- DIRIS Digiware M-50 / M-70 BACnet IP gateway (per-load measurement objects)
Power meter gateway (electrical measurement) · BACnet points list
Socomec DIRIS Digiware M-50 / M-70 BACnet IP gateway (per-load measurement objects) BACnet points list
Updated 12 November 2026Unofficial source
The DIRIS Digiware M-50 / M-70 is a BACnet IP gateway for Socomec metering. Each downstream device appears as its own BACnet device (instance 100 + its Modbus address) with Analog Input objects per load: voltages, currents, unbalance, active, reactive and apparent power and power factor per phase and total, load-curve values, THD and energy counters. The object number is the load number times 100 plus a fixed measurement index (0-61); this list shows load 1.
This page lists 62 BACnet objects for the Socomec DIRIS Digiware M-50 / M-70 BACnet IP gateway (per-load measurement objects) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Socomec’s documentation hosted by Instrumentation2000, not by Socomec itself, so treat it as unofficial.
- Manufacturer
- Socomec
- Model
- DIRIS Digiware M-50 / M-70 BACnet IP gateway (per-load measurement objects)
- Equipment
- Power meter gateway (electrical measurement)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 62 (0 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Default device instance
- 100
- Also known as
- DIRIS Digiware M-50, DIRIS Digiware M-70, Digiware M-50, Digiware M-70, M-50, M-70, 548751D, DIRIS Digiware BACnet
- Source document
- DIRIS Digiware M-50 / M-70 instruction manual, Annex B BACnet communication · 548751D (unofficial copy, hosted by Instrumentation2000)
Reference only, provided as-is: verify against Socomec’s current documentation and the live device before use. Not official Socomec information. Terms of use.
BMS integration notes: Socomec DIRIS Digiware M-50 / M-70 BACnet IP gateway (per-load measurement objects)
Discover one BACnet device per metered device (instance 100 + Modbus address) behind the gateway, then read the per-load Analog Inputs: total power, energy, current, voltage and power factor. All values are read-only.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 121 | TotalPowerActive | Total active power, W (load 1) | Read |
| AI 156 | A+ | Imported active energy, Wh (load 1) | Read |
| AI 102 | CurrentSyst | System current, A (load 1) | Read |
| AI 100 | VystPhN | System phase-neutral voltage, V (load 1) | Read |
| AI 124 | TotalPowerFactor | Total power factor (load 1) | Read |
| AI 103 | Frequency | Frequency, Hz (load 1) | Read |
Enable & remote start
BACnet IP is switched on in Easy Config System or the web server (BACnet activation).
Network setup
- Main instance ID defaults to 100 and must be unique; a virtual network ID must also be set and be unique.
- UDP port is fixed at 47808.
- The PICS is on socomec.com.
Watch out for
- Object numbers repeat per load: load 2 adds 100 to every instance.
- Unsupported measurements read 0, not an error.
Socomec DIRIS Digiware M-50 / M-70 BACnet IP gateway (per-load measurement objects) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 100 | VystPhN | System Ph-N Voltage (index 0, unsigned) | V | Read | |
| AI | 101 | VystPhPh | System Ph-Ph Voltage (index 1, unsigned) | V | Read | |
| AImin | 102 | CurrentSyst | System Current (index 2, unsigned) | A | Read | |
| AImin | 103 | Frequency | System Frequency (index 3, unsigned) | Hz | Read | |
| AI | 104 | VoltPhNV1 | Ph-N Voltage V1 (index 4, unsigned) | V | Read | |
| AI | 105 | VoltPhNV2 | Ph-N Voltage V2 (index 5, unsigned) | V | Read | |
| AI | 106 | VoltPhNV3 | Ph-N Voltage V3 (index 6, unsigned) | V | Read | |
| AI | 107 | VoltPhNVn | Ph-N Voltage Vn (index 7, unsigned) | V | Read | |
| AI | 108 | VoltPhPhU12 | Ph-Ph Voltage U12 (index 8, unsigned) | V | Read | |
| AI | 109 | VoltPhPhU23 | Ph-Ph Voltage U23 (index 9, unsigned) | V | Read | |
| AI | 110 | VoltPhPhU31 | Ph-Ph Voltage U31 (index 10, unsigned) | V | Read | |
| AI | 111 | CurrentI1 | Current I1 (index 11, unsigned) | A | Read | |
