Socomec DIRIS Digiware M-50 / M-70 BACnet IP gateway (per-load measurement objects) BACnet points list

Updated 12 November 2026Unofficial source

Short answer

The DIRIS Digiware M-50 / M-70 is a BACnet IP gateway for Socomec metering. Each downstream device appears as its own BACnet device (instance 100 + its Modbus address) with Analog Input objects per load: voltages, currents, unbalance, active, reactive and apparent power and power factor per phase and total, load-curve values, THD and energy counters. The object number is the load number times 100 plus a fixed measurement index (0-61); this list shows load 1.

This page lists 62 BACnet objects for the Socomec DIRIS Digiware M-50 / M-70 BACnet IP gateway (per-load measurement objects) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Socomec’s documentation hosted by Instrumentation2000, not by Socomec itself, so treat it as unofficial.

Manufacturer
Socomec
Model
DIRIS Digiware M-50 / M-70 BACnet IP gateway (per-load measurement objects)
Equipment
Power meter gateway (electrical measurement)
Equipment type
Thermostats, sensors & meters
BACnet objects
62 (0 writable)
Transport
BACnet IP
Firmware
Not stated
Default device instance
100
Also known as
DIRIS Digiware M-50, DIRIS Digiware M-70, Digiware M-50, Digiware M-70, M-50, M-70, 548751D, DIRIS Digiware BACnet
Source document
DIRIS Digiware M-50 / M-70 instruction manual, Annex B BACnet communication · 548751D (unofficial copy, hosted by Instrumentation2000)
Download CSV 62 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Socomec’s current documentation and the live device before use. Not official Socomec information. Terms of use.

BMS integration notes: Socomec DIRIS Digiware M-50 / M-70 BACnet IP gateway (per-load measurement objects)

Integration in brief

Discover one BACnet device per metered device (instance 100 + Modbus address) behind the gateway, then read the per-load Analog Inputs: total power, energy, current, voltage and power factor. All values are read-only.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 121TotalPowerActiveTotal active power, W (load 1)Read
AI 156A+Imported active energy, Wh (load 1)Read
AI 102CurrentSystSystem current, A (load 1)Read
AI 100VystPhNSystem phase-neutral voltage, V (load 1)Read
AI 124TotalPowerFactorTotal power factor (load 1)Read
AI 103FrequencyFrequency, Hz (load 1)Read

Enable & remote start

BACnet IP is switched on in Easy Config System or the web server (BACnet activation).

Network setup

Watch out for

Socomec DIRIS Digiware M-50 / M-70 BACnet IP gateway (per-load measurement objects) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

