Heat pump controller · BACnet points list

ait-deutschland Novelan heat pump controller GLT (BACnet IP) BACnet points list

Updated 12 November 2026Unofficial source

Short answer

The GLT option turns on BACnet IP (or Modbus TCP) on the Ethernet port of the ait-deutschland heating and heat pump controller used in Novelan heat pumps. Every data point is an Analog Input, Multistate Input, Binary Input or Accumulator; the writable ones also appear as Analog Values or Multistate Values with their own instance numbers (outdoor temperature, return and mixing-circuit setpoints, DHW setpoint, heating curves, operating modes, compressor release) and Binary Outputs reset faults or force pumps on. The guide lists data point names in German.

This page lists 144 BACnet objects for the ait-deutschland Novelan heat pump controller GLT (BACnet IP) — 37 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of ait-deutschland’s documentation hosted by ioBroker forum, not by ait-deutschland itself, so treat it as unofficial.

Manufacturer
ait-deutschland
Model
Novelan heat pump controller GLT (BACnet IP)
Equipment
Heat pump controller
Equipment type
Heat pumps
BACnet objects
144 (37 writable)
Transport
BACnet IP
Firmware
Controller software V1.60 or later (BACnet IP)
Also known as
Novelan GLT, GLT, Novelan GLT Tool, Novelan, 83055703hDE
Source document
Betriebsanleitung Zubehör für Wärmepumpen - Anbindung an eine Gebäudeleittechnik via BACnet/IP | ModBus/TCP - Novelan GLT · 83055703hDE (unofficial copy, hosted by ioBroker forum)
Download CSV 144 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against ait-deutschland’s current documentation and the live device before use. Not official ait-deutschland information. Terms of use.

BMS integration notes: ait-deutschland Novelan heat pump controller GLT (BACnet IP)

Integration in brief

Release the heat pump with MV 1, set the heating and hot water modes (MV 2 / MV 3) and write setpoints such as the DHW setpoint (AV 6) or a mixing circuit flow setpoint. Read the operating state (MI 1), flow and return temperatures, and the two fault BIs; reset latching faults with BO 1.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1Sperre / Freigabe WärmepumpeLock heat pump (1) or release 1 / 2 compressors (2 / 3)Write
MV 2Betriebsart HeizenHeating mode (1 = Automatik, 5 = Aus)Write
MV 3Betriebsart TrinkwarmwasserHot water mode (1 = Automatik, 5 = Aus)Write
AV 6Trinkwarmwasser WunschwertHot water setpoint, °CWrite
BO 1FehlerresetFault reset (1 = reset)Write
MI 1BetriebszustandOperating state (heating, DHW, defrost, off ...)Read
AI 1VorlauftemperaturFlow temperatureRead
AI 2RücklauftemperaturReturn temperatureRead
BI 1Selbst zurücksetzende StörungSelf-resetting fault activeRead
BI 2Nicht selbst zurücksetzende StörungLatching fault activeRead

Enable & remote start

MV 1 (Sperre / Freigabe Wärmepumpe) locks the heat pump or releases one or two compressors; the operating modes for heating, DHW, mixing circuits, cooling, ventilation and pool are set with MV 2-10.

Sensors & values from the BMS

The outdoor temperature can be written to AV 1 (Außentemperatur); the guide says to disconnect the heat pump's own outdoor sensor when doing so.

Network setup

Watch out for

ait-deutschland Novelan heat pump controller GLT (BACnet IP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

