Ducted split system BMS gateway · BACnet points list

ActronAir GW100K BMS Gateway Controller (ICUNO-MOD systems) BACnet points list

Updated 12 November 2026

Short answer

The GW100K translates the Modbus RTU data of up to ten ActronAir ICUNO-MOD cards to BACnet IP, BACnet MS/TP or Modbus TCP. Each system gets the same 121-point block (on/off, mode, setpoint, fan, economiser, zones, temperatures, compressor data, alarms, error codes); this list shows system 1 plus the 24 shared gateway I/O points (Device 11).

This page lists 145 BACnet objects for the ActronAir GW100K BMS Gateway Controller (ICUNO-MOD systems) — 65 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from ActronAir’s own free documentation, linked below.

Manufacturer
ActronAir
Model
GW100K BMS Gateway Controller (ICUNO-MOD systems)
Equipment
Ducted split system BMS gateway
Equipment type
VRF & split air conditioners
BACnet objects
145 (65 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
GW100K, ICUNO-MOD, 9590-3038-03, ActronAir BMS gateway, Actron Air GW100K, ActronAir Advance, ActronAir Aires, Classic Series 2, VCC
Source document
BMS Gateway Controller GW100K - BMS Register Table · 9590-3038-03 V1.0.1
Download CSV 145 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against ActronAir’s current documentation and the live device before use. Not official ActronAir information. Terms of use.

BMS integration notes: ActronAir GW100K BMS Gateway Controller (ICUNO-MOD systems)

Integration in brief

Turn the system on with D101, choose the mode with I103 and the setpoint with A101, and the fan with I101. Read room temperature, running capacity, compressor status and the alarm and error code points.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1D101AC on/off (1 = on)Write
IV 542I103Mode: heat, cool, auto, fan onlyWrite
AV 517A101Master setpoint, 16-30 °CWrite
IV 540I101Supply fan: low, medium, high, autoWrite
AV 869A115Room temperatureRead
AV 885A135Running capacity, %Read
BV 286D125Compressor 1 runningRead
BV 276D115Alarm outputRead
IV 897I116Current error codeRead
BV 282D121No comms with indoor unitRead

Enable & remote start

Capacity demand (A131), supply fan speed demand (A132) and heat request (D106) only work in Advanced BMS mode; I110 reports the BMS demand mode (0 none, 1 basic, 2 advanced).

Network setup

Watch out for

ActronAir GW100K BMS Gateway Controller (ICUNO-MOD systems) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

