Easy BACnet
  1. Home
  2. BACnet points lists
  3. UV Partners
  4. UV Angel Clean Air Active (102-2200-01-00-30)

Germicidal UV air treatment fixture · BACnet points list

UV Partners UV Angel Clean Air Active (102-2200-01-00-30) BACnet points list

Updated 12 November 2026Unofficial source

Short answer

UV Angel Clean Air Active is an upper-room germicidal UV (GUV) air treatment unit with UV bulbs, filters and fans. On BACnet IP it reports bulb and filter life, treatment status and mode, built-in temperature, humidity, CO2, VOC and IAQ readings, and door, lamp and fan faults. The BMS can set the treatment mode and downlight brightness.

This page lists 20 BACnet objects for the UV Partners UV Angel Clean Air Active (102-2200-01-00-30) — 3 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of UV Partners’s documentation hosted by BACnet International catalog, not by UV Partners itself, so treat it as unofficial.

Manufacturer
UV Partners
Model
UV Angel Clean Air Active (102-2200-01-00-30)
Equipment
Germicidal UV air treatment fixture
Equipment type
Other equipment
BACnet objects
20 (3 writable)
Transport
BACnet IP
Firmware
4.5.5.0 (application 1.26.007.18.55.B1.S)
Also known as
UV Angel Clean Air Active, UV Angel, 102-2200-01-00-30, 102-2200-01-xx-30, air20, UV Angel BACnet
Source document
BACnet Protocol Implementation Conformance Statement, UV Angel Clean Air Active · rev. 2026-01-28 (unofficial copy, hosted by BACnet International catalog)
Download CSV 20 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against UV Partners’s current documentation and the live device before use. Not official UV Partners information. Terms of use.

BMS integration notes: UV Partners UV Angel Clean Air Active (102-2200-01-00-30)

Integration in brief

Write AO 11 to pick standby or one of five speeds and read AI 9 to confirm the mode actually running. Watch BI 12 for treatment status and the door, lamp, fan and end-of-life flags for service needs.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AO 11Desired Treatment ModeTreatment mode: 0 = standby, 1-5 = speedWrite
AI 9Reported Treatment ModeRunning mode; -1 = errorRead
BI 12UV Treatment StatusUV treatment activeRead
AI 0UV Bulb Remaining Life (%)Bulb life left, %Read
AI 1Air Filter Remaining Life (%)Filter life left, %Read
BI 14Lamp ErrorLamp needs troubleshootingRead
BI 16Fan ErrorFans need troubleshootingRead
BI 15Door FaultDoor faultRead

Enable & remote start

BO 19 BACnet Enabled must stay true; writing false reboots the unit into cloud-connected mode until told to return to BACnet mode.

Network setup

Watch out for

UV Partners UV Angel Clean Air Active (102-2200-01-00-30) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

20 of 20 shown
Type
Access
Show
UV Partners UV Angel Clean Air Active (102-2200-01-00-30) BACnet Points List
DescriptionStates
AImin0UV Bulb Remaining Life (%)Remaining UV bulb life, 0-100%Read
AImin1Air Filter Remaining Life (%)Remaining filter life, 0-100%Read
AI2Lifetime Treatment Duration (Seconds)Total UV treatment timesRead
AI3Boot Count (#)Number of rebootsRead
AI4Sensor Value (TEMP)Temperature, 10-50°CRead
AI5Sensor Value (HUMIDITY)Relative humidity, 10-95%Read
AI6Sensor Value (CO2)CO2, 0-10000ppmRead
AI7Sensor Value (VOC)VOC, 0-1000ppmRead
AI8Sensor Value (IAQ)IAQ score, 0-500Read
AImin9Reported Treatment ModeActual treatment modeRead-1=Error, 0=Standby, 1-5=static speeds
AO10Downlight Brightness (%)Downlight brightness, 0-100 (units with a downlight)%Write
AOmin11Desired Treatment ModeTreatment mode commandWrite0=Standby, 1-5=static speeds
BImin12UV Treatment StatusUV treatment running (bulbs and filters on)Read
BI13Door OpenMaintenance door openRead0=closed, 1=open
BImin14Lamp ErrorLamp needs troubleshootingRead
BImin15Door FaultDoor faultRead0=No Fault, 1=Fault
BImin16Fan ErrorFans need troubleshootingRead
BI17Filter EOLFilters at end of lifeRead
BI18Lamp EOLLamp at end of lifeRead
BO19BACnet EnabledBACnet mode vs cloud mode; false reboots to cloud modeWrite
Object ID lookup: UV Partners UV Angel Clean Air Active point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the UV Angel Clean Air Active (102-2200-01-00-30) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the UV Partners UV Angel Clean Air Active (102-2200-01-00-30)

How many BACnet points does the UV Partners UV Angel Clean Air Active (102-2200-01-00-30) have?

This list has 20 BACnet objects: 10 analog inputs, 2 analog outputs, 7 binary inputs, 1 binary output. The exact set on a given unit depends on its firmware, installed options and configuration.

Which UV Partners UV Angel Clean Air Active (102-2200-01-00-30) BACnet points are writable?

3 of the 20 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official UV Partners UV Angel Clean Air Active (102-2200-01-00-30) BACnet documentation?

UV Partners does not publish it on its own website. This list comes from BACnet Protocol Implementation Conformance Statement, UV Angel Clean Air Active, revision 2026-01-28, a copy hosted by BACnet International catalog at https://www.bacnetinternational.net/catalog/manu/uv%20partners,%20inc/PICS%20air20_bacnet_final_2026jan28_revised.pdf. Ask UV Partners or its representative for the current revision.

What are the minimum BACnet points to integrate the UV Partners UV Angel Clean Air Active (102-2200-01-00-30)?

Start with AO 11 Desired Treatment Mode (Treatment mode: 0 = standby, 1-5 = speed); AI 9 Reported Treatment Mode (Running mode; -1 = error); BI 12 UV Treatment Status (UV treatment active); AI 0 UV Bulb Remaining Life (%) (Bulb life left, %); AI 1 Air Filter Remaining Life (%) (Filter life left, %); BI 14 Lamp Error (Lamp needs troubleshooting); BI 16 Fan Error (Fans need troubleshooting); BI 15 Door Fault (Door fault).

How do I enable BMS control of the UV Partners UV Angel Clean Air Active (102-2200-01-00-30)?

BO 19 BACnet Enabled must stay true; writing false reboots the unit into cloud-connected mode until told to return to BACnet mode.

How do I check these points on the real UV Angel Clean Air Active (102-2200-01-00-30)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: BACnet Protocol Implementation Conformance Statement, UV Angel Clean Air Active · rev. 2026-01-28. Object names, instances and units are reproduced as published; descriptions are our own.