144 of 144 shown
Type
Other
Access
Show
ait-deutschland Novelan heat pump controller GLT (BACnet IP) BACnet Points List
DescriptionStates
AImin1VorlauftemperaturFlow temperature°CRead
AImin2RücklauftemperaturReturn temperature°CRead
AI3HeissgastemperaturHot gas temperature°CRead
AI4Wärmequelle EintrittHeat source inlet temperature°CRead
AI5Wärmequelle AustrittHeat source outlet temperature°CRead
AI6Mischkreis 1 VorlaufMixing circuit 1 flow temperature°CRead
AI7Rücklauf externExternal return temperature°CRead
AI8Raumfernversteller 1Remote room adjuster 1°CRead
AI9Mischkreis 2 VorlaufMixing circuit 2 flow temperature°CRead
AI10Raumfernversteller 2Remote room adjuster 2°CRead
AI11Mischkreis 3 VorlaufMixing circuit 3 flow temperature°CRead
AI12Raumfernversteller 3Remote room adjuster 3°CRead
AI13SolarkollektorSolar collector temperature°CRead
AI14SolarspeicherSolar storage tank temperature°CRead
AI15Externe EnergiequelleExternal energy source temperature°CRead
AI16AußentemperaturOutdoor temperature°CRead
AI17Rücklauf SollwertReturn temperature setpoint°CRead
AI18Mischkreis 1 Sollwert VorlaufMixing circuit 1 flow setpoint°CRead
AI19Mischkreis 2 Sollwert VorlaufMixing circuit 2 flow setpoint°CRead
AI20Mischkreis 3 Sollwert VorlaufMixing circuit 3 flow setpoint°CRead
AI21ZulufttemperaturSupply air temperature°CRead
AI22Trinkwarmwasser Ist-TemperaturDomestic hot water actual temperature°CRead
AI23Trinkwarmwasser WunschwertDomestic hot water setpoint°CRead
AI24Ansaugtemperatur VerdichterCompressor suction temperature°CRead
AI25Ansaugtemperatur VerdampferEvaporator suction temperature°CRead
AI26Temperatur VerdichterheizungCompressor heater temperature°CRead
AI27ÜberhitzungSuperheatKRead
AI28Überhitzung SollSuperheat setpointKRead
AI29Druck HD (Hochdruck)High pressurebarRead
AI30Druck ND (Niederdruck)Low pressurebarRead
AI31RBE Raumtemperatur IstRoom unit actual temperature°CRead
AI32RBE Raumtemperatur SollRoom unit temperature setpoint°CRead
AI33Aktueller DurchflussCurrent flow ratel/hRead
AI34Heizkurve Heizung EndpunktHeating curve end point°CRead
AI35Heizkurve Heizung ParallelverschiebungHeating curve parallel shift°CRead
AI36Heizkurve Mischkreis 1 EndpunktMixing circuit 1 curve end point°CRead
AI37Heizkurve Mischkreis 1 ParallelverschiebungMixing circuit 1 curve parallel shift°CRead
AI38Heizkurve Mischkreis 2 EndpunktMixing circuit 2 curve end point°CRead
AI39Heizkurve Mischkreis 2 ParallelverschiebungMixing circuit 2 curve parallel shift°CRead
AI40Heizkurve Mischkreis 3 EndpunktMixing circuit 3 curve end point°CRead
AI41Heizkurve Mischkreis 3 ParallelverschiebungMixing circuit 3 curve parallel shift°CRead
AI42Temperatur + –Temperature +/- offset°CRead
AI43Leistung IstActual outputkWRead
AV1AußentemperaturOutdoor temperature (write)°CWrite
AV2Rücklauf SollwertReturn temperature setpoint (write)°CWrite
AV3Mischkreis 1 Sollwert VorlaufMixing circuit 1 flow setpoint (write)°CWrite
AV4Mischkreis 2 Sollwert VorlaufMixing circuit 2 flow setpoint (write)°CWrite
AV5Mischkreis 3 Sollwert VorlaufMixing circuit 3 flow setpoint (write)°CWrite
AVmin6Trinkwarmwasser WunschwertDomestic hot water setpoint (write)°CWrite
AV7Heizkurve Heizung EndpunktHeating curve end point (write)°CWrite
AV8Heizkurve Heizung ParallelverschiebungHeating curve parallel shift (write)°CWrite
AV9Heizkurve Mischkreis 1 EndpunktMixing circuit 1 curve end point (write)°CWrite
