- TA640FC-BAC touch-screen thermostat (BACnet MS/TP)
Fan coil thermostat (24 VAC) · BACnet points list
Avantec TA640FC-BAC touch-screen thermostat (BACnet MS/TP) BACnet points list
Updated 4 November 2026
The TA640FC-BAC is a 24 VAC fan coil thermostat with BACnet MS/TP. Most values are read-only Analog Inputs (room and external temperature, mode, fan mode and status, PI outputs, spans); the BMS can write the room setpoint, the PI bands and 0-10 V offset, forced ventilation and the screen saver.
This page lists 20 BACnet objects for the Avantec TA640FC-BAC touch-screen thermostat (BACnet MS/TP) — 7 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Avantec’s own free documentation, linked below.
- Manufacturer
- Avantec
- Model
- TA640FC-BAC touch-screen thermostat (BACnet MS/TP)
- Equipment
- Fan coil thermostat (24 VAC)
- Equipment type
- VAV boxes & fan coils
- BACnet objects
- 20 (7 writable)
- Transport
- BACnet MS/TP
- Firmware
- v137
- Also known as
- TA640FC-BAC, TA640FC BACnet, Avantec TA640 BACnet, TA640FC
Reference only, provided as-is: verify against Avantec’s current documentation and the live device before use. Not official Avantec information. Terms of use.
BMS integration notes: Avantec TA640FC-BAC touch-screen thermostat (BACnet MS/TP)
Give the thermostat a unique device instance, write the room setpoint (AV 3) and read room temperature (AI 0), mode (AI 1), fan status (AI 3) and the PI outputs. The on/off object BV 2 is marked reserved, so on/off and mode are not controlled over BACnet.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 3 | Room Temp setpoint | Room setpoint, 10-35 °C | Write |
| AI 0 | Room Temperature | Room temperature, °C | Read |
| AI 1 | Heat/Cool Mode | 0 Heat, 1 Cool | Read |
| AI 2 | Fan Mode | 0 Auto, 1 Low, 2 Mid, 3 High | Read |
| AI 3 | Fan Status | Running fan speed, 0 = off | Read |
| AI 6 | PI Cool Output % | Cooling output, % | Read |
Network setup
- BACnet MS/TP; device ID range 0-3FFFF (hex).
Watch out for
- Reserved (*) objects AI 10, AI 11, BI 0 and BV 2 have no effect; do not map them as controls.
Avantec TA640FC-BAC touch-screen thermostat (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 0 | Room Temperature | Room temperature, 5.0-40.0 | °C | Read | |
| AImin | 1 | Heat/Cool Mode | Present mode | Read | 0=Heat, 1=Cool | |
| AImin | 2 | Fan Mode | Selected fan mode | Read | 0=Auto, 1=Low, 2=Mid, 3=High | |
| AImin | 3 | Fan Status | Running fan speed | Read | 0=Off, 1=Low, 2=Mid, 3=High | |
| AI | 4 | External Sensor Temp | External sensor temperature, 5.0-40.0 | °C | Read | |
| AI | 5 | PI Heat Output % | PI heating output, 0-100 | % | Read | |
| AImin | 6 | PI Cool Output % | PI cooling output, 0-100 | % | Read | |
| AI | 7 | Room Temp Offset | Room sensor offset, -5 to +5 | °C | Read | |
| AI | 8 | Cool mode span | Cooling span, 2-4 | °C | Read | |
| AI | 9 | Heat mode span | Heating span, 2-4 | °C | Read | |
| AI | 10 | Cool mode setpoint(*) | Reserved; no effect on operation | °C | Read | |
| AI | 11 | Heat mode setpoint(*) | Reserved; no effect on operation | °C | Read | |
| AV | 0 | P.I. Cool mode P-Band | Cooling proportional band, 0.5-8 (default 2) | °C | Write | |
| AV | 1 | P.I. Heat mode P-Band | Heating proportional band, 0.5-8 (default 2) | °C | Write | |
| AV | 2 | P.I. 0~10V output offset | 0-10 V output offset, 30-70 steps (default 50) | Write | ||
| AVmin | 3 | Room Temp setpoint | Room setpoint, 10-35 | °C | Write | |
| BI | 0 | Occupancy mode status(*) | Reserved; no effect on operation | Read | On / Off | |
| BV | 0 | Forced Ventilation | Forced ventilation | Write | Enable / Disable | |
| BV | 1 | User Interface Screen Saver | Display screen saver | Write | Standard / Off | |
| BV | 2 | System On/Off mode(*) | Reserved; no effect on operation | Write | On / Off |
No points match these filters.
Object ID lookup: Avantec TA640FC-BAC touch-screen thermostat point IDs by name
AI0Room TemperatureAI1Heat/Cool ModeAI2Fan ModeAI3Fan StatusAI4External Sensor TempAI5PI Heat Output %AI6PI Cool Output %AI7Room Temp OffsetAI8Cool mode spanAI9Heat mode spanAI10Cool mode setpoint(*)AI11Heat mode setpoint(*)AV0P.I. Cool mode P-BandAV1P.I. Heat mode P-BandAV2P.I. 0~10V output offsetAV3Room Temp setpointBI0Occupancy mode status(*)BV0Forced VentilationBV1User Interface Screen SaverBV2System On/Off mode(*)
Integration notes
- Objects marked (*) are reserved: their values have no effect on operation (AI 10, AI 11, BI 0, BV 2).
- Mode, fan mode and fan status are reported as Analog Inputs with coded values, not multistate objects.
- Binary state texts are printed without numbers (On / Off, Enable / Disable, Standard / Off).
- Source: Avantec functional specification of TA640FC-BAC, 4 November 2022.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TA640FC-BAC touch-screen thermostat (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Avantec TA640FC-BAC touch-screen thermostat (BACnet MS/TP)
How many BACnet points does the Avantec TA640FC-BAC touch-screen thermostat (BACnet MS/TP) have?
This list has 20 BACnet objects: 12 analog inputs, 4 analog values, 1 binary input, 3 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Avantec TA640FC-BAC touch-screen thermostat (BACnet MS/TP) BACnet points are writable?
7 of the 20 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Avantec TA640FC-BAC touch-screen thermostat (BACnet MS/TP) BACnet documentation?
The source is Functional Specification of TA640FC-BAC (TA640FC-BAC-2022.11.4), revision 2022-11-04, published free by Avantec at https://avantec-thingsboard.readthedocs.io/en/latest/_downloads/a3cb1fa3de0f1bf3380cd7ab06b7890c/TA640FC-BAC-2022.11.4.pdf.
What are the minimum BACnet points to integrate the Avantec TA640FC-BAC touch-screen thermostat (BACnet MS/TP)?
Start with AV 3 Room Temp setpoint (Room setpoint, 10-35 °C); AI 0 Room Temperature (Room temperature, °C); AI 1 Heat/Cool Mode (0 Heat, 1 Cool); AI 2 Fan Mode (0 Auto, 1 Low, 2 Mid, 3 High); AI 3 Fan Status (Running fan speed, 0 = off); AI 6 PI Cool Output % (Cooling output, %).
How do I check these points on the real TA640FC-BAC touch-screen thermostat (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Avantec BACnet points lists
Source: Functional Specification of TA640FC-BAC · TA640FC-BAC-2022.11.4 · rev. 2022-11-04. Object names, instances and units are reproduced as published; descriptions are our own.