- TotalAlert 360 (TA360-S) controller - scroll medical air systems
Medical gas source plant controller (monitoring only) · BACnet points list
BeaconMedaes TotalAlert 360 (TA360-S) controller - scroll medical air systems BACnet points list
Updated 12 November 2026Unofficial source
The TA360 source controller runs BeaconMedaes medical air and vacuum source plants and serves BACnet IP as a BACnet Smart Sensor. For scroll air systems the map has 103 read-only objects: system pressure, ambient temperature, dew point and CO, running hours per unit (up to 6) and per dryer, dryer cycles, system and per-unit alarm/service/shutdown flags, individual alarms, and running, sequence and operation modes for units and dryers.
This page lists 103 BACnet objects for the BeaconMedaes TotalAlert 360 (TA360-S) controller - scroll medical air systems — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of BeaconMedaes’s documentation hosted by BACnet International, not by BeaconMedaes itself, so treat it as unofficial.
- Manufacturer
- BeaconMedaes
- Model
- TotalAlert 360 (TA360-S) controller - scroll medical air systems
- Equipment
- Medical gas source plant controller (monitoring only)
- Equipment type
- Other equipment
- BACnet objects
- 103 (0 writable)
- Transport
- BACnet IP
- Firmware
- 4107600055 Rev07 and above
- Also known as
- TA360, TotalAlert 360, TA360-S, TA360 Source Controller, BeaconMedaes TA360, Beacon Medaes
- Source document
- BACnet Protocol Implementation Conformance Statement - TA360 Systems (Object Mapping for TA360 Systems) · 4107 9010 48 Rev02 · rev. 2025-07-16 (unofficial copy, hosted by BACnet International)
Reference only, provided as-is: verify against BeaconMedaes’s current documentation and the live device before use. Not official BeaconMedaes information. Terms of use.
BMS integration notes: BeaconMedaes TotalAlert 360 (TA360-S) controller - scroll medical air systems
Discover the TA360 controller over BACnet IP and read its Object_List to see which objects apply to the installed plant. Map the system alarm, shutdown and service flags and the main pressure or vacuum value first; the BMS cannot command the plant.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 0 | Any System Alarms | Any system alarm | Read |
| BV 2 | Any System Shutdowns | Any shutdown active | Read |
| BV 1 | Any System Service | Service due | Read |
| AV 0 | System Pressure | Plant outlet pressure | Read |
| AV 4 | Dew Point | Medical air dew point | Read |
| AV 6 | CO Level | CO level, ppm | Read |
| MV 0 | Unit 1 Running Mode | Unit 1 running state | Read |
| BV 200 | Unit 1 Alarms | Unit 1 alarm | Read |
Enable & remote start
Monitoring only: the PICS lists no writable objects.
Network setup
- BACnet IP (ISO 8802-3 / Annex J); B-SS profile; max APDU 1456.
Watch out for
- Objects for units 1-6, dryers and optional sensors exist even when that equipment is not installed; ignore them.
- Multistate values start at 1.
