ait-deutschland Novelan heat pump controller GLT (BACnet IP) BACnet points list
Updated 12 November 2026Unofficial source
The GLT option turns on BACnet IP (or Modbus TCP) on the Ethernet port of the ait-deutschland heating and heat pump controller used in Novelan heat pumps. Every data point is an Analog Input, Multistate Input, Binary Input or Accumulator; the writable ones also appear as Analog Values or Multistate Values with their own instance numbers (outdoor temperature, return and mixing-circuit setpoints, DHW setpoint, heating curves, operating modes, compressor release) and Binary Outputs reset faults or force pumps on. The guide lists data point names in German.
This page lists 144 BACnet objects for the ait-deutschland Novelan heat pump controller GLT (BACnet IP) — 37 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of ait-deutschland’s documentation hosted by ioBroker forum, not by ait-deutschland itself, so treat it as unofficial.
- Manufacturer
- ait-deutschland
- Model
- Novelan heat pump controller GLT (BACnet IP)
- Equipment
- Heat pump controller
- Equipment type
- Heat pumps
- BACnet objects
- 144 (37 writable)
- Transport
- BACnet IP
- Firmware
- Controller software V1.60 or later (BACnet IP)
- Also known as
- Novelan GLT, GLT, Novelan GLT Tool, Novelan, 83055703hDE
- Source document
- Betriebsanleitung Zubehör für Wärmepumpen - Anbindung an eine Gebäudeleittechnik via BACnet/IP | ModBus/TCP - Novelan GLT · 83055703hDE (unofficial copy, hosted by ioBroker forum)
Reference only, provided as-is: verify against ait-deutschland’s current documentation and the live device before use. Not official ait-deutschland information. Terms of use.
BMS integration notes: ait-deutschland Novelan heat pump controller GLT (BACnet IP)
Release the heat pump with MV 1, set the heating and hot water modes (MV 2 / MV 3) and write setpoints such as the DHW setpoint (AV 6) or a mixing circuit flow setpoint. Read the operating state (MI 1), flow and return temperatures, and the two fault BIs; reset latching faults with BO 1.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 1 | Sperre / Freigabe Wärmepumpe | Lock heat pump (1) or release 1 / 2 compressors (2 / 3) | Write |
| MV 2 | Betriebsart Heizen | Heating mode (1 = Automatik, 5 = Aus) | Write |
| MV 3 | Betriebsart Trinkwarmwasser | Hot water mode (1 = Automatik, 5 = Aus) | Write |
| AV 6 | Trinkwarmwasser Wunschwert | Hot water setpoint, °C | Write |
| BO 1 | Fehlerreset | Fault reset (1 = reset) | Write |
| MI 1 | Betriebszustand | Operating state (heating, DHW, defrost, off ...) | Read |
| AI 1 | Vorlauftemperatur | Flow temperature | Read |
| AI 2 | Rücklauftemperatur | Return temperature | Read |
| BI 1 | Selbst zurücksetzende Störung | Self-resetting fault active | Read |
| BI 2 | Nicht selbst zurücksetzende Störung | Latching fault active | Read |
Enable & remote start
MV 1 (Sperre / Freigabe Wärmepumpe) locks the heat pump or releases one or two compressors; the operating modes for heating, DHW, mixing circuits, cooling, ventilation and pool are set with MV 2-10.
Sensors & values from the BMS
The outdoor temperature can be written to AV 1 (Außentemperatur); the guide says to disconnect the heat pump's own outdoor sensor when doing so.
Network setup
- BACnet IP on UDP 47808 over the controller's Ethernet port; IP settings via DHCP server, DHCP client or manual entry on the controller (Service > Systemsteuerung).
- Device name, device ID, model name and location are set with the Novelan GLT Tool; the device ID must be unique on the network.
- A wrong broadcast address stops the heat pump being found over BACnet IP.
Watch out for
- Software older than V1.74/V2.74/V3.76/V4.76 supports only BACnet IP, not Modbus TCP; switching between them needs the GLT Tool.
