VAV diffuser (thermal-electric / motorized) · BACnet points list

Acutherm E-Series interoperable VAV diffusers BACnet points list

Updated 6 November 2026

Short answer

E-Series diffusers are self-contained VAV diffusers that can run stand-alone or take commands over BACnet MS/TP. The object list has 44 objects: room, supply air and airflow readings, effective setpoint and terminal load, occupied/unoccupied/standby setpoints and flow limits, BMS overrides for occupancy, heat/cool mode, setpoint, room and supply temperature, airflow and damper position, and diagnostics.

This page lists 44 BACnet objects for the Acutherm E-Series interoperable VAV diffusers — 33 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Acutherm’s own free documentation, linked below.

Manufacturer
Acutherm
Model
E-Series interoperable VAV diffusers
Equipment
VAV diffuser (thermal-electric / motorized)
Equipment type
VAV boxes & fan coils
BACnet objects
44 (33 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
E-Series, Acutherm E-Series, Form 090.202, 090p202
Source document
E-Series Interoperable VAV Diffusers - BACnet Object List · Form 090.202 · rev. Rev 1704
Download CSV 44 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Acutherm’s current documentation and the live device before use. Not official Acutherm information. Terms of use.

BMS integration notes: Acutherm E-Series interoperable VAV diffusers

Integration in brief

Run the diffuser from the BMS by writing AV_21 iOccMode and AV_23 iTempSetpt (and AV_26 iRmTemp if the BMS supplies room temperature); read AI_0 room temperature, AI_3 effective setpoint, AI_2 airflow and AI_4 terminal load.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 21iOccModeOccupancy override: 0 occupied, 1 unoccupied, 2 standbyWrite
AV 23iTempSetptOccupied room setpoint from BMS (3276 = none)Write
AI 0oRmTempRoom temperature used for controlRead
AI 3oEffectStptEffective room setpointRead
AI 1oSATempSupply air temperatureRead
AI 2oAirFlowAir flow rate, cfmRead
AI 4oTmnlLoadTerminal load: + cooling, - heating, %Read

Enable & remote start

The diffuser defaults to occupied mode; AV_21 iOccMode overrides it to unoccupied or standby. AV_22 iHCMode overrides the heat/cool choice (9 = invalid, ignored).

Sensors & values from the BMS

AV_26 iRmTemp, AV_27 iSATemp and AV_28 iFlowRate replace the built-in sensors; AV_29 iCO2Level feeds a CO2 value for the purge function. Write the invalid value to go back to the built-in sensor.

Network setup

Watch out for

Acutherm E-Series interoperable VAV diffusers BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

