- UV Angel Clean Air Active (102-2200-01-00-30)
Germicidal UV air treatment fixture · BACnet points list
UV Partners UV Angel Clean Air Active (102-2200-01-00-30) BACnet points list
Updated 12 November 2026Unofficial source
UV Angel Clean Air Active is an upper-room germicidal UV (GUV) air treatment unit with UV bulbs, filters and fans. On BACnet IP it reports bulb and filter life, treatment status and mode, built-in temperature, humidity, CO2, VOC and IAQ readings, and door, lamp and fan faults. The BMS can set the treatment mode and downlight brightness.
This page lists 20 BACnet objects for the UV Partners UV Angel Clean Air Active (102-2200-01-00-30) — 3 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of UV Partners’s documentation hosted by BACnet International catalog, not by UV Partners itself, so treat it as unofficial.
- Manufacturer
- UV Partners
- Model
- UV Angel Clean Air Active (102-2200-01-00-30)
- Equipment
- Germicidal UV air treatment fixture
- Equipment type
- Other equipment
- BACnet objects
- 20 (3 writable)
- Transport
- BACnet IP
- Firmware
- 4.5.5.0 (application 1.26.007.18.55.B1.S)
- Also known as
- UV Angel Clean Air Active, UV Angel, 102-2200-01-00-30, 102-2200-01-xx-30, air20, UV Angel BACnet
- Source document
- BACnet Protocol Implementation Conformance Statement, UV Angel Clean Air Active · rev. 2026-01-28 (unofficial copy, hosted by BACnet International catalog)
Reference only, provided as-is: verify against UV Partners’s current documentation and the live device before use. Not official UV Partners information. Terms of use.
BMS integration notes: UV Partners UV Angel Clean Air Active (102-2200-01-00-30)
Write AO 11 to pick standby or one of five speeds and read AI 9 to confirm the mode actually running. Watch BI 12 for treatment status and the door, lamp, fan and end-of-life flags for service needs.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AO 11 | Desired Treatment Mode | Treatment mode: 0 = standby, 1-5 = speed | Write |
| AI 9 | Reported Treatment Mode | Running mode; -1 = error | Read |
| BI 12 | UV Treatment Status | UV treatment active | Read |
| AI 0 | UV Bulb Remaining Life (%) | Bulb life left, % | Read |
| AI 1 | Air Filter Remaining Life (%) | Filter life left, % | Read |
| BI 14 | Lamp Error | Lamp needs troubleshooting | Read |
| BI 16 | Fan Error | Fans need troubleshooting | Read |
| BI 15 | Door Fault | Door fault | Read |
Enable & remote start
BO 19 BACnet Enabled must stay true; writing false reboots the unit into cloud-connected mode until told to return to BACnet mode.
Network setup
- BACnet IP only; normal or foreign-device mode, BBMD address and subscription lifetime are writable on the Network Port object.
- DHCP or static IP; static address, DNS and gateway are writable when DHCP is off.
- Device object name and device ID are writable.
Watch out for
- Writing BO 19 = false takes the unit off BACnet until it is switched back.
UV Partners UV Angel Clean Air Active (102-2200-01-00-30) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 0 | UV Bulb Remaining Life (%) | Remaining UV bulb life, 0-100 | % | Read | |
| AImin | 1 | Air Filter Remaining Life (%) | Remaining filter life, 0-100 | % | Read | |
| AI | 2 | Lifetime Treatment Duration (Seconds) | Total UV treatment time | s | Read | |
| AI | 3 | Boot Count (#) | Number of reboots | Read | ||
| AI | 4 | Sensor Value (TEMP) | Temperature, 10-50 | °C | Read | |
| AI | 5 | Sensor Value (HUMIDITY) | Relative humidity, 10-95 | % | Read | |
| AI | 6 | Sensor Value (CO2) | CO2, 0-10000 | ppm | Read | |
| AI | 7 | Sensor Value (VOC) | VOC, 0-1000 | ppm | Read | |
| AI | 8 | Sensor Value (IAQ) | IAQ score, 0-500 | Read | ||
| AImin | 9 | Reported Treatment Mode | Actual treatment mode | Read | -1=Error, 0=Standby, 1-5=static speeds | |
| AO | 10 | Downlight Brightness (%) | Downlight brightness, 0-100 (units with a downlight) | % | Write | |
| AOmin | 11 | Desired Treatment Mode | Treatment mode command | Write | 0=Standby, 1-5=static speeds | |
| BImin | 12 | UV Treatment Status | UV treatment running (bulbs and filters on) | Read | ||
| BI | 13 | Door Open | Maintenance door open | Read | 0=closed, 1=open | |
| BImin | 14 | Lamp Error | Lamp needs troubleshooting | Read | ||
| BImin | 15 | Door Fault | Door fault | Read | 0=No Fault, 1=Fault | |
| BImin | 16 | Fan Error | Fans need troubleshooting | Read | ||
| BI | 17 | Filter EOL | Filters at end of life | Read | ||
| BI | 18 | Lamp EOL | Lamp at end of life | Read | ||
| BO | 19 | BACnet Enabled | BACnet mode vs cloud mode; false reboots to cloud mode | Write |
No points match these filters.