BeaconMedaes TotalAlert 360 (TA360-S) controller - scroll medical air systems BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 0 | System Pressure | PSI/kPa/bar/inHg/mmHg | Read | ||
| AV | 3 | Ambient Temperature | °F | Read | ||
| AVmin | 4 | Dew Point | °C | Read | ||
| AVmin | 6 | CO Level | CO reading | ppm | Read | |
| AV | 100 | Unit 1 Running Hours | h | Read | ||
| AV | 101 | Unit 2 Running Hours | h | Read | ||
| AV | 102 | Unit 3 Running Hours | h | Read | ||
| AV | 103 | Unit 4 Running Hours | h | Read | ||
| AV | 104 | Unit 5 Running Hours | h | Read | ||
| AV | 105 | Unit 6 Running Hours | h | Read | ||
| AV | 200 | Dryer 1 Hours | h | Read | ||
| AV | 201 | Dryer 2 Hours | h | Read | ||
| IV | 1 | Dryer 1 Cycles | Dryer cycle count | Read | ||
| IV | 2 | Dryer 2 Cycles | Dryer cycle count | Read | ||
| BVmin | 0 | Any System Alarms | Read | 0=No Alarms, 1=Alarms | ||
| BVmin | 1 | Any System Service | Read | 0=No Service Due, 1=Service Due | ||
| BVmin | 2 | Any System Shutdowns | Read | 0=No Shutdowns, 1=Shutdowns | ||
| BV | 100 | High Dew Point Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 101 | High CO Level Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 102 | Lag Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 103 | High Ambient Temperature Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 105 | Control Circuit Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 107 | Dryer 1 Switch Failure Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 108 | Dryer 2 Switch Failure Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 109 | Low Outlet Pressure Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 110 | Tank Water Level Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 111 | Dryer 1 Outlet Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 112 | Dryer 2 Outlet Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 113 | Line Filter DeltaP Dryer 1 Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 114 | Line Filter DeltaP Dryer 2 Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 117 | High Outlet Pressure | Read | 0=Not In Alarm, 1=In Alarm | ||
| BVmin | 200 | Unit 1 Alarms | Read | 0=No Alarms, 1=Alarms | ||
| BV | 201 | Unit 2 Alarms | Read | 0=No Alarms, 1=Alarms | ||
| BV | 202 | Unit 3 Alarms | Read | 0=No Alarms, 1=Alarms | ||
| BV | 203 | Unit 4 Alarms | Read | 0=No Alarms, 1=Alarms | ||
| BV | 204 | Unit 5 Alarms | Read | 0=No Alarms, 1=Alarms | ||
| BV | 205 | Unit 6 Alarms | Read | 0=No Alarms, 1=Alarms | ||
| BV | 206 | Unit 1 Service | Read | 0=No Service Due, 1=Service Due | ||
| BV | 207 | Unit 2 Service | Read | 0=No Service Due, 1=Service Due | ||
| BV | 208 | Unit 3 Service | Read | 0=No Service Due, 1=Service Due | ||
| BV | 209 | Unit 4 Service | Read | 0=No Service Due, 1=Service Due | ||
| BV | 210 | Unit 5 Service | Read | 0=No Service Due, 1=Service Due | ||
| BV | 211 | Unit 6 Service | Read | 0=No Service Due, 1=Service Due | ||
| BV | 212 | Unit 1 Shutdowns | Read | 0=No Shutdowns, 1=Shutdowns | ||
| BV | 213 | Unit 2 Shutdowns | Read | 0=No Shutdowns, 1=Shutdowns | ||
| BV | 214 | Unit 3 Shutdowns | Read | 0=No Shutdowns, 1=Shutdowns | ||
| BV | 215 | Unit 4 Shutdowns | Read | 0=No Shutdowns, 1=Shutdowns | ||
| BV | 216 | Unit 5 Shutdowns | Read | 0=No Shutdowns, 1=Shutdowns | ||
| BV | 217 | Unit 6 Shutdowns | Read | 0=No Shutdowns, 1=Shutdowns | ||
| BV | 218 | Unit 1 Motor Overload Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 219 | Unit 1 Discharge Temp Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 220 | Unit 1 Inlet Vacuum Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 221 | Unit 1 Aftercooler Temp Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 222 | Unit 1 Fail to Load Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 225 | Unit 2 Motor Overload Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 226 | Unit 2 Discharge Temp Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 227 | Unit 2 Inlet Vacuum Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 228 | Unit 2 Aftercooler Temp Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 229 | Unit 2 Fail to Load Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 232 | Unit 3 Motor Overload Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 233 | Unit 3 Discharge Temp Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 234 | Unit 3 Inlet Vacuum Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 235 | Unit 3 Aftercooler Temp Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 236 | Unit 3 Fail to Load Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 239 | Unit 4 Motor Overload Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 240 | Unit 4 Discharge Temp Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 241 | Unit 4 Inlet Vacuum Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 242 | Unit 4 Aftercooler Temp Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 243 | Unit 4 Fail to Load Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 246 | Unit 5 Motor Overload Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 247 | Unit 5 Discharge Temp Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 248 | Unit 5 Inlet Vacuum Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 249 | Unit 5 Aftercooler Temp Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 250 | Unit 5 Fail to Load Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 253 | Unit 6 Motor Overload Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 254 | Unit 6 Discharge Temp Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 255 | Unit 6 Inlet Vacuum Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 256 | Unit 6 Aftercooler Temp Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 257 | Unit 6 Fail to Load Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| MVmin | 0 | Unit 1 Running Mode | Read | 1=Unit Stopped, 2=Unit Running DOL, 3=Unit Running VSD, 4=Emergency Comms, 5=Emergency Transducer, 6=Purge DOL, 7=Purge VSD, 8=Bump DOL | ||
| MV | 1 | Unit 2 Running Mode | Read | 1=Unit Stopped, 2=Unit Running DOL, 3=Unit Running VSD, 4=Emergency Comms, 5=Emergency Transducer, 6=Purge DOL, 7=Purge VSD, 8=Bump DOL | ||
| MV | 2 | Unit 3 Running Mode | Read | 1=Unit Stopped, 2=Unit Running DOL, 3=Unit Running VSD, 4=Emergency Comms, 5=Emergency Transducer, 6=Purge DOL, 7=Purge VSD, 8=Bump DOL | ||
| MV | 3 | Unit 4 Running Mode | Read | 1=Unit Stopped, 2=Unit Running DOL, 3=Unit Running VSD, 4=Emergency Comms, 5=Emergency Transducer, 6=Purge DOL, 7=Purge VSD, 8=Bump DOL | ||
| MV | 4 | Unit 5 Running Mode | Read | 1=Unit Stopped, 2=Unit Running DOL, 3=Unit Running VSD, 4=Emergency Comms, 5=Emergency Transducer, 6=Purge DOL, 7=Purge VSD, 8=Bump DOL | ||
| MV | 5 | Unit 6 Running Mode | Read | 1=Unit Stopped, 2=Unit Running DOL, 3=Unit Running VSD, 4=Emergency Comms, 5=Emergency Transducer, 6=Purge DOL, 7=Purge VSD, 8=Bump DOL | ||
| MV | 6 | Unit 1 Sequence | Sequence position | Read | 1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4, 6=Lag 5 | |
| MV | 7 | Unit 2 Sequence | Sequence position | Read | 1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4, 6=Lag 5 | |
| MV | 8 | Unit 3 Sequence | Sequence position | Read | 1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4, 6=Lag 5 | |
| MV | 9 | Unit 4 Sequence | Sequence position | Read | 1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4, 6=Lag 5 | |
| MV | 10 | Unit 5 Sequence | Sequence position | Read | 1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4, 6=Lag 5 | |
| MV | 11 | Unit 6 Sequence | Sequence position | Read | 1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4, 6=Lag 5 | |
| MV | 12 | Unit 1 Operation Mode | Read | 1=Off, 2=Manual, 3=Automatic, 4=Override Off, 5=Override On, 6=Emergency Comms, 7=Emergency Transducer, 8=Purge Off | ||
| MV | 13 | Unit 2 Operation Mode | Read | 1=Off, 2=Manual, 3=Automatic, 4=Override Off, 5=Override On, 6=Emergency Comms, 7=Emergency Transducer, 8=Purge Off | ||
| MV | 14 | Unit 3 Operation Mode | Read | 1=Off, 2=Manual, 3=Automatic, 4=Override Off, 5=Override On, 6=Emergency Comms, 7=Emergency Transducer, 8=Purge Off | ||
| MV | 15 | Unit 4 Operation Mode | Read | 1=Off, 2=Manual, 3=Automatic, 4=Override Off, 5=Override On, 6=Emergency Comms, 7=Emergency Transducer, 8=Purge Off | ||
| MV | 16 | Unit 5 Operation Mode | Read | 1=Off, 2=Manual, 3=Automatic, 4=Override Off, 5=Override On, 6=Emergency Comms, 7=Emergency Transducer, 8=Purge Off | ||
| MV | 17 | Unit 6 Operation Mode | Read | 1=Off, 2=Manual, 3=Automatic, 4=Override Off, 5=Override On, 6=Emergency Comms, 7=Emergency Transducer, 8=Purge Off | ||
| MV | 300 | Dryer 1 Operation Mode | Read | 1=Off, 2=Manual, 3=Automatic, 4=Override Off, 5=Override On | ||
| MV | 301 | Dryer 2 Operation Mode | Read | 1=Off, 2=Manual, 3=Automatic, 4=Override Off, 5=Override On | ||
| MV | 302 | Dryer 1 Tower A Mode | Read | 1=None, 2=Drying, 3=Purging, 4=Ready | ||
| MV | 303 | Dryer 2 Tower A Mode | Read | 1=None, 2=Drying, 3=Purging, 4=Ready | ||
| MV | 304 | Dryer 1 Tower B Mode | Read | 1=None, 2=Drying, 3=Purging, 4=Ready | ||
| MV | 305 | Dryer 2 Tower B Mode | Read | 1=None, 2=Drying, 3=Purging, 4=Ready |
No points match these filters.