AV10Heizkurve Mischkreis 1 ParallelverschiebungMixing circuit 1 curve parallel shift (write)°CWrite
AV11Heizkurve Mischkreis 2 EndpunktMixing circuit 2 curve end point (write)°CWrite
AV12Heizkurve Mischkreis 2 ParallelverschiebungMixing circuit 2 curve parallel shift (write)°CWrite
AV13Heizkurve Mischkreis 3 EndpunktMixing circuit 3 curve end point (write)°CWrite
AV14Heizkurve Mischkreis 3 ParallelverschiebungMixing circuit 3 curve parallel shift (write)°CWrite
AV15Temperatur + –Temperature +/- offset (write)°CWrite
MImin1BetriebszustandOperating stateRead1=Heizbetrieb, 2=Trinkwarmwasser, 3=Schwimmbad, 4=EVU-Sperre, 5=Abtauen, 6=Aus, 7=Externe Energiequelle, 8=Kühlung
MI2Aus / mit Anzahl aktiver VerdichterOff / number of compressors runningRead1=Aus, 2=1 Verdichter läuft, 3=2 Verdichter laufen
MVmin1Sperre / Freigabe WärmepumpeHeat pump lock / compressors released (write)Write1=Sperre Wärmepumpe, 2=Freigabe 1 Verdichter, 3=Freigabe 2 Verdichter
MI3Betriebsart HeizenHeating operating modeRead1=Automatik, 2=Zusätzlicher Wärmeerzeuger, 3=Party, 4=Ferien, 5=Aus
MVmin2Betriebsart HeizenHeating operating mode (write)Write1=Automatik, 2=Zusätzlicher Wärmeerzeuger, 3=Party, 4=Ferien, 5=Aus
MI4Betriebsart TrinkwarmwasserDomestic hot water operating modeRead1=Automatik, 2=Zusätzlicher Wärmeerzeuger, 3=Party, 4=Ferien, 5=Aus
MVmin3Betriebsart TrinkwarmwasserDomestic hot water operating mode (write)Write1=Automatik, 2=Zusätzlicher Wärmeerzeuger, 3=Party, 4=Ferien, 5=Aus
MI6Betriebsart Mischkreis 2Mixing circuit 2 operating modeRead1=Automatik, 2=Zusätzlicher Wärmeerzeuger, 3=Party, 4=Ferien, 5=Aus
MV5Betriebsart Mischkreis 2Mixing circuit 2 operating mode (write)Write1=Automatik, 2=Zusätzlicher Wärmeerzeuger, 3=Party, 4=Ferien, 5=Aus
MI7Betriebsart Mischkreis 3Mixing circuit 3 operating modeRead1=Automatik, 2=Zusätzlicher Wärmeerzeuger, 3=Party, 4=Ferien, 5=Aus
MV6Betriebsart Mischkreis 3Mixing circuit 3 operating mode (write)Write1=Automatik, 2=Zusätzlicher Wärmeerzeuger, 3=Party, 4=Ferien, 5=Aus
MI8Betriebsart KühlungCooling operating modeRead1=Aus, 2=Automatik
MV7Betriebsart KühlungCooling operating mode (write)Write1=Aus, 2=Automatik
MI9Betriebsart LüftungVentilation operating modeRead1=Automatik, 2=Party, 3=Ferien, 4=Aus
MV8Betriebsart LüftungVentilation operating mode (write)Write1=Automatik, 2=Party, 3=Ferien, 4=Aus
MI10Betriebsart SchwimmbadPool operating modeRead1=Automatik, 2=nicht benutzt, 3=Party, 4=Ferien, 5=Aus
MV9Betriebsart SchwimmbadPool operating mode (write)Write1=Automatik, 2=nicht benutzt, 3=Party, 4=Ferien, 5=Aus
MI11Smart GridSmart Grid stateRead1=EVU-Sperre, 2=Smart Grid Low, 3=Standard, 4=Smart Grid High
MV10Smart GridSmart Grid state (write)Write1=EVU-Sperre, 2=Smart Grid Low, 3=Standard, 4=Smart Grid High
BImin1Selbst zurücksetzende StörungSelf-resetting fault (fault number in Active_Text)Read0=Inactive (no fault), 1=Active (self-resetting fault)
BImin2Nicht selbst zurücksetzende StörungLatching fault (fault number in Active_Text)Read0=Inactive (no fault), 1=Active (fault)
BI3HUPHeating circulation pumpRead0=Aus, 1=An
BI4VENFanRead0=Aus, 1=An
BI5ZUPAdditional circulation pumpRead0=Aus, 1=An
BI6BUPDHW circulation pumpRead0=Aus, 1=An
BI7Ventil_BOSUPFan / well or brine circulation pumpRead0=Aus, 1=An
BI8ZIPRecirculation pumpRead0=Aus, 1=An
BI9FUP2Floor heating pump 2Read0=Aus, 1=An
BI10FUP3Floor heating pump 3Read0=Aus, 1=An
BI11SLPSolar charging pumpRead0=Aus, 1=An
BI12SUPPool circulation pumpRead0=Aus, 1=An
