AVmin4Dew Point°CRead
AVmin6CO LevelCO readingppmRead
AV100Unit 1 Running HourshRead
AV101Unit 2 Running HourshRead
AV102Unit 3 Running HourshRead
AV103Unit 4 Running HourshRead
AV104Unit 5 Running HourshRead
AV105Unit 6 Running HourshRead
AV200Dryer 1 HourshRead
AV201Dryer 2 HourshRead
IV1Dryer 1 CyclesDryer cycle countRead
IV2Dryer 2 CyclesDryer cycle countRead
BVmin0Any System AlarmsRead0=No Alarms, 1=Alarms
BVmin1Any System ServiceRead0=No Service Due, 1=Service Due
BVmin2Any System ShutdownsRead0=No Shutdowns, 1=Shutdowns
BV100High Dew Point AlarmRead0=Not In Alarm, 1=In Alarm
BV101High CO Level AlarmRead0=Not In Alarm, 1=In Alarm
BV102Lag AlarmRead0=Not In Alarm, 1=In Alarm
BV103High Ambient Temperature AlarmRead0=Not In Alarm, 1=In Alarm
BV105Control Circuit AlarmRead0=Not In Alarm, 1=In Alarm
BV107Dryer 1 Switch Failure AlarmRead0=Not In Alarm, 1=In Alarm
BV108Dryer 2 Switch Failure AlarmRead0=Not In Alarm, 1=In Alarm
BV109Low Outlet Pressure AlarmRead0=Not In Alarm, 1=In Alarm
BV110Tank Water Level AlarmRead0=Not In Alarm, 1=In Alarm
BV111Dryer 1 Outlet AlarmRead0=Not In Alarm, 1=In Alarm
BV112Dryer 2 Outlet AlarmRead0=Not In Alarm, 1=In Alarm
BV113Line Filter DeltaP Dryer 1 AlarmRead0=Not In Alarm, 1=In Alarm
BV114Line Filter DeltaP Dryer 2 AlarmRead0=Not In Alarm, 1=In Alarm
BV117High Outlet PressureRead0=Not In Alarm, 1=In Alarm
BVmin200Unit 1 AlarmsRead0=No Alarms, 1=Alarms
BV201Unit 2 AlarmsRead0=No Alarms, 1=Alarms
BV202Unit 3 AlarmsRead0=No Alarms, 1=Alarms
BV203Unit 4 AlarmsRead0=No Alarms, 1=Alarms
BV204Unit 5 AlarmsRead0=No Alarms, 1=Alarms
BV205Unit 6 AlarmsRead0=No Alarms, 1=Alarms
BV206Unit 1 ServiceRead0=No Service Due, 1=Service Due
BV207Unit 2 ServiceRead0=No Service Due, 1=Service Due
BV208Unit 3 ServiceRead0=No Service Due, 1=Service Due
BV209Unit 4 ServiceRead0=No Service Due, 1=Service Due
BV210Unit 5 ServiceRead0=No Service Due, 1=Service Due
BV211Unit 6 ServiceRead0=No Service Due, 1=Service Due
BV212Unit 1 ShutdownsRead0=No Shutdowns, 1=Shutdowns
BV213Unit 2 ShutdownsRead0=No Shutdowns, 1=Shutdowns
BV214Unit 3 ShutdownsRead0=No Shutdowns, 1=Shutdowns
BV215Unit 4 ShutdownsRead0=No Shutdowns, 1=Shutdowns
BV216Unit 5 ShutdownsRead0=No Shutdowns, 1=Shutdowns
BV217Unit 6 ShutdownsRead0=No Shutdowns, 1=Shutdowns
BV218Unit 1 Motor Overload AlarmRead0=Not In Alarm, 1=In Alarm
BV219Unit 1 Discharge Temp AlarmRead0=Not In Alarm, 1=In Alarm
BV220Unit 1 Inlet Vacuum AlarmRead0=Not In Alarm, 1=In Alarm
BV221Unit 1 Aftercooler Temp AlarmRead0=Not In Alarm, 1=In Alarm
BV222Unit 1 Fail to Load AlarmRead0=Not In Alarm, 1=In Alarm
BV225Unit 2 Motor Overload AlarmRead0=Not In Alarm, 1=In Alarm
BV226Unit 2 Discharge Temp AlarmRead0=Not In Alarm, 1=In Alarm
BV227Unit 2 Inlet Vacuum AlarmRead0=Not In Alarm, 1=In Alarm
BV228Unit 2 Aftercooler Temp AlarmRead0=Not In Alarm, 1=In Alarm
BV229Unit 2 Fail to Load AlarmRead0=Not In Alarm, 1=In Alarm
BV232Unit 3 Motor Overload AlarmRead0=Not In Alarm, 1=In Alarm
BV233Unit 3 Discharge Temp AlarmRead0=Not In Alarm, 1=In Alarm
BV234Unit 3 Inlet Vacuum AlarmRead0=Not In Alarm, 1=In Alarm
BV235Unit 3 Aftercooler Temp AlarmRead0=Not In Alarm, 1=In Alarm
BV236Unit 3 Fail to Load AlarmRead0=Not In Alarm, 1=In Alarm
BV239Unit 4 Motor Overload AlarmRead0=Not In Alarm, 1=In Alarm
BV240Unit 4 Discharge Temp AlarmRead0=Not In Alarm, 1=In Alarm
BV241Unit 4 Inlet Vacuum AlarmRead0=Not In Alarm, 1=In Alarm
BV242Unit 4 Aftercooler Temp AlarmRead0=Not In Alarm, 1=In Alarm
BV243Unit 4 Fail to Load AlarmRead0=Not In Alarm, 1=In Alarm
BV246Unit 5 Motor Overload AlarmRead0=Not In Alarm, 1=In Alarm
BV247Unit 5 Discharge Temp AlarmRead0=Not In Alarm, 1=In Alarm
BV248Unit 5 Inlet Vacuum AlarmRead0=Not In Alarm, 1=In Alarm
