Fan coil thermostat (230 VAC, 4-pipe) · BACnet points list

Avantec TA692FC-BAC fan coil thermostat (BACnet MS/TP) BACnet points list

Updated 4 November 2026

Short answer

The TA692FC-BAC is a 230 VAC touch-key fan coil thermostat with BACnet MS/TP (B-ASC profile). Its small fixed object list covers on/off, system mode, fan mode, heating and cooling setpoints, deadband, valve outputs, fan relay states, occupancy input and room and remote temperatures.

This page lists 20 BACnet objects for the Avantec TA692FC-BAC fan coil thermostat (BACnet MS/TP) — 13 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Avantec’s own free documentation, linked below.

Manufacturer
Avantec
Model
TA692FC-BAC fan coil thermostat (BACnet MS/TP)
Equipment
Fan coil thermostat (230 VAC, 4-pipe)
Equipment type
VAV boxes & fan coils
BACnet objects
20 (13 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
5
Also known as
TA692FC-BAC, TA692FC BACnet, Avantec fan coil thermostat BACnet, TA692FC
Source document
Functional Specification of TA692FC-BAC · TA692FC-BAC-20230504a · rev. 2023-05-04
Download CSV 20 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Avantec’s current documentation and the live device before use. Not official Avantec information. Terms of use.

BMS integration notes: Avantec TA692FC-BAC fan coil thermostat (BACnet MS/TP)

Integration in brief

Give the thermostat a unique MS/TP address and device instance, then switch it on (BV 0), set the system mode (AV 0), fan mode (AV 2) and the heat/cool setpoints (AV 6/7). Read room temperature (AI 0), the valve outputs and the fan relay states.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 0Room Unit On/OffThermostat on/off, 1 = onWrite
AV 0System mode0 Heat, 1 Cool, 2 AutoWrite
AV 2Fan Mode0 Off, 1 Low, 2 Med, 3 Hi, 4 AutoWrite
AV 6Heat Set PointHeating setpoint, °CWrite
AV 7Cool Set PointCooling setpoint, °CWrite
AI 0Room TemperatureRoom temperature, °CRead
BV 3Heat valveHeating valve stateWrite
BV 4Cool valveCooling valve stateWrite
BI 0Occupancy SensorOccupancy contact: 0 Comfort, 1 EcoRead

Network setup

Watch out for

Avantec TA692FC-BAC fan coil thermostat (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

20 of 20 shown
Type
Access
Show
Avantec TA692FC-BAC fan coil thermostat (BACnet MS/TP) BACnet Points List
DescriptionStates
BVmin0Room Unit On/OffThermostat on/off (default off)Write0=Off, 1=On
BV1Force VentilationForced ventilation (default disabled)Write0=Disable, 1=Enable
BV2Temperature UnitDisplay unit (default Celsius)Write0=Celsius, 1=Fahrenheit
BVmin3Heat valveHeating valve outputWrite0=Off, 1=On
BVmin4Cool valveCooling valve outputWrite0=Off, 1=On
BImin0Occupancy SensorOccupancy contact input (default Comfort)Read0=Comfort, 1=Eco
BI1Fan AutoFan in auto modeRead0=Manual, 1=Auto
BI2Fan LowLow fan speed relayRead0=Off, 1=On
BI3Fan MedMedium fan speed relayRead0=Off, 1=On
BI4Fan HiHigh fan speed relayRead0=Off, 1=On
AImin0Room TemperatureRoom temperature, 5.0-35.0°CRead
AI1Remote Sensor TemperatureExternal NTC sensor temperature, 5.0-35.0°CRead
AVmin0System modeHeat, Cool or Auto (default Heat)Write0=Heat, 1=Cool, 2=Auto
AV1Dead band1.0-4.0 in 0.5 steps (default 2)°CWrite
AVmin2Fan ModeFan speed selection (default Off)Write0=Off, 1=Low, 2=Med, 3=Hi, 4=Auto
AV3Temperature CalibrationRoom sensor offset, -4 to 4 (default 0)°CWrite
AV4Fan Span HeatHeating fan speed span, 1-4 (default 1)°CWrite
AV5Fan Span CoolCooling fan speed span, 1-4 (default 1)°CWrite
AVmin6Heat Set PointHeating setpoint, 5.0-35.0 (default 20)°CWrite
AVmin7Cool Set PointCooling setpoint, 5.0-35.0 (default 25)°CWrite
Object ID lookup: Avantec TA692FC-BAC fan coil thermostat point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TA692FC-BAC fan coil thermostat (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Avantec TA692FC-BAC fan coil thermostat (BACnet MS/TP)

How many BACnet points does the Avantec TA692FC-BAC fan coil thermostat (BACnet MS/TP) have?

This list has 20 BACnet objects: 2 analog inputs, 8 analog values, 5 binary inputs, 5 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Avantec TA692FC-BAC fan coil thermostat (BACnet MS/TP) BACnet points are writable?

13 of the 20 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Avantec TA692FC-BAC fan coil thermostat (BACnet MS/TP) BACnet documentation?

The source is Functional Specification of TA692FC-BAC (TA692FC-BAC-20230504a), revision 2023-05-04, published free by Avantec at https://avantec-thingsboard.readthedocs.io/en/latest/_downloads/ce39f363848fc926bccf89d3868da2b4/TA692FC-BAC-20230504a.pdf.

What are the minimum BACnet points to integrate the Avantec TA692FC-BAC fan coil thermostat (BACnet MS/TP)?

Start with BV 0 Room Unit On/Off (Thermostat on/off, 1 = on); AV 0 System mode (0 Heat, 1 Cool, 2 Auto); AV 2 Fan Mode (0 Off, 1 Low, 2 Med, 3 Hi, 4 Auto); AV 6 Heat Set Point (Heating setpoint, °C); AV 7 Cool Set Point (Cooling setpoint, °C); AI 0 Room Temperature (Room temperature, °C); BV 3 Heat valve (Heating valve state); BV 4 Cool valve (Cooling valve state); BI 0 Occupancy Sensor (Occupancy contact: 0 Comfort, 1 Eco).

How do I check these points on the real TA692FC-BAC fan coil thermostat (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Avantec BACnet points lists

Source: Functional Specification of TA692FC-BAC · TA692FC-BAC-20230504a · rev. 2023-05-04. Object names, instances and units are reproduced as published; descriptions are our own.