 "manufacturer": "ait-deutschland",
 "manufacturer_slug": "ait-deutschland",
 "model": "Novelan heat pump controller GLT (BACnet IP)",
 "model_slug": "novelan-glt-heat-pump-controller-bacnet-ip",
 "aliases": [
  "Novelan GLT",
  "GLT",
  "Novelan GLT Tool",
  "Novelan",
  "83055703hDE"
 ],
 "equipment_type": "Heat pump controller",
 "applies_to": "Novelan heat pumps made by ait-deutschland whose heating and heat pump controller runs software V1.60 or later with the GLT licence enabled.",
 "summary": "The GLT option turns on BACnet IP (or Modbus TCP) on the Ethernet port of the ait-deutschland heating and heat pump controller used in Novelan heat pumps. Every data point is an Analog Input, Multistate Input, Binary Input or Accumulator; the writable ones also appear as Analog Values or Multistate Values with their own instance numbers (outdoor temperature, return and mixing-circuit setpoints, DHW setpoint, heating curves, operating modes, compressor release) and Binary Outputs reset faults or force pumps on. The guide lists data point names in German.",
 "bacnet_transport": [
  "BACnet IP"
 ],
 "firmware": "Controller software V1.60 or later (BACnet IP)",
 "default_device_instance": null,
 "access_inferred": true,
 "notes": [
  "The guide gives one table per object type with an Analog Input / Analog Value (or Multistate Input / Value) instance pair per row; AV and MV objects are the writable copies.",
  "Names are the guide's German data point labels; descriptions are ours in English. Abbreviations follow the guide's list (HUP heating pump, BUP DHW pump, ZWE additional heat generator, EVU utility lock-out).",
  "Points shaded in the guide need a comfort / expansion or ventilation board; points marked * apply to units with LIN or Modbus parts. Values not shown on the controller's display are invalid.",
  "There is no MI 5 / MV 4 or BO 2 in the guide.",
  "Resolution is 0.1 for temperatures, 0.01 for pressures and power.",
  "GLT runs for 4 hours as a test after setup with the Novelan GLT Tool and is enabled permanently with a licence from the supplied USB dongle."
 ],
 "source": {
  "title": "Betriebsanleitung Zubehör für Wärmepumpen - Anbindung an eine Gebäudeleittechnik via BACnet/IP | ModBus/TCP - Novelan GLT",
  "doc_number": "83055703hDE",
  "revision_date": null,
  "url": "https://forum.iobroker.net/assets/uploads/files/1732701258966-83055703hde_novelan_glt.pdf",
  "unofficial": true,
  "host": "ioBroker forum"
 },
 "integration": {
  "summary": "Release the heat pump with MV 1, set the heating and hot water modes (MV 2 / MV 3) and write setpoints such as the DHW setpoint (AV 6) or a mixing circuit flow setpoint. Read the operating state (MI 1), flow and return temperatures, and the two fault BIs; reset latching faults with BO 1.",
  "minimum_points": [
   {
    "ref": "MV 1",
    "name": "Sperre / Freigabe Wärmepumpe",
    "why": "Lock heat pump (1) or release 1 / 2 compressors (2 / 3)"
   },
   {
    "ref": "MV 2",
    "name": "Betriebsart Heizen",
    "why": "Heating mode (1 = Automatik, 5 = Aus)"
   },
   {
    "ref": "MV 3",
    "name": "Betriebsart Trinkwarmwasser",
    "why": "Hot water mode (1 = Automatik, 5 = Aus)"
   },
   {
    "ref": "AV 6",
    "name": "Trinkwarmwasser Wunschwert",
    "why": "Hot water setpoint, °C"
   },
   {
    "ref": "BO 1",
    "name": "Fehlerreset",
    "why": "Fault reset (1 = reset)"
   },
   {
    "ref": "MI 1",
    "name": "Betriebszustand",
    "why": "Operating state (heating, DHW, defrost, off ...)"
