- TotalAlert 360 (TA360-S) controller - claw and lube medical vacuum systems
Medical gas source plant controller (monitoring only) · BACnet points list
BeaconMedaes TotalAlert 360 (TA360-S) controller - claw and lube medical vacuum systems BACnet points list
Updated 12 November 2026Unofficial source
The TA360 source controller runs BeaconMedaes medical air and vacuum source plants and serves BACnet IP as a BACnet Smart Sensor. For claw and lube vacuum systems the map has 82 read-only objects: system vacuum, ambient and cabinet temperature, running hours per unit (up to 6), VSD speed, system and per-unit alarm/service/shutdown flags, VSD and per-unit alarms, and running, sequence and operation modes per unit.
This page lists 82 BACnet objects for the BeaconMedaes TotalAlert 360 (TA360-S) controller - claw and lube medical vacuum systems — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of BeaconMedaes’s documentation hosted by BACnet International, not by BeaconMedaes itself, so treat it as unofficial.
- Manufacturer
- BeaconMedaes
- Model
- TotalAlert 360 (TA360-S) controller - claw and lube medical vacuum systems
- Equipment
- Medical gas source plant controller (monitoring only)
- Equipment type
- Other equipment
- BACnet objects
- 82 (0 writable)
- Transport
- BACnet IP
- Firmware
- 4107600055 Rev07 and above
- Also known as
- TA360, TotalAlert 360, TA360-S, TA360 Source Controller, BeaconMedaes TA360, Beacon Medaes
- Source document
- BACnet Protocol Implementation Conformance Statement - TA360 Systems (Object Mapping for TA360 Systems) · 4107 9010 48 Rev02 · rev. 2025-07-16 (unofficial copy, hosted by BACnet International)
Reference only, provided as-is: verify against BeaconMedaes’s current documentation and the live device before use. Not official BeaconMedaes information. Terms of use.
BMS integration notes: BeaconMedaes TotalAlert 360 (TA360-S) controller - claw and lube medical vacuum systems
Discover the TA360 controller over BACnet IP and read its Object_List to see which objects apply to the installed plant. Map the system alarm, shutdown and service flags and the main pressure or vacuum value first; the BMS cannot command the plant.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 0 | Any System Alarms | Any system alarm | Read |
| BV 2 | Any System Shutdowns | Any shutdown active | Read |
| BV 1 | Any System Service | Service due | Read |
| AV 2 | System Vacuum | Plant vacuum level | Read |
| IV 0 | VSD Speed | VSD speed, Hz | Read |
| MV 0 | Unit 1 Running Mode | Unit 1 running state | Read |
| BV 200 | Unit 1 Alarms | Unit 1 alarm | Read |
| BV 115 | VSD Fault Alarm | VSD fault | Read |
Enable & remote start
Monitoring only: the PICS lists no writable objects.
Network setup
- BACnet IP (ISO 8802-3 / Annex J); B-SS profile; max APDU 1456.
Watch out for
- Objects for units 1-6, dryers and optional sensors exist even when that equipment is not installed; ignore them.
- Multistate values start at 1.