145 of 145 shown
Type
AnalogBinaryOther
Access
Show
ActronAir GW100K BMS Gateway Controller (ICUNO-MOD systems) BACnet Points List
DescriptionStates
AVmin517A101Set Master Setpoint Temperature (16 to 30)°CWrite
AV519A103Economiser Temperature Difference (0 to 10)°CWrite
AV520A104Economiser Outside Min Temperature (0 to 22.5)°CWrite
AV521A105Economiser Outside Max Temperature (0 to 26)°CWrite
AV522A106Economiser Minimum Damper (0 to 10)VWrite
AV523A107Economiser Maximum Damper (0 to 10)VWrite
AV524A108Economiser Outside Max Moisture (0 to 100)g/kgWrite
AV525A109Economiser Outside Max Dew Point (0 to 100)°CWrite
AV527A110Economiser Outside Max Enthalpy (0 to 100)kJ/kgWrite
AV528A111Economiser Enthalpy Delta (0 to 10)kJ/kgWrite
AV529A112Economiser CO₂ Minimum Damper (0 to 10)VWrite
AV530A113Economiser CO₂ Maximum Damper (0 to 10)VWrite
AVmin869A115Room Temperature (-99.9 to 99.9)°CRead
AV870A116Indoor Room Temperature (-99.9 to 99.9)°CRead
AV871A117Outside Temperature (-99.9 to 99.9)°CRead
AV872A118Outside Air Temperature (-99.9 to 99.9)°CRead
AV873A119Compressor 1 Suction Temperature (-999.9 to 999.9)°CRead
AV874A120Compressor 1 Discharge Temperature (-999.9 to 999.9)°CRead
AV875A121Compressor 1 Suction SuperHeat (-99.9 to 99.9)°CRead
AV876A122Compressor 1 Suction SuperHeat Target (-99.9 to 99.9)°CRead
AV877A123Outdoor Coil 1 Temperature (-99.9 to 99.9)°CRead
AV878A124Indoor Coil 1 Temperature (-99.9 to 99.9)°CRead
AV879A125Wall Control 1 Temperature (-99.9 to 99.9)°CRead
AV880A126Wall Control 2 Temperature (-99.9 to 99.9)°CRead
AV881A127Wall Control 3 Temperature (-99.9 to 99.9)°CRead
AV882A128Auxillary Sensor 1 Temperature (-99.9 to 99.9)°CRead
AV883A129Auxillary Sensor 2 Temperature (-99.9 to 99.9)°CRead
AV884A130Auxillary Sensor 3 Temperature (-99.9 to 99.9)°CRead
AV531A131Set System Capacity Demand (Advanced BMS mode only) (0 to 100)%Write
AV532A132Set Supply Fan Speed Demand (Advanced BMS mode only) (0 to 100)%Write
AV533A133Reduced Airflow Speed (0 to 100)%Write
AV534A134Economiser Outside Max Humidity (0 to 100)%Write
AVmin885A135Actual System Running Capacity (0 to 100)%Read
AV886A136Compressor 1 Demand (0 to 100)%Read
AV887A137Compressor 1 Speed (0 to 100)%Read
AV888A138Indoor Coil 1 Fan Speed (0 to 100)%Read
AV889A139Compressor 1 EEV position (0 to 100)%Read
AV535A140Generic Analog 01Write
AV536A141Generic Analog 02Write
AV537A142Generic Analog 03Write
AV538A143Generic Analog 04Write
AV539A144Generic Analog 05Write
BVmin1D101Turns the AC Off/On (0=Off, 1=On)Write0=Off, 1=On
BV2D102Reset Air Filter Notification (0=Off, 1=Reset)Write0=Off, 1=Reset
BV3D103Set Supply Fan Controls (0=Standard, 1=Continuous)Write0=Standard, 1=Continuous
BV4D104Set Turbo Mode (0=Off, 1=On)Write0=Off, 1=On
BV5D105Set Quiet Mode (0=Off, 1=On)Write0=Off, 1=On
BV6D106Set Heat Request (0=Off, 1=On) (Advanced BMS mode only)Write0=Off, 1=On
BV9D109Enable Outside Air Damper (0=Off, 1=On)Write0=Off, 1=On
BV10D110Enable Economiser (0=Off, 1=On)Write0=Off, 1=On
BV11D111Enable Humidity ControlWrite
BV12D112Humidity Sensor Configuration (0=Outdoor, 1=Outdoor&Indoor)Write0=Outdoor, 1=Outdoor&Indoor
BV13D113Moisture Control Config (0=Moisture, 1=Enthalpy)Write0=Moisture, 1=Enthalpy
BV14D114Enable CO₂ Control (0=Off, 1=On)Write0=Off, 1=On
BVmin276D115Alarm Output (0=Off, 1=On)Read0=Off, 1=On
BV277D116Air Filter NotificationRead
BV280D119Reduce Airflow Active (0=Off, 1=On)Read0=Off, 1=On
BV281D120Remote On/Off (0=Low, 1=High)Read0=Low, 1=High
BVmin282D121No Communication with Indoor Unit (0=No Error, 1=Off Line)Read0=No Error, 1=Off Line
BV283D122No Communication with Outdoor Unit (0=No Error, 1=Off Line)Read0=No Error, 1=Off Line
BV284D123Room Temperature Sensor Status (0=OK, 1=Error)Read0=OK, 1=Error
BV285D124Outside Air Temperature Sensor Status (0=OK, 1=Error)Read0=OK, 1=Error
BVmin286D125Compressor 1 running status (0=Off, 1=On)Read0=Off, 1=On
BV287D126Compressor 1 Heating (0=Off, 1=On)Read0=Off, 1=On
BV288D127Compressor 1 Unit Defrosting (0=Off, 1=Defrost)Read0=Off, 1=Defrost
BV289D128Compressor 1 LP switch (0=OK, 1=Tripped)Read0=OK, 1=Tripped
BV290D129Compressor 1 HP switch (0=OK, 1=Tripped)Read0=OK, 1=Tripped
BV291D130Compressor 1 HP or LP Lockout (0=Off, 1=Lockout)Read0=Off, 1=Lockout
BV292D131Compressor 1 Discharge Temp HighRead
