  4. KTRBUu217.456 BACnet room controller - application 2KD001 (2-pipe heating/cooling ceiling with dew point monitor)

Room controller (chilled ceiling) · BACnet points list

ALRE KTRBUu217.456 BACnet room controller - application 2KD001 (2-pipe heating/cooling ceiling with dew point monitor) BACnet points list

Updated 4 November 2026

Short answer

The KTRBUu217.456 is a flush-mounted 230 V room controller with display and BACnet MS/TP (B-AAC). Each built-in application loads its own object set; this entry is application 2KD001, chilled/heated ceiling, 2-pipe. The BMS sets the operation mode, heating/cooling mode and setpoints, writes window, presence and fire-alarm states, and must keep a heartbeat going to stay in online mode.

This page lists 35 BACnet objects for the ALRE KTRBUu217.456 BACnet room controller - application 2KD001 (2-pipe heating/cooling ceiling with dew point monitor) — 22 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from ALRE’s own free documentation, linked below.

Manufacturer
ALRE
Model
KTRBUu217.456 BACnet room controller - application 2KD001 (2-pipe heating/cooling ceiling with dew point monitor)
Equipment
Room controller (chilled ceiling)
Equipment type
Thermostats, sensors & meters
BACnet objects
35 (22 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
78
Also known as
KTRBUu217.456, KTRBUu-217.456, ALRE BACnet Raumregler, 2KD001
Source document
EDE data KTRBUu (file 2KD001-EDE.csv) · rev. EDE timestamp 2019-10-21
Download CSV 35 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against ALRE’s current documentation and the live device before use. Not official ALRE information. Terms of use.

BMS integration notes: ALRE KTRBUu217.456 BACnet room controller - application 2KD001 (2-pipe heating/cooling ceiling with dew point monitor)

Integration in brief

Set device instance, MAC address (1-127), baud rate, Max Master and Max Info Frames on the controller. From the BMS, write Operation Mode BMS and (where present) Control-Mode BMS, the setpoints, and the window/presence states, and keep rewriting Heartbeat Input so the controller stays online.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 2Operation Mode BMSProtection, economy, pre-comfort or comfortWrite
MV 4Control-Mode BMSHeating or cooling (change-over)Write
AV 15Setpoint COMFORT HeatingComfort heating setpointWrite
AV 25Setpoint COMFORT CoolingComfort cooling setpointWrite
BV 2Window StateWindow open from the BMS, 1 = openWrite
AV 30Heartbeat InputRewrite seconds before it counts down to 0Write
MV 3Active Operation ModeOperation mode in forceRead
AI 1TemperatureRoom temperatureRead
AV 1Active SetpointSetpoint in useRead
BI 1Dew point sensorDew point alarm (1 = wet)Read

Enable & remote start

Operation Mode BMS (MV 2) selects protection, economy, pre-comfort or comfort; the schedule object can also drive it. Fire Alarm (BV 6) puts the controller into its fire-alarm state.

Heartbeat & communication loss

Heartbeat Input (AV 30): the BMS writes a number of seconds and the controller counts it down once per second. At 0 the controller goes to offline mode (local operation only); the BMS must write a new value before it reaches 0.

Sensors & values from the BMS

Window State (BV 2) and Presence Detector (BV 3) are written by the BMS from its own window contacts and presence sensors; the controller reads window open from BV 2.

Network setup

Watch out for

ALRE KTRBUu217.456 BACnet room controller - application 2KD001 (2-pipe heating/cooling ceiling with dew point monitor) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