BI13VSKBypass damperRead0=Aus, 1=An
BI14FRHDefrost heater contactorRead0=Aus, 1=An
BI15Verdichter 1Compressor 1Read0=Aus, 1=An
BI16Verdichter 2Compressor 2Read0=Aus, 1=An
BI17ZWE1Additional heat generator 1Read0=Aus, 1=An
BI18ZWE2_SSTAdditional heat generator 2 / fault outputRead0=Aus, 1=An
BI19ZWE3Additional heat generator 3Read0=Aus, 1=An
BI20ASDDefrost, brine pressure, flow inputRead0=Aus, 1=An
BI21BWTDHW thermostat inputRead0=Aus, 1=An
BI22EVUUtility lock-out inputRead0=Aus, 1=An
BI23HDHigh pressure switchRead0=Aus, 1=An
BI24MOTMotor protectionRead0=Aus, 1=An
BI25NDLow pressure switchRead0=Aus, 1=An
BI26PEXImpressed-current anode monitorRead0=Aus, 1=An
BI27SWTPool thermostat inputRead0=Aus, 1=An
BI28SAXRemote control: boost ventilationRead0=Aus, 1=An
BI29SPLVentilation shut-off contactRead0=Aus, 1=An
BI30EVU2Smart Grid input (with EVU)Read0=Reduced mode (EVU=0) / EVU lock-out (EVU=1), 1=Normal mode (EVU=0) / raised mode (EVU=1)
BOmin1FehlerresetFault reset; returns to 0 after a 1 is sentWrite0=ohne Wirkung, 1=Reset auslösen
BO3HUPHeating circulation pump output overrideWrite0=Automatisch, 1=An
BO4VENFan output overrideWrite0=Automatisch, 1=An
BO5ZUPAdditional circulation pump output overrideWrite0=Automatisch, 1=An
BO6BUPDHW circulation pump output overrideWrite0=Automatisch, 1=An
BO7Ventil_BOSUPFan / well or brine circulation pump output overrideWrite0=Automatisch, 1=An
BO8ZIPRecirculation pump output overrideWrite0=Automatisch, 1=An
BO9FUP2Floor heating pump 2 output overrideWrite0=Automatisch, 1=An
BO10FUP3Floor heating pump 3 output overrideWrite0=Automatisch, 1=An
BO11SLPSolar charging pump output overrideWrite0=Automatisch, 1=An
BO12SUPPool circulation pump output overrideWrite0=Automatisch, 1=An
BO13VSKBypass damper output overrideWrite0=Automatisch, 1=An
BO14FRHDefrost heater contactor output overrideWrite0=Automatisch, 1=An
ACC1Wärmemenge HeizungHeat quantity, heatingkWhRead
ACC2Wärmemenge TrinkwarmwasserHeat quantity, DHWkWhRead
ACC3Wärmemenge SchwimmbadHeat quantity, poolkWhRead
ACC4Wärmemenge gesamtHeat quantity, totalkWhRead
ACC5Betriebstund. VD1Compressor 1 run hourshRead
ACC6Impulse Verdichter 1Compressor 1 startsRead
ACC7Betriebstund. VD2Compressor 2 run hourshRead
ACC8Impulse Verdichter 2Compressor 2 startsRead
ACC9Betriebstunden ZWE1Additional heater 1 run hourshRead
ACC10Betriebstunden ZWE2Additional heater 2 run hourshRead
ACC11Betriebstunden ZWE3Additional heater 3 run hourshRead
ACC12Betriebstunden WPHeat pump run hourshRead
ACC13Betriebstunden Heiz.Heating run hourshRead
ACC14Betriebstunden WWDHW run hourshRead
ACC15Betriebstunden KuehlCooling run hourshRead
ACC16Betriebstunden SWoPVPool or PV run hourshRead
ACC17Betriebstunden SolarSolar run hourshRead
ACC18FehlerspeicherCurrent fault (fault memory)Read
ACC19Wärmemenge KühlungHeat quantity, coolingkWhRead
ACC20Eingesetzte Energie HeizungEnergy used, heatingkWhRead
ACC21Eingesetzte Energie TrinkwarmwasserEnergy used, DHWkWhRead
ACC22Eingesetzte Energie KühlungEnergy used, coolingkWhRead
ACC23Eingesetzte Energie SchwimmbadEnergy used, poolkWhRead
ACC24Eingesetzte Energie gesamtEnergy used, totalkWhRead
Object ID lookup: ait-deutschland Novelan heat pump controller GLT point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Novelan heat pump controller GLT (BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the ait-deutschland Novelan heat pump controller GLT (BACnet IP)