BV293D132Compressor 1 LP Status (0=OK, 1=Error)Read0=OK, 1=Error
BV294D133Compressor 1 HP Status (0=OK, 1=Error)Read0=OK, 1=Error
BV295D134Compressor 1 Suction Temperature Status (0=OK, 1=Error)Read0=OK, 1=Error
BV296D135Compressor 1 Duscharge Temperature Status (0=OK, 1=Error)Read0=OK, 1=Error
BV297D136Outdoor Coil Temperature Status (0=OK, 1=Error)Read0=OK, 1=Error
BV298D137Indoor Coil 1 Temperature Status (0=OK, 1=Error)Read0=OK, 1=Error
BV15D138Set zone 1 (0=Off, 1=On)Write0=Off, 1=On
BV16D139Set zone 2 (0=Off, 1=On)Write0=Off, 1=On
BV17D140Set zone 3 (0=Off, 1=On)Write0=Off, 1=On
BV18D141Set zone 4 (0=Off, 1=On)Write0=Off, 1=On
BV19D142Set zone 5 (0=Off, 1=On)Write0=Off, 1=On
BV20D143Set zone 6 (0=Off, 1=On)Write0=Off, 1=On
BV21D144Set zone 7 (0=Off, 1=On)Write0=Off, 1=On
BV22D145Set zone 8 (0=Off, 1=On)Write0=Off, 1=On
BV23D146Generic Digital 1Write
BV24D147Generic Digital 2Write
BV25D148Generic Digital 3Write
BV26D149Generic Digital 4Write
BV27D150Generic Digital 5Write
IVmin540I101Set the Supply Fan Mode (1=low,2=medium,3=high,4=Auto) (1 to 4)Write1=low, 2=medium, 3=high, 4=Auto
IV541I102Set Air Filter Notification Timer (1 to 10000)hWrite
IVmin542I103Mode of Operation (1=Heat only, 2=Cool only, 3=Auto c/o, 4=Fan only) (1 to 4)Write1=Heat only, 2=Cool only, 3=Auto c/o, 4=Fan only
IV543I104Target Airflow (0 to 6000)l/sWrite
IV544I105Enable Volumetric Airflow (0 to 6000)l/sWrite
IV545I106Indoor Pressure Filter level warning (0 to 6000)PaWrite
IV546I107Economiser CO₂ Low Level (0 to 1000)ppmWrite
IV547I108Economiser CO₂ High Level (0 to 1000)ppmWrite
IV890I109BMS card Software version (0 to 32767)Read
IV891I110BMS Demand mode (0=No BMS, 1=Basic BMS, 2=Advanced BMS) (0 to 2)Read0=No BMS, 1=Basic BMS, 2=Advanced BMS
IV892I111Air Filter Run Timer (0 to 10000)hRead
IV893I112Demand Response (0=No DRM, 1=DRM1, 2=DRM2, 3=DRM3) (0 to 4)Read0=No DRM, 1=DRM1, 2=DRM2, 3=DRM3
IV894I113Indoor Airflow (0 to 6000)l/sRead
IV895I114Indoor Static Pressure (0 to 6000)PaRead
IV896I115Measured CO₂ level (0 to 1000)ppmRead
IVmin897I116Current Error Code (Actron document 9590-0000-05) (0 to 100)Read
IV898I117Error History Log, 1 error ago (0 to 100)Read
IV899I118Error History Log, 2 errors ago (0 to 100)Read
IV900I119Error History Log, 3 errors ago (0 to 100)Read
IV901I120Error History Log, 4 errors ago (0 to 100)Read
IV902I121Error History Log, 5 errors ago (0 to 100)Read
IV903I122Outdoor Unit 1 Model (0 to 32767)Read
IV904I123Outdoor Unit 1 Software version (0 to 32767)Read
IV905I124Compressor 1 Type (0 to 100)Read
IV906I125Compressor 1 Suction Pressure (0 to 6000)kPaRead
IV907I126Compressor 1 Discharge Pressure (0 to 6000)kPaRead
IV908I127Outdoor Coil 1 Fan Speed Setting (0=Off,1=Low,2=Medium,3=High) (0 to 3)Read0=Off, 1=Low, 2=Medium, 3=High
IV909I128Indoor Coil 1 Fan 1 Speed (0 to 9999)rpmRead
IV548I129Generic Integer 1Write
IV549I130Generic Integer 2Write
IV550I131Generic Integer 3Write
IV551I132Generic Integer 4Write
IV552I133Generic Integer 5Write
AV1289A1102Device 11 Universal I/O - U2Read
AV1290A1103Device 11 Universal I/O - U3Read
AV1291A1104Device 11 Universal I/O - U4Read
AV1292A1105Device 11 Universal I/O - U5Read
AV867A1106Device 11 Universal I/O - U6Write
AV1293A1107Device 11 Universal I/O - U7Read
AV1294A1108Device 11 Universal I/O - U8Read
AV1295A1109Device 11 Universal I/O - U9Read
AV1296A1110Device 11 Universal I/O - U10Read
BV271D1101Device 11 relay 1Write
BV272D1102Device 11 relay 2Write
BV273D1103Device 11 relay 3Write
BV274D1104Device 11 relay 4Write
BV275D1105Device 11 relay 5Write
BV506D1106Device 11 relay 6 General AlarmRead
BV507D1111Device 11 Universal I/O - U1Read
BV508D1112Device 11 Universal I/O - U2Read
BV509D1113Device 11 Universal I/O - U3Read
BV510D1114Device 11 Universal I/O - U4Read
BV511D1115Device 11 Universal I/O - U5Read
BV513D1117Device 11 Universal I/O - U7Read
BV514D1118Device 11 Universal I/O - U8Read
BV515D1119Device 11 Universal I/O - U9Read
BV516D1120Device 11 Universal I/O - U10Read
Object ID lookup: ActronAir GW100K BMS Gateway Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the GW100K BMS Gateway Controller (ICUNO-MOD systems) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the ActronAir GW100K BMS Gateway Controller (ICUNO-MOD systems)

