- Home
- BACnet points lists
- ActronAir
- GW100K BMS Gateway Controller (ICUNO-MOD systems)
Ducted split system BMS gateway · BACnet points list
ActronAir GW100K BMS Gateway Controller (ICUNO-MOD systems) BACnet points list
Updated 12 November 2026
The GW100K translates the Modbus RTU data of up to ten ActronAir ICUNO-MOD cards to BACnet IP, BACnet MS/TP or Modbus TCP. Each system gets the same 121-point block (on/off, mode, setpoint, fan, economiser, zones, temperatures, compressor data, alarms, error codes); this list shows system 1 plus the 24 shared gateway I/O points (Device 11).
This page lists 145 BACnet objects for the ActronAir GW100K BMS Gateway Controller (ICUNO-MOD systems) — 65 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from ActronAir’s own free documentation, linked below.
- Manufacturer
- ActronAir
- Model
- GW100K BMS Gateway Controller (ICUNO-MOD systems)
- Equipment
- Ducted split system BMS gateway
- Equipment type
- VRF & split air conditioners
- BACnet objects
- 145 (65 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- GW100K, ICUNO-MOD, 9590-3038-03, ActronAir BMS gateway, Actron Air GW100K, ActronAir Advance, ActronAir Aires, Classic Series 2, VCC
Reference only, provided as-is: verify against ActronAir’s current documentation and the live device before use. Not official ActronAir information. Terms of use.
BMS integration notes: ActronAir GW100K BMS Gateway Controller (ICUNO-MOD systems)
Turn the system on with D101, choose the mode with I103 and the setpoint with A101, and the fan with I101. Read room temperature, running capacity, compressor status and the alarm and error code points.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 1 | D101 | AC on/off (1 = on) | Write |
| IV 542 | I103 | Mode: heat, cool, auto, fan only | Write |
| AV 517 | A101 | Master setpoint, 16-30 °C | Write |
| IV 540 | I101 | Supply fan: low, medium, high, auto | Write |
| AV 869 | A115 | Room temperature | Read |
| AV 885 | A135 | Running capacity, % | Read |
| BV 286 | D125 | Compressor 1 running | Read |
| BV 276 | D115 | Alarm output | Read |
| IV 897 | I116 | Current error code | Read |
| BV 282 | D121 | No comms with indoor unit | Read |
Enable & remote start
Capacity demand (A131), supply fan speed demand (A132) and heat request (D106) only work in Advanced BMS mode; I110 reports the BMS demand mode (0 none, 1 basic, 2 advanced).
Network setup
- Up to 10 ICUNO-MOD systems per gateway; protocol (BACnet IP, BACnet MS/TP or Modbus TCP) is chosen on the gateway.
- BMS configuration details are in the ICUNO-MOD and system manuals, not in the register table.
Watch out for
- Each system's points have their own instance blocks; map system 2-10 from their own sheets rather than adding a fixed offset.
