- Aidoo Pro BACnet (Wi-Fi + BACnet MS/TP AC interface)
Split / ducted AC unit interface (BACnet MS/TP) · BACnet points list
Airzone Aidoo Pro BACnet (Wi-Fi + BACnet MS/TP AC interface) BACnet points list
Updated 12 November 2026Unofficial source
Aidoo Pro plugs into an air-conditioning indoor unit and offers cloud control plus a BACnet MS/TP slave port. The integration manual lists 11 objects: on/off, setpoint, room temperature, mode, fan speed, louvre position, communication and error flags, a digital input, auxiliary heat status and an error-code string.
This page lists 11 BACnet objects for the Airzone Aidoo Pro BACnet (Wi-Fi + BACnet MS/TP AC interface) — 5 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Airzone’s documentation hosted by Total Home Supply, not by Airzone itself, so treat it as unofficial.
- Manufacturer
- Airzone
- Model
- Aidoo Pro BACnet (Wi-Fi + BACnet MS/TP AC interface)
- Equipment
- Split / ducted AC unit interface (BACnet MS/TP)
- Equipment type
- VRF & split air conditioners
- BACnet objects
- 11 (5 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- Aidoo Pro, Airzone Aidoo Pro, Aidoo Pro BACnet, Aidoo Pro Wi-Fi BACnet, Airzone Aidoo
- Source document
- Integration Manual Aidoo Pro - BACnet (unofficial copy, hosted by Total Home Supply)
Reference only, provided as-is: verify against Airzone’s current documentation and the live device before use. Not official Airzone information. Terms of use.
BMS integration notes: Airzone Aidoo Pro BACnet (Wi-Fi + BACnet MS/TP AC interface)
In the Airzone Cloud app (Airtools, Bluetooth advanced setup, Integration) set the output to BACnet MS/TP and give the slave address, then wire the RS-485 bus. Write on/off, mode, setpoint and fan speed and read room temperature and the error flags.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 0 | Switching the zone | On/off (1 = on) | Write |
| MV 0 | Modes | Mode command | Write |
| AV 0 | Set-point | Setpoint | Write |
| MV 1 | Speed | Fan speed (0 = auto) | Write |
| AV 1 | Localtemp | Room temperature | Read |
| BI 0 | IU communication | 1 = indoor unit communicating | Read |
| BI 1 | IU errors | Indoor unit error | Read |
| CSV 1 | Errors | Error code text | Read |
Network setup
- The MS/TP slave address is set in the Airzone Cloud app (Airtools > Integration).
- RS-485 port 300-115200 bps, 8 data bits, 1 stop bit, no flow control.
Watch out for
- Values are only valid while Out_Of_Service is FALSE.
- The two mode tables in the manual disagree; confirm the codes on site.
Airzone Aidoo Pro BACnet (Wi-Fi + BACnet MS/TP AC interface) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BVmin | 0 | Switching the zone | Zone / unit on-off | Write | 0=Off, 1=On | |
| BImin | 0 | IU communication | Indoor unit communication | Read | 0=No communication, 1=IU ready | |
| BImin | 1 | IU errors | Indoor unit error | Read | 0=No error, 1=IU with error | |
| BI | 2 | Digital input | Digital input state | Read | 0=Inactive, 1=Active | |
| BO | 0 | Auxiliary heat | Auxiliary heat status (read only) | Read | 0=Inactive, 1=Active | |
| AVmin | 0 | Set-point | Setpoint temperature | Write | ||
| AVmin | 1 | Localtemp | Room temperature | Read | ||
| MVmin | 0 | Modes | Operation mode | Write | 1=Auto, 2=Cooling, 3=Heating, 4=Ventilation, 5=Dry | |
| MVmin | 1 | Speed | Fan speed | Write | 0=Automatic, 1=Speed 1, 2=Speed 2, 3=Speed 3 | |
| MV | 2 | Slats | Louvre position | Write | 1-9=Position 1-9, 10=Swing | |
| CSVmin | 1 | Errors | Indoor unit error codes | Read |
No points match these filters.
Object ID lookup: Airzone Aidoo Pro point IDs by name
Integration notes
- Object names are the Description column of the list of objects; the table gives object type, instance (registration), R/W and values.
- Mode values differ inside the manual: the object table gives 1 Auto, 2 Cooling, 3 Heating, 4 Ventilation, 5 Dry, while the detailed description gives 0 Stop, 2 Cooling, 3 Heating, 4 Dry, 6 Ventilation. The table values are shown; check by reading the state text.
- BO 0 Auxiliary heat is listed as read-only. An object is only valid while its Out_Of_Service is FALSE; availability depends on the connected unit.
- Setpoint and room temperature units are not printed in the manual.
- Copy hosted on a retailer manual site (Total Home Supply); no Airzone-hosted copy was found.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Aidoo Pro BACnet (Wi-Fi + BACnet MS/TP AC interface) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Airzone Aidoo Pro BACnet (Wi-Fi + BACnet MS/TP AC interface)
How many BACnet points does the Airzone Aidoo Pro BACnet (Wi-Fi + BACnet MS/TP AC interface) have?
This list has 11 BACnet objects: 2 analog values, 3 binary inputs, 1 binary output, 1 binary value, 3 multi-state values, 1 characterstring value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Airzone Aidoo Pro BACnet (Wi-Fi + BACnet MS/TP AC interface) BACnet points are writable?
5 of the 11 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Airzone Aidoo Pro BACnet (Wi-Fi + BACnet MS/TP AC interface) BACnet documentation?
Airzone does not publish it on its own website. This list comes from Integration Manual Aidoo Pro - BACnet, a copy hosted by Total Home Supply at https://manuals.totalhomesupply.com/wp-content/uploads/manuals/BACNET-Integration.pdf. Ask Airzone or its representative for the current revision.
What are the minimum BACnet points to integrate the Airzone Aidoo Pro BACnet (Wi-Fi + BACnet MS/TP AC interface)?
Start with BV 0 Switching the zone (On/off (1 = on)); MV 0 Modes (Mode command); AV 0 Set-point (Setpoint); MV 1 Speed (Fan speed (0 = auto)); AV 1 Localtemp (Room temperature); BI 0 IU communication (1 = indoor unit communicating); BI 1 IU errors (Indoor unit error); CSV 1 Errors (Error code text).
How do I check these points on the real Aidoo Pro BACnet (Wi-Fi + BACnet MS/TP AC interface)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
Source: Integration Manual Aidoo Pro - BACnet. Object names, instances and units are reproduced as published; descriptions are our own.