Digital VAV diffuser (master unit) · BACnet points list

Acutherm Advantage Digital VAV Diffuser BACnet points list

Updated 28 October 2026

Short answer

The Advantage is a motorised VAV diffuser: each master unit has its own controller and wall thermostat and can drive up to five drone diffusers with a 0-10 V signal. With the optional native BACnet module each master is a BACnet MS/TP device; drones have no BACnet presence. The BMS overrides setpoint, room temperature and occupancy through the Net* objects rather than writing the room setpoint directly. All objects are AVs and AIs, with codes in place of binary or multistate objects.

This page lists 56 BACnet objects for the Acutherm Advantage Digital VAV Diffuser — 26 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Acutherm’s own free documentation, linked below.

Manufacturer
Acutherm
Model
Advantage Digital VAV Diffuser
Equipment
Digital VAV diffuser (master unit)
Equipment type
VAV boxes & fan coils
BACnet objects
56 (26 writable)
Transport
BACnet MS/TP
Firmware
3.0.5 Rev A 1027v
Default device instance
100 plus the MAC address (e.g. 101)
Also known as
Advantage, ADV, ADVM, ADVS, ADVR, Acutherm Advantage
Source document
Manual - List of BACnet Objects: Advantage Digital VAV Diffusers · v001 · rev. 2021-12-29
Download CSV 56 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Acutherm Advantage Digital VAV Diffuser

Integration in brief

Set each master's MAC (1-99) and device instance from the LCD thermostat, keep 76800 baud, then map the Net* override objects for occupancy and setpoint plus room temperature, load and damper position. Drones follow their master and are not on the network.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 30Net OccupancyOccupancy: 0 normal, 1 force occ, 2 force unoccWrite
AV 28Net SetpointRoom setpoint from the BMSWrite
AV 2OccupancyCurrent occupancy (0 = Unoccupied, 1 = Occupied)Read
AV 14Controller StatusRoom load, -100 % cooling to +100 % heatingRead
AI 1Room TemperatureRoom temperatureRead
AV 6Room SetpointActive room setpointRead
AV 18Current Damper PositionDamper position, %; 999 = recalibratingRead
AV 41AirflowMeasured airflow (needs the DMS flow sensor)Read

Enable & remote start

No enable point. The BMS forces occupancy with AV 30 Net Occupancy (0 = Normal Operation, 1 = Force Occupied, 2 = Force Unoccupied) and sets the room setpoint through AV 28 Net Setpoint. AV 25 overrides the damper (0 = automatic) for balancing.

Sensors & values from the BMS

AV 29 Net Room Temp overrides the room temperature from the BACnet network (default 0). AV 31 Net Lights overrides the room lights output (0 = normal, 1 = on, 2 = off).

Network setup

Watch out for

Acutherm Advantage Digital VAV Diffuser BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