ActronAir GW100K BMS Gateway Controller (ICUNO-MOD systems) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 517 | A101 | Set Master Setpoint Temperature (16 to 30) | °C | Write | |
| AV | 519 | A103 | Economiser Temperature Difference (0 to 10) | °C | Write | |
| AV | 520 | A104 | Economiser Outside Min Temperature (0 to 22.5) | °C | Write | |
| AV | 521 | A105 | Economiser Outside Max Temperature (0 to 26) | °C | Write | |
| AV | 522 | A106 | Economiser Minimum Damper (0 to 10) | V | Write | |
| AV | 523 | A107 | Economiser Maximum Damper (0 to 10) | V | Write | |
| AV | 524 | A108 | Economiser Outside Max Moisture (0 to 100) | g/kg | Write | |
| AV | 525 | A109 | Economiser Outside Max Dew Point (0 to 100) | °C | Write | |
| AV | 527 | A110 | Economiser Outside Max Enthalpy (0 to 100) | kJ/kg | Write | |
| AV | 528 | A111 | Economiser Enthalpy Delta (0 to 10) | kJ/kg | Write | |
| AV | 529 | A112 | Economiser CO₂ Minimum Damper (0 to 10) | V | Write | |
| AV | 530 | A113 | Economiser CO₂ Maximum Damper (0 to 10) | V | Write | |
| AVmin | 869 | A115 | Room Temperature (-99.9 to 99.9) | °C | Read | |
| AV | 870 | A116 | Indoor Room Temperature (-99.9 to 99.9) | °C | Read | |
| AV | 871 | A117 | Outside Temperature (-99.9 to 99.9) | °C | Read | |
| AV | 872 | A118 | Outside Air Temperature (-99.9 to 99.9) | °C | Read | |
| AV | 873 | A119 | Compressor 1 Suction Temperature (-999.9 to 999.9) | °C | Read | |
| AV | 874 | A120 | Compressor 1 Discharge Temperature (-999.9 to 999.9) | °C | Read | |
| AV | 875 | A121 | Compressor 1 Suction SuperHeat (-99.9 to 99.9) | °C | Read | |
| AV | 876 | A122 | Compressor 1 Suction SuperHeat Target (-99.9 to 99.9) | °C | Read | |
| AV | 877 | A123 | Outdoor Coil 1 Temperature (-99.9 to 99.9) | °C | Read | |
| AV | 878 | A124 | Indoor Coil 1 Temperature (-99.9 to 99.9) | °C | Read | |
| AV | 879 | A125 | Wall Control 1 Temperature (-99.9 to 99.9) | °C | Read | |
| AV | 880 | A126 | Wall Control 2 Temperature (-99.9 to 99.9) | °C | Read | |
| AV | 881 | A127 | Wall Control 3 Temperature (-99.9 to 99.9) | °C | Read | |
| AV | 882 | A128 | Auxillary Sensor 1 Temperature (-99.9 to 99.9) | °C | Read | |
| AV | 883 | A129 | Auxillary Sensor 2 Temperature (-99.9 to 99.9) | °C | Read | |
| AV | 884 | A130 | Auxillary Sensor 3 Temperature (-99.9 to 99.9) | °C | Read | |
| AV | 531 | A131 | Set System Capacity Demand (Advanced BMS mode only) (0 to 100) | % | Write | |
| AV | 532 | A132 | Set Supply Fan Speed Demand (Advanced BMS mode only) (0 to 100) | % | Write | |
| AV | 533 | A133 | Reduced Airflow Speed (0 to 100) | % | Write | |
| AV | 534 | A134 | Economiser Outside Max Humidity (0 to 100) | % | Write | |
| AVmin | 885 | A135 | Actual System Running Capacity (0 to 100) | % | Read | |
| AV | 886 | A136 | Compressor 1 Demand (0 to 100) | % | Read | |