- BO 1 Fehlerreset returns to 0 by itself after a 1 is written.
ait-deutschland Novelan heat pump controller GLT (BACnet IP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Vorlauftemperatur | Flow temperature | °C | Read | |
| AImin | 2 | Rücklauftemperatur | Return temperature | °C | Read | |
| AI | 3 | Heissgastemperatur | Hot gas temperature | °C | Read | |
| AI | 4 | Wärmequelle Eintritt | Heat source inlet temperature | °C | Read | |
| AI | 5 | Wärmequelle Austritt | Heat source outlet temperature | °C | Read | |
| AI | 6 | Mischkreis 1 Vorlauf | Mixing circuit 1 flow temperature | °C | Read | |
| AI | 7 | Rücklauf extern | External return temperature | °C | Read | |
| AI | 8 | Raumfernversteller 1 | Remote room adjuster 1 | °C | Read | |
| AI | 9 | Mischkreis 2 Vorlauf | Mixing circuit 2 flow temperature | °C | Read | |
| AI | 10 | Raumfernversteller 2 | Remote room adjuster 2 | °C | Read | |
| AI | 11 | Mischkreis 3 Vorlauf | Mixing circuit 3 flow temperature | °C | Read | |
| AI | 12 | Raumfernversteller 3 | Remote room adjuster 3 | °C | Read | |
| AI | 13 | Solarkollektor | Solar collector temperature | °C | Read | |
| AI | 14 | Solarspeicher | Solar storage tank temperature | °C | Read | |
| AI | 15 | Externe Energiequelle | External energy source temperature | °C | Read | |
| AI | 16 | Außentemperatur | Outdoor temperature | °C | Read | |
| AI | 17 | Rücklauf Sollwert | Return temperature setpoint | °C | Read | |
| AI | 18 | Mischkreis 1 Sollwert Vorlauf | Mixing circuit 1 flow setpoint | °C | Read | |
| AI | 19 | Mischkreis 2 Sollwert Vorlauf | Mixing circuit 2 flow setpoint | °C | Read | |
| AI | 20 | Mischkreis 3 Sollwert Vorlauf | Mixing circuit 3 flow setpoint | °C | Read | |
| AI | 21 | Zulufttemperatur | Supply air temperature | °C | Read | |
| AI | 22 | Trinkwarmwasser Ist-Temperatur | Domestic hot water actual temperature | °C | Read | |
| AI | 23 | Trinkwarmwasser Wunschwert | Domestic hot water setpoint | °C | Read | |
| AI | 24 | Ansaugtemperatur Verdichter | Compressor suction temperature | °C | Read | |
| AI | 25 | Ansaugtemperatur Verdampfer | Evaporator suction temperature | °C | Read | |
| AI | 26 | Temperatur Verdichterheizung | Compressor heater temperature | °C | Read | |
| AI | 27 | Überhitzung | Superheat | K | Read | |
| AI | 28 | Überhitzung Soll | Superheat setpoint | K | Read | |
| AI | 29 | Druck HD (Hochdruck) | High pressure | bar | Read | |
| AI | 30 | Druck ND (Niederdruck) | Low pressure | bar | Read | |
| AI | 31 | RBE Raumtemperatur Ist | Room unit actual temperature | °C | Read | |
| AI | 32 | RBE Raumtemperatur Soll | Room unit temperature setpoint | °C | Read | |
| AI | 33 | Aktueller Durchfluss | Current flow rate | l/h | Read | |
| AI | 34 | Heizkurve Heizung Endpunkt | Heating curve end point | °C | Read | |
| AI | 35 | Heizkurve Heizung Parallelverschiebung | Heating curve parallel shift | °C | Read | |
| AI | 36 | Heizkurve Mischkreis 1 Endpunkt | Mixing circuit 1 curve end point | °C | Read | |
| AI | 37 | Heizkurve Mischkreis 1 Parallelverschiebung | Mixing circuit 1 curve parallel shift | °C | Read | |
| AI | 38 | Heizkurve Mischkreis 2 Endpunkt | Mixing circuit 2 curve end point | °C | Read | |
| AI | 39 | Heizkurve Mischkreis 2 Parallelverschiebung | Mixing circuit 2 curve parallel shift | °C | Read | |