   },
   {
    "ref": "AI 1",
    "name": "Vorlauftemperatur",
    "why": "Flow temperature"
   },
   {
    "ref": "AI 2",
    "name": "Rücklauftemperatur",
    "why": "Return temperature"
   },
   {
    "ref": "BI 1",
    "name": "Selbst zurücksetzende Störung",
    "why": "Self-resetting fault active"
   },
   {
    "ref": "BI 2",
    "name": "Nicht selbst zurücksetzende Störung",
    "why": "Latching fault active"
   }
  ],
  "enable": "MV 1 (Sperre / Freigabe Wärmepumpe) locks the heat pump or releases one or two compressors; the operating modes for heating, DHW, mixing circuits, cooling, ventilation and pool are set with MV 2-10.",
  "heartbeat": null,
  "remote_sensors": "The outdoor temperature can be written to AV 1 (Außentemperatur); the guide says to disconnect the heat pump's own outdoor sensor when doing so.",
  "setup": [
   "BACnet IP on UDP 47808 over the controller's Ethernet port; IP settings via DHCP server, DHCP client or manual entry on the controller (Service > Systemsteuerung).",
   "Device name, device ID, model name and location are set with the Novelan GLT Tool; the device ID must be unique on the network.",
   "A wrong broadcast address stops the heat pump being found over BACnet IP."
  ],
  "gotchas": [
   "Software older than V1.74/V2.74/V3.76/V4.76 supports only BACnet IP, not Modbus TCP; switching between them needs the GLT Tool.",
   "BO 1 Fehlerreset returns to 0 by itself after a 1 is written."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 1,
   "name": "Vorlauftemperatur",
   "description": "Flow temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "Rücklauftemperatur",
   "description": "Return temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "Heissgastemperatur",
   "description": "Hot gas temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "Wärmequelle Eintritt",
   "description": "Heat source inlet temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "Wärmequelle Austritt",
   "description": "Heat source outlet temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "Mischkreis 1 Vorlauf",
   "description": "Mixing circuit 1 flow temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "Rücklauf extern",
   "description": "External return temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "Raumfernversteller 1",
   "description": "Remote room adjuster 1",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "Mischkreis 2 Vorlauf",
   "description": "Mixing circuit 2 flow temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "Raumfernversteller 2",
   "description": "Remote room adjuster 2",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 11,
   "name": "Mischkreis 3 Vorlauf",
   "description": "Mixing circuit 3 flow temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 12,
   "name": "Raumfernversteller 3",
   "description": "Remote room adjuster 3",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 13,
   "name": "Solarkollektor",
   "description": "Solar collector temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 14,
   "name": "Solarspeicher",
   "description": "Solar storage tank temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "Externe Energiequelle",
   "description": "External energy source temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 16,
   "name": "Außentemperatur",
   "description": "Outdoor temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 17,
   "name": "Rücklauf Sollwert",
   "description": "Return temperature setpoint",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 18,
   "name": "Mischkreis 1 Sollwert Vorlauf",
   "description": "Mixing circuit 1 flow setpoint",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 19,
   "name": "Mischkreis 2 Sollwert Vorlauf",
   "description": "Mixing circuit 2 flow setpoint",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 20,
   "name": "Mischkreis 3 Sollwert Vorlauf",
   "description": "Mixing circuit 3 flow setpoint",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 21,
   "name": "Zulufttemperatur",
   "description": "Supply air temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 22,
   "name": "Trinkwarmwasser Ist-Temperatur",
   "description": "Domestic hot water actual temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 23,