Object ID lookup: BeaconMedaes TotalAlert 360 (TA360-S) controller - scroll medical air systems point IDs by name
AV0System PressureAV3Ambient TemperatureAV4Dew PointAV6CO LevelAV100Unit 1 Running HoursAV101Unit 2 Running HoursAV102Unit 3 Running HoursAV103Unit 4 Running HoursAV104Unit 5 Running HoursAV105Unit 6 Running HoursAV200Dryer 1 HoursAV201Dryer 2 HoursIV1Dryer 1 CyclesIV2Dryer 2 CyclesBV0Any System AlarmsBV1Any System ServiceBV2Any System ShutdownsBV100High Dew Point AlarmBV101High CO Level AlarmBV102Lag AlarmBV103High Ambient Temperature AlarmBV105Control Circuit AlarmBV107Dryer 1 Switch Failure AlarmBV108Dryer 2 Switch Failure AlarmBV109Low Outlet Pressure AlarmBV110Tank Water Level AlarmBV111Dryer 1 Outlet AlarmBV112Dryer 2 Outlet AlarmBV113Line Filter DeltaP Dryer 1 AlarmBV114Line Filter DeltaP Dryer 2 AlarmBV117High Outlet PressureBV200Unit 1 AlarmsBV201Unit 2 AlarmsBV202Unit 3 AlarmsBV203Unit 4 AlarmsBV204Unit 5 AlarmsBV205Unit 6 AlarmsBV206Unit 1 ServiceBV207Unit 2 ServiceBV208Unit 3 ServiceBV209Unit 4 ServiceBV210Unit 5 ServiceBV211Unit 6 ServiceBV212Unit 1 ShutdownsBV213Unit 2 ShutdownsBV214Unit 3 ShutdownsBV215Unit 4 ShutdownsBV216Unit 5 ShutdownsBV217Unit 6 ShutdownsBV218Unit 1 Motor Overload AlarmBV219Unit 1 Discharge Temp AlarmBV220Unit 1 Inlet Vacuum AlarmBV221Unit 1 Aftercooler Temp AlarmBV222Unit 1 Fail to Load AlarmBV225Unit 2 Motor Overload AlarmBV226Unit 2 Discharge Temp AlarmBV227Unit 2 Inlet Vacuum AlarmBV228Unit 2 Aftercooler Temp AlarmBV229Unit 2 Fail to Load AlarmBV232Unit 3 Motor Overload AlarmBV233Unit 3 Discharge Temp AlarmBV234Unit 3 Inlet Vacuum AlarmBV235Unit 3 Aftercooler Temp AlarmBV236Unit 3 Fail to Load AlarmBV239Unit 4 Motor Overload AlarmBV240Unit 4 Discharge Temp AlarmBV241Unit 4 Inlet Vacuum AlarmBV242Unit 4 Aftercooler Temp AlarmBV243Unit 4 Fail to Load AlarmBV246Unit 5 Motor Overload AlarmBV247Unit 5 Discharge Temp AlarmBV248Unit 5 Inlet Vacuum AlarmBV249Unit 5 Aftercooler Temp AlarmBV250Unit 5 Fail to Load AlarmBV253Unit 6 Motor Overload AlarmBV254Unit 6 Discharge Temp AlarmBV255Unit 6 Inlet Vacuum AlarmBV256Unit 6 Aftercooler Temp AlarmBV257Unit 6 Fail to Load AlarmMV0Unit 1 Running ModeMV1Unit 2 Running ModeMV2Unit 3 Running ModeMV3Unit 4 Running ModeMV4Unit 5 Running ModeMV5Unit 6 Running ModeMV6Unit 1 SequenceMV7Unit 2 SequenceMV8Unit 3 SequenceMV9Unit 4 SequenceMV10Unit 5 SequenceMV11Unit 6 SequenceMV12Unit 1 Operation ModeMV13Unit 2 Operation ModeMV14Unit 3 Operation ModeMV15Unit 4 Operation ModeMV16Unit 5 Operation ModeMV17Unit 6 Operation ModeMV300Dryer 1 Operation ModeMV301Dryer 2 Operation ModeMV302Dryer 1 Tower A ModeMV303Dryer 2 Tower A ModeMV304Dryer 1 Tower B ModeMV305Dryer 2 Tower B Mode
Integration notes
- From the PICS object mapping tables (object name, instance, present value, units / state description). All objects are read-only (B-SS profile); the PICS lists no write access.