| AI | 40 | Heizkurve Mischkreis 3 Endpunkt | Mixing circuit 3 curve end point | °C | Read | |
| AI | 41 | Heizkurve Mischkreis 3 Parallelverschiebung | Mixing circuit 3 curve parallel shift | °C | Read | |
| AI | 42 | Temperatur + – | Temperature +/- offset | °C | Read | |
| AI | 43 | Leistung Ist | Actual output | kW | Read | |
| AV | 1 | Außentemperatur | Outdoor temperature (write) | °C | Write | |
| AV | 2 | Rücklauf Sollwert | Return temperature setpoint (write) | °C | Write | |
| AV | 3 | Mischkreis 1 Sollwert Vorlauf | Mixing circuit 1 flow setpoint (write) | °C | Write | |
| AV | 4 | Mischkreis 2 Sollwert Vorlauf | Mixing circuit 2 flow setpoint (write) | °C | Write | |
| AV | 5 | Mischkreis 3 Sollwert Vorlauf | Mixing circuit 3 flow setpoint (write) | °C | Write | |
| AVmin | 6 | Trinkwarmwasser Wunschwert | Domestic hot water setpoint (write) | °C | Write | |
| AV | 7 | Heizkurve Heizung Endpunkt | Heating curve end point (write) | °C | Write | |
| AV | 8 | Heizkurve Heizung Parallelverschiebung | Heating curve parallel shift (write) | °C | Write | |
| AV | 9 | Heizkurve Mischkreis 1 Endpunkt | Mixing circuit 1 curve end point (write) | °C | Write | |
| AV | 10 | Heizkurve Mischkreis 1 Parallelverschiebung | Mixing circuit 1 curve parallel shift (write) | °C | Write | |
| AV | 11 | Heizkurve Mischkreis 2 Endpunkt | Mixing circuit 2 curve end point (write) | °C | Write | |
| AV | 12 | Heizkurve Mischkreis 2 Parallelverschiebung | Mixing circuit 2 curve parallel shift (write) | °C | Write | |
| AV | 13 | Heizkurve Mischkreis 3 Endpunkt | Mixing circuit 3 curve end point (write) | °C | Write | |
| AV | 14 | Heizkurve Mischkreis 3 Parallelverschiebung | Mixing circuit 3 curve parallel shift (write) | °C | Write | |
| AV | 15 | Temperatur + – | Temperature +/- offset (write) | °C | Write | |
| MImin | 1 | Betriebszustand | Operating state | Read | 1=Heizbetrieb, 2=Trinkwarmwasser, 3=Schwimmbad, 4=EVU-Sperre, 5=Abtauen, 6=Aus, 7=Externe Energiequelle, 8=Kühlung | |
| MI | 2 | Aus / mit Anzahl aktiver Verdichter | Off / number of compressors running | Read | 1=Aus, 2=1 Verdichter läuft, 3=2 Verdichter laufen | |
| MVmin | 1 | Sperre / Freigabe Wärmepumpe | Heat pump lock / compressors released (write) | Write | 1=Sperre Wärmepumpe, 2=Freigabe 1 Verdichter, 3=Freigabe 2 Verdichter | |
| MI | 3 | Betriebsart Heizen | Heating operating mode | Read | 1=Automatik, 2=Zusätzlicher Wärmeerzeuger, 3=Party, 4=Ferien, 5=Aus | |
| MVmin | 2 | Betriebsart Heizen | Heating operating mode (write) | Write | 1=Automatik, 2=Zusätzlicher Wärmeerzeuger, 3=Party, 4=Ferien, 5=Aus | |
| MI | 4 | Betriebsart Trinkwarmwasser | Domestic hot water operating mode | Read | 1=Automatik, 2=Zusätzlicher Wärmeerzeuger, 3=Party, 4=Ferien, 5=Aus | |
| MVmin | 3 | Betriebsart Trinkwarmwasser | Domestic hot water operating mode (write) | Write | 1=Automatik, 2=Zusätzlicher Wärmeerzeuger, 3=Party, 4=Ferien, 5=Aus | |
| MI | 6 | Betriebsart Mischkreis 2 | Mixing circuit 2 operating mode | Read | 1=Automatik, 2=Zusätzlicher Wärmeerzeuger, 3=Party, 4=Ferien, 5=Aus | |
| MV | 5 | Betriebsart Mischkreis 2 | Mixing circuit 2 operating mode (write) | Write | 1=Automatik, 2=Zusätzlicher Wärmeerzeuger, 3=Party, 4=Ferien, 5=Aus | |