   "name": "Trinkwarmwasser Wunschwert",
   "description": "Domestic hot water setpoint",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 24,
   "name": "Ansaugtemperatur Verdichter",
   "description": "Compressor suction temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 25,
   "name": "Ansaugtemperatur Verdampfer",
   "description": "Evaporator suction temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 26,
   "name": "Temperatur Verdichterheizung",
   "description": "Compressor heater temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 27,
   "name": "Überhitzung",
   "description": "Superheat",
   "units": "K",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 28,
   "name": "Überhitzung Soll",
   "description": "Superheat setpoint",
   "units": "K",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 29,
   "name": "Druck HD (Hochdruck)",
   "description": "High pressure",
   "units": "bar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 30,
   "name": "Druck ND (Niederdruck)",
   "description": "Low pressure",
   "units": "bar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 31,
   "name": "RBE Raumtemperatur Ist",
   "description": "Room unit actual temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 32,
   "name": "RBE Raumtemperatur Soll",
   "description": "Room unit temperature setpoint",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 33,
   "name": "Aktueller Durchfluss",
   "description": "Current flow rate",
   "units": "l/h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 34,
   "name": "Heizkurve Heizung Endpunkt",
   "description": "Heating curve end point",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 35,
   "name": "Heizkurve Heizung Parallelverschiebung",
   "description": "Heating curve parallel shift",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 36,
   "name": "Heizkurve Mischkreis 1 Endpunkt",
   "description": "Mixing circuit 1 curve end point",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 37,
   "name": "Heizkurve Mischkreis 1 Parallelverschiebung",
   "description": "Mixing circuit 1 curve parallel shift",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 38,
   "name": "Heizkurve Mischkreis 2 Endpunkt",
   "description": "Mixing circuit 2 curve end point",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 39,
   "name": "Heizkurve Mischkreis 2 Parallelverschiebung",
   "description": "Mixing circuit 2 curve parallel shift",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 40,
   "name": "Heizkurve Mischkreis 3 Endpunkt",
   "description": "Mixing circuit 3 curve end point",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 41,
   "name": "Heizkurve Mischkreis 3 Parallelverschiebung",
   "description": "Mixing circuit 3 curve parallel shift",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 42,
   "name": "Temperatur + –",
   "description": "Temperature +/- offset",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 43,
   "name": "Leistung Ist",
   "description": "Actual output",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "Außentemperatur",
   "description": "Outdoor temperature (write)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "Rücklauf Sollwert",
   "description": "Return temperature setpoint (write)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "Mischkreis 1 Sollwert Vorlauf",
   "description": "Mixing circuit 1 flow setpoint (write)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "Mischkreis 2 Sollwert Vorlauf",
   "description": "Mixing circuit 2 flow setpoint (write)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "Mischkreis 3 Sollwert Vorlauf",
   "description": "Mixing circuit 3 flow setpoint (write)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "Trinkwarmwasser Wunschwert",
   "description": "Domestic hot water setpoint (write)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "Heizkurve Heizung Endpunkt",
   "description": "Heating curve end point (write)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "Heizkurve Heizung Parallelverschiebung",
   "description": "Heating curve parallel shift (write)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "Heizkurve Mischkreis 1 Endpunkt",
