Verkada SV21, SV23 and SV25 sensors can act as BACnet IP smart sensors once BACnet is enabled in Verkada Command. Each exposes Analog Inputs at fixed instances for temperature, humidity, CO2 and derived indices; the SV23 and SV25 add particulates, TVOC, noise, motion, vape and AQI values, and the SV25 adds CO, light, pressure and formaldehyde.

This page lists 21 BACnet objects for the Verkada SV21 / SV23 / SV25 Air Quality Sensors — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Verkada’s own free documentation, linked below.

Manufacturer
Verkada
Model
SV21 / SV23 / SV25 Air Quality Sensors
Equipment
Indoor air quality sensor
Equipment type
Thermostats, sensors & meters
BACnet objects
21 (0 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
SV21, SV23, SV25, Verkada SV20 series, Verkada air quality sensor
Source document
Configure BACnet on Air Quality Sensors (Verkada Help Center)
Download CSV 21 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Verkada’s current documentation and the live device before use. Not official Verkada information. Terms of use.

BMS integration notes: Verkada SV21 / SV23 / SV25 Air Quality Sensors

Integration in brief

Enable BACnet in Verkada Command, give each sensor a device ID, then poll the AIs that exist on your model, typically temperature, humidity and CO2, plus PM2.5 and TVOC on the SV23/SV25.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 2Temperature (C)Temperature, °CRead
AI 3HumidityRelative humidityRead
AI 4CO2CO2 concentrationRead
AI 9PM 2.5PM2.5 (SV23/SV25)Read
AI 8TVOC IndexTVOC index (SV23/SV25)Read
AI 10TamperTamper indicationRead

Enable & remote start

Enable Sensor BACnet under Admin > Feature Manager in Verkada Command, then enable BACnet on each sensor under its settings.

Network setup

Watch out for

Verkada SV21 / SV23 / SV25 Air Quality Sensors BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

21 of 21 shown
Type
Analog
Show
Verkada SV21 / SV23 / SV25 Air Quality Sensors BACnet Points List
DescriptionStates
AI1Vape IndexModels: SV23, SV25Read
AImin2Temperature (C)Models: SV21, SV23, SV25°CRead
AImin3HumidityModels: SV21, SV23, SV25%RHRead
AImin4CO2Models: SV21, SV23, SV25ppmRead
AI5Carbon MonoxideModels: SV25ppmRead
AI6NoiseModels: SV23, SV25dBRead
AI7AQIModels: SV23, SV25Read
AImin8TVOC IndexModels: SV23, SV25Read
AImin9PM 2.5Models: SV23, SV25µg/m³Read
AImin10TamperModels: SV21, SV23, SV25Read
AI11MotionModels: SV23, SV25Read
AI12LightModels: SV25luxRead
AI13PressureModels: SV25hPaRead
AI14FormaldehydeModels: SV25ppbRead
AI15PM 4.0Models: SV23, SV25µg/m³Read
AI16PM 10.0Models: SV23, SV25µg/m³Read
AI17Heat IndexModels: SV21, SV23, SV25°CRead
AI18Dew PointModels: SV21, SV23, SV25°CRead
AI19HumidexModels: SV21, SV23, SV25Read
AI20Mold Risk IndexModels: SV21, SV23, SV25Read
AI21Reset Viral IndexModels: SV23, SV25%Read
Object ID lookup: Verkada SV21 / SV23 / SV25 Air Quality Sensors point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SV21 / SV23 / SV25 Air Quality Sensors and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Verkada SV21 / SV23 / SV25 Air Quality Sensors

How many BACnet points does the Verkada SV21 / SV23 / SV25 Air Quality Sensors have?

This list has 21 BACnet objects: 21 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Verkada SV21 / SV23 / SV25 Air Quality Sensors BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official Verkada SV21 / SV23 / SV25 Air Quality Sensors BACnet documentation?

The source is Configure BACnet on Air Quality Sensors (Verkada Help Center), published free by Verkada at https://help.verkada.com/air-quality/configuration/bacnet-for-verkada-air-quality-sensors/configure-bacnet-on-air-quality-sensors.

What are the minimum BACnet points to integrate the Verkada SV21 / SV23 / SV25 Air Quality Sensors?

Start with AI 2 Temperature (C) (Temperature, °C); AI 3 Humidity (Relative humidity); AI 4 CO2 (CO2 concentration); AI 9 PM 2.5 (PM2.5 (SV23/SV25)); AI 8 TVOC Index (TVOC index (SV23/SV25)); AI 10 Tamper (Tamper indication).

How do I enable BMS control of the Verkada SV21 / SV23 / SV25 Air Quality Sensors?

Enable Sensor BACnet under Admin > Feature Manager in Verkada Command, then enable BACnet on each sensor under its settings.

How do I check these points on the real SV21 / SV23 / SV25 Air Quality Sensors?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: Configure BACnet on Air Quality Sensors (Verkada Help Center). Object names, instances and units are reproduced as published; descriptions are our own.