| MI | 7 | Betriebsart Mischkreis 3 | Mixing circuit 3 operating mode | Read | 1=Automatik, 2=Zusätzlicher Wärmeerzeuger, 3=Party, 4=Ferien, 5=Aus | |
| MV | 6 | Betriebsart Mischkreis 3 | Mixing circuit 3 operating mode (write) | Write | 1=Automatik, 2=Zusätzlicher Wärmeerzeuger, 3=Party, 4=Ferien, 5=Aus | |
| MI | 8 | Betriebsart Kühlung | Cooling operating mode | Read | 1=Aus, 2=Automatik | |
| MV | 7 | Betriebsart Kühlung | Cooling operating mode (write) | Write | 1=Aus, 2=Automatik | |
| MI | 9 | Betriebsart Lüftung | Ventilation operating mode | Read | 1=Automatik, 2=Party, 3=Ferien, 4=Aus | |
| MV | 8 | Betriebsart Lüftung | Ventilation operating mode (write) | Write | 1=Automatik, 2=Party, 3=Ferien, 4=Aus | |
| MI | 10 | Betriebsart Schwimmbad | Pool operating mode | Read | 1=Automatik, 2=nicht benutzt, 3=Party, 4=Ferien, 5=Aus | |
| MV | 9 | Betriebsart Schwimmbad | Pool operating mode (write) | Write | 1=Automatik, 2=nicht benutzt, 3=Party, 4=Ferien, 5=Aus | |
| MI | 11 | Smart Grid | Smart Grid state | Read | 1=EVU-Sperre, 2=Smart Grid Low, 3=Standard, 4=Smart Grid High | |
| MV | 10 | Smart Grid | Smart Grid state (write) | Write | 1=EVU-Sperre, 2=Smart Grid Low, 3=Standard, 4=Smart Grid High | |
| BImin | 1 | Selbst zurücksetzende Störung | Self-resetting fault (fault number in Active_Text) | Read | 0=Inactive (no fault), 1=Active (self-resetting fault) | |
| BImin | 2 | Nicht selbst zurücksetzende Störung | Latching fault (fault number in Active_Text) | Read | 0=Inactive (no fault), 1=Active (fault) | |
| BI | 3 | HUP | Heating circulation pump | Read | 0=Aus, 1=An | |
| BI | 4 | VEN | Fan | Read | 0=Aus, 1=An | |
| BI | 5 | ZUP | Additional circulation pump | Read | 0=Aus, 1=An | |
| BI | 6 | BUP | DHW circulation pump | Read | 0=Aus, 1=An | |
| BI | 7 | Ventil_BOSUP | Fan / well or brine circulation pump | Read | 0=Aus, 1=An | |
| BI | 8 | ZIP | Recirculation pump | Read | 0=Aus, 1=An | |
| BI | 9 | FUP2 | Floor heating pump 2 | Read | 0=Aus, 1=An | |
| BI | 10 | FUP3 | Floor heating pump 3 | Read | 0=Aus, 1=An | |
| BI | 11 | SLP | Solar charging pump | Read | 0=Aus, 1=An | |
| BI | 12 | SUP | Pool circulation pump | Read | 0=Aus, 1=An | |
| BI | 13 | VSK | Bypass damper | Read | 0=Aus, 1=An | |
| BI | 14 | FRH | Defrost heater contactor | Read | 0=Aus, 1=An | |
| BI | 15 | Verdichter 1 | Compressor 1 | Read | 0=Aus, 1=An | |
| BI | 16 | Verdichter 2 | Compressor 2 | Read | 0=Aus, 1=An | |
| BI | 17 | ZWE1 | Additional heat generator 1 | Read | 0=Aus, 1=An | |
| BI | 18 | ZWE2_SST | Additional heat generator 2 / fault output | Read | 0=Aus, 1=An | |
| BI | 19 | ZWE3 | Additional heat generator 3 | Read | 0=Aus, 1=An | |
| BI | 20 | ASD | Defrost, brine pressure, flow input | Read | 0=Aus, 1=An | |
| BI | 21 | BWT | DHW thermostat input | Read | 0=Aus, 1=An | |
| BI | 22 | EVU | Utility lock-out input | Read | 0=Aus, 1=An | |
| BI | 23 | HD | High pressure switch | Read | 0=Aus, 1=An | |
| BI | 24 | MOT | Motor protection | Read | 0=Aus, 1=An | |
| BI | 25 | ND | Low pressure switch | Read | 0=Aus, 1=An | |
| BI | 26 | PEX | Impressed-current anode monitor | Read | 0=Aus, 1=An | |
| BI | 27 | SWT | Pool thermostat input | Read | 0=Aus, 1=An | |