   "description": "Mixing circuit 1 curve end point (write)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "Heizkurve Mischkreis 1 Parallelverschiebung",
   "description": "Mixing circuit 1 curve parallel shift (write)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "Heizkurve Mischkreis 2 Endpunkt",
   "description": "Mixing circuit 2 curve end point (write)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "Heizkurve Mischkreis 2 Parallelverschiebung",
   "description": "Mixing circuit 2 curve parallel shift (write)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "Heizkurve Mischkreis 3 Endpunkt",
   "description": "Mixing circuit 3 curve end point (write)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "Heizkurve Mischkreis 3 Parallelverschiebung",
   "description": "Mixing circuit 3 curve parallel shift (write)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "Temperatur + –",
   "description": "Temperature +/- offset (write)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "MI",
   "instance": 1,
   "name": "Betriebszustand",
   "description": "Operating state",
   "units": "",
   "access": "R",
   "states": "1=Heizbetrieb, 2=Trinkwarmwasser, 3=Schwimmbad, 4=EVU-Sperre, 5=Abtauen, 6=Aus, 7=Externe Energiequelle, 8=Kühlung"
  },
  {
   "type": "MI",
   "instance": 2,
   "name": "Aus / mit Anzahl aktiver Verdichter",
   "description": "Off / number of compressors running",
   "units": "",
   "access": "R",
   "states": "1=Aus, 2=1 Verdichter läuft, 3=2 Verdichter laufen"
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "Sperre / Freigabe Wärmepumpe",
   "description": "Heat pump lock / compressors released (write)",
   "units": "",
   "access": "W",
   "states": "1=Sperre Wärmepumpe, 2=Freigabe 1 Verdichter, 3=Freigabe 2 Verdichter"
  },
  {
   "type": "MI",
   "instance": 3,
   "name": "Betriebsart Heizen",
   "description": "Heating operating mode",
   "units": "",
   "access": "R",
   "states": "1=Automatik, 2=Zusätzlicher Wärmeerzeuger, 3=Party, 4=Ferien, 5=Aus"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "Betriebsart Heizen",
   "description": "Heating operating mode (write)",
   "units": "",
   "access": "W",
   "states": "1=Automatik, 2=Zusätzlicher Wärmeerzeuger, 3=Party, 4=Ferien, 5=Aus"
  },
  {
   "type": "MI",
   "instance": 4,
   "name": "Betriebsart Trinkwarmwasser",
   "description": "Domestic hot water operating mode",
   "units": "",
   "access": "R",
   "states": "1=Automatik, 2=Zusätzlicher Wärmeerzeuger, 3=Party, 4=Ferien, 5=Aus"
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "Betriebsart Trinkwarmwasser",
   "description": "Domestic hot water operating mode (write)",
   "units": "",
   "access": "W",
   "states": "1=Automatik, 2=Zusätzlicher Wärmeerzeuger, 3=Party, 4=Ferien, 5=Aus"
  },
  {
   "type": "MI",
   "instance": 6,
   "name": "Betriebsart Mischkreis 2",
   "description": "Mixing circuit 2 operating mode",
   "units": "",
   "access": "R",
   "states": "1=Automatik, 2=Zusätzlicher Wärmeerzeuger, 3=Party, 4=Ferien, 5=Aus"
  },
  {
   "type": "MV",
   "instance": 5,
   "name": "Betriebsart Mischkreis 2",
   "description": "Mixing circuit 2 operating mode (write)",
   "units": "",
   "access": "W",
   "states": "1=Automatik, 2=Zusätzlicher Wärmeerzeuger, 3=Party, 4=Ferien, 5=Aus"
  },
  {
   "type": "MI",
   "instance": 7,
   "name": "Betriebsart Mischkreis 3",
   "description": "Mixing circuit 3 operating mode",
   "units": "",
   "access": "R",
   "states": "1=Automatik, 2=Zusätzlicher Wärmeerzeuger, 3=Party, 4=Ferien, 5=Aus"
  },
  {
   "type": "MV",
   "instance": 6,
   "name": "Betriebsart Mischkreis 3",
   "description": "Mixing circuit 3 operating mode (write)",
   "units": "",
   "access": "W",
   "states": "1=Automatik, 2=Zusätzlicher Wärmeerzeuger, 3=Party, 4=Ferien, 5=Aus"
  },
  {
   "type": "MI",
   "instance": 8,
   "name": "Betriebsart Kühlung",
   "description": "Cooling operating mode",
   "units": "",
   "access": "R",
   "states": "1=Aus, 2=Automatik"
  },
  {
   "type": "MV",
   "instance": 7,
   "name": "Betriebsart Kühlung",
   "description": "Cooling operating mode (write)",
   "units": "",
   "access": "W",
   "states": "1=Aus, 2=Automatik"
  },
  {
   "type": "MI",
   "instance": 9,
   "name": "Betriebsart Lüftung",
   "description": "Ventilation operating mode",
   "units": "",
   "access": "R",
