Networked room thermostat (energy management) · BACnet points list

Verdant VX4 Energy Management Thermostats with BACnet Integration BACnet points list

Updated 4 November 2026

Short answer

Verdant VX4 thermostats talk to each other over a proprietary 900 MHz mesh, and one Online Connection Kit puts the whole network on the building's BACnet network. Every room gets the same 15 objects; the object instance is a fixed base number per object plus the room number. The sheet does not name BACnet IP or MS/TP; its network drawing shows the kit on the building automation LAN.

This page lists 15 BACnet objects for the Verdant VX4 Energy Management Thermostats with BACnet Integration — 7 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Verdant’s own free documentation, linked below.

Manufacturer
Verdant
Model
VX4 Energy Management Thermostats with BACnet Integration
Equipment
Networked room thermostat (energy management)
Equipment type
Thermostats, sensors & meters
BACnet objects
15 (7 writable)
Transport
—
Firmware
Not stated
Also known as
VX4-XX-XXX, Verdant VX4, Copeland Verdant, Verdant EMS BACnet, Online Connection Kit
Source document
VX4 Energy Management Thermostats with BACnet Integration (spec sheet) · VX4-XX-XXX · rev. 2024-10

Instance calculator. This list prints one unit; the other units follow a formula. Verdant VX4 thermostats (Online Connection Kit) instance calculator →

Download CSV 15 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Verdant’s current documentation and the live device before use. Not official Verdant information. Terms of use.

BMS integration notes: Verdant VX4 Energy Management Thermostats with BACnet Integration

Integration in brief

The sheet lists 15 objects per room, reached through the Online Connection Kit; work out each room's instances from the base numbers plus the room number read as hex. Write System Mode, Fan Speed and Guest Setpoint per room; read Room Temperature, Occupancy State, Thermostat Status and the setpoints. Watch Gateway Online Status for loss of the thermostat network.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 1000000System ModeRoom mode: 0 auto, 1 heat, 2 coolWrite
AV 1100000Fan SpeedFan command; write codes differ from read codesWrite
AV 300000Guest SetpointWritable room setpoint, 60-90 °FWrite
AV 400000Thermostat StatusOn, off or in setback (unoccupied)Write
AV 500000Room TemperatureRoom temperature, °FRead
BV 700000Occupancy StateRoom occupied or notRead
AV 100000Cool SetpointCooling setpoint in effectRead
AV 200000Heat SetpointHeating setpoint in effectRead
BV 1400000Gateway Online Status0 = offline, 1 = onlineRead

Network setup

Watch out for

Verdant VX4 Energy Management Thermostats with BACnet Integration BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

15 of 15 shown
Type
AnalogBinary
Access
Show
Verdant VX4 Energy Management Thermostats with BACnet Integration BACnet Points List
DescriptionStates
AVmin100000Cool SetpointCooling setpoint of the room; base + room no.°FRead
AVmin200000Heat SetpointHeating setpoint of the room; base + room no.°FRead
AVmin300000Guest SetpointGuest setpoint of the room, 60-90; base + room no.°FWrite
AVmin400000Thermostat StatusHeat/cool on, off or in setback; base + room no.Write0 = TSTAT_STATE_REGULAR_ON, 1 = TSTAT_STATE_REGULAR_OFF, 2 = TSTAT_STATE_INSETBACK_ON, 3 = TSTAT_STATE_INSETBACK_OFF
AVmin500000Room TemperatureRoom temperature; base + room no.°FRead
AV600000Room HumidityRoom relative humidity; base + room no.%RHRead
BVmin700000Occupancy StateRoom occupancy state; base + room no.Read
AV800000Battery PercentageThermostat battery level, 0-100; base + room no.%Read
AV900000Last Updated TimestampLast packet received from the room; base + room no.Read
AVmin1000000System ModeSystem mode of the room; base + room no.Write0 = SYSTEM_AUTO, 1 = SYSTEM_HEAT, 2 = SYSTEM_COOL
AVmin1100000Fan SpeedFan mode and speed; base + room no.WriteRead: 0 = Fan Off, 1 = Fan Low, 2 = Fan Low and High, 3 = Fan High; Write: 0 = FAN_AUTO, 1 = FAN_OFF, 85 = FAN_LOW, 170 = FAN_MEDIUM, 254 = FAN_HIGH, 255 = FAN_INVALID
AV1200000Minimum Setpoint LimitLowest setpoint allowed in the room; base + room no.°FWrite
AV1300000Maximum setpoint limitHighest setpoint allowed in the room; base + room no.°FWrite
BVmin1400000Gateway Online StatusGateway online status; base + room no.Read0 = Offline, 1 = Online
AV1500000Heat EQP LockoutHeat equipment lockout for the room; base + room no.Write0 = No Lockout, 1 = Electric Lockout, 2 = Compressor Lockout
Object ID lookup: Verdant VX4 BACnet point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VX4 Energy Management Thermostats with BACnet Integration and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Verdant VX4 Energy Management Thermostats with BACnet Integration

How many BACnet points does the Verdant VX4 Energy Management Thermostats with BACnet Integration have?

This list has 15 BACnet objects: 13 analog values, 2 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Verdant VX4 Energy Management Thermostats with BACnet Integration BACnet points are writable?

7 of the 15 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Verdant VX4 Energy Management Thermostats with BACnet Integration BACnet documentation?

The source is VX4 Energy Management Thermostats with BACnet Integration (spec sheet) (VX4-XX-XXX), revision 2024-10, published free by Verdant at https://verdant.copeland.com/wp-content/uploads/2024/10/VX4-XXX-BACnet-Spec-Sheet-1024.pdf.

What are the minimum BACnet points to integrate the Verdant VX4 Energy Management Thermostats with BACnet Integration?

Start with AV 1000000 System Mode (Room mode: 0 auto, 1 heat, 2 cool); AV 1100000 Fan Speed (Fan command; write codes differ from read codes); AV 300000 Guest Setpoint (Writable room setpoint, 60-90 °F); AV 400000 Thermostat Status (On, off or in setback (unoccupied)); AV 500000 Room Temperature (Room temperature, °F); BV 700000 Occupancy State (Room occupied or not); AV 100000 Cool Setpoint (Cooling setpoint in effect); AV 200000 Heat Setpoint (Heating setpoint in effect); BV 1400000 Gateway Online Status (0 = offline, 1 = online).

How do I check these points on the real VX4 Energy Management Thermostats with BACnet Integration?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: VX4 Energy Management Thermostats with BACnet Integration (spec sheet) · VX4-XX-XXX · rev. 2024-10. Object names, instances and units are reproduced as published; descriptions are our own.