- VX4 Energy Management Thermostats with BACnet Integration
Networked room thermostat (energy management) · BACnet points list
Verdant VX4 Energy Management Thermostats with BACnet Integration BACnet points list
Updated 4 November 2026
Verdant VX4 thermostats talk to each other over a proprietary 900 MHz mesh, and one Online Connection Kit puts the whole network on the building's BACnet network. Every room gets the same 15 objects; the object instance is a fixed base number per object plus the room number. The sheet does not name BACnet IP or MS/TP; its network drawing shows the kit on the building automation LAN.
This page lists 15 BACnet objects for the Verdant VX4 Energy Management Thermostats with BACnet Integration — 7 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Verdant’s own free documentation, linked below.
- Manufacturer
- Verdant
- Model
- VX4 Energy Management Thermostats with BACnet Integration
- Equipment
- Networked room thermostat (energy management)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 15 (7 writable)
- Transport
- —
- Firmware
- Not stated
- Also known as
- VX4-XX-XXX, Verdant VX4, Copeland Verdant, Verdant EMS BACnet, Online Connection Kit
Instance calculator. This list prints one unit; the other units follow a formula. Verdant VX4 thermostats (Online Connection Kit) instance calculator →
Reference only, provided as-is: verify against Verdant’s current documentation and the live device before use. Not official Verdant information. Terms of use.
BMS integration notes: Verdant VX4 Energy Management Thermostats with BACnet Integration
The sheet lists 15 objects per room, reached through the Online Connection Kit; work out each room's instances from the base numbers plus the room number read as hex. Write System Mode, Fan Speed and Guest Setpoint per room; read Room Temperature, Occupancy State, Thermostat Status and the setpoints. Watch Gateway Online Status for loss of the thermostat network.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 1000000 | System Mode | Room mode: 0 auto, 1 heat, 2 cool | Write |
| AV 1100000 | Fan Speed | Fan command; write codes differ from read codes | Write |
| AV 300000 | Guest Setpoint | Writable room setpoint, 60-90 °F | Write |
| AV 400000 | Thermostat Status | On, off or in setback (unoccupied) | Write |
| AV 500000 | Room Temperature | Room temperature, °F | Read |
| BV 700000 | Occupancy State | Room occupied or not | Read |
| AV 100000 | Cool Setpoint | Cooling setpoint in effect | Read |
| AV 200000 | Heat Setpoint | Heating setpoint in effect | Read |
| BV 1400000 | Gateway Online Status | 0 = offline, 1 = online | Read |
Network setup
- One Online Connection Kit links the 900 MHz thermostat mesh to the BACnet network; no Wi-Fi is needed at the rooms.
- Object instance = printed base + room number read as hex and converted to decimal (room 101 -> 257, so Room Temperature is AV 500257).
Watch out for
- Fan Speed reads back 0-3 but must be written with 0, 1, 85, 170 or 254.
- Cool Setpoint and Heat Setpoint are read-only; use Guest Setpoint to change the room setpoint.
- Min/Max Setpoint Limit and Heat EQP Lockout are configuration values; don't write them cyclically.