   "states": "1=Automatik, 2=Party, 3=Ferien, 4=Aus"
  },
  {
   "type": "MV",
   "instance": 8,
   "name": "Betriebsart Lüftung",
   "description": "Ventilation operating mode (write)",
   "units": "",
   "access": "W",
   "states": "1=Automatik, 2=Party, 3=Ferien, 4=Aus"
  },
  {
   "type": "MI",
   "instance": 10,
   "name": "Betriebsart Schwimmbad",
   "description": "Pool operating mode",
   "units": "",
   "access": "R",
   "states": "1=Automatik, 2=nicht benutzt, 3=Party, 4=Ferien, 5=Aus"
  },
  {
   "type": "MV",
   "instance": 9,
   "name": "Betriebsart Schwimmbad",
   "description": "Pool operating mode (write)",
   "units": "",
   "access": "W",
   "states": "1=Automatik, 2=nicht benutzt, 3=Party, 4=Ferien, 5=Aus"
  },
  {
   "type": "MI",
   "instance": 11,
   "name": "Smart Grid",
   "description": "Smart Grid state",
   "units": "",
   "access": "R",
   "states": "1=EVU-Sperre, 2=Smart Grid Low, 3=Standard, 4=Smart Grid High"
  },
  {
   "type": "MV",
   "instance": 10,
   "name": "Smart Grid",
   "description": "Smart Grid state (write)",
   "units": "",
   "access": "W",
   "states": "1=EVU-Sperre, 2=Smart Grid Low, 3=Standard, 4=Smart Grid High"
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "Selbst zurücksetzende Störung",
   "description": "Self-resetting fault (fault number in Active_Text)",
   "units": "",
   "access": "R",
   "states": "0=Inactive (no fault), 1=Active (self-resetting fault)"
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "Nicht selbst zurücksetzende Störung",
   "description": "Latching fault (fault number in Active_Text)",
   "units": "",
   "access": "R",
   "states": "0=Inactive (no fault), 1=Active (fault)"
  },
  {
   "type": "BI",
   "instance": 3,
   "name": "HUP",
   "description": "Heating circulation pump",
   "units": "",
   "access": "R",
   "states": "0=Aus, 1=An"
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "VEN",
   "description": "Fan",
   "units": "",
   "access": "R",
   "states": "0=Aus, 1=An"
  },
  {
   "type": "BI",
   "instance": 5,
   "name": "ZUP",
   "description": "Additional circulation pump",
   "units": "",
   "access": "R",
   "states": "0=Aus, 1=An"
  },
  {
   "type": "BI",
   "instance": 6,
   "name": "BUP",
   "description": "DHW circulation pump",
   "units": "",
   "access": "R",
   "states": "0=Aus, 1=An"
  },
  {
   "type": "BI",
   "instance": 7,
   "name": "Ventil_BOSUP",
   "description": "Fan / well or brine circulation pump",
   "units": "",
   "access": "R",
   "states": "0=Aus, 1=An"
  },
  {
   "type": "BI",
   "instance": 8,
   "name": "ZIP",
   "description": "Recirculation pump",
   "units": "",
   "access": "R",
   "states": "0=Aus, 1=An"
  },
  {
   "type": "BI",
   "instance": 9,
   "name": "FUP2",
   "description": "Floor heating pump 2",
   "units": "",
   "access": "R",
   "states": "0=Aus, 1=An"
  },
  {
   "type": "BI",
   "instance": 10,
   "name": "FUP3",
   "description": "Floor heating pump 3",
   "units": "",
   "access": "R",
   "states": "0=Aus, 1=An"
  },
  {
   "type": "BI",
   "instance": 11,
   "name": "SLP",
   "description": "Solar charging pump",
   "units": "",
   "access": "R",
   "states": "0=Aus, 1=An"
  },
  {
   "type": "BI",
   "instance": 12,
   "name": "SUP",
   "description": "Pool circulation pump",
   "units": "",
   "access": "R",
   "states": "0=Aus, 1=An"
  },
  {
   "type": "BI",
   "instance": 13,
   "name": "VSK",
   "description": "Bypass damper",
   "units": "",
   "access": "R",
   "states": "0=Aus, 1=An"
  },
  {
   "type": "BI",
   "instance": 14,
   "name": "FRH",
   "description": "Defrost heater contactor",
   "units": "",
   "access": "R",
   "states": "0=Aus, 1=An"
  },
  {
   "type": "BI",
   "instance": 15,
   "name": "Verdichter 1",
   "description": "Compressor 1",
   "units": "",
   "access": "R",
   "states": "0=Aus, 1=An"
  },
  {
   "type": "BI",
   "instance": 16,
   "name": "Verdichter 2",
   "description": "Compressor 2",
   "units": "",
   "access": "R",
   "states": "0=Aus, 1=An"
  },
  {
   "type": "BI",
   "instance": 17,
   "name": "ZWE1",
   "description": "Additional heat generator 1",
   "units": "",
   "access": "R",
   "states": "0=Aus, 1=An"
  },
  {
   "type": "BI",
   "instance": 18,
   "name": "ZWE2_SST",
   "description": "Additional heat generator 2 / fault output",