| AV | 887 | A137 | Compressor 1 Speed (0 to 100) | % | Read | |
| AV | 888 | A138 | Indoor Coil 1 Fan Speed (0 to 100) | % | Read | |
| AV | 889 | A139 | Compressor 1 EEV position (0 to 100) | % | Read | |
| AV | 535 | A140 | Generic Analog 01 | Write | ||
| AV | 536 | A141 | Generic Analog 02 | Write | ||
| AV | 537 | A142 | Generic Analog 03 | Write | ||
| AV | 538 | A143 | Generic Analog 04 | Write | ||
| AV | 539 | A144 | Generic Analog 05 | Write | ||
| BVmin | 1 | D101 | Turns the AC Off/On (0=Off, 1=On) | Write | 0=Off, 1=On | |
| BV | 2 | D102 | Reset Air Filter Notification (0=Off, 1=Reset) | Write | 0=Off, 1=Reset | |
| BV | 3 | D103 | Set Supply Fan Controls (0=Standard, 1=Continuous) | Write | 0=Standard, 1=Continuous | |
| BV | 4 | D104 | Set Turbo Mode (0=Off, 1=On) | Write | 0=Off, 1=On | |
| BV | 5 | D105 | Set Quiet Mode (0=Off, 1=On) | Write | 0=Off, 1=On | |
| BV | 6 | D106 | Set Heat Request (0=Off, 1=On) (Advanced BMS mode only) | Write | 0=Off, 1=On | |
| BV | 9 | D109 | Enable Outside Air Damper (0=Off, 1=On) | Write | 0=Off, 1=On | |
| BV | 10 | D110 | Enable Economiser (0=Off, 1=On) | Write | 0=Off, 1=On | |
| BV | 11 | D111 | Enable Humidity Control | Write | ||
| BV | 12 | D112 | Humidity Sensor Configuration (0=Outdoor, 1=Outdoor&Indoor) | Write | 0=Outdoor, 1=Outdoor&Indoor | |
| BV | 13 | D113 | Moisture Control Config (0=Moisture, 1=Enthalpy) | Write | 0=Moisture, 1=Enthalpy | |
| BV | 14 | D114 | Enable CO₂ Control (0=Off, 1=On) | Write | 0=Off, 1=On | |
| BVmin | 276 | D115 | Alarm Output (0=Off, 1=On) | Read | 0=Off, 1=On | |
| BV | 277 | D116 | Air Filter Notification | Read | ||
| BV | 280 | D119 | Reduce Airflow Active (0=Off, 1=On) | Read | 0=Off, 1=On | |
| BV | 281 | D120 | Remote On/Off (0=Low, 1=High) | Read | 0=Low, 1=High | |
| BVmin | 282 | D121 | No Communication with Indoor Unit (0=No Error, 1=Off Line) | Read | 0=No Error, 1=Off Line | |
| BV | 283 | D122 | No Communication with Outdoor Unit (0=No Error, 1=Off Line) | Read | 0=No Error, 1=Off Line | |
| BV | 284 | D123 | Room Temperature Sensor Status (0=OK, 1=Error) | Read | 0=OK, 1=Error | |
| BV | 285 | D124 | Outside Air Temperature Sensor Status (0=OK, 1=Error) | Read | 0=OK, 1=Error | |
| BVmin | 286 | D125 | Compressor 1 running status (0=Off, 1=On) | Read | 0=Off, 1=On | |
| BV | 287 | D126 | Compressor 1 Heating (0=Off, 1=On) | Read | 0=Off, 1=On | |
| BV | 288 | D127 | Compressor 1 Unit Defrosting (0=Off, 1=Defrost) | Read | 0=Off, 1=Defrost | |
| BV | 289 | D128 | Compressor 1 LP switch (0=OK, 1=Tripped) | Read | 0=OK, 1=Tripped | |
| BV | 290 | D129 | Compressor 1 HP switch (0=OK, 1=Tripped) | Read | 0=OK, 1=Tripped | |
| BV | 291 | D130 | Compressor 1 HP or LP Lockout (0=Off, 1=Lockout) | Read | 0=Off, 1=Lockout | |
