  4. KTRBUu217.456 BACnet room controller - application 4HRKR001 / 4RAKR001 (4-pipe fan coil (alone or with radiator))

Room controller (fan coil) · BACnet points list

ALRE KTRBUu217.456 BACnet room controller - application 4HRKR001 / 4RAKR001 (4-pipe fan coil (alone or with radiator)) BACnet points list

Updated 4 November 2026

Short answer

The KTRBUu217.456 is a flush-mounted 230 V room controller with display and BACnet MS/TP (B-AAC). Each built-in application loads its own object set; this entry is application 4HRKR001 / 4RAKR001, fan coil, 4-pipe. The BMS sets the operation mode, heating/cooling mode and setpoints, writes window, presence and fire-alarm states, and must keep a heartbeat going to stay in online mode.

This page lists 38 BACnet objects for the ALRE KTRBUu217.456 BACnet room controller - application 4HRKR001 / 4RAKR001 (4-pipe fan coil (alone or with radiator)) — 25 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from ALRE’s own free documentation, linked below.

Manufacturer
ALRE
Model
KTRBUu217.456 BACnet room controller - application 4HRKR001 / 4RAKR001 (4-pipe fan coil (alone or with radiator))
Equipment
Room controller (fan coil)
Equipment type
VAV boxes & fan coils
BACnet objects
38 (25 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
78
Also known as
KTRBUu217.456, KTRBUu-217.456, ALRE BACnet Raumregler, 4HRKR001, 4RAKR001
Source document
EDE data KTRBUu (file 4HRKR001-EDE.csv) · rev. EDE timestamp 2019-10-21
Download CSV 38 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against ALRE’s current documentation and the live device before use. Not official ALRE information. Terms of use.

BMS integration notes: ALRE KTRBUu217.456 BACnet room controller - application 4HRKR001 / 4RAKR001 (4-pipe fan coil (alone or with radiator))

Integration in brief

Set device instance, MAC address (1-127), baud rate, Max Master and Max Info Frames on the controller. From the BMS, write Operation Mode BMS and (where present) Control-Mode BMS, the setpoints, and the window/presence states, and keep rewriting Heartbeat Input so the controller stays online.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 2Operation Mode BMSProtection, economy, pre-comfort or comfortWrite
MV 4Control-Mode BMSHeating, cooling or automaticWrite
AV 15Setpoint COMFORT HeatingComfort heating setpointWrite
AV 25Setpoint COMFORT CoolingComfort cooling setpointWrite
BV 2Window StateWindow open from the BMS, 1 = openWrite
AV 30Heartbeat InputRewrite seconds before it counts down to 0Write
MV 3Active Operation ModeOperation mode in forceRead
AI 1TemperatureRoom temperatureRead
AV 1Active SetpointSetpoint in useRead

Enable & remote start

Operation Mode BMS (MV 2) selects protection, economy, pre-comfort or comfort; the schedule object can also drive it. Fire Alarm (BV 6) puts the controller into its fire-alarm state.

Heartbeat & communication loss

Heartbeat Input (AV 30): the BMS writes a number of seconds and the controller counts it down once per second. At 0 the controller goes to offline mode (local operation only); the BMS must write a new value before it reaches 0.

Sensors & values from the BMS

Window State (BV 2) and Presence Detector (BV 3) are written by the BMS from its own window contacts and presence sensors; the controller reads window open from BV 2.

Network setup

Watch out for

ALRE KTRBUu217.456 BACnet room controller - application 4HRKR001 / 4RAKR001 (4-pipe fan coil (alone or with radiator)) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