   "units": "",
   "access": "R",
   "states": "0=Aus, 1=An"
  },
  {
   "type": "BI",
   "instance": 19,
   "name": "ZWE3",
   "description": "Additional heat generator 3",
   "units": "",
   "access": "R",
   "states": "0=Aus, 1=An"
  },
  {
   "type": "BI",
   "instance": 20,
   "name": "ASD",
   "description": "Defrost, brine pressure, flow input",
   "units": "",
   "access": "R",
   "states": "0=Aus, 1=An"
  },
  {
   "type": "BI",
   "instance": 21,
   "name": "BWT",
   "description": "DHW thermostat input",
   "units": "",
   "access": "R",
   "states": "0=Aus, 1=An"
  },
  {
   "type": "BI",
   "instance": 22,
   "name": "EVU",
   "description": "Utility lock-out input",
   "units": "",
   "access": "R",
   "states": "0=Aus, 1=An"
  },
  {
   "type": "BI",
   "instance": 23,
   "name": "HD",
   "description": "High pressure switch",
   "units": "",
   "access": "R",
   "states": "0=Aus, 1=An"
  },
  {
   "type": "BI",
   "instance": 24,
   "name": "MOT",
   "description": "Motor protection",
   "units": "",
   "access": "R",
   "states": "0=Aus, 1=An"
  },
  {
   "type": "BI",
   "instance": 25,
   "name": "ND",
   "description": "Low pressure switch",
   "units": "",
   "access": "R",
   "states": "0=Aus, 1=An"
  },
  {
   "type": "BI",
   "instance": 26,
   "name": "PEX",
   "description": "Impressed-current anode monitor",
   "units": "",
   "access": "R",
   "states": "0=Aus, 1=An"
  },
  {
   "type": "BI",
   "instance": 27,
   "name": "SWT",
   "description": "Pool thermostat input",
   "units": "",
   "access": "R",
   "states": "0=Aus, 1=An"
  },
  {
   "type": "BI",
   "instance": 28,
   "name": "SAX",
   "description": "Remote control: boost ventilation",
   "units": "",
   "access": "R",
   "states": "0=Aus, 1=An"
  },
  {
   "type": "BI",
   "instance": 29,
   "name": "SPL",
   "description": "Ventilation shut-off contact",
   "units": "",
   "access": "R",
   "states": "0=Aus, 1=An"
  },
  {
   "type": "BI",
   "instance": 30,
   "name": "EVU2",
   "description": "Smart Grid input (with EVU)",
   "units": "",
   "access": "R",
   "states": "0=Reduced mode (EVU=0) / EVU lock-out (EVU=1), 1=Normal mode (EVU=0) / raised mode (EVU=1)"
  },
  {
   "type": "BO",
   "instance": 1,
   "name": "Fehlerreset",
   "description": "Fault reset; returns to 0 after a 1 is sent",
   "units": "",
   "access": "W",
   "states": "0=ohne Wirkung, 1=Reset auslösen"
  },
  {
   "type": "BO",
   "instance": 3,
   "name": "HUP",
   "description": "Heating circulation pump output override",
   "units": "",
   "access": "W",
   "states": "0=Automatisch, 1=An"
  },
  {
   "type": "BO",
   "instance": 4,
   "name": "VEN",
   "description": "Fan output override",
   "units": "",
   "access": "W",
   "states": "0=Automatisch, 1=An"
  },
  {
   "type": "BO",
   "instance": 5,
   "name": "ZUP",
   "description": "Additional circulation pump output override",
   "units": "",
   "access": "W",
   "states": "0=Automatisch, 1=An"
  },
  {
   "type": "BO",
   "instance": 6,
   "name": "BUP",
   "description": "DHW circulation pump output override",
   "units": "",
   "access": "W",
   "states": "0=Automatisch, 1=An"
  },
  {
   "type": "BO",
   "instance": 7,
   "name": "Ventil_BOSUP",
   "description": "Fan / well or brine circulation pump output override",
   "units": "",
   "access": "W",
   "states": "0=Automatisch, 1=An"
  },
  {
   "type": "BO",
   "instance": 8,
   "name": "ZIP",
   "description": "Recirculation pump output override",
   "units": "",
   "access": "W",
   "states": "0=Automatisch, 1=An"
  },
  {
   "type": "BO",
   "instance": 9,
   "name": "FUP2",
   "description": "Floor heating pump 2 output override",
   "units": "",
   "access": "W",
   "states": "0=Automatisch, 1=An"
  },
  {
   "type": "BO",
   "instance": 10,
   "name": "FUP3",
   "description": "Floor heating pump 3 output override",
   "units": "",
   "access": "W",
   "states": "0=Automatisch, 1=An"
  },
  {
   "type": "BO",
   "instance": 11,
   "name": "SLP",
   "description": "Solar charging pump output override",
   "units": "",
   "access": "W",
   "states": "0=Automatisch, 1=An"
  },
  {
   "type": "BO",
   "instance": 12,
   "name": "SUP",
   "description": "Pool circulation pump output override",
   "units": "",
   "access": "W",