| BV | 292 | D131 | Compressor 1 Discharge Temp High | Read | ||
| BV | 293 | D132 | Compressor 1 LP Status (0=OK, 1=Error) | Read | 0=OK, 1=Error | |
| BV | 294 | D133 | Compressor 1 HP Status (0=OK, 1=Error) | Read | 0=OK, 1=Error | |
| BV | 295 | D134 | Compressor 1 Suction Temperature Status (0=OK, 1=Error) | Read | 0=OK, 1=Error | |
| BV | 296 | D135 | Compressor 1 Duscharge Temperature Status (0=OK, 1=Error) | Read | 0=OK, 1=Error | |
| BV | 297 | D136 | Outdoor Coil Temperature Status (0=OK, 1=Error) | Read | 0=OK, 1=Error | |
| BV | 298 | D137 | Indoor Coil 1 Temperature Status (0=OK, 1=Error) | Read | 0=OK, 1=Error | |
| BV | 15 | D138 | Set zone 1 (0=Off, 1=On) | Write | 0=Off, 1=On | |
| BV | 16 | D139 | Set zone 2 (0=Off, 1=On) | Write | 0=Off, 1=On | |
| BV | 17 | D140 | Set zone 3 (0=Off, 1=On) | Write | 0=Off, 1=On | |
| BV | 18 | D141 | Set zone 4 (0=Off, 1=On) | Write | 0=Off, 1=On | |
| BV | 19 | D142 | Set zone 5 (0=Off, 1=On) | Write | 0=Off, 1=On | |
| BV | 20 | D143 | Set zone 6 (0=Off, 1=On) | Write | 0=Off, 1=On | |
| BV | 21 | D144 | Set zone 7 (0=Off, 1=On) | Write | 0=Off, 1=On | |
| BV | 22 | D145 | Set zone 8 (0=Off, 1=On) | Write | 0=Off, 1=On | |
| BV | 23 | D146 | Generic Digital 1 | Write | ||
| BV | 24 | D147 | Generic Digital 2 | Write | ||
| BV | 25 | D148 | Generic Digital 3 | Write | ||
| BV | 26 | D149 | Generic Digital 4 | Write | ||
| BV | 27 | D150 | Generic Digital 5 | Write | ||
| IVmin | 540 | I101 | Set the Supply Fan Mode (1=low,2=medium,3=high,4=Auto) (1 to 4) | Write | 1=low, 2=medium, 3=high, 4=Auto | |
| IV | 541 | I102 | Set Air Filter Notification Timer (1 to 10000) | h | Write | |
| IVmin | 542 | I103 | Mode of Operation (1=Heat only, 2=Cool only, 3=Auto c/o, 4=Fan only) (1 to 4) | Write | 1=Heat only, 2=Cool only, 3=Auto c/o, 4=Fan only | |
| IV | 543 | I104 | Target Airflow (0 to 6000) | l/s | Write | |
| IV | 544 | I105 | Enable Volumetric Airflow (0 to 6000) | l/s | Write | |
| IV | 545 | I106 | Indoor Pressure Filter level warning (0 to 6000) | Pa | Write | |
| IV | 546 | I107 | Economiser CO₂ Low Level (0 to 1000) | ppm | Write | |
| IV | 547 | I108 | Economiser CO₂ High Level (0 to 1000) | ppm | Write | |
| IV | 890 | I109 | BMS card Software version (0 to 32767) | Read | ||
| IV | 891 | I110 | BMS Demand mode (0=No BMS, 1=Basic BMS, 2=Advanced BMS) (0 to 2) | Read | 0=No BMS, 1=Basic BMS, 2=Advanced BMS | |
| IV | 892 | I111 | Air Filter Run Timer (0 to 10000) | h | Read | |
| IV | 893 | I112 | Demand Response (0=No DRM, 1=DRM1, 2=DRM2, 3=DRM3) (0 to 4) | Read | 0=No DRM, 1=DRM1, 2=DRM2, 3=DRM3 | |
| IV | 894 | I113 | Indoor Airflow (0 to 6000) | l/s | Read | |
| IV | 895 | I114 | Indoor Static Pressure (0 to 6000) | Pa | Read | |
| IV | 896 | I115 | Measured CO₂ level (0 to 1000) | ppm | Read | |