| BI | 28 | SAX | Remote control: boost ventilation | Read | 0=Aus, 1=An | |
| BI | 29 | SPL | Ventilation shut-off contact | Read | 0=Aus, 1=An | |
| BI | 30 | EVU2 | Smart Grid input (with EVU) | Read | 0=Reduced mode (EVU=0) / EVU lock-out (EVU=1), 1=Normal mode (EVU=0) / raised mode (EVU=1) | |
| BOmin | 1 | Fehlerreset | Fault reset; returns to 0 after a 1 is sent | Write | 0=ohne Wirkung, 1=Reset auslösen | |
| BO | 3 | HUP | Heating circulation pump output override | Write | 0=Automatisch, 1=An | |
| BO | 4 | VEN | Fan output override | Write | 0=Automatisch, 1=An | |
| BO | 5 | ZUP | Additional circulation pump output override | Write | 0=Automatisch, 1=An | |
| BO | 6 | BUP | DHW circulation pump output override | Write | 0=Automatisch, 1=An | |
| BO | 7 | Ventil_BOSUP | Fan / well or brine circulation pump output override | Write | 0=Automatisch, 1=An | |
| BO | 8 | ZIP | Recirculation pump output override | Write | 0=Automatisch, 1=An | |
| BO | 9 | FUP2 | Floor heating pump 2 output override | Write | 0=Automatisch, 1=An | |
| BO | 10 | FUP3 | Floor heating pump 3 output override | Write | 0=Automatisch, 1=An | |
| BO | 11 | SLP | Solar charging pump output override | Write | 0=Automatisch, 1=An | |
| BO | 12 | SUP | Pool circulation pump output override | Write | 0=Automatisch, 1=An | |
| BO | 13 | VSK | Bypass damper output override | Write | 0=Automatisch, 1=An | |
| BO | 14 | FRH | Defrost heater contactor output override | Write | 0=Automatisch, 1=An | |
| ACC | 1 | Wärmemenge Heizung | Heat quantity, heating | kWh | Read | |
| ACC | 2 | Wärmemenge Trinkwarmwasser | Heat quantity, DHW | kWh | Read | |
| ACC | 3 | Wärmemenge Schwimmbad | Heat quantity, pool | kWh | Read | |
| ACC | 4 | Wärmemenge gesamt | Heat quantity, total | kWh | Read | |
| ACC | 5 | Betriebstund. VD1 | Compressor 1 run hours | h | Read | |
| ACC | 6 | Impulse Verdichter 1 | Compressor 1 starts | Read | ||
| ACC | 7 | Betriebstund. VD2 | Compressor 2 run hours | h | Read | |
| ACC | 8 | Impulse Verdichter 2 | Compressor 2 starts | Read | ||
| ACC | 9 | Betriebstunden ZWE1 | Additional heater 1 run hours | h | Read | |
| ACC | 10 | Betriebstunden ZWE2 | Additional heater 2 run hours | h | Read | |
| ACC | 11 | Betriebstunden ZWE3 | Additional heater 3 run hours | h | Read | |
| ACC | 12 | Betriebstunden WP | Heat pump run hours | h | Read | |
| ACC | 13 | Betriebstunden Heiz. | Heating run hours | h | Read | |
| ACC | 14 | Betriebstunden WW | DHW run hours | h | Read | |
| ACC | 15 | Betriebstunden Kuehl | Cooling run hours | h | Read | |
| ACC | 16 | Betriebstunden SWoPV | Pool or PV run hours | h | Read | |
| ACC | 17 | Betriebstunden Solar | Solar run hours | h | Read | |
| ACC | 18 | Fehlerspeicher | Current fault (fault memory) | Read | ||
| ACC | 19 | Wärmemenge Kühlung | Heat quantity, cooling | kWh | Read | |
| ACC | 20 | Eingesetzte Energie Heizung | Energy used, heating | kWh | Read | |
| ACC | 21 | Eingesetzte Energie Trinkwarmwasser | Energy used, DHW | kWh | Read | |
| ACC | 22 | Eingesetzte Energie Kühlung | Energy used, cooling | kWh | Read | |
| ACC | 23 | Eingesetzte Energie Schwimmbad | Energy used, pool | kWh | Read | |
| ACC | 24 | Eingesetzte Energie gesamt | Energy used, total | kWh | Read |
No points match these filters.