   "states": "0=Automatisch, 1=An"
  },
  {
   "type": "BO",
   "instance": 13,
   "name": "VSK",
   "description": "Bypass damper output override",
   "units": "",
   "access": "W",
   "states": "0=Automatisch, 1=An"
  },
  {
   "type": "BO",
   "instance": 14,
   "name": "FRH",
   "description": "Defrost heater contactor output override",
   "units": "",
   "access": "W",
   "states": "0=Automatisch, 1=An"
  },
  {
   "type": "ACC",
   "instance": 1,
   "name": "Wärmemenge Heizung",
   "description": "Heat quantity, heating",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "ACC",
   "instance": 2,
   "name": "Wärmemenge Trinkwarmwasser",
   "description": "Heat quantity, DHW",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "ACC",
   "instance": 3,
   "name": "Wärmemenge Schwimmbad",
   "description": "Heat quantity, pool",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "ACC",
   "instance": 4,
   "name": "Wärmemenge gesamt",
   "description": "Heat quantity, total",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "ACC",
   "instance": 5,
   "name": "Betriebstund. VD1",
   "description": "Compressor 1 run hours",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "ACC",
   "instance": 6,
   "name": "Impulse Verdichter 1",
   "description": "Compressor 1 starts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "ACC",
   "instance": 7,
   "name": "Betriebstund. VD2",
   "description": "Compressor 2 run hours",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "ACC",
   "instance": 8,
   "name": "Impulse Verdichter 2",
   "description": "Compressor 2 starts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "ACC",
   "instance": 9,
   "name": "Betriebstunden ZWE1",
   "description": "Additional heater 1 run hours",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "ACC",
   "instance": 10,
   "name": "Betriebstunden ZWE2",
   "description": "Additional heater 2 run hours",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "ACC",
   "instance": 11,
   "name": "Betriebstunden ZWE3",
   "description": "Additional heater 3 run hours",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "ACC",
   "instance": 12,
   "name": "Betriebstunden WP",
   "description": "Heat pump run hours",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "ACC",
   "instance": 13,
   "name": "Betriebstunden Heiz.",
   "description": "Heating run hours",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "ACC",
   "instance": 14,
   "name": "Betriebstunden WW",
   "description": "DHW run hours",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "ACC",
   "instance": 15,
   "name": "Betriebstunden Kuehl",
   "description": "Cooling run hours",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "ACC",
   "instance": 16,
   "name": "Betriebstunden SWoPV",
   "description": "Pool or PV run hours",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "ACC",
   "instance": 17,
   "name": "Betriebstunden Solar",
   "description": "Solar run hours",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "ACC",
   "instance": 18,
   "name": "Fehlerspeicher",
   "description": "Current fault (fault memory)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "ACC",
   "instance": 19,
   "name": "Wärmemenge Kühlung",
   "description": "Heat quantity, cooling",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "ACC",
   "instance": 20,
   "name": "Eingesetzte Energie Heizung",
   "description": "Energy used, heating",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "ACC",
   "instance": 21,
   "name": "Eingesetzte Energie Trinkwarmwasser",
   "description": "Energy used, DHW",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "ACC",
   "instance": 22,
   "name": "Eingesetzte Energie Kühlung",
   "description": "Energy used, cooling",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "ACC",
   "instance": 23,
   "name": "Eingesetzte Energie Schwimmbad",
   "description": "Energy used, pool",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "ACC",
   "instance": 24,
   "name": "Eingesetzte Energie gesamt",
   "description": "Energy used, total",
   "units": "kWh",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/ait-deutschland/novelan-glt-heat-pump-controller-bacnet-ip",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}