BV249Unit 5 Aftercooler Temp AlarmRead0=Not In Alarm, 1=In Alarm
BV250Unit 5 Fail to Load AlarmRead0=Not In Alarm, 1=In Alarm
BV253Unit 6 Motor Overload AlarmRead0=Not In Alarm, 1=In Alarm
BV254Unit 6 Discharge Temp AlarmRead0=Not In Alarm, 1=In Alarm
BV255Unit 6 Inlet Vacuum AlarmRead0=Not In Alarm, 1=In Alarm
BV256Unit 6 Aftercooler Temp AlarmRead0=Not In Alarm, 1=In Alarm
BV257Unit 6 Fail to Load AlarmRead0=Not In Alarm, 1=In Alarm
MVmin0Unit 1 Running ModeRead1=Unit Stopped, 2=Unit Running DOL, 3=Unit Running VSD, 4=Emergency Comms, 5=Emergency Transducer, 6=Purge DOL, 7=Purge VSD, 8=Bump DOL
MV1Unit 2 Running ModeRead1=Unit Stopped, 2=Unit Running DOL, 3=Unit Running VSD, 4=Emergency Comms, 5=Emergency Transducer, 6=Purge DOL, 7=Purge VSD, 8=Bump DOL
MV2Unit 3 Running ModeRead1=Unit Stopped, 2=Unit Running DOL, 3=Unit Running VSD, 4=Emergency Comms, 5=Emergency Transducer, 6=Purge DOL, 7=Purge VSD, 8=Bump DOL
MV3Unit 4 Running ModeRead1=Unit Stopped, 2=Unit Running DOL, 3=Unit Running VSD, 4=Emergency Comms, 5=Emergency Transducer, 6=Purge DOL, 7=Purge VSD, 8=Bump DOL
MV4Unit 5 Running ModeRead1=Unit Stopped, 2=Unit Running DOL, 3=Unit Running VSD, 4=Emergency Comms, 5=Emergency Transducer, 6=Purge DOL, 7=Purge VSD, 8=Bump DOL
MV5Unit 6 Running ModeRead1=Unit Stopped, 2=Unit Running DOL, 3=Unit Running VSD, 4=Emergency Comms, 5=Emergency Transducer, 6=Purge DOL, 7=Purge VSD, 8=Bump DOL
MV6Unit 1 SequenceSequence positionRead1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4, 6=Lag 5
MV7Unit 2 SequenceSequence positionRead1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4, 6=Lag 5
MV8Unit 3 SequenceSequence positionRead1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4, 6=Lag 5
MV9Unit 4 SequenceSequence positionRead1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4, 6=Lag 5
MV10Unit 5 SequenceSequence positionRead1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4, 6=Lag 5
MV11Unit 6 SequenceSequence positionRead1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4, 6=Lag 5
MV12Unit 1 Operation ModeRead1=Off, 2=Manual, 3=Automatic, 4=Override Off, 5=Override On, 6=Emergency Comms, 7=Emergency Transducer, 8=Purge Off
MV13Unit 2 Operation ModeRead1=Off, 2=Manual, 3=Automatic, 4=Override Off, 5=Override On, 6=Emergency Comms, 7=Emergency Transducer, 8=Purge Off
MV14Unit 3 Operation ModeRead1=Off, 2=Manual, 3=Automatic, 4=Override Off, 5=Override On, 6=Emergency Comms, 7=Emergency Transducer, 8=Purge Off
MV15Unit 4 Operation ModeRead1=Off, 2=Manual, 3=Automatic, 4=Override Off, 5=Override On, 6=Emergency Comms, 7=Emergency Transducer, 8=Purge Off
MV16Unit 5 Operation ModeRead1=Off, 2=Manual, 3=Automatic, 4=Override Off, 5=Override On, 6=Emergency Comms, 7=Emergency Transducer, 8=Purge Off
MV17Unit 6 Operation ModeRead1=Off, 2=Manual, 3=Automatic, 4=Override Off, 5=Override On, 6=Emergency Comms, 7=Emergency Transducer, 8=Purge Off
MV300Dryer 1 Operation ModeRead1=Off, 2=Manual, 3=Automatic, 4=Override Off, 5=Override On
MV301Dryer 2 Operation ModeRead1=Off, 2=Manual, 3=Automatic, 4=Override Off, 5=Override On
MV302Dryer 1 Tower A ModeRead1=None, 2=Drying, 3=Purging, 4=Ready
MV303Dryer 2 Tower A ModeRead1=None, 2=Drying, 3=Purging, 4=Ready
MV304Dryer 1 Tower B ModeRead1=None, 2=Drying, 3=Purging, 4=Ready
MV305Dryer 2 Tower B ModeRead1=None, 2=Drying, 3=Purging, 4=Ready
Object ID lookup: BeaconMedaes TotalAlert 360 (TA360-S) controller - scroll medical air systems point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TotalAlert 360 (TA360-S) controller - scroll medical air systems and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the BeaconMedaes TotalAlert 360 (TA360-S) controller - scroll medical air systems