| AI | 112 | CurrentI2 | Current I2 (index 12, unsigned) | A | Read | |
| AI | 113 | CurrentI3 | Current I3 (index 13, unsigned) | A | Read | |
| AI | 114 | CurrentIn | Current In (index 14, unsigned) | A | Read | |
| AI | 115 | CurrentInba | Current Inba (index 15, unsigned) | % | Read | |
| AI | 116 | CurrentIdir | Current Idir (index 16, unsigned) | A | Read | |
| AI | 117 | CurrentIinv | Current Iinv (index 17, unsigned) | A | Read | |
| AI | 118 | CurrentIhom | Current Ihom (index 18, unsigned) | A | Read | |
| AI | 119 | CurrentInb | Current Inb (index 19, unsigned) | % | Read | |
| AI | 120 | PowerApparentNom | Nominal Apparent Power (index 20, unsigned) | VA | Read | |
| AImin | 121 | TotalPowerActive | Total Active Power (index 21, signed) | W | Read | |
| AI | 122 | TotalPowerRActive | Total Reactive Power (index 22, signed) | var | Read | |
| AI | 123 | TotalPowerApparent | Total Apparent Power (index 23, unsigned) | VA | Read | |
| AImin | 124 | TotalPowerFactor | Total Power Factor (index 24, signed) | Read | ||
| AI | 125 | TotalPowerFactorType | Total Power Factor Type (index 25, unsigned) | Read | ||
| AI | 126 | PowerActiveP1 | P1 Active Power (index 26, signed) | W | Read | |
| AI | 127 | PowerActiveP2 | P2 Active Power (index 27, signed) | W | Read | |
| AI | 128 | PowerActiveP3 | P3 Active Power (index 28, signed) | W | Read | |
| AI | 129 | PowerRActiveQ1 | Q1 Reactive Power (index 29, signed) | var | Read | |
| AI | 130 | PowerRActiveQ2 | Q2 Reactive Power (index 30, signed) | var | Read | |
| AI | 131 | PowerRActiveQ3 | Q3 Reactive Power (index 31, signed) | var | Read | |
| AI | 132 | PowerApparentS1 | S1 Apparent Power (index 32, unsigned) | VA | Read | |
| AI | 133 | PowerApparentS2 | S2 Apparent Power (index 33, unsigned) | VA | Read | |
| AI | 134 | PowerApparentS3 | S3 Apparent Power (index 34, unsigned) | VA | Read | |
| AI | 135 | PowerFactorPF1 | PF1 Power Factor (index 35, signed) | Read | ||
| AI | 136 | PowerFactorTypeSPF1 | sPF1 Power Factor Type (index 36, unsigned) | Read | ||
| AI | 137 | PowerFactorPF2 | PF2 Power Factor (index 37, signed) | Read | ||
| AI | 138 | PowerFactorTypeSPF2 | sPF1 Power Factor Type (index 38, unsigned) | Read | ||
| AI | 139 | PowerFactorPF3 | PF3 Power Factor (index 39, signed) | Read | ||
| AI | 140 | PowerFactorTypeSPF3 | sPF1 Power Factor Type (index 40, unsigned) | Read | ||
| AI | 141 | LoadCurve_P+ | Load Curve Positive Active Power (index 41, unsigned) | W | Read | |
| AI | 142 | LoadCurve_P- | Load Curve Negative Active Power (index 42, unsigned) | W | Read | |
| AI | 143 | LoadCurve_Q+ | Load Curve Positive Reactive Power (index 43, unsigned) | var | Read | |
| AI | 144 | LoadCurve_Q- | Load Curve Negative Reactive Power (index 44, unsigned) | var | Read | |
| AI | 145 | LoadCurve_S | Load Curve Apparent Power (index 45, unsigned) | VA | Read | |
| AI | 146 | THD_I1 | THD I1 (index 46, unsigned) | % | Read | |
| AI | 147 | THD_I2 | THD I2 (index 47, unsigned) | % | Read | |
| AI | 148 | THD_I3 | THD I3 (index 48, unsigned) | % | Read | |
| AI | 149 | THD_In | THD In (index 49, unsigned) | % | Read | |
| AI | 150 | THD_V1 | THD V1 (index 50, unsigned) | % | Read | |
| AI | 151 | THD_V2 | THD V2 (index 51, unsigned) | % | Read | |
| AI | 152 | THD_V3 | THD V3 (index 52, unsigned) | % | Read | |
| AI | 153 | THD_U12 | THD U12 (index 53, unsigned) | % | Read | |
| AI | 154 | THD_U23 | THD U23 (index 54, unsigned) | % | Read | |
| AI | 155 | THD_U31 | THD U31 (index 55, unsigned) | % | Read | |
| AImin | 156 | A+ | Positive Active Energy (index 56, unsigned) | Wh | Read | |
| AI | 157 | A- | Negative Active Energy (index 57, unsigned) | Wh | Read | |
| AI | 158 | ER+ | Positive Reactive Energy (index 58, unsigned) | varh | Read | |
| AI | 159 | ER- | Negative Reactive Energy (index 59, unsigned) | varh | Read | |
| AI | 160 | ES | Apparent Energy (index 60, unsigned) | VAh | Read | |
| AI | 161 | Mff | Multifluid feeder (index 61, signed) | Read |
No points match these filters.