Object ID lookup: UV Partners UV Angel Clean Air Active point IDs by name
AI0UV Bulb Remaining Life (%)AI1Air Filter Remaining Life (%)AI2Lifetime Treatment Duration (Seconds)AI3Boot Count (#)AI4Sensor Value (TEMP)AI5Sensor Value (HUMIDITY)AI6Sensor Value (CO2)AI7Sensor Value (VOC)AI8Sensor Value (IAQ)AI9Reported Treatment ModeAO10Downlight Brightness (%)AO11Desired Treatment ModeBI12UV Treatment StatusBI13Door OpenBI14Lamp ErrorBI15Door FaultBI16Fan ErrorBI17Filter EOLBI18Lamp EOLBO19BACnet Enabled
Integration notes
- The PICS prints no access column; the AOs and BO 19 are marked writable from their descriptions.
- BO 19 is printed as 'BO:19' under a Binary Values heading.
- Bulb and filter life reset when the bulbs and filters are replaced during maintenance.
- No units column; units come from the object names and descriptions.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the UV Angel Clean Air Active (102-2200-01-00-30) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the UV Partners UV Angel Clean Air Active (102-2200-01-00-30)
How many BACnet points does the UV Partners UV Angel Clean Air Active (102-2200-01-00-30) have?
This list has 20 BACnet objects: 10 analog inputs, 2 analog outputs, 7 binary inputs, 1 binary output. The exact set on a given unit depends on its firmware, installed options and configuration.
Which UV Partners UV Angel Clean Air Active (102-2200-01-00-30) BACnet points are writable?
3 of the 20 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official UV Partners UV Angel Clean Air Active (102-2200-01-00-30) BACnet documentation?
UV Partners does not publish it on its own website. This list comes from BACnet Protocol Implementation Conformance Statement, UV Angel Clean Air Active, revision 2026-01-28, a copy hosted by BACnet International catalog at https://www.bacnetinternational.net/catalog/manu/uv%20partners,%20inc/PICS%20air20_bacnet_final_2026jan28_revised.pdf. Ask UV Partners or its representative for the current revision.
What are the minimum BACnet points to integrate the UV Partners UV Angel Clean Air Active (102-2200-01-00-30)?
Start with AO 11 Desired Treatment Mode (Treatment mode: 0 = standby, 1-5 = speed); AI 9 Reported Treatment Mode (Running mode; -1 = error); BI 12 UV Treatment Status (UV treatment active); AI 0 UV Bulb Remaining Life (%) (Bulb life left, %); AI 1 Air Filter Remaining Life (%) (Filter life left, %); BI 14 Lamp Error (Lamp needs troubleshooting); BI 16 Fan Error (Fans need troubleshooting); BI 15 Door Fault (Door fault).
How do I enable BMS control of the UV Partners UV Angel Clean Air Active (102-2200-01-00-30)?
BO 19 BACnet Enabled must stay true; writing false reboots the unit into cloud-connected mode until told to return to BACnet mode.
How do I check these points on the real UV Angel Clean Air Active (102-2200-01-00-30)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
Source: BACnet Protocol Implementation Conformance Statement, UV Angel Clean Air Active · rev. 2026-01-28. Object names, instances and units are reproduced as published; descriptions are our own.