38 of 38 shown
Type
Multi-state
Access
Show
ALRE KTRBUu217.456 BACnet room controller - application 4HRKR001 / 4RAKR001 (4-pipe fan coil (alone or with radiator)) BACnet Points List
DescriptionStates
AImin1TemperatureRoom temperature used for control°CRead
AI2Fan-Air TemperatureFan discharge air temperature (external sensor)°CRead
AO1Fan ControlFan speed signal%Command
AO11Control Value HeatingHeating valve signal%Command
AO21Control Value CoolingCooling valve signal%Command
AVmin1Active SetpointSetpoint currently in use°CRead
AV2Air Temperature Max-OffsetFan is reduced when room minus air temperature exceeds this°CWrite
AV4Local Config PINPIN for the local configuration menuWrite
AV5Maximum Local OffsetMaximum setpoint shift allowed at the unitWrite
AV12Setpoint PROTECTION HeatingSetpoint PROTECTION Heating°CWrite
AV13Setpoint ECONOMY HeatingSetpoint ECONOMY Heating°CWrite
AV14Setpoint PRE COMFORT HeatingSetpoint PRE COMFORT Heating°CWrite
AVmin15Setpoint COMFORT HeatingSetpoint COMFORT Heating°CWrite
AV22Setpoint PROTECTION CoolingSetpoint PROTECTION Cooling°CWrite
AV23Setpoint ECONOMY CoolingSetpoint ECONOMY Cooling°CWrite
AV24Setpoint PRE COMFORT CoolingSetpoint PRE COMFORT Cooling°CWrite
AVmin25Setpoint COMFORT CoolingSetpoint COMFORT Cooling°CWrite
AVmin30Heartbeat InputBMS heartbeat: seconds until offline modeWrite
BO1Output HeatingHeating relay outputCommand0=off, 1=on
BO2Output CoolingCooling relay outputCommand0=off, 1=on
BVmin2Window StateWindow open/closed, written by the BMSWrite0=closed, 1=open
BV3Presence DetectorPresence, written by the BMSWrite0=Person Absence, 1=Person Presence
BV4User ResetReset the user's local settingsWrite0=done, 1=Reset
BV5User Control LockLock all local controlsWrite0=Usercontrol unlocked, 1=Usercontrol locked
BV6Fire AlarmFire alarm from the BMSWrite0=Fire alarm not active, 1=Fire alarm active
MVmin2Operation Mode BMSOperation mode requested by the BMSWrite1=PROTECTION, 2=ECONOMY, 3=PRE COMFORT, 4=COMFORT
MVmin3Active Operation ModeOperation mode currently activeRead1=PROTECTION, 2=ECONOMY, 3=PRE COMFORT, 4=COMFORT, 5=EXTENDED PRESENCE, 6=VALVE PROTECTION, 7=BOOST MODE, 8=SLEEP MODE, 9=EMERGENCY-OPERATION, 10=FIRE ALARM
MVmin4Control-Mode BMSHeating/cooling mode requested by the BMSWrite1=Heating, 2=Cooling, 3=Automatic
MV5Active Control-ModeHeating/cooling mode currently activeRead1=Heating, 2=Cooling
LO10Regulator HeatingHeating PID loopRead
LO20Regulator CoolingCooling PID loopRead
SCH1Operation-Mode-ScheduleWeekly schedule of operation modesWrite
NC10Notificationclass for AlarmsNotification class for alarmsRead
NC20Notificationclass for FaultsNotification class for faultsRead
NC30Notificationclass for Operational MessagesNotification class for operational messagesRead
FILE100checksum.sezConfiguration fileRead
FILE101customer.luaConfiguration fileRead
Other1PRG0000001_BOOTProgram objectRead
Object ID lookup: ALRE KTRBUu217.456 4HRKR001 / 4RAKR001 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the KTRBUu217.456 BACnet room controller - application 4HRKR001 / 4RAKR001 (4-pipe fan coil (alone or with radiator)) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the ALRE KTRBUu217.456 BACnet room controller - application 4HRKR001 / 4RAKR001 (4-pipe fan coil (alone or with radiator))

How many BACnet points does the ALRE KTRBUu217.456 BACnet room controller - application 4HRKR001 / 4RAKR001 (4-pipe fan coil (alone or with radiator)) have?

This list has 38 BACnet objects: 2 analog inputs, 3 analog outputs, 13 analog values, 2 binary outputs, 5 binary values, 2 files, 2 loops, 3 notification classs, 1 schedule, 4 multi-state values, 1 other. The exact set on a given unit depends on its firmware, installed options and configuration.

Which ALRE KTRBUu217.456 BACnet room controller - application 4HRKR001 / 4RAKR001 (4-pipe fan coil (alone or with radiator)) BACnet points are writable?

25 of the 38 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official ALRE KTRBUu217.456 BACnet room controller - application 4HRKR001 / 4RAKR001 (4-pipe fan coil (alone or with radiator)) BACnet documentation?

The source is EDE data KTRBUu (file 4HRKR001-EDE.csv), revision EDE timestamp 2019-10-21, published free by ALRE at https://alre.de/wp-content/uploads/2026/11/EDE_Daten_KTRBUu.zip.

What are the minimum BACnet points to integrate the ALRE KTRBUu217.456 BACnet room controller - application 4HRKR001 / 4RAKR001 (4-pipe fan coil (alone or with radiator))?

Start with MV 2 Operation Mode BMS (Protection, economy, pre-comfort or comfort); MV 4 Control-Mode BMS (Heating, cooling or automatic); AV 15 Setpoint COMFORT Heating (Comfort heating setpoint); AV 25 Setpoint COMFORT Cooling (Comfort cooling setpoint); BV 2 Window State (Window open from the BMS, 1 = open); AV 30 Heartbeat Input (Rewrite seconds before it counts down to 0); MV 3 Active Operation Mode (Operation mode in force); AI 1 Temperature (Room temperature); AV 1 Active Setpoint (Setpoint in use).

How do I enable BMS control of the ALRE KTRBUu217.456 BACnet room controller - application 4HRKR001 / 4RAKR001 (4-pipe fan coil (alone or with radiator))?

Operation Mode BMS (MV 2) selects protection, economy, pre-comfort or comfort; the schedule object can also drive it. Fire Alarm (BV 6) puts the controller into its fire-alarm state.

Does the ALRE KTRBUu217.456 BACnet room controller - application 4HRKR001 / 4RAKR001 (4-pipe fan coil (alone or with radiator)) need a BACnet heartbeat or have a communication timeout?

Heartbeat Input (AV 30): the BMS writes a number of seconds and the controller counts it down once per second. At 0 the controller goes to offline mode (local operation only); the BMS must write a new value before it reaches 0.

Can the BMS supply sensor values to the ALRE KTRBUu217.456 BACnet room controller - application 4HRKR001 / 4RAKR001 (4-pipe fan coil (alone or with radiator))?

Window State (BV 2) and Presence Detector (BV 3) are written by the BMS from its own window contacts and presence sensors; the controller reads window open from BV 2.

How do I check these points on the real KTRBUu217.456 BACnet room controller - application 4HRKR001 / 4RAKR001 (4-pipe fan coil (alone or with radiator))?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More ALRE BACnet points lists

Source: EDE data KTRBUu (file 4HRKR001-EDE.csv) · rev. EDE timestamp 2019-10-21. Object names, instances and units are reproduced as published; descriptions are our own.