How many BACnet points does the BeaconMedaes TotalAlert 360 (TA360-S) controller - scroll medical air systems have?

This list has 103 BACnet objects: 12 analog values, 65 binary values, 24 multi-state values, 2 integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which BeaconMedaes TotalAlert 360 (TA360-S) controller - scroll medical air systems BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official BeaconMedaes TotalAlert 360 (TA360-S) controller - scroll medical air systems BACnet documentation?

BeaconMedaes does not publish it on its own website. This list comes from BACnet Protocol Implementation Conformance Statement - TA360 Systems (Object Mapping for TA360 Systems) (4107 9010 48 Rev02), revision 2025-07-16, a copy hosted by BACnet International at https://www.bacnetinternational.net/catalog/manu/beaconmedaes/PICS%20TA360%20Systems.pdf. Ask BeaconMedaes or its representative for the current revision.

What are the minimum BACnet points to integrate the BeaconMedaes TotalAlert 360 (TA360-S) controller - scroll medical air systems?

Start with BV 0 Any System Alarms (Any system alarm); BV 2 Any System Shutdowns (Any shutdown active); BV 1 Any System Service (Service due); AV 0 System Pressure (Plant outlet pressure); AV 4 Dew Point (Medical air dew point); AV 6 CO Level (CO level, ppm); MV 0 Unit 1 Running Mode (Unit 1 running state); BV 200 Unit 1 Alarms (Unit 1 alarm).

How do I enable BMS control of the BeaconMedaes TotalAlert 360 (TA360-S) controller - scroll medical air systems?

Monitoring only: the PICS lists no writable objects.

How do I check these points on the real TotalAlert 360 (TA360-S) controller - scroll medical air systems?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More BeaconMedaes BACnet points lists

Source: BACnet Protocol Implementation Conformance Statement - TA360 Systems (Object Mapping for TA360 Systems) · 4107 9010 48 Rev02 · rev. 2025-07-16. Object names, instances and units are reproduced as published; descriptions are our own.