Object ID lookup: ait-deutschland Novelan heat pump controller GLT point IDs by name
AI1VorlauftemperaturAI2RücklauftemperaturAI3HeissgastemperaturAI4Wärmequelle EintrittAI5Wärmequelle AustrittAI6Mischkreis 1 VorlaufAI7Rücklauf externAI8Raumfernversteller 1AI9Mischkreis 2 VorlaufAI10Raumfernversteller 2AI11Mischkreis 3 VorlaufAI12Raumfernversteller 3AI13SolarkollektorAI14SolarspeicherAI15Externe EnergiequelleAI16AußentemperaturAI17Rücklauf SollwertAI18Mischkreis 1 Sollwert VorlaufAI19Mischkreis 2 Sollwert VorlaufAI20Mischkreis 3 Sollwert VorlaufAI21ZulufttemperaturAI22Trinkwarmwasser Ist-TemperaturAI23Trinkwarmwasser WunschwertAI24Ansaugtemperatur VerdichterAI25Ansaugtemperatur VerdampferAI26Temperatur VerdichterheizungAI27ÜberhitzungAI28Überhitzung SollAI29Druck HD (Hochdruck)AI30Druck ND (Niederdruck)AI31RBE Raumtemperatur IstAI32RBE Raumtemperatur SollAI33Aktueller DurchflussAI34Heizkurve Heizung EndpunktAI35Heizkurve Heizung ParallelverschiebungAI36Heizkurve Mischkreis 1 EndpunktAI37Heizkurve Mischkreis 1 ParallelverschiebungAI38Heizkurve Mischkreis 2 EndpunktAI39Heizkurve Mischkreis 2 ParallelverschiebungAI40Heizkurve Mischkreis 3 EndpunktAI41Heizkurve Mischkreis 3 ParallelverschiebungAI42Temperatur + –AI43Leistung IstAV1AußentemperaturAV2Rücklauf SollwertAV3Mischkreis 1 Sollwert VorlaufAV4Mischkreis 2 Sollwert VorlaufAV5Mischkreis 3 Sollwert VorlaufAV6Trinkwarmwasser WunschwertAV7Heizkurve Heizung EndpunktAV8Heizkurve Heizung ParallelverschiebungAV9Heizkurve Mischkreis 1 EndpunktAV10Heizkurve Mischkreis 1 ParallelverschiebungAV11Heizkurve Mischkreis 2 EndpunktAV12Heizkurve Mischkreis 2 ParallelverschiebungAV13Heizkurve Mischkreis 3 EndpunktAV14Heizkurve Mischkreis 3 ParallelverschiebungAV15Temperatur + –MI1BetriebszustandMI2Aus / mit Anzahl aktiver VerdichterMV1Sperre / Freigabe WärmepumpeMI3Betriebsart HeizenMV2Betriebsart HeizenMI4Betriebsart TrinkwarmwasserMV3Betriebsart TrinkwarmwasserMI6Betriebsart Mischkreis 2MV5Betriebsart Mischkreis 2MI7Betriebsart Mischkreis 3MV6Betriebsart Mischkreis 3MI8Betriebsart KühlungMV7Betriebsart KühlungMI9Betriebsart LüftungMV8Betriebsart LüftungMI10Betriebsart SchwimmbadMV9Betriebsart SchwimmbadMI11Smart GridMV10Smart GridBI1Selbst zurücksetzende StörungBI2Nicht selbst zurücksetzende StörungBI3HUPBI4VENBI5ZUPBI6BUPBI7Ventil_BOSUPBI8ZIPBI9FUP2BI10FUP3BI11SLPBI12SUPBI13VSKBI14FRHBI15Verdichter 1BI16Verdichter 2BI17ZWE1BI18ZWE2_SSTBI19ZWE3BI20ASDBI21BWTBI22EVUBI23HDBI24MOTBI25NDBI26PEXBI27SWTBI28SAXBI29SPLBI30EVU2BO1FehlerresetBO3HUPBO4VENBO5ZUPBO6BUPBO7Ventil_BOSUPBO8ZIPBO9FUP2BO10FUP3BO11SLPBO12SUPBO13VSKBO14FRHACC1Wärmemenge HeizungACC2Wärmemenge TrinkwarmwasserACC3Wärmemenge SchwimmbadACC4Wärmemenge gesamtACC5Betriebstund. VD1ACC6Impulse Verdichter 1ACC7Betriebstund. VD2ACC8Impulse Verdichter 2ACC9Betriebstunden ZWE1ACC10Betriebstunden ZWE2ACC11Betriebstunden ZWE3ACC12Betriebstunden WPACC13Betriebstunden Heiz.ACC14Betriebstunden WWACC15Betriebstunden KuehlACC16Betriebstunden SWoPVACC17Betriebstunden SolarACC18FehlerspeicherACC19Wärmemenge KühlungACC20Eingesetzte Energie HeizungACC21Eingesetzte Energie TrinkwarmwasserACC22Eingesetzte Energie KühlungACC23Eingesetzte Energie SchwimmbadACC24Eingesetzte Energie gesamt
Integration notes
- The guide gives one table per object type with an Analog Input / Analog Value (or Multistate Input / Value) instance pair per row; AV and MV objects are the writable copies.