| IVmin | 897 | I116 | Current Error Code (Actron document 9590-0000-05) (0 to 100) | Read | ||
| IV | 898 | I117 | Error History Log, 1 error ago (0 to 100) | Read | ||
| IV | 899 | I118 | Error History Log, 2 errors ago (0 to 100) | Read | ||
| IV | 900 | I119 | Error History Log, 3 errors ago (0 to 100) | Read | ||
| IV | 901 | I120 | Error History Log, 4 errors ago (0 to 100) | Read | ||
| IV | 902 | I121 | Error History Log, 5 errors ago (0 to 100) | Read | ||
| IV | 903 | I122 | Outdoor Unit 1 Model (0 to 32767) | Read | ||
| IV | 904 | I123 | Outdoor Unit 1 Software version (0 to 32767) | Read | ||
| IV | 905 | I124 | Compressor 1 Type (0 to 100) | Read | ||
| IV | 906 | I125 | Compressor 1 Suction Pressure (0 to 6000) | kPa | Read | |
| IV | 907 | I126 | Compressor 1 Discharge Pressure (0 to 6000) | kPa | Read | |
| IV | 908 | I127 | Outdoor Coil 1 Fan Speed Setting (0=Off,1=Low,2=Medium,3=High) (0 to 3) | Read | 0=Off, 1=Low, 2=Medium, 3=High | |
| IV | 909 | I128 | Indoor Coil 1 Fan 1 Speed (0 to 9999) | rpm | Read | |
| IV | 548 | I129 | Generic Integer 1 | Write | ||
| IV | 549 | I130 | Generic Integer 2 | Write | ||
| IV | 550 | I131 | Generic Integer 3 | Write | ||
| IV | 551 | I132 | Generic Integer 4 | Write | ||
| IV | 552 | I133 | Generic Integer 5 | Write | ||
| AV | 1289 | A1102 | Device 11 Universal I/O - U2 | Read | ||
| AV | 1290 | A1103 | Device 11 Universal I/O - U3 | Read | ||
| AV | 1291 | A1104 | Device 11 Universal I/O - U4 | Read | ||
| AV | 1292 | A1105 | Device 11 Universal I/O - U5 | Read | ||
| AV | 867 | A1106 | Device 11 Universal I/O - U6 | Write | ||
| AV | 1293 | A1107 | Device 11 Universal I/O - U7 | Read | ||
| AV | 1294 | A1108 | Device 11 Universal I/O - U8 | Read | ||
| AV | 1295 | A1109 | Device 11 Universal I/O - U9 | Read | ||
| AV | 1296 | A1110 | Device 11 Universal I/O - U10 | Read | ||
| BV | 271 | D1101 | Device 11 relay 1 | Write | ||
| BV | 272 | D1102 | Device 11 relay 2 | Write | ||
| BV | 273 | D1103 | Device 11 relay 3 | Write | ||
| BV | 274 | D1104 | Device 11 relay 4 | Write | ||
| BV | 275 | D1105 | Device 11 relay 5 | Write | ||
| BV | 506 | D1106 | Device 11 relay 6 General Alarm | Read | ||
| BV | 507 | D1111 | Device 11 Universal I/O - U1 | Read | ||
| BV | 508 | D1112 | Device 11 Universal I/O - U2 | Read | ||
| BV | 509 | D1113 | Device 11 Universal I/O - U3 | Read | ||
| BV | 510 | D1114 | Device 11 Universal I/O - U4 | Read | ||
| BV | 511 | D1115 | Device 11 Universal I/O - U5 | Read | ||
| BV | 513 | D1117 | Device 11 Universal I/O - U7 | Read | ||
| BV | 514 | D1118 | Device 11 Universal I/O - U8 | Read | ||
| BV | 515 | D1119 | Device 11 Universal I/O - U9 | Read | ||
| BV | 516 | D1120 | Device 11 Universal I/O - U10 | Read |
No points match these filters.