35 of 35 shown
Type
Multi-state
Access
Show
ALRE KTRBUu217.456 BACnet room controller - application 2KD001 (2-pipe heating/cooling ceiling with dew point monitor) BACnet Points List
DescriptionStates
AImin1TemperatureRoom temperature used for control°CRead
AO11Control Value HeatingHeating valve signal%Command
AO21Control Value CoolingCooling valve signal%Command
AVmin1Active SetpointSetpoint currently in use°CRead
AV4Local Config PINPIN for the local configuration menuWrite
AV5Maximum Local OffsetMaximum setpoint shift allowed at the unitWrite
AV12Setpoint PROTECTION HeatingSetpoint PROTECTION Heating°CWrite
AV13Setpoint ECONOMY HeatingSetpoint ECONOMY Heating°CWrite
AV14Setpoint PRE COMFORT HeatingSetpoint PRE COMFORT Heating°CWrite
AVmin15Setpoint COMFORT HeatingSetpoint COMFORT Heating°CWrite
AV22Setpoint PROTECTION CoolingSetpoint PROTECTION Cooling°CWrite
AV23Setpoint ECONOMY CoolingSetpoint ECONOMY Cooling°CWrite
AV24Setpoint PRE COMFORT CoolingSetpoint PRE COMFORT Cooling°CWrite
AVmin25Setpoint COMFORT CoolingSetpoint COMFORT Cooling°CWrite
AVmin30Heartbeat InputBMS heartbeat: seconds until offline modeWrite
BImin1Dew point sensorDew point sensor (dry/wet)Read0=dewpoint-sensor dry, 1=dewpoint-sensor wet
BO1Output Heating/CoolingHeating/cooling relay outputCommand0=off, 1=on
BVmin2Window StateWindow open/closed, written by the BMSWrite0=closed, 1=open
BV3Presence DetectorPresence, written by the BMSWrite0=Person Absence, 1=Person Presence
BV4User ResetReset the user's local settingsWrite0=done, 1=Reset
BV5User Control LockLock all local controlsWrite0=Usercontrol unlocked, 1=Usercontrol locked
BV6Fire AlarmFire alarm from the BMSWrite0=Fire alarm not active, 1=Fire alarm active
MVmin2Operation Mode BMSOperation mode requested by the BMSWrite1=PROTECTION, 2=ECONOMY, 3=PRE COMFORT, 4=COMFORT
MVmin3Active Operation ModeOperation mode currently activeRead1=PROTECTION, 2=ECONOMY, 3=PRE COMFORT, 4=COMFORT, 5=EXTENDED PRESENCE, 6=VALVE PROTECTION, 7=BOOST MODE, 8=SLEEP MODE, 9=EMERGENCY-OPERATION, 10=FIRE ALARM
MVmin4Control-Mode BMSHeating/cooling mode requested by the BMSWrite1=Heating, 2=Cooling
MV5Active Control-ModeHeating/cooling mode currently activeRead1=Heating, 2=Cooling
LO10Regulator HeatingHeating PID loopRead
LO20Regulator CoolingCooling PID loopRead
SCH1Operation-Mode-ScheduleWeekly schedule of operation modesWrite
NC10Notificationclass for AlarmsNotification class for alarmsRead
NC20Notificationclass for FaultsNotification class for faultsRead
NC30Notificationclass for Operational MessagesNotification class for operational messagesRead
FILE100checksum.sezConfiguration fileRead
FILE101customer.luaConfiguration fileRead
Other1PRG0000001_BOOTProgram objectRead
Object ID lookup: ALRE KTRBUu217.456 2KD001 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the KTRBUu217.456 BACnet room controller - application 2KD001 (2-pipe heating/cooling ceiling with dew point monitor) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the ALRE KTRBUu217.456 BACnet room controller - application 2KD001 (2-pipe heating/cooling ceiling with dew point monitor)

How many BACnet points does the ALRE KTRBUu217.456 BACnet room controller - application 2KD001 (2-pipe heating/cooling ceiling with dew point monitor) have?

This list has 35 BACnet objects: 1 analog input, 2 analog outputs, 12 analog values, 1 binary input, 1 binary output, 5 binary values, 2 files, 2 loops, 3 notification classs, 1 schedule, 4 multi-state values, 1 other. The exact set on a given unit depends on its firmware, installed options and configuration.

Which ALRE KTRBUu217.456 BACnet room controller - application 2KD001 (2-pipe heating/cooling ceiling with dew point monitor) BACnet points are writable?

22 of the 35 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official ALRE KTRBUu217.456 BACnet room controller - application 2KD001 (2-pipe heating/cooling ceiling with dew point monitor) BACnet documentation?

The source is EDE data KTRBUu (file 2KD001-EDE.csv), revision EDE timestamp 2019-10-21, published free by ALRE at https://alre.de/wp-content/uploads/2026/11/EDE_Daten_KTRBUu.zip.

What are the minimum BACnet points to integrate the ALRE KTRBUu217.456 BACnet room controller - application 2KD001 (2-pipe heating/cooling ceiling with dew point monitor)?

Start with MV 2 Operation Mode BMS (Protection, economy, pre-comfort or comfort); MV 4 Control-Mode BMS (Heating or cooling (change-over)); AV 15 Setpoint COMFORT Heating (Comfort heating setpoint); AV 25 Setpoint COMFORT Cooling (Comfort cooling setpoint); BV 2 Window State (Window open from the BMS, 1 = open); AV 30 Heartbeat Input (Rewrite seconds before it counts down to 0); MV 3 Active Operation Mode (Operation mode in force); AI 1 Temperature (Room temperature); AV 1 Active Setpoint (Setpoint in use); BI 1 Dew point sensor (Dew point alarm (1 = wet)).

How do I enable BMS control of the ALRE KTRBUu217.456 BACnet room controller - application 2KD001 (2-pipe heating/cooling ceiling with dew point monitor)?

Operation Mode BMS (MV 2) selects protection, economy, pre-comfort or comfort; the schedule object can also drive it. Fire Alarm (BV 6) puts the controller into its fire-alarm state.

Does the ALRE KTRBUu217.456 BACnet room controller - application 2KD001 (2-pipe heating/cooling ceiling with dew point monitor) need a BACnet heartbeat or have a communication timeout?

Heartbeat Input (AV 30): the BMS writes a number of seconds and the controller counts it down once per second. At 0 the controller goes to offline mode (local operation only); the BMS must write a new value before it reaches 0.

Can the BMS supply sensor values to the ALRE KTRBUu217.456 BACnet room controller - application 2KD001 (2-pipe heating/cooling ceiling with dew point monitor)?

Window State (BV 2) and Presence Detector (BV 3) are written by the BMS from its own window contacts and presence sensors; the controller reads window open from BV 2.

How do I check these points on the real KTRBUu217.456 BACnet room controller - application 2KD001 (2-pipe heating/cooling ceiling with dew point monitor)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More ALRE BACnet points lists

Source: EDE data KTRBUu (file 2KD001-EDE.csv) · rev. EDE timestamp 2019-10-21. Object names, instances and units are reproduced as published; descriptions are our own.