Fuel tank monitoring console via BACnet gateway · BACnet points list

Veeder-Root TLS console system points (QuickServer gateway) BACnet points list

Updated 7 November 2026Unofficial source

Short answer

The QuickServer reads a TLS console over its serial V-R interface and serves BACnet IP or BACnet MS/TP. The system-wide points are fixed: 29 Binary Inputs for console alarms and warnings (printer, battery, self-test, clock, poll timeout, database and similar) and 3 Analog Inputs that report alarms from unknown device types. Tank, sensor and input points are added per device with numbers that depend on the node ID.

This page lists 32 BACnet objects for the Veeder-Root TLS console system points (QuickServer gateway) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Veeder-Root’s documentation hosted by Global Fueling Systems (distributor), not by Veeder-Root itself, so treat it as unofficial.

Manufacturer
Veeder-Root
Model
TLS console system points (QuickServer gateway)
Equipment
Fuel tank monitoring console via BACnet gateway
Equipment type
Other equipment
BACnet objects
32 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
50000
Also known as
TLS-450PLUS BACnet, TLS4 BACnet, TLS-350 BACnet, 577014-367, Veeder-Root QuickServer
Source document
QuickServer Industrial Protocol Gateway Startup Guide · 577014-367 · rev. Revision D (unofficial copy, hosted by Global Fueling Systems (distributor))
Download CSV 32 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Veeder-Root’s current documentation and the live device before use. Not official Veeder-Root information. Terms of use.

BMS integration notes: Veeder-Root TLS console system points (QuickServer gateway)

Integration in brief

Set the console's serial port to 9600 baud, odd parity, 7 data bits, 1 stop bit, add a profile per tank or sensor (node IDs sequential from 1, address = the console's tank or sensor number), then read the system and per-device alarm points.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BI 18System Device Poll TimeoutConsole lost contact with a polled deviceRead
BI 16System Self Test ErrorConsole self-test errorRead
BI 4Battery OffConsole battery offRead
BI 12Protective Cover AlarmProtective cover alarmRead
BI 21Database ErrorConsole database errorRead
AI 2Unknown Alarm CategoryAlarm category from an unknown deviceRead

Network setup

Watch out for

Veeder-Root TLS console system points (QuickServer gateway) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

32 of 32 shown
Type
AnalogBinary
Show
Veeder-Root TLS console system points (QuickServer gateway) BACnet Points List
DescriptionStates
BI1Printer out of PaperRead
BI2Printer ErrorRead
BI3EEPROM Configuration ErrorRead
BImin4Battery OffRead
BI5Too Many TanksRead
BI6System Security WarningRead
BI7ROM Revision WarningRead
BI8Remote Display Communications ErrorRead
BI9Autodial ErrorRead
BI10Software Module WarningRead
BI11Tank Test Shutdown WarningRead
BImin12Protective Cover AlarmRead
BI13BIR Shift Close PendingRead
BI14BIR Daily Close PendingRead
BI15PC(H8) Revision WarningRead
BImin16System Self Test ErrorRead
BI17System Clock Incorrect WarningRead
BImin18System Device Poll TimeoutRead
BI19Maintenance Tracker NVMemRead
BI20Maintenance Tracker Communication ModuleRead
BImin21Database ErrorRead
BI22File System ErrorRead
BI23BIR Status WarningRead
BI24VR Bus Power Outage WarningRead
BI25Software Upgrade Failure AlarmRead
BI26iButton Fault WarningRead
BI27iButton Fault AlarmRead
BI28Version Upgrade AvailableRead
BI29Expansion Box UnsupportedRead
AI1Unknown Device AddressUnidentified device alarm dataRead
AImin2Unknown Alarm CategoryUnidentified device alarm dataRead
AI3Unknown Alarm TypeUnidentified device alarm dataRead
Object ID lookup: Veeder-Root TLS console system points point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TLS console system points (QuickServer gateway) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Veeder-Root TLS console system points (QuickServer gateway)

How many BACnet points does the Veeder-Root TLS console system points (QuickServer gateway) have?

This list has 32 BACnet objects: 3 analog inputs, 29 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Veeder-Root TLS console system points (QuickServer gateway) BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Veeder-Root TLS console system points (QuickServer gateway) BACnet documentation?

Veeder-Root does not publish it on its own website. This list comes from QuickServer Industrial Protocol Gateway Startup Guide (577014-367), revision Revision D, a copy hosted by Global Fueling Systems (distributor) at https://globalfuelingsystems.com/content/577014-367.pdf. Ask Veeder-Root or its representative for the current revision.

What are the minimum BACnet points to integrate the Veeder-Root TLS console system points (QuickServer gateway)?

Start with BI 18 System Device Poll Timeout (Console lost contact with a polled device); BI 16 System Self Test Error (Console self-test error); BI 4 Battery Off (Console battery off); BI 12 Protective Cover Alarm (Protective cover alarm); BI 21 Database Error (Console database error); AI 2 Unknown Alarm Category (Alarm category from an unknown device).

How do I check these points on the real TLS console system points (QuickServer gateway)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: QuickServer Industrial Protocol Gateway Startup Guide · 577014-367 · rev. Revision D. Object names, instances and units are reproduced as published; descriptions are our own.