Object ID lookup: ActronAir GW100K BMS Gateway Controller point IDs by name
AV517A101AV519A103AV520A104AV521A105AV522A106AV523A107AV524A108AV525A109AV527A110AV528A111AV529A112AV530A113AV869A115AV870A116AV871A117AV872A118AV873A119AV874A120AV875A121AV876A122AV877A123AV878A124AV879A125AV880A126AV881A127AV882A128AV883A129AV884A130AV531A131AV532A132AV533A133AV534A134AV885A135AV886A136AV887A137AV888A138AV889A139AV535A140AV536A141AV537A142AV538A143AV539A144BV1D101BV2D102BV3D103BV4D104BV5D105BV6D106BV9D109BV10D110BV11D111BV12D112BV13D113BV14D114BV276D115BV277D116BV280D119BV281D120BV282D121BV283D122BV284D123BV285D124BV286D125BV287D126BV288D127BV289D128BV290D129BV291D130BV292D131BV293D132BV294D133BV295D134BV296D135BV297D136BV298D137BV15D138BV16D139BV17D140BV18D141BV19D142BV20D143BV21D144BV22D145BV23D146BV24D147BV25D148BV26D149BV27D150IV540I101IV541I102IV542I103IV543I104IV544I105IV545I106IV546I107IV547I108IV890I109IV891I110IV892I111IV893I112IV894I113IV895I114IV896I115IV897I116IV898I117IV899I118IV900I119IV901I120IV902I121IV903I122IV904I123IV905I124IV906I125IV907I126IV908I127IV909I128IV548I129IV549I130IV550I131IV551I132IV552I133AV1289A1102AV1290A1103AV1291A1104AV1292A1105AV867A1106AV1293A1107AV1294A1108AV1295A1109AV1296A1110BV271D1101BV272D1102BV273D1103BV274D1104BV275D1105BV506D1106BV507D1111BV508D1112BV509D1113BV510D1114BV511D1115BV513D1117BV514D1118BV515D1119BV516D1120
Integration notes
- Points are system (Device) 1 from the register table; systems 2-10 repeat the same 121 points with object names A2xx/D2xx/I2xx ... A10xx and their own instances (see sheets Device 2-10 in the XLSX).
- Instances do not follow one offset: from system 1 to system 2, writable AVs/IVs move +35 (some writable AVs +36), read-only AVs/IVs +42, writable BVs +27 and read-only BVs +23. The table also prints system 10's A1010 at instance 526, out of sequence.
- Device 11 points (A11xx, D11xx) are the gateway's own universal I/O and relays, shared by all systems.
- Points marked Advanced BMS mode only (A131, A132, D106) need the ICUNO-MOD in Advanced BMS mode (I110 shows the mode).
- Error codes (I116-I121) are listed in ActronAir document 9590-0000-05.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the GW100K BMS Gateway Controller (ICUNO-MOD systems) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the ActronAir GW100K BMS Gateway Controller (ICUNO-MOD systems)
How many BACnet points does the ActronAir GW100K BMS Gateway Controller (ICUNO-MOD systems) have?
This list has 145 BACnet objects: 51 analog values, 61 binary values, 33 integer values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which ActronAir GW100K BMS Gateway Controller (ICUNO-MOD systems) BACnet points are writable?
65 of the 145 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official ActronAir GW100K BMS Gateway Controller (ICUNO-MOD systems) BACnet documentation?
The source is BMS Gateway Controller GW100K - BMS Register Table (9590-3038-03 V1.0.1), published free by ActronAir at https://actronair.com.au/wp-content/uploads/2025/03/9590-3038-03-BMS-Gateway-Register-Table.xlsx.
What are the minimum BACnet points to integrate the ActronAir GW100K BMS Gateway Controller (ICUNO-MOD systems)?
Start with BV 1 D101 (AC on/off (1 = on)); IV 542 I103 (Mode: heat, cool, auto, fan only); AV 517 A101 (Master setpoint, 16-30 °C); IV 540 I101 (Supply fan: low, medium, high, auto); AV 869 A115 (Room temperature); AV 885 A135 (Running capacity, %); BV 286 D125 (Compressor 1 running); BV 276 D115 (Alarm output); IV 897 I116 (Current error code); BV 282 D121 (No comms with indoor unit).
How do I enable BMS control of the ActronAir GW100K BMS Gateway Controller (ICUNO-MOD systems)?
Capacity demand (A131), supply fan speed demand (A132) and heat request (D106) only work in Advanced BMS mode; I110 reports the BMS demand mode (0 none, 1 basic, 2 advanced).
How do I check these points on the real GW100K BMS Gateway Controller (ICUNO-MOD systems)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
Source: BMS Gateway Controller GW100K - BMS Register Table · 9590-3038-03 V1.0.1. Object names, instances and units are reproduced as published; descriptions are our own.