Fan coil thermostat (24 VAC) · BACnet points list

Avantec TA640FC-BAC touch-screen thermostat (BACnet MS/TP) BACnet points list

Updated 4 November 2026

Short answer

The TA640FC-BAC is a 24 VAC fan coil thermostat with BACnet MS/TP. Most values are read-only Analog Inputs (room and external temperature, mode, fan mode and status, PI outputs, spans); the BMS can write the room setpoint, the PI bands and 0-10 V offset, forced ventilation and the screen saver.

This page lists 20 BACnet objects for the Avantec TA640FC-BAC touch-screen thermostat (BACnet MS/TP) — 7 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Avantec’s own free documentation, linked below.

Manufacturer
Avantec
Model
TA640FC-BAC touch-screen thermostat (BACnet MS/TP)
Equipment
Fan coil thermostat (24 VAC)
Equipment type
VAV boxes & fan coils
BACnet objects
20 (7 writable)
Transport
BACnet MS/TP
Firmware
v137
Also known as
TA640FC-BAC, TA640FC BACnet, Avantec TA640 BACnet, TA640FC
Source document
Functional Specification of TA640FC-BAC · TA640FC-BAC-2022.11.4 · rev. 2022-11-04
Download CSV 20 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Avantec’s current documentation and the live device before use. Not official Avantec information. Terms of use.

BMS integration notes: Avantec TA640FC-BAC touch-screen thermostat (BACnet MS/TP)

Integration in brief

Give the thermostat a unique device instance, write the room setpoint (AV 3) and read room temperature (AI 0), mode (AI 1), fan status (AI 3) and the PI outputs. The on/off object BV 2 is marked reserved, so on/off and mode are not controlled over BACnet.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 3Room Temp setpointRoom setpoint, 10-35 °CWrite
AI 0Room TemperatureRoom temperature, °CRead
AI 1Heat/Cool Mode0 Heat, 1 CoolRead
AI 2Fan Mode0 Auto, 1 Low, 2 Mid, 3 HighRead
AI 3Fan StatusRunning fan speed, 0 = offRead
AI 6PI Cool Output %Cooling output, %Read

Network setup

Watch out for

Avantec TA640FC-BAC touch-screen thermostat (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

20 of 20 shown
Type
Access
Show
Avantec TA640FC-BAC touch-screen thermostat (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin0Room TemperatureRoom temperature, 5.0-40.0°CRead
AImin1Heat/Cool ModePresent modeRead0=Heat, 1=Cool
AImin2Fan ModeSelected fan modeRead0=Auto, 1=Low, 2=Mid, 3=High
AImin3Fan StatusRunning fan speedRead0=Off, 1=Low, 2=Mid, 3=High
AI4External Sensor TempExternal sensor temperature, 5.0-40.0°CRead
AI5PI Heat Output %PI heating output, 0-100%Read
AImin6PI Cool Output %PI cooling output, 0-100%Read
AI7Room Temp OffsetRoom sensor offset, -5 to +5°CRead
AI8Cool mode spanCooling span, 2-4°CRead
AI9Heat mode spanHeating span, 2-4°CRead
AI10Cool mode setpoint(*)Reserved; no effect on operation°CRead
AI11Heat mode setpoint(*)Reserved; no effect on operation°CRead
AV0P.I. Cool mode P-BandCooling proportional band, 0.5-8 (default 2)°CWrite
AV1P.I. Heat mode P-BandHeating proportional band, 0.5-8 (default 2)°CWrite
AV2P.I. 0~10V output offset0-10 V output offset, 30-70 steps (default 50)Write
AVmin3Room Temp setpointRoom setpoint, 10-35°CWrite
BI0Occupancy mode status(*)Reserved; no effect on operationReadOn / Off
BV0Forced VentilationForced ventilationWriteEnable / Disable
BV1User Interface Screen SaverDisplay screen saverWriteStandard / Off
BV2System On/Off mode(*)Reserved; no effect on operationWriteOn / Off
Object ID lookup: Avantec TA640FC-BAC touch-screen thermostat point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TA640FC-BAC touch-screen thermostat (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Avantec TA640FC-BAC touch-screen thermostat (BACnet MS/TP)

How many BACnet points does the Avantec TA640FC-BAC touch-screen thermostat (BACnet MS/TP) have?

This list has 20 BACnet objects: 12 analog inputs, 4 analog values, 1 binary input, 3 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Avantec TA640FC-BAC touch-screen thermostat (BACnet MS/TP) BACnet points are writable?

7 of the 20 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Avantec TA640FC-BAC touch-screen thermostat (BACnet MS/TP) BACnet documentation?

The source is Functional Specification of TA640FC-BAC (TA640FC-BAC-2022.11.4), revision 2022-11-04, published free by Avantec at https://avantec-thingsboard.readthedocs.io/en/latest/_downloads/a3cb1fa3de0f1bf3380cd7ab06b7890c/TA640FC-BAC-2022.11.4.pdf.

What are the minimum BACnet points to integrate the Avantec TA640FC-BAC touch-screen thermostat (BACnet MS/TP)?

Start with AV 3 Room Temp setpoint (Room setpoint, 10-35 °C); AI 0 Room Temperature (Room temperature, °C); AI 1 Heat/Cool Mode (0 Heat, 1 Cool); AI 2 Fan Mode (0 Auto, 1 Low, 2 Mid, 3 High); AI 3 Fan Status (Running fan speed, 0 = off); AI 6 PI Cool Output % (Cooling output, %).

How do I check these points on the real TA640FC-BAC touch-screen thermostat (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.