62 of 62 shown
Type
Analog
Show
Socomec DIRIS Digiware M-50 / M-70 BACnet IP gateway (per-load measurement objects) BACnet Points List
DescriptionStates
AImin100VystPhNSystem Ph-N Voltage (index 0, unsigned)VRead
AI101VystPhPhSystem Ph-Ph Voltage (index 1, unsigned)VRead
AImin102CurrentSystSystem Current (index 2, unsigned)ARead
AImin103FrequencySystem Frequency (index 3, unsigned)HzRead
AI104VoltPhNV1Ph-N Voltage V1 (index 4, unsigned)VRead
AI105VoltPhNV2Ph-N Voltage V2 (index 5, unsigned)VRead
AI106VoltPhNV3Ph-N Voltage V3 (index 6, unsigned)VRead
AI107VoltPhNVnPh-N Voltage Vn (index 7, unsigned)VRead
AI108VoltPhPhU12Ph-Ph Voltage U12 (index 8, unsigned)VRead
AI109VoltPhPhU23Ph-Ph Voltage U23 (index 9, unsigned)VRead
AI110VoltPhPhU31Ph-Ph Voltage U31 (index 10, unsigned)VRead
AI111CurrentI1Current I1 (index 11, unsigned)ARead
AI112CurrentI2Current I2 (index 12, unsigned)ARead
AI113CurrentI3Current I3 (index 13, unsigned)ARead
AI114CurrentInCurrent In (index 14, unsigned)ARead
AI115CurrentInbaCurrent Inba (index 15, unsigned)%Read
AI116CurrentIdirCurrent Idir (index 16, unsigned)ARead
AI117CurrentIinvCurrent Iinv (index 17, unsigned)ARead
AI118CurrentIhomCurrent Ihom (index 18, unsigned)ARead
AI119CurrentInbCurrent Inb (index 19, unsigned)%Read
AI120PowerApparentNomNominal Apparent Power (index 20, unsigned)VARead
AImin121TotalPowerActiveTotal Active Power (index 21, signed)WRead
AI122TotalPowerRActiveTotal Reactive Power (index 22, signed)varRead
AI123TotalPowerApparentTotal Apparent Power (index 23, unsigned)VARead
AImin124TotalPowerFactorTotal Power Factor (index 24, signed)Read
AI125TotalPowerFactorTypeTotal Power Factor Type (index 25, unsigned)Read
AI126PowerActiveP1P1 Active Power (index 26, signed)WRead
AI127PowerActiveP2P2 Active Power (index 27, signed)WRead
AI128PowerActiveP3P3 Active Power (index 28, signed)WRead
AI129PowerRActiveQ1Q1 Reactive Power (index 29, signed)varRead
AI130PowerRActiveQ2Q2 Reactive Power (index 30, signed)varRead
AI131PowerRActiveQ3Q3 Reactive Power (index 31, signed)varRead
AI132PowerApparentS1S1 Apparent Power (index 32, unsigned)VARead
AI133PowerApparentS2S2 Apparent Power (index 33, unsigned)VARead
AI134PowerApparentS3S3 Apparent Power (index 34, unsigned)VARead
AI135PowerFactorPF1PF1 Power Factor (index 35, signed)Read
AI136PowerFactorTypeSPF1sPF1 Power Factor Type (index 36, unsigned)Read
AI137PowerFactorPF2PF2 Power Factor (index 37, signed)Read
AI138PowerFactorTypeSPF2sPF1 Power Factor Type (index 38, unsigned)Read
AI139PowerFactorPF3PF3 Power Factor (index 39, signed)Read
AI140PowerFactorTypeSPF3sPF1 Power Factor Type (index 40, unsigned)Read
AI141LoadCurve_P+Load Curve Positive Active Power (index 41, unsigned)WRead
AI142LoadCurve_P-Load Curve Negative Active Power (index 42, unsigned)WRead
AI143LoadCurve_Q+Load Curve Positive Reactive Power (index 43, unsigned)varRead
AI144LoadCurve_Q-Load Curve Negative Reactive Power (index 44, unsigned)varRead
AI145LoadCurve_SLoad Curve Apparent Power (index 45, unsigned)VARead
AI146THD_I1THD I1 (index 46, unsigned)%Read
AI147THD_I2THD I2 (index 47, unsigned)%Read
AI148THD_I3THD I3 (index 48, unsigned)%Read
AI149THD_InTHD In (index 49, unsigned)%Read
AI150THD_V1THD V1 (index 50, unsigned)%Read
AI151THD_V2THD V2 (index 51, unsigned)%Read
AI152THD_V3THD V3 (index 52, unsigned)%Read
AI153THD_U12THD U12 (index 53, unsigned)%Read
AI154THD_U23THD U23 (index 54, unsigned)%Read
AI155THD_U31THD U31 (index 55, unsigned)%Read
AImin156A+Positive Active Energy (index 56, unsigned)WhRead
AI157A-Negative Active Energy (index 57, unsigned)WhRead
AI158ER+Positive Reactive Energy (index 58, unsigned)varhRead
AI159ER-Negative Reactive Energy (index 59, unsigned)varhRead
AI160ESApparent Energy (index 60, unsigned)VAhRead
AI161MffMultifluid feeder (index 61, signed)Read
Object ID lookup: Socomec DIRIS Digiware M-50 / M-70 BACnet IP gateway point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the DIRIS Digiware M-50 / M-70 BACnet IP gateway (per-load measurement objects) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Socomec DIRIS Digiware M-50 / M-70 BACnet IP gateway (per-load measurement objects)

How many BACnet points does the Socomec DIRIS Digiware M-50 / M-70 BACnet IP gateway (per-load measurement objects) have?

This list has 62 BACnet objects: 62 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Socomec DIRIS Digiware M-50 / M-70 BACnet IP gateway (per-load measurement objects) BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Socomec DIRIS Digiware M-50 / M-70 BACnet IP gateway (per-load measurement objects) BACnet documentation?

Socomec does not publish it on its own website. This list comes from DIRIS Digiware M-50 / M-70 instruction manual, Annex B BACnet communication (548751D), a copy hosted by Instrumentation2000 at https://www.instrumentation2000.com//media/pdf/socomec-m-50-m-70-manual.pdf. Ask Socomec or its representative for the current revision.

What are the minimum BACnet points to integrate the Socomec DIRIS Digiware M-50 / M-70 BACnet IP gateway (per-load measurement objects)?

Start with AI 121 TotalPowerActive (Total active power, W (load 1)); AI 156 A+ (Imported active energy, Wh (load 1)); AI 102 CurrentSyst (System current, A (load 1)); AI 100 VystPhN (System phase-neutral voltage, V (load 1)); AI 124 TotalPowerFactor (Total power factor (load 1)); AI 103 Frequency (Frequency, Hz (load 1)).

How do I enable BMS control of the Socomec DIRIS Digiware M-50 / M-70 BACnet IP gateway (per-load measurement objects)?

BACnet IP is switched on in Easy Config System or the web server (BACnet activation).

How do I check these points on the real DIRIS Digiware M-50 / M-70 BACnet IP gateway (per-load measurement objects)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: DIRIS Digiware M-50 / M-70 instruction manual, Annex B BACnet communication · 548751D. Object names, instances and units are reproduced as published; descriptions are our own.