- Every possible object is listed; objects for units, dryers or sensors that are not installed should be ignored. Reading the device Object_List shows only the objects relevant to the system.
- Multistate values start at 1 (as corrected in Rev 1 of the PICS).
- The same TA360-S controller covers scroll air and claw/lube vacuum plants; the two plant types have separate object maps.
- Dew point is printed in degC while the other temperatures are degF; system pressure units follow the controller setting (PSI, kPa, bar, inHg or mmHg).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TotalAlert 360 (TA360-S) controller - scroll medical air systems and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the BeaconMedaes TotalAlert 360 (TA360-S) controller - scroll medical air systems
How many BACnet points does the BeaconMedaes TotalAlert 360 (TA360-S) controller - scroll medical air systems have?
This list has 103 BACnet objects: 12 analog values, 65 binary values, 24 multi-state values, 2 integer values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which BeaconMedaes TotalAlert 360 (TA360-S) controller - scroll medical air systems BACnet points are writable?
None of the listed objects are marked writable in the source documentation.
Where is the official BeaconMedaes TotalAlert 360 (TA360-S) controller - scroll medical air systems BACnet documentation?
BeaconMedaes does not publish it on its own website. This list comes from BACnet Protocol Implementation Conformance Statement - TA360 Systems (Object Mapping for TA360 Systems) (4107 9010 48 Rev02), revision 2025-07-16, a copy hosted by BACnet International at https://www.bacnetinternational.net/catalog/manu/beaconmedaes/PICS%20TA360%20Systems.pdf. Ask BeaconMedaes or its representative for the current revision.
What are the minimum BACnet points to integrate the BeaconMedaes TotalAlert 360 (TA360-S) controller - scroll medical air systems?
Start with BV 0 Any System Alarms (Any system alarm); BV 2 Any System Shutdowns (Any shutdown active); BV 1 Any System Service (Service due); AV 0 System Pressure (Plant outlet pressure); AV 4 Dew Point (Medical air dew point); AV 6 CO Level (CO level, ppm); MV 0 Unit 1 Running Mode (Unit 1 running state); BV 200 Unit 1 Alarms (Unit 1 alarm).
How do I enable BMS control of the BeaconMedaes TotalAlert 360 (TA360-S) controller - scroll medical air systems?
Monitoring only: the PICS lists no writable objects.
How do I check these points on the real TotalAlert 360 (TA360-S) controller - scroll medical air systems?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More BeaconMedaes BACnet points lists
Source: BACnet Protocol Implementation Conformance Statement - TA360 Systems (Object Mapping for TA360 Systems) · 4107 9010 48 Rev02 · rev. 2025-07-16. Object names, instances and units are reproduced as published; descriptions are our own.