BeaconMedaes TotalAlert 360 (TA360-S) controller - claw and lube medical vacuum systems BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 2 | System Vacuum | PSI/kPa/bar/inHg/mmHg | Read | ||
| AV | 3 | Ambient Temperature | °F | Read | ||
| AV | 5 | Cabinet Temperature | °F | Read | ||
| AV | 100 | Unit 1 Running Hours | h | Read | ||
| AV | 101 | Unit 2 Running Hours | h | Read | ||
| AV | 102 | Unit 3 Running Hours | h | Read | ||
| AV | 103 | Unit 4 Running Hours | h | Read | ||
| AV | 104 | Unit 5 Running Hours | h | Read | ||
| AV | 105 | Unit 6 Running Hours | h | Read | ||
| IVmin | 0 | VSD Speed | Hz | Read | ||
| BVmin | 0 | Any System Alarms | Read | 0=No Alarms, 1=Alarms | ||
| BVmin | 1 | Any System Service | Read | 0=No Service Due, 1=Service Due | ||
| BVmin | 2 | Any System Shutdowns | Read | 0=No Shutdowns, 1=Shutdowns | ||
| BV | 102 | Lag Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 103 | High Ambient Temperature Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 104 | High Cabinet Temperature Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 105 | Control Circuit Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 109 | Low Outlet Pressure Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 110 | Tank Water Level Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BVmin | 115 | VSD Fault Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 116 | VSD Off Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 117 | High Outlet Pressure | Read | 0=Not In Alarm, 1=In Alarm | ||
| BVmin | 200 | Unit 1 Alarms | Read | 0=No Alarms, 1=Alarms | ||
| BV | 201 | Unit 2 Alarms | Read | 0=No Alarms, 1=Alarms | ||
| BV | 202 | Unit 3 Alarms | Read | 0=No Alarms, 1=Alarms | ||
| BV | 203 | Unit 4 Alarms | Read | 0=No Alarms, 1=Alarms | ||
| BV | 204 | Unit 5 Alarms | Read | 0=No Alarms, 1=Alarms | ||
| BV | 205 | Unit 6 Alarms | Read | 0=No Alarms, 1=Alarms | ||
| BV | 206 | Unit 1 Service | Read | 0=No Service Due, 1=Service Due | ||
| BV | 207 | Unit 2 Service | Read | 0=No Service Due, 1=Service Due | ||
| BV | 208 | Unit 3 Service | Read | 0=No Service Due, 1=Service Due | ||
| BV | 209 | Unit 4 Service | Read | 0=No Service Due, 1=Service Due | ||
| BV | 210 | Unit 5 Service | Read | 0=No Service Due, 1=Service Due | ||
| BV | 211 | Unit 6 Service | Read | 0=No Service Due, 1=Service Due | ||
| BV | 212 | Unit 1 Shutdowns | Read | 0=No Shutdowns, 1=Shutdowns | ||
| BV | 213 | Unit 2 Shutdowns | Read | 0=No Shutdowns, 1=Shutdowns | ||
| BV | 214 | Unit 3 Shutdowns | Read | 0=No Shutdowns, 1=Shutdowns | ||
| BV | 215 | Unit 4 Shutdowns | Read | 0=No Shutdowns, 1=Shutdowns | ||
| BV | 216 | Unit 5 Shutdowns | Read | 0=No Shutdowns, 1=Shutdowns | ||
| BV | 217 | Unit 6 Shutdowns | Read | 0=No Shutdowns, 1=Shutdowns | ||
| BV | 218 | Unit 1 Motor Overload Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 219 | Unit 1 Discharge Temp Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 222 | Unit 1 Fail to Load Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 223 | Unit 1 VSD Starter Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 225 | Unit 2 Motor Overload Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 226 | Unit 2 Discharge Temp Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 229 | Unit 2 Fail to Load Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 230 | Unit 2 VSD Starter Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 232 | Unit 3 Motor Overload Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 233 | Unit 3 Discharge Temp Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 236 | Unit 3 Fail to Load Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 237 | Unit 3 VSD Starter Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 239 | Unit 4 Motor Overload Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 240 | Unit 4 Discharge Temp Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 243 | Unit 4 Fail to Load Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 244 | Unit 4 VSD Starter Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 246 | Unit 5 Motor Overload Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 247 | Unit 5 Discharge Temp Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 250 | Unit 5 Fail to Load Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 251 | Unit 5 VSD Starter Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 253 | Unit 6 Motor Overload Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 254 | Unit 6 Discharge Temp Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 257 | Unit 6 Fail to Load Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| BV | 258 | Unit 6 VSD Starter Alarm | Read | 0=Not In Alarm, 1=In Alarm | ||
