Easy BACnet
  1. Home
  2. BACnet points lists
  3. WAREMA
  4. BACnet 4M230.8I AP sun-shading controller (4 blinds, 8 inputs)

Sun-shading (blind) motor controller · BACnet points list

WAREMA BACnet 4M230.8I AP sun-shading controller (4 blinds, 8 inputs) BACnet points list

Updated 12 November 2026Unofficial source

Short answer

The 4M230.8I AP is a BACnet MS/TP application specific controller with four two-stage relay outputs for blind motors and eight digital inputs for local UP/DOWN keys. Each blind has a multistate drive command, position and slat angle commands with feedback, and a set of travel-time and slat set-up values. The PICS prints the object layout as per-blind instance ranges.

This page lists 23 BACnet objects for the WAREMA BACnet 4M230.8I AP sun-shading controller (4 blinds, 8 inputs) — 18 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of WAREMA’s documentation hosted by BACnet International catalog, not by WAREMA itself, so treat it as unofficial.

Manufacturer
WAREMA
Model
BACnet 4M230.8I AP sun-shading controller (4 blinds, 8 inputs)
Equipment
Sun-shading (blind) motor controller
Equipment type
Other equipment
BACnet objects
23 (18 writable)
Transport
BACnet MS/TP
Firmware
1.0
Default device instance
1345000 + MS/TP address
Also known as
4M230.8I AP, BACnet 4M230.8I, 2047 065, 2047065, WAREMA Renkhoff BACnet actuator, WAREMA blind controller BACnet
Source document
PICS BACnet 4M230.8I AP · 2047 065, PICS v1.0 · rev. 2022-04-21 (unofficial copy, hosted by BACnet International catalog)
Download CSV 23 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against WAREMA’s current documentation and the live device before use. Not official WAREMA information. Terms of use.

BMS integration notes: WAREMA BACnet 4M230.8I AP sun-shading controller (4 blinds, 8 inputs)

Integration in brief

Set the MS/TP address and baud rate on the DIP switches. Drive each blind with its multistate command (MV 1-4) or position and slat angle values (AV 1-8), and read back position, slat angle and the in-motion flags.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1Blind 1Blind 1 command: OFF, STOP, UP, DOWN, TURN UP/DOWNWrite
AV 1Blind length 1Blind 1 position command, 0-100 %Write
AV 5Slat position 1Blind 1 slat angle commandWrite
BV 5Safety runSafety run; position writes are blocked while onWrite
AV 9Blind lengthFB 1Blind 1 position feedback, %Read
AV 13Slat positionFB 1Blind 1 slat angle feedbackRead
BV 1Blind 1 in motionRunning flag (stopped / running)Read

Network setup

Watch out for

WAREMA BACnet 4M230.8I AP sun-shading controller (4 blinds, 8 inputs) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

23 of 23 shown
Type
AnalogMulti-state
Access
Show
WAREMA BACnet 4M230.8I AP sun-shading controller (4 blinds, 8 inputs) BACnet Points List
DescriptionStates
AVmin1Blind length 1Blind 1 position command, 0-100 %percentWrite
AVmin5Slat position 1Blind 1 slat angle command, -180 to 180degrees-angularWrite
AVmin9Blind lengthFB 1Blind 1 position feedbackpercentRead
AVmin13Slat positionFB 1Blind 1 slat angle feedbackdegrees-angularRead
AV17Run time UP 1Blind 1 full travel time up (default 90)secondsWrite
AV21Run time DOWN 1Blind 1 full travel time down (default 90)secondsWrite
AV25Slat min. angle 1Blind 1 slat minimum angle (default -75)degrees-angularWrite
AV29Slat max. angle 1Blind 1 slat maximum angle (default 75)degrees-angularWrite
AV33Slat turning time 1Blind 1 slat turning time (default 1600)millisecondsWrite
AV37Slat step angle 1Blind 1 slat step angle (default 15)degrees-angularWrite
AV41Slat DOWN angle 1Blind 1 slat DOWN angle (default 38)degrees-angularWrite
AV45Additional run time UP 1Blind 1 extra run time up (default 3)secondsWrite
AV49Additional run time DOWN 1Blind 1 extra run time down (default 0)secondsWrite
AV53Switchover pause 1Blind 1 pause on direction change (default 500)millisecondsWrite
AV57Long push of the buttonLong key press time (default 2)secondsWrite
MVmin1Blind 1Blind 1 drive command / stateWrite1=OFF, 2=STOP, 3=UP, 4=DOWN, 5=TURN UP, 6=TURN DOWN
MV5File accessConfiguration/update file access stateWrite1=IDLE OK, 2=IDLE ERROR, 3=BACKUP CONFIG, 4=RESTORE CONFIG, 5=READ CONFIG, 6=WRITE CONFIG, 7=ACTIVATE CONFIG, 8=WRITE UPDATE
BVmin1Blind 1 in motionBlind 1 runningReadstopped / running
BVmin5Safety runSafety run; blocks position writes while onWriteoff / on
BV6Reference runStart a reference runWriteoff / on
BV7Direction of motor rotation 1Blind 1 motor directionWritenormal / reverse
BI1Input 1 UPExternal UP key input 1Readoff / on
BI2Input 1 DOWNExternal DOWN key input 1Readoff / on
Object ID lookup: WAREMA BACnet 4M230.8I AP point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the BACnet 4M230.8I AP sun-shading controller (4 blinds, 8 inputs) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the WAREMA BACnet 4M230.8I AP sun-shading controller (4 blinds, 8 inputs)

How many BACnet points does the WAREMA BACnet 4M230.8I AP sun-shading controller (4 blinds, 8 inputs) have?

This list has 23 BACnet objects: 15 analog values, 2 binary inputs, 4 binary values, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which WAREMA BACnet 4M230.8I AP sun-shading controller (4 blinds, 8 inputs) BACnet points are writable?

18 of the 23 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official WAREMA BACnet 4M230.8I AP sun-shading controller (4 blinds, 8 inputs) BACnet documentation?

WAREMA does not publish it on its own website. This list comes from PICS BACnet 4M230.8I AP (2047 065, PICS v1.0), revision 2022-04-21, a copy hosted by BACnet International catalog at https://www.bacnetinternational.net/catalog/manu/warema%20renkhoff%20se/PICS_BACnet-4M230.8I-AP_v1.0.pdf. Ask WAREMA or its representative for the current revision.

What are the minimum BACnet points to integrate the WAREMA BACnet 4M230.8I AP sun-shading controller (4 blinds, 8 inputs)?

Start with MV 1 Blind 1 (Blind 1 command: OFF, STOP, UP, DOWN, TURN UP/DOWN); AV 1 Blind length 1 (Blind 1 position command, 0-100 %); AV 5 Slat position 1 (Blind 1 slat angle command); BV 5 Safety run (Safety run; position writes are blocked while on); AV 9 Blind lengthFB 1 (Blind 1 position feedback, %); AV 13 Slat positionFB 1 (Blind 1 slat angle feedback); BV 1 Blind 1 in motion (Running flag (stopped / running)).

How do I check these points on the real BACnet 4M230.8I AP sun-shading controller (4 blinds, 8 inputs)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: PICS BACnet 4M230.8I AP · 2047 065, PICS v1.0 · rev. 2022-04-21. Object names, instances and units are reproduced as published; descriptions are our own.