How many BACnet points does the ActronAir GW100K BMS Gateway Controller (ICUNO-MOD systems) have?

This list has 145 BACnet objects: 51 analog values, 61 binary values, 33 integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which ActronAir GW100K BMS Gateway Controller (ICUNO-MOD systems) BACnet points are writable?

65 of the 145 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official ActronAir GW100K BMS Gateway Controller (ICUNO-MOD systems) BACnet documentation?

The source is BMS Gateway Controller GW100K - BMS Register Table (9590-3038-03 V1.0.1), published free by ActronAir at https://actronair.com.au/wp-content/uploads/2025/03/9590-3038-03-BMS-Gateway-Register-Table.xlsx.

What are the minimum BACnet points to integrate the ActronAir GW100K BMS Gateway Controller (ICUNO-MOD systems)?

Start with BV 1 D101 (AC on/off (1 = on)); IV 542 I103 (Mode: heat, cool, auto, fan only); AV 517 A101 (Master setpoint, 16-30 °C); IV 540 I101 (Supply fan: low, medium, high, auto); AV 869 A115 (Room temperature); AV 885 A135 (Running capacity, %); BV 286 D125 (Compressor 1 running); BV 276 D115 (Alarm output); IV 897 I116 (Current error code); BV 282 D121 (No comms with indoor unit).

How do I enable BMS control of the ActronAir GW100K BMS Gateway Controller (ICUNO-MOD systems)?

Capacity demand (A131), supply fan speed demand (A132) and heat request (D106) only work in Advanced BMS mode; I110 reports the BMS demand mode (0 none, 1 basic, 2 advanced).

How do I check these points on the real GW100K BMS Gateway Controller (ICUNO-MOD systems)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: BMS Gateway Controller GW100K - BMS Register Table · 9590-3038-03 V1.0.1. Object names, instances and units are reproduced as published; descriptions are our own.