| MVmin | 0 | Unit 1 Running Mode | Read | 1=Unit Stopped, 2=Unit Running DOL, 3=Unit Running VSD, 4=Emergency Comms, 5=Emergency Transducer, 6=Purge DOL, 7=Purge VSD, 8=Bump DOL | ||
| MV | 1 | Unit 2 Running Mode | Read | 1=Unit Stopped, 2=Unit Running DOL, 3=Unit Running VSD, 4=Emergency Comms, 5=Emergency Transducer, 6=Purge DOL, 7=Purge VSD, 8=Bump DOL | ||
| MV | 2 | Unit 3 Running Mode | Read | 1=Unit Stopped, 2=Unit Running DOL, 3=Unit Running VSD, 4=Emergency Comms, 5=Emergency Transducer, 6=Purge DOL, 7=Purge VSD, 8=Bump DOL | ||
| MV | 3 | Unit 4 Running Mode | Read | 1=Unit Stopped, 2=Unit Running DOL, 3=Unit Running VSD, 4=Emergency Comms, 5=Emergency Transducer, 6=Purge DOL, 7=Purge VSD, 8=Bump DOL | ||
| MV | 4 | Unit 5 Running Mode | Read | 1=Unit Stopped, 2=Unit Running DOL, 3=Unit Running VSD, 4=Emergency Comms, 5=Emergency Transducer, 6=Purge DOL, 7=Purge VSD, 8=Bump DOL | ||
| MV | 5 | Unit 6 Running Mode | Read | 1=Unit Stopped, 2=Unit Running DOL, 3=Unit Running VSD, 4=Emergency Comms, 5=Emergency Transducer, 6=Purge DOL, 7=Purge VSD, 8=Bump DOL | ||
| MV | 6 | Unit 1 Sequence | Sequence position | Read | 1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4, 6=Lag 5 | |
| MV | 7 | Unit 2 Sequence | Sequence position | Read | 1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4, 6=Lag 5 | |
| MV | 8 | Unit 3 Sequence | Sequence position | Read | 1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4, 6=Lag 5 | |
| MV | 9 | Unit 4 Sequence | Sequence position | Read | 1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4, 6=Lag 5 | |
| MV | 10 | Unit 5 Sequence | Sequence position | Read | 1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4, 6=Lag 5 | |
| MV | 11 | Unit 6 Sequence | Sequence position | Read | 1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4, 6=Lag 5 | |
| MV | 12 | Unit 1 Operation Mode | Read | 1=Off, 2=Manual, 3=Automatic, 4=Override Off, 5=Override On, 6=Emergency Comms, 7=Emergency Transducer, 8=Purge Off | ||
| MV | 13 | Unit 2 Operation Mode | Read | 1=Off, 2=Manual, 3=Automatic, 4=Override Off, 5=Override On, 6=Emergency Comms, 7=Emergency Transducer, 8=Purge Off | ||
| MV | 14 | Unit 3 Operation Mode | Read | 1=Off, 2=Manual, 3=Automatic, 4=Override Off, 5=Override On, 6=Emergency Comms, 7=Emergency Transducer, 8=Purge Off | ||
| MV | 15 | Unit 4 Operation Mode | Read | 1=Off, 2=Manual, 3=Automatic, 4=Override Off, 5=Override On, 6=Emergency Comms, 7=Emergency Transducer, 8=Purge Off | ||
| MV | 16 | Unit 5 Operation Mode | Read | 1=Off, 2=Manual, 3=Automatic, 4=Override Off, 5=Override On, 6=Emergency Comms, 7=Emergency Transducer, 8=Purge Off | ||
| MV | 17 | Unit 6 Operation Mode | Read | 1=Off, 2=Manual, 3=Automatic, 4=Override Off, 5=Override On, 6=Emergency Comms, 7=Emergency Transducer, 8=Purge Off |
No points match these filters.
Object ID lookup: BeaconMedaes TotalAlert 360 (TA360-S) controller - claw and lube medical vacuum systems point IDs by name
AV2System VacuumAV3Ambient TemperatureAV5Cabinet TemperatureAV100Unit 1 Running HoursAV101Unit 2 Running HoursAV102Unit 3 Running HoursAV103Unit 4 Running HoursAV104Unit 5 Running HoursAV105Unit 6 Running HoursIV0VSD SpeedBV0Any System AlarmsBV1Any System ServiceBV2Any System ShutdownsBV102Lag AlarmBV103High Ambient Temperature AlarmBV104High Cabinet Temperature AlarmBV105Control Circuit AlarmBV109Low Outlet Pressure AlarmBV110Tank Water Level AlarmBV115VSD Fault AlarmBV116VSD Off AlarmBV117High Outlet PressureBV200Unit 1 AlarmsBV201Unit 2 AlarmsBV202Unit 3 AlarmsBV203Unit 4 AlarmsBV204Unit 5 AlarmsBV205Unit 6 AlarmsBV206Unit 1 ServiceBV207Unit 2 ServiceBV208Unit 