Object ID lookup: Socomec DIRIS Digiware M-50 / M-70 BACnet IP gateway point IDs by name
AI100VystPhNAI101VystPhPhAI102CurrentSystAI103FrequencyAI104VoltPhNV1AI105VoltPhNV2AI106VoltPhNV3AI107VoltPhNVnAI108VoltPhPhU12AI109VoltPhPhU23AI110VoltPhPhU31AI111CurrentI1AI112CurrentI2AI113CurrentI3AI114CurrentInAI115CurrentInbaAI116CurrentIdirAI117CurrentIinvAI118CurrentIhomAI119CurrentInbAI120PowerApparentNomAI121TotalPowerActiveAI122TotalPowerRActiveAI123TotalPowerApparentAI124TotalPowerFactorAI125TotalPowerFactorTypeAI126PowerActiveP1AI127PowerActiveP2AI128PowerActiveP3AI129PowerRActiveQ1AI130PowerRActiveQ2AI131PowerRActiveQ3AI132PowerApparentS1AI133PowerApparentS2AI134PowerApparentS3AI135PowerFactorPF1AI136PowerFactorTypeSPF1AI137PowerFactorPF2AI138PowerFactorTypeSPF2AI139PowerFactorPF3AI140PowerFactorTypeSPF3AI141LoadCurve_P+AI142LoadCurve_P-AI143LoadCurve_Q+AI144LoadCurve_Q-AI145LoadCurve_SAI146THD_I1AI147THD_I2AI148THD_I3AI149THD_InAI150THD_V1AI151THD_V2AI152THD_V3AI153THD_U12AI154THD_U23AI155THD_U31AI156A+AI157A-AI158ER+AI159ER-AI160ESAI161Mff
Integration notes
- Only the index table is printed. Instance = load number x 100 + index (load 1 = AI 100-161, load 2 = AI 200-261 and so on); load 1 is listed here.
- Device instances: the gateway itself is the main instance (default 100); a downstream device with Modbus address xx is device 100 + xx.
- A device returns 0 for measurements it does not support (for example THD on a DIRIS Digiware I-30).
- The manual also mentions Binary Input and Binary Output objects (auxiliary contacts, IO-10 outputs) but gives no table for them; they are not listed.
- The guide gives no read/write column; all listed measurement objects are read-only values.
- Copied from a distributor-hosted copy of the Socomec manual; socomec.com blocks automated downloads.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the DIRIS Digiware M-50 / M-70 BACnet IP gateway (per-load measurement objects) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Socomec DIRIS Digiware M-50 / M-70 BACnet IP gateway (per-load measurement objects)
How many BACnet points does the Socomec DIRIS Digiware M-50 / M-70 BACnet IP gateway (per-load measurement objects) have?
This list has 62 BACnet objects: 62 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Socomec DIRIS Digiware M-50 / M-70 BACnet IP gateway (per-load measurement objects) BACnet points are writable?
None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.
Where is the official Socomec DIRIS Digiware M-50 / M-70 BACnet IP gateway (per-load measurement objects) BACnet documentation?
Socomec does not publish it on its own website. This list comes from DIRIS Digiware M-50 / M-70 instruction manual, Annex B BACnet communication (548751D), a copy hosted by Instrumentation2000 at https://www.instrumentation2000.com//media/pdf/socomec-m-50-m-70-manual.pdf. Ask Socomec or its representative for the current revision.
What are the minimum BACnet points to integrate the Socomec DIRIS Digiware M-50 / M-70 BACnet IP gateway (per-load measurement objects)?
Start with AI 121 TotalPowerActive (Total active power, W (load 1)); AI 156 A+ (Imported active energy, Wh (load 1)); AI 102 CurrentSyst (System current, A (load 1)); AI 100 VystPhN (System phase-neutral voltage, V (load 1)); AI 124 TotalPowerFactor (Total power factor (load 1)); AI 103 Frequency (Frequency, Hz (load 1)).
How do I enable BMS control of the Socomec DIRIS Digiware M-50 / M-70 BACnet IP gateway (per-load measurement objects)?
BACnet IP is switched on in Easy Config System or the web server (BACnet activation).
How do I check these points on the real DIRIS Digiware M-50 / M-70 BACnet IP gateway (per-load measurement objects)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
Source: DIRIS Digiware M-50 / M-70 instruction manual, Annex B BACnet communication · 548751D. Object names, instances and units are reproduced as published; descriptions are our own.