How many BACnet points does the ait-deutschland Novelan heat pump controller GLT (BACnet IP) have?

This list has 144 BACnet objects: 43 analog inputs, 15 analog values, 30 binary inputs, 13 binary outputs, 10 multi-state inputs, 9 multi-state values, 24 accumulators. The exact set on a given unit depends on its firmware, installed options and configuration.

Which ait-deutschland Novelan heat pump controller GLT (BACnet IP) BACnet points are writable?

37 of the 144 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official ait-deutschland Novelan heat pump controller GLT (BACnet IP) BACnet documentation?

ait-deutschland does not publish it on its own website. This list comes from Betriebsanleitung Zubehör für Wärmepumpen - Anbindung an eine Gebäudeleittechnik via BACnet/IP | ModBus/TCP - Novelan GLT (83055703hDE), a copy hosted by ioBroker forum at https://forum.iobroker.net/assets/uploads/files/1732701258966-83055703hde_novelan_glt.pdf. Ask ait-deutschland or its representative for the current revision.

What are the minimum BACnet points to integrate the ait-deutschland Novelan heat pump controller GLT (BACnet IP)?

Start with MV 1 Sperre / Freigabe Wärmepumpe (Lock heat pump (1) or release 1 / 2 compressors (2 / 3)); MV 2 Betriebsart Heizen (Heating mode (1 = Automatik, 5 = Aus)); MV 3 Betriebsart Trinkwarmwasser (Hot water mode (1 = Automatik, 5 = Aus)); AV 6 Trinkwarmwasser Wunschwert (Hot water setpoint, °C); BO 1 Fehlerreset (Fault reset (1 = reset)); MI 1 Betriebszustand (Operating state (heating, DHW, defrost, off ...)); AI 1 Vorlauftemperatur (Flow temperature); AI 2 Rücklauftemperatur (Return temperature); BI 1 Selbst zurücksetzende Störung (Self-resetting fault active); BI 2 Nicht selbst zurücksetzende Störung (Latching fault active).

How do I enable BMS control of the ait-deutschland Novelan heat pump controller GLT (BACnet IP)?

MV 1 (Sperre / Freigabe Wärmepumpe) locks the heat pump or releases one or two compressors; the operating modes for heating, DHW, mixing circuits, cooling, ventilation and pool are set with MV 2-10.

Can the BMS supply sensor values to the ait-deutschland Novelan heat pump controller GLT (BACnet IP)?

The outdoor temperature can be written to AV 1 (Außentemperatur); the guide says to disconnect the heat pump's own outdoor sensor when doing so.

How do I check these points on the real Novelan heat pump controller GLT (BACnet IP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: Betriebsanleitung Zubehör für Wärmepumpen - Anbindung an eine Gebäudeleittechnik via BACnet/IP | ModBus/TCP - Novelan GLT · 83055703hDE. Object names, instances and units are reproduced as published; descriptions are our own.