56 of 56 shown
Type
Access
Show
Acutherm Advantage Digital VAV Diffuser BACnet Points List
DescriptionStates
AImin1Room TemperatureCurrent Room Temperature°F/°CRead
AI2N/AUnused placeholderRead
AI3Supply Air TemperatureCurrent Supply Air Temperature°F/°CRead
AI4Analog Input J18Spare 0-10 V input (J18)VRead
AI5Analog Input 4Spare 0-10 V input, IO board AI4VRead
AI6Analog Input 5Spare 0-10 V input, IO board AI5VRead
AI7Analog Input 6Spare 0-10 V input, IO board AI6VRead
AI8Wireless Signal Strength or N/ASignal strength from the wireless thermostat%Read
AI9Wireless Battery Code or N/ABattery code from the wireless thermostatRead
AI10Room CO²Current CO² at the T-StatppmRead
AI11Room HumidityCurrent Relative Humidity at the T-Stat%RHRead
AV1Control ModelSetpoint source (thermostat or not connected)Read2=Thermostat Setpoint, 3=T-Stat not connected
AVmin2OccupancyCurrent occupancy stateRead0=Unoccupied, 1=Occupied
AV3Occupancy SourceWhat set the current occupancyRead0=Occupied Default Mode, 2=Occupied from Contact Closure, 3=Occupied from T-Stat Button Press, 4=Occupied from Motion Sensor, 5=Occupied from Network Override (AV30), 12=Unoccupied from Contact Closure, 14=Unoccupied from Motion Sensor, 15=Unoccupied from Network Override
AV4Room Setpoint - Low LimitLowest user-adjustable room setpoint°F/°CWrite
AV5Room Setpoint - High LimitHighest user-adjustable room setpoint°F/°CWrite
AVmin6Room SetpointCurrent room setpoint (limited by AV 4/AV 5)°F/°CRead
AV7Night Heat SetpointUnoccupied heating setpoint°F/°CWrite
AV8Night Cool SetpointUnoccupied cooling setpoint°F/°CWrite
AV9Binary Output ApplicationSpare binary output functionWrite0=On in heat, 1=On in cooling, 2=On in heat & cool, 3=On in deadband, 4=Room lights (motion stat), 5=Off (override), 6=On (override)
AV10Binary Output Signal TypeSpare binary output signal typeRead1=PWM, 2=PDM, 3=On/Off, 4=PWM (off with hot duct air), 5=PDM (off with hot duct air), 6=On/Off (off with hot duct air)
AV11Binary Output StatusSpare binary output state (0/1 or 0-100 %)Read
AV12Unoccupied (Night) Damper PositionDamper position held during unoccupied periods%Write
AV13PingWrite n to make the thermostat beep n timesWrite
AVmin14Controller StatusRoom load (PI): + heating, 0 deadband, - cooling%Read
AV15Proportional BandBand over which the PI load goes 1-100 %°F/°CWrite
AV16Day DifferentialBand either side of setpoint treated as satisfied°F/°CWrite
AV17Inlet SizeDiffuser inlet size: 6, 8, 10 or 12 ininWrite
AVmin18Current Damper PositionCurrent damper position; 999 = recalibrating%Read
AV19Damper TargetDamper position target%Read
AV20Damper Neutral Supply PositionDamper position when supply air is neutral%Write
AV21Damper Cool Min PositionMinimum damper position in cooling%Write
AV22Damper Cool Max PositionMaximum damper position in cooling%Write
AV23Damper Heat Min PositionMinimum damper position in heating%Write
AV24Damper Heat Max PositionMaximum damper position in heating%Write
AV25Remote Mode Flag (Damper Position Override)Damper override (remote mode)Write0=Automatic control, 1=Target Cool Min, 2=Target Cool Max, 3=Target Heat Min, 4=Target Heat Max, 5=Target Neutral Airflow, 6=Open Damper 100%, 7=Close Damper (0%)
AV26Drone Output Voltage0-10 V signal to drone diffusersVRead
AV27Aux Analog Output VoltageSpare voltage output (J17)VRead
AVmin28Net SetpointRoom setpoint override from the BACnet network°F/°CWrite
AV29Net Room TempRoom temperature override from the BACnet network°F/°CWrite
AVmin30Net OccupancyOccupancy override from the BACnet networkWrite0=Normal Operation, 1=Force Occupied, 2=Force Unoccupied
AV31Net LightsRoom lights override from the BACnet networkWrite0=Normal Operation, 1=Force Lights On, 2=Force Lights Off
AV32Power FrequencySupply power frequencyHzWrite50=50 Hz, 60=60 Hz
AV33Contact Closure One ApplicationContact closure function on J14Write0=Not Used, 1=Unoccupied, 2=Occupied, 3=Full Open, 4=Full Close
AV34Contact Closure One StatusContact closure state on J14Read0=Not Contacted, 1=Contacted
AV35Contact Closure Two ApplicationContact closure function on AI4Write0=Not Used, 1=Unoccupied, 2=Occupied, 3=Full Open, 4=Full Close
AV36Contact Closure Two StatusContact closure state on AI4Read0=Not Contacted, 1=Contacted
AV37Contact Closure Three ApplicationContact closure function on AI5Write0=Not Used, 1=Unoccupied, 2=Occupied, 3=Full Open, 4=Full Close
AV38Contact Closure Three StatusContact closure state on AI5Read0=Not Contacted, 1=Contacted
AV39Contact Closure Four ApplicationContact closure function on AI6Write0=Not Used, 1=Unoccupied, 2=Occupied, 3=Full Open, 4=Full Close
AV40Contact Closure Four StatusContact closure state on AI6Read0=Not Contacted, 1=Contacted
AVmin41AirflowMeasured airflow (DMS flow sensor)CFM, LPS or CMHRead
AV42K FactorK-factor used to calculate airflowWrite
AV43Airflow Sensor Connection StatusAirflow sensor connection statusRead0=Not Connected, 1=Connected
AV44Airflow UnitsAirflow unitsRead1=CFM, 2=LPS, 3=CMH
AV45Show User SettingsReserved for manufacturerRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Advantage Digital VAV Diffuser and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Acutherm Advantage Digital VAV Diffuser

How many BACnet points does the Acutherm Advantage Digital VAV Diffuser have?

This list has 56 BACnet objects: 11 analog inputs, 45 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Acutherm Advantage Digital VAV Diffuser BACnet points are writable?

26 of the 56 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Acutherm Advantage Digital VAV Diffuser BACnet documentation?

The source is Manual - List of BACnet Objects: Advantage Digital VAV Diffusers (v001), revision 2021-12-29, published free by Acutherm at https://holyoake.com/wp-content/uploads/2023/03/Manual_ADV_BACNet_001_v001_3.pdf.

What are the minimum BACnet points to integrate the Acutherm Advantage Digital VAV Diffuser?

Start with AV 30 Net Occupancy (Occupancy: 0 normal, 1 force occ, 2 force unocc); AV 28 Net Setpoint (Room setpoint from the BMS); AV 2 Occupancy (Current occupancy (0 = Unoccupied, 1 = Occupied)); AV 14 Controller Status (Room load, -100 % cooling to +100 % heating); AI 1 Room Temperature (Room temperature); AV 6 Room Setpoint (Active room setpoint); AV 18 Current Damper Position (Damper position, %; 999 = recalibrating); AV 41 Airflow (Measured airflow (needs the DMS flow sensor)).

How do I enable BMS control of the Acutherm Advantage Digital VAV Diffuser?

No enable point. The BMS forces occupancy with AV 30 Net Occupancy (0 = Normal Operation, 1 = Force Occupied, 2 = Force Unoccupied) and sets the room setpoint through AV 28 Net Setpoint. AV 25 overrides the damper (0 = automatic) for balancing.

Can the BMS supply sensor values to the Acutherm Advantage Digital VAV Diffuser?

AV 29 Net Room Temp overrides the room temperature from the BACnet network (default 0). AV 31 Net Lights overrides the room lights output (0 = normal, 1 = on, 2 = off).

How do I check these points on the real Advantage Digital VAV Diffuser?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: Manual - List of BACnet Objects: Advantage Digital VAV Diffusers · v001 · rev. 2021-12-29. Object names, instances and units are reproduced as published; descriptions are our own.