Thermal energy meter · BACnet points list
Sontex BACnet MS/TP module for Supercal 531 / Superstatic 440 / Superstatic 449 BACnet points list
Updated 12 November 2026Unofficial source
The Sontex BACnet MS/TP module plugs into a Supercal 531 / Superstatic 449 integrator (or a Superstatic 440 meter) and serves its readings as read-only Analog Inputs: energy and volume totals and per-tariff values, two auxiliary pulse counters, flow and return temperatures, power, flow and running hours, plus the same totals stored on two set days. Units follow the meter's configuration.
This page lists 31 BACnet objects for the Sontex BACnet MS/TP module for Supercal 531 / Superstatic 440 / Superstatic 449 — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Sontex’s documentation hosted by BACnet International, not by Sontex itself, so treat it as unofficial.
- Manufacturer
- Sontex
- Model
- BACnet MS/TP module for Supercal 531 / Superstatic 440 / Superstatic 449
- Equipment
- Thermal energy meter
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 31 (0 writable)
- Transport
- BACnet MS/TP
- Firmware
- Supercal 531 / Superstatic 449 FW 3.7 or later; module software since V2.42.0.10
- Default device instance
- Unique ID from the module MCU (readable in Prog531 / Prog449)
- Also known as
- Supercal 531 BACnet, Superstatic 440 BACnet, Superstatic 449 BACnet, 0531A071, Sontex BACnet MS/TP module
- Source document
- BACnet MS/TP module for Sontex Thermal Energy Meters (data sheet with PICS) · rev. 28-10-2016 (unofficial copy, hosted by BACnet International)
Reference only, provided as-is: verify against Sontex’s current documentation and the live device before use. Not official Sontex information. Terms of use.
BMS integration notes: Sontex BACnet MS/TP module for Supercal 531 / Superstatic 440 / Superstatic 449
Set a unique MS/TP MAC address with Prog531 / Prog449 (the default 255 is auto-MAC), read the device instance from the software, then read energy, power, flow and temperatures.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 0 | AI-0-Energy | Energy total | Read |
| AI 10 | AI-10-Power | Thermal power, W or kW | Read |
| AI 11 | AI-11-Flow | Flow, m3/h | Read |
| AI 8 | AI-8–High-temperature | High (flow) temperature, °C | Read |
| AI 9 | AI-9–Low-temperature | Low (return) temperature, °C | Read |
| AI 1 | AI-1-Volume | Volume total | Read |
Network setup
- MS/TP master or slave, MAC 0-127; default MAC 255 (AutoMAC). Change it with Prog531 / Prog449.
- Baud 9600-115200 or auto baud.
- Bus termination by DIP switch S1.
Watch out for
- Energy and volume units depend on the meter configuration (MJ, GJ, Wh, kWh, MWh, BTU; m3 or US gallons).
Sontex BACnet MS/TP module for Supercal 531 / Superstatic 440 / Superstatic 449 BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 0 | AI-0-Energy | Energy total | MJ, GJ, Wh, kWh, MWh, BTU | Read | |
| AImin | 1 | AI-1-Volume | Volume total | m3, USGallon | Read | |
| AI | 2 | AI-2-Energy-T1 | Energy, tariff 1 | MJ, GJ, Wh, kWh, MWh, BTU | Read | |
| AI | 3 | AI-3-Volume-T1 | Volume, tariff 1 | m3, USGallon | Read | |
| AI | 4 | AI-4-Energy-T2 | Energy, tariff 2 | MJ, GJ, Wh, kWh, MWh, BTU | Read | |
| AI | 5 | AI-5-Volume-T2 | Volume, tariff 2 | m3, USGallon | Read | |
| AI | 6 | AI-6-Auxiliary-A1 | Auxiliary pulse input 1 | none, MJ, GJ, Wh, kWh, MWh, BTU, m3, USGallon | Read | |
| AI | 7 | AI-7-Auxiliary-A2 | Auxiliary pulse input 2 | none, MJ, GJ, Wh, kWh, MWh, BTU, m3, USGallon | Read | |
| AImin | 8 | AI-8–High-temperature | High (flow) temperature | °C | Read | |
| AImin | 9 | AI-9–Low-temperature | Low (return) temperature | °C | Read | |
| AImin | 10 | AI-10-Power | Thermal power | W, kW | Read | |
| AImin | 11 | AI-11-Flow | Flow rate | m3/h | Read | |
| AI | 12 | AI-12-Runnings-hours | Running hours | Hours | Read | |
| CAL | 0 | CA-0-Set-Day1 | Stored-value set day 1 | Read | ||
| AI | 13 | AI-13-Energy-stored-ST1 | Energy total, stored on set day 1 | MJ, GJ, Wh, kWh, MWh, BTU | Read | |
| AI | 14 | AI-14-Volume-stored ST1 | Volume total, stored on set day 1 | m3, USGallon | Read | |
| AI | 15 | AI-15-Energy-T1-stored ST1 | Energy, tariff 1, stored on set day 1 | MJ, GJ, Wh, kWh, MWh, BTU | Read | |
| AI | 16 | AI-16-Volume-T1-stored-ST1 | Volume, tariff 1, stored on set day 1 | m3, USGallon | Read | |
| AI | 17 | AI-17-Energy-T2-stored ST1 | Energy, tariff 2, stored on set day 1 | MJ, GJ, Wh, kWh, MWh, BTU | Read | |
| AI | 18 | AI-18-Volume-T2-stored-ST1 | Volume, tariff 2, stored on set day 1 | m3, USGallon | Read | |