3 ServiceBV209Unit 4 ServiceBV210Unit 5 ServiceBV211Unit 6 ServiceBV212Unit 1 ShutdownsBV213Unit 2 ShutdownsBV214Unit 3 ShutdownsBV215Unit 4 ShutdownsBV216Unit 5 ShutdownsBV217Unit 6 ShutdownsBV218Unit 1 Motor Overload AlarmBV219Unit 1 Discharge Temp AlarmBV222Unit 1 Fail to Load AlarmBV223Unit 1 VSD Starter AlarmBV225Unit 2 Motor Overload AlarmBV226Unit 2 Discharge Temp AlarmBV229Unit 2 Fail to Load AlarmBV230Unit 2 VSD Starter AlarmBV232Unit 3 Motor Overload AlarmBV233Unit 3 Discharge Temp AlarmBV236Unit 3 Fail to Load AlarmBV237Unit 3 VSD Starter AlarmBV239Unit 4 Motor Overload AlarmBV240Unit 4 Discharge Temp AlarmBV243Unit 4 Fail to Load AlarmBV244Unit 4 VSD Starter AlarmBV246Unit 5 Motor Overload AlarmBV247Unit 5 Discharge Temp AlarmBV250Unit 5 Fail to Load AlarmBV251Unit 5 VSD Starter AlarmBV253Unit 6 Motor Overload AlarmBV254Unit 6 Discharge Temp AlarmBV257Unit 6 Fail to Load AlarmBV258Unit 6 VSD Starter AlarmMV0Unit 1 Running ModeMV1Unit 2 Running ModeMV2Unit 3 Running ModeMV3Unit 4 Running ModeMV4Unit 5 Running ModeMV5Unit 6 Running ModeMV6Unit 1 SequenceMV7Unit 2 SequenceMV8Unit 3 SequenceMV9Unit 4 SequenceMV10Unit 5 SequenceMV11Unit 6 SequenceMV12Unit 1 Operation ModeMV13Unit 2 Operation ModeMV14Unit 3 Operation ModeMV15Unit 4 Operation ModeMV16Unit 5 Operation ModeMV17Unit 6 Operation Mode
Integration notes
- From the PICS object mapping tables (object name, instance, present value, units / state description). All objects are read-only (B-SS profile); the PICS lists no write access.
- Every possible object is listed; objects for units, dryers or sensors that are not installed should be ignored. Reading the device Object_List shows only the objects relevant to the system.
- Multistate values start at 1 (as corrected in Rev 1 of the PICS).
- The same TA360-S controller covers scroll air and claw/lube vacuum plants; the two plant types have separate object maps.
- System vacuum units follow the controller setting (PSI, kPa, bar, inHg or mmHg); temperatures are degF.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TotalAlert 360 (TA360-S) controller - claw and lube medical vacuum systems and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the BeaconMedaes TotalAlert 360 (TA360-S) controller - claw and lube medical vacuum systems
How many BACnet points does the BeaconMedaes TotalAlert 360 (TA360-S) controller - claw and lube medical vacuum systems have?
This list has 82 BACnet objects: 9 analog values, 54 binary values, 18 multi-state values, 1 integer value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which BeaconMedaes TotalAlert 360 (TA360-S) controller - claw and lube medical vacuum systems BACnet points are writable?
None of the listed objects are marked writable in the source documentation.
Where is the official BeaconMedaes TotalAlert 360 (TA360-S) controller - claw and lube medical vacuum systems BACnet documentation?
BeaconMedaes does not publish it on its own website. This list comes from BACnet Protocol Implementation Conformance Statement - TA360 Systems (Object Mapping for TA360 Systems) (4107 9010 48 Rev02), revision 2025-07-16, a copy hosted by BACnet International at https://www.bacnetinternational.net/catalog/manu/beaconmedaes/PICS%20TA360%20Systems.pdf. Ask BeaconMedaes or its representative for the current revision.
What are the minimum BACnet points to integrate the BeaconMedaes TotalAlert 360 (TA360-S) controller - claw and lube medical vacuum systems?
Start with BV 0 Any System Alarms (Any system alarm); BV 2 Any System Shutdowns (Any shutdown active); BV 1 Any System Service (Service due); AV 2 System Vacuum (Plant vacuum level); IV 0 VSD Speed (VSD speed, Hz); MV 0 Unit 1 Running Mode (Unit 1 running state); BV 200 Unit 1 Alarms (Unit 1 alarm); BV 115 VSD Fault Alarm (VSD fault).
How do I enable BMS control of the BeaconMedaes TotalAlert 360 (TA360-S) controller - claw and lube medical vacuum systems?
Monitoring only: the PICS lists no writable objects.
How do I check these points on the real TotalAlert 360 (TA360-S) controller - claw and lube medical vacuum systems?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More BeaconMedaes BACnet points lists