44 of 44 shown
Type
Binary
Access
Show
Acutherm E-Series interoperable VAV diffusers BACnet Points List
DescriptionStates
BV0iVacancyModeVacancyWrite0=off, 1=on
BV1iPowerDbgDiagnosticsWrite0=off, 1=on
BV2iFlowDbgDiagnosticsWrite0=off, 1=on
AV0cMaxFlowMaximum Flow Set PointcfmWrite
AV1cMinFlowMinimum Flow Set PointcfmWrite
AV2cMinStbyFlowMinimum Flow Standby Set PointcfmWrite
AV3cCO2spCO2 Set PointppmWrite
AV4cOccCoolspCooling Set Point Occupied Mode°FWrite
AV5cUnocCoolspCooling Set Point Unoccupied Mode°FWrite
AV6cStndbyCoolspCooling Set Point Standby Mode°FWrite
AV7cOccHeatspHeating Set Point Occupied Mode°FWrite
AV8cUnocHeatspHeating Set Point Unoccupied Mode°FWrite
AV9cStndbyHeatspHeating Set Point Standby Mode°FWrite
AV10cStPtLimitSet Point Limit°FWrite
AV11cStPtResetSet Point ResetWrite0=off, 1=on
AV12cMaxHeatspMaximum Air Flow in Heating%Write
AV13cHCModeHeating/Cooling ModeWrite0=automatic, 1=cooling, 2=heating
AV14cBaudrateBaud RateWrite0=38400, 1=9600, 2=19200, 3=57600
AV15cVacSpOfstVacancy Set Point Offset°FWrite
AV16cRmOffsetFactory Calibration (room temperature offset)°F x 100Write
AV17cSAOffsetFactory Calibration (supply air temperature offset)°F x 100Write
AV18cFlowOffsetFactory Calibration (air flow rate offset)cfmWrite
AV19cFlowScalerFactory Calibration (air flow multiplier)%Write
AV20cFBoffsetFactory Calibration (over temp protection offset)Write
AVmin21iOccModeOverride Occupancy ModeWrite0=occupied, 1=unoccupied, 2=standby
AV22iHCModeOverride Heating/Cooling ModeWrite0=automatic, 1=cooling, 2=heating
AVmin23iTempSetptRoom Temperature Set Point°FWrite
AV24iFlowSetptAirflow (option 5) or damper % (option 6) target for AV_25cfm or %Write
AV25iOverrideOverride Diffuser Damper PositionWrite0=automatic, 1=full open, 2=full closed, 3=cMaxFlow, 4=cMinFlow, 5=iFlowSetpt (cfm), 6=iFlowSetpt (% open, motorized units only)
AV26iRmTempOverride Room Temperature°FWrite
AV27iSATempOverride Supply Air Temperature°FWrite
AV28iFlowRateOverride Air Flow RatecfmWrite
AV29iCO2LevelInput from CO2 SensorppmWrite
AImin0oRmTempRoom Temperature°FRead
AImin1oSATempSupply Air Temperature°FRead
AImin2oAirFlowAir Flow RatecfmRead
AImin3oEffectStptRoom Temperature Set Point°FRead
AImin4oTmnlLoadTerminal load: + in cooling, - in heating%Read
AI5oDbg1Diagnostics (output dependent upon iFlowDbg and iPowerDbg)Read
AI6oDbg2Diagnostics (output dependent upon iFlowDbg and iPowerDbg)Read
AI7oDbg3Diagnostics (output dependent upon iFlowDbg and iPowerDbg)Read
AI8oDbg4Diagnostics (output dependent upon iFlowDbg and iPowerDbg)Read
AI9oDbg5Diagnostics (output dependent upon iFlowDbg and iPowerDbg)Read
AI10oDbg6Diagnostics (output dependent upon iFlowDbg and iPowerDbg)Read
Object ID lookup: Acutherm E-Series interoperable VAV diffusers point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the E-Series interoperable VAV diffusers and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Acutherm E-Series interoperable VAV diffusers

How many BACnet points does the Acutherm E-Series interoperable VAV diffusers have?

This list has 44 BACnet objects: 11 analog inputs, 30 analog values, 3 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Acutherm E-Series interoperable VAV diffusers BACnet points are writable?

33 of the 44 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Acutherm E-Series interoperable VAV diffusers BACnet documentation?

The source is E-Series Interoperable VAV Diffusers - BACnet Object List (Form 090.202), revision Rev 1704, published free by Acutherm at https://acutherm.com/wp-content/uploads/2023/07/090p202_E-Series_BACnet_Object_List.pdf.

What are the minimum BACnet points to integrate the Acutherm E-Series interoperable VAV diffusers?

Start with AV 21 iOccMode (Occupancy override: 0 occupied, 1 unoccupied, 2 standby); AV 23 iTempSetpt (Occupied room setpoint from BMS (3276 = none)); AI 0 oRmTemp (Room temperature used for control); AI 3 oEffectStpt (Effective room setpoint); AI 1 oSATemp (Supply air temperature); AI 2 oAirFlow (Air flow rate, cfm); AI 4 oTmnlLoad (Terminal load: + cooling, - heating, %).

How do I enable BMS control of the Acutherm E-Series interoperable VAV diffusers?

The diffuser defaults to occupied mode; AV_21 iOccMode overrides it to unoccupied or standby. AV_22 iHCMode overrides the heat/cool choice (9 = invalid, ignored).

Can the BMS supply sensor values to the Acutherm E-Series interoperable VAV diffusers?

AV_26 iRmTemp, AV_27 iSATemp and AV_28 iFlowRate replace the built-in sensors; AV_29 iCO2Level feeds a CO2 value for the purge function. Write the invalid value to go back to the built-in sensor.

How do I check these points on the real E-Series interoperable VAV diffusers?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Acutherm BACnet points lists

Source: E-Series Interoperable VAV Diffusers - BACnet Object List · Form 090.202 · rev. Rev 1704. Object names, instances and units are reproduced as published; descriptions are our own.