| AI | 19 | AI-19-Auxiliary-A1-stored-ST1 | Auxiliary pulse input 1, stored on set day 1 | none, MJ, GJ, Wh, kWh, MWh, BTU, m3, USGallon | Read | |
| AI | 20 | AI-20-Auxiliary-A2-stored-ST1 | Auxiliary pulse input 2, stored on set day 1 | none, MJ, GJ, Wh, kWh, MWh, BTU, m3, USGallon | Read | |
| CAL | 0 | CA-0-Set-Day2 | Stored-value set day 2 | Read | ||
| AI | 21 | AI-21-Energy-stored-ST2 | Energy total, stored on set day 2 | MJ, GJ, Wh, kWh, MWh, BTU | Read | |
| AI | 22 | AI-22-Volume-stored ST2 | Volume total, stored on set day 2 | m3, USGallon | Read | |
| AI | 23 | AI-23-Energy-T1-stored ST2 | Energy, tariff 1, stored on set day 2 | MJ, GJ, Wh, kWh, MWh, BTU | Read | |
| AI | 24 | AI-24-Volume-T1-stored-ST2 | Volume, tariff 1, stored on set day 2 | m3, USGallon | Read | |
| AI | 25 | AI-25-Energy-T2-stored ST2 | Energy, tariff 2, stored on set day 2 | MJ, GJ, Wh, kWh, MWh, BTU | Read | |
| AI | 26 | AI-26-Volume-T2-stored-ST2 | Volume, tariff 2, stored on set day 2 | m3, USGallon | Read | |
| AI | 27 | AI-27-Auxiliary-A1-stored-ST2 | Auxiliary pulse input 1, stored on set day 2 | none, MJ, GJ, Wh, kWh, MWh, BTU, m3, USGallon | Read | |
| AI | 28 | AI-28-Auxiliary-A2-stored-ST2 | Auxiliary pulse input 2, stored on set day 2 | none, MJ, GJ, Wh, kWh, MWh, BTU, m3, USGallon | Read |
No points match these filters.
Object ID lookup: Sontex BACnet MS/TP module for Supercal 531 / Superstatic 440 / Superstatic 449 point IDs by name
AI0AI-0-EnergyAI1AI-1-VolumeAI2AI-2-Energy-T1AI3AI-3-Volume-T1AI4AI-4-Energy-T2AI5AI-5-Volume-T2AI6AI-6-Auxiliary-A1AI7AI-7-Auxiliary-A2AI8AI-8–High-temperatureAI9AI-9–Low-temperatureAI10AI-10-PowerAI11AI-11-FlowAI12AI-12-Runnings-hoursCAL0CA-0-Set-Day1AI13AI-13-Energy-stored-ST1AI14AI-14-Volume-stored ST1AI15AI-15-Energy-T1-stored ST1AI16AI-16-Volume-T1-stored-ST1AI17AI-17-Energy-T2-stored ST1AI18AI-18-Volume-T2-stored-ST1AI19AI-19-Auxiliary-A1-stored-ST1AI20AI-20-Auxiliary-A2-stored-ST1CAL0CA-0-Set-Day2AI21AI-21-Energy-stored-ST2AI22AI-22-Volume-stored ST2AI23AI-23-Energy-T1-stored ST2AI24AI-24-Volume-T1-stored-ST2AI25AI-25-Energy-T2-stored ST2AI26AI-26-Volume-T2-stored-ST2AI27AI-27-Auxiliary-A1-stored-ST2AI28AI-28-Auxiliary-A2-stored-ST2
Integration notes
- Object names carry the instance (e.g. 'AI-10-Power'); they are kept as printed.
- Both set-day date objects are printed as 'CA-0' (CA-0-Set-Day1 and CA-0-Set-Day2); they are listed as printed, so the second one clashes with the first. They hold a BACnet date (year, month, day). Check the second calendar's real instance with a device scan.
- Units are a list of allowed units; the one in use depends on the meter setup.
- The data sheet gives no read/write column; all objects are measurements and are listed read-only.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the BACnet MS/TP module for Supercal 531 / Superstatic 440 / Superstatic 449 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Sontex BACnet MS/TP module for Supercal 531 / Superstatic 440 / Superstatic 449
How many BACnet points does the Sontex BACnet MS/TP module for Supercal 531 / Superstatic 440 / Superstatic 449 have?
This list has 31 BACnet objects: 29 analog inputs, 2 calendars. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Sontex BACnet MS/TP module for Supercal 531 / Superstatic 440 / Superstatic 449 BACnet points are writable?
None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.
Where is the official Sontex BACnet MS/TP module for Supercal 531 / Superstatic 440 / Superstatic 449 BACnet documentation?
Sontex does not publish it on its own website. This list comes from BACnet MS/TP module for Sontex Thermal Energy Meters (data sheet with PICS), revision 28-10-2016, a copy hosted by BACnet International at https://www.bacnetinternational.net/catalog/manu/sontex%20sa/data_sheet_bacnet_ms-tp_module_en_28-10-2016.pdf. Ask Sontex or its representative for the current revision.
What are the minimum BACnet points to integrate the Sontex BACnet MS/TP module for Supercal 531 / Superstatic 440 / Superstatic 449?
Start with AI 0 AI-0-Energy (Energy total); AI 10 AI-10-Power (Thermal power, W or kW); AI 11 AI-11-Flow (Flow, m3/h); AI 8 AI-8–High-temperature (High (flow) temperature, °C); AI 9 AI-9–Low-temperature (Low (return) temperature, °C); AI 1 AI-1-Volume (Volume total).
How do I check these points on the real BACnet MS/TP module for Supercal 531 / Superstatic 440 / Superstatic 449?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
Source: BACnet MS/TP module for Sontex Thermal Energy Meters (data sheet with PICS) · rev. 28-10-2016. Object names, instances and units are reproduced as published; descriptions are our own.