- Names are the guide's German data point labels; descriptions are ours in English. Abbreviations follow the guide's list (HUP heating pump, BUP DHW pump, ZWE additional heat generator, EVU utility lock-out).
- Points shaded in the guide need a comfort / expansion or ventilation board; points marked * apply to units with LIN or Modbus parts. Values not shown on the controller's display are invalid.
- There is no MI 5 / MV 4 or BO 2 in the guide.
- Resolution is 0.1 for temperatures, 0.01 for pressures and power.
- GLT runs for 4 hours as a test after setup with the Novelan GLT Tool and is enabled permanently with a licence from the supplied USB dongle.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Novelan heat pump controller GLT (BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the ait-deutschland Novelan heat pump controller GLT (BACnet IP)
How many BACnet points does the ait-deutschland Novelan heat pump controller GLT (BACnet IP) have?
This list has 144 BACnet objects: 43 analog inputs, 15 analog values, 30 binary inputs, 13 binary outputs, 10 multi-state inputs, 9 multi-state values, 24 accumulators. The exact set on a given unit depends on its firmware, installed options and configuration.
Which ait-deutschland Novelan heat pump controller GLT (BACnet IP) BACnet points are writable?
37 of the 144 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official ait-deutschland Novelan heat pump controller GLT (BACnet IP) BACnet documentation?
ait-deutschland does not publish it on its own website. This list comes from Betriebsanleitung Zubehör für Wärmepumpen - Anbindung an eine Gebäudeleittechnik via BACnet/IP | ModBus/TCP - Novelan GLT (83055703hDE), a copy hosted by ioBroker forum at https://forum.iobroker.net/assets/uploads/files/1732701258966-83055703hde_novelan_glt.pdf. Ask ait-deutschland or its representative for the current revision.
What are the minimum BACnet points to integrate the ait-deutschland Novelan heat pump controller GLT (BACnet IP)?
Start with MV 1 Sperre / Freigabe Wärmepumpe (Lock heat pump (1) or release 1 / 2 compressors (2 / 3)); MV 2 Betriebsart Heizen (Heating mode (1 = Automatik, 5 = Aus)); MV 3 Betriebsart Trinkwarmwasser (Hot water mode (1 = Automatik, 5 = Aus)); AV 6 Trinkwarmwasser Wunschwert (Hot water setpoint, °C); BO 1 Fehlerreset (Fault reset (1 = reset)); MI 1 Betriebszustand (Operating state (heating, DHW, defrost, off ...)); AI 1 Vorlauftemperatur (Flow temperature); AI 2 Rücklauftemperatur (Return temperature); BI 1 Selbst zurücksetzende Störung (Self-resetting fault active); BI 2 Nicht selbst zurücksetzende Störung (Latching fault active).
How do I enable BMS control of the ait-deutschland Novelan heat pump controller GLT (BACnet IP)?
MV 1 (Sperre / Freigabe Wärmepumpe) locks the heat pump or releases one or two compressors; the operating modes for heating, DHW, mixing circuits, cooling, ventilation and pool are set with MV 2-10.
Can the BMS supply sensor values to the ait-deutschland Novelan heat pump controller GLT (BACnet IP)?
The outdoor temperature can be written to AV 1 (Außentemperatur); the guide says to disconnect the heat pump's own outdoor sensor when doing so.
How do I check these points on the real Novelan heat pump controller GLT (BACnet IP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
Source: Betriebsanleitung Zubehör für Wärmepumpen - Anbindung an eine Gebäudeleittechnik via BACnet/IP | ModBus/TCP - Novelan GLT · 83055703hDE. Object names, instances and units are reproduced as published; descriptions are our own.