Verdant VX4 Energy Management Thermostats with BACnet Integration BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 100000 | Cool Setpoint | Cooling setpoint of the room; base + room no. | °F | Read | |
| AVmin | 200000 | Heat Setpoint | Heating setpoint of the room; base + room no. | °F | Read | |
| AVmin | 300000 | Guest Setpoint | Guest setpoint of the room, 60-90; base + room no. | °F | Write | |
| AVmin | 400000 | Thermostat Status | Heat/cool on, off or in setback; base + room no. | Write | 0 = TSTAT_STATE_REGULAR_ON, 1 = TSTAT_STATE_REGULAR_OFF, 2 = TSTAT_STATE_INSETBACK_ON, 3 = TSTAT_STATE_INSETBACK_OFF | |
| AVmin | 500000 | Room Temperature | Room temperature; base + room no. | °F | Read | |
| AV | 600000 | Room Humidity | Room relative humidity; base + room no. | %RH | Read | |
| BVmin | 700000 | Occupancy State | Room occupancy state; base + room no. | Read | ||
| AV | 800000 | Battery Percentage | Thermostat battery level, 0-100; base + room no. | % | Read | |
| AV | 900000 | Last Updated Timestamp | Last packet received from the room; base + room no. | Read | ||
| AVmin | 1000000 | System Mode | System mode of the room; base + room no. | Write | 0 = SYSTEM_AUTO, 1 = SYSTEM_HEAT, 2 = SYSTEM_COOL | |
| AVmin | 1100000 | Fan Speed | Fan mode and speed; base + room no. | Write | Read: 0 = Fan Off, 1 = Fan Low, 2 = Fan Low and High, 3 = Fan High; Write: 0 = FAN_AUTO, 1 = FAN_OFF, 85 = FAN_LOW, 170 = FAN_MEDIUM, 254 = FAN_HIGH, 255 = FAN_INVALID | |
| AV | 1200000 | Minimum Setpoint Limit | Lowest setpoint allowed in the room; base + room no. | °F | Write | |
| AV | 1300000 | Maximum setpoint limit | Highest setpoint allowed in the room; base + room no. | °F | Write | |
| BVmin | 1400000 | Gateway Online Status | Gateway online status; base + room no. | Read | 0 = Offline, 1 = Online | |
| AV | 1500000 | Heat EQP Lockout | Heat equipment lockout for the room; base + room no. | Write | 0 = No Lockout, 1 = Electric Lockout, 2 = Compressor Lockout |
No points match these filters.
Object ID lookup: Verdant VX4 BACnet point IDs by name
AV100000Cool SetpointAV200000Heat SetpointAV300000Guest SetpointAV400000Thermostat StatusAV500000Room TemperatureAV600000Room HumidityBV700000Occupancy StateAV800000Battery PercentageAV900000Last Updated TimestampAV1000000System ModeAV1100000Fan SpeedAV1200000Minimum Setpoint LimitAV1300000Maximum setpoint limitBV1400000Gateway Online StatusAV1500000Heat EQP Lockout
Integration notes
- Instances shown are the printed base values. The sheet gives each room's instance as base + hex2dec(room number): read the room number as a hexadecimal number, convert it to decimal and add it to the base. For example, room 101 is 0x101 = 257, so its Room Temperature is AV 500257. The sheet gives no worked example, so confirm against a discovered device.
- Cool Setpoint and Heat Setpoint are read-only; the writable setpoint is Guest Setpoint (60-90 °F).
- Fan Speed uses different codes for reading and writing (see states).
- Thermostat Status combined with System Mode gives the heating/cooling state; values 2 and 3 mean the room is in setback (unoccupied).
- The spec sheet does not state the BACnet transport; the network drawing places the Online Connection Kit on the building automation LAN.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VX4 Energy Management Thermostats with BACnet Integration and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Verdant VX4 Energy Management Thermostats with BACnet Integration
How many BACnet points does the Verdant VX4 Energy Management Thermostats with BACnet Integration have?
This list has 15 BACnet objects: 13 analog values, 2 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Verdant VX4 Energy Management Thermostats with BACnet Integration BACnet points are writable?
7 of the 15 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Verdant VX4 Energy Management Thermostats with BACnet Integration BACnet documentation?
The source is VX4 Energy Management Thermostats with BACnet Integration (spec sheet) (VX4-XX-XXX), revision 2024-10, published free by Verdant at https://verdant.copeland.com/wp-content/uploads/2024/10/VX4-XXX-BACnet-Spec-Sheet-1024.pdf.
What are the minimum BACnet points to integrate the Verdant VX4 Energy Management Thermostats with BACnet Integration?
Start with AV 1000000 System Mode (Room mode: 0 auto, 1 heat, 2 cool); AV 1100000 Fan Speed (Fan command; write codes differ from read codes); AV 300000 Guest Setpoint (Writable room setpoint, 60-90 °F); AV 400000 Thermostat Status (On, off or in setback (unoccupied)); AV 500000 Room Temperature (Room temperature, °F); BV 700000 Occupancy State (Room occupied or not); AV 100000 Cool Setpoint (Cooling setpoint in effect); AV 200000 Heat Setpoint (Heating setpoint in effect); BV 1400000 Gateway Online Status (0 = offline, 1 = online).
How do I check these points on the real VX4 Energy Management Thermostats with BACnet Integration?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
Source: VX4 Energy Management Thermostats with BACnet Integration (spec sheet) · VX4-XX-XXX · rev. 2024-10. Object names, instances and units are reproduced as published; descriptions are our own.