Indoor pool dehumidifier (air handler) controller · BACnet points list

Seresco CommandCenter Dehumidifier Controller - BACnet Objects 5.8.0 BACnet points list

Updated 28 October 2026

Short answer

Seresco's CommandCenter controller uses one BACnet object list across its NE/NV pool units, OA make-up air units and the NP/NW series; the source marks each object as standard or optional per series. Sensors are AI objects, setpoints and analog outputs are AV objects, and component status, modes, commands and alarms are BV objects. The BMS can override any sensor by setting it Out Of Service and writing its value, with a heartbeat timer to fall back to the unit's sensors. Command objects must first be enabled at the unit.

This page lists 137 BACnet objects for the Seresco CommandCenter Dehumidifier Controller - BACnet Objects 5.8.0 — 27 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Seresco’s own free documentation, linked below.

Manufacturer
Seresco
Model
CommandCenter Dehumidifier Controller - BACnet Objects 5.8.0
Equipment
Indoor pool dehumidifier (air handler) controller
Equipment type
Dehumidifiers
BACnet objects
137 (27 writable)
Transport
—
Firmware
BACnet objects document 5.8.0
Default device instance
150
Also known as
CommandCenter, Seresco BACnet Objects, BACnetObjects_5.8.0, NE series, NP series, NV series, NW series, OA series
Source document
Seresco BACnet Objects · BACnetObjects_5.8.0 · rev. 2012-01-03
Download CSV 137 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Seresco CommandCenter Dehumidifier Controller - BACnet Objects 5.8.0

Integration in brief

Enable the BACnet command objects at the unit first. Then use Blower Enabled (BV 512) for start/stop and Occupied (BV 516) for occupancy, and write the room temperature, humidity and pool setpoints (AV 0-2). Monitor the blower contactor, the mode BVs, return air conditions and the alarm count. If the BMS supplies sensor values, set the heartbeat timer (AV 515) so the unit falls back to its own sensors.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 512Blower EnabledStart/stop the blower; stopping it stops the unitWrite
BV 516OccupiedOccupancy command (active = occupied)Write
AV 0Room Temperature SetpointRoom air setpoint, 55-95 °FWrite
AV 1Humidity SetpointRoom RH setpoint, 35-85 %Write
AV 2Pool Temperature SetpointPool water setpoint, 60-108 °F (pool units)Write
BV 0Blower ContactorBlower runningRead
BV 260Dehumidification ModeUnit is dehumidifyingRead
AI 0Return Air HumidityReturn (space) air RH, %Read
AI 1Return Air TemperatureReturn (space) air temperatureRead
AV 518Alarm CountAlarm count; nonzero means an alarmRead

Enable & remote start

Command objects (BV 512-526) only work after they are enabled at the unit itself. BV 512 Blower Enabled starts and stops the main blower; stopping it stops all other components except a pool unit's auxiliary pool heater. BV 516 Occupied replaces the built-in occupancy scheduler. BV 524/525 A/C and Heat Override take over room temperature control and stay in effect until the unit restarts.

Heartbeat & communication loss

AV 515 Heartbeat Timer (0-600 s) applies when the BMS supplies sensor values. With a value above 0, the unit returns to its own sensors if no BACnet message arrives within that time, so BMS-written sensor values must be refreshed within the timer even if unchanged. 0 disables the fallback.

Sensors & values from the BMS

Any AI sensor can be taken over by setting its Out_Of_Service property to True and writing Present_Value from the BMS. Set AV 515 above 0 so the unit falls back to its installed sensors if BACnet communication stops.

Network setup

Watch out for

Seresco CommandCenter Dehumidifier Controller - BACnet Objects 5.8.0 BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

137 of 137 shown
Type
Binary
Access
Show
Seresco CommandCenter Dehumidifier Controller - BACnet Objects 5.8.0 BACnet Points List
DescriptionStates
AImin0Return Air HumidityStd: NE/NP/NV/NW/OA%Read
AImin1Return Air TemperatureStd: NE/NP/NV/NW/OA°F / °CRead
AI2Refrigerant High Pressure, Compressor 1Std: NE/NP/OApsiRead
AI3Refrigerant Low Pressure, Compressor 1Std: NE/NP/OApsiRead
AI4Refrigerant High Pressure, Compressor 2opt: NE/NPpsiRead
AI5Refrigerant Low Pressure, Compressor 2opt: NE/NPpsiRead
AI6Evaporator Temperature, Compressor 1Std: NE/NP/OA°F / °CRead
AI7Evaporator Temperature, Compressor 2opt: NE/NP°F / °CRead
AI8Supply Air TemperatureStd: NE/NP/NV/NW/OA°F / °CRead
AI9Suction Temperature, Compressor 1Std: NE/NP/OA°F / °CRead
AI10Suction Temperature, Compressor 2opt: NE/NP°F / °CRead
AI12Outdoor Air TemperatureStd: NE/NP/NV/NW/OA°F / °CRead
AI13Pool Water In Temperatureopt: NE/NP°F / °CRead
AI14Pool Water Out Temperatureopt: NE/NP°F / °CRead
AI26Discharge Temperature, Compressor 1Std: NE/NP/OA°F / °CRead
AI27Discharge Temperature, Compressor 2opt: NE/NP°F / °CRead
AI30Exhaust Air TemperatureStd: NV/NW; opt: NE/NP°F / °CRead
AI31Reheat Temperatureopt: NE/NP°F / °CRead
AI32Pool 2 Water In Temperatureopt: NE/NP°F / °CRead
AI33Pool 2 Water Out Temperatureopt: NE/NP°F / °CRead
AI34Outdoor Air HumidityStd: NW/OA; opt: NE/NP/NV%Read
AI35Outdoor Air Dew PointStd: NW/OA; opt: NE/NP/NV°F / °CRead
AI36Superheat, Compressor 1Std: NE/NP/OA°F / °CRead
AI37Superheat, Compressor 2opt: NE/NP°F / °CRead
AI40Return Air Dew PointStd: NW; opt: NE/NP/NV/OA°F / °CRead
AI41Wall Temperatureopt: NE/NP°F / °CRead
AI42Unit Currentopt: NE/NP/NV/NW/OAARead
AVmin0Room Temperature Setpoint55-95 °F (13-35 °C); Std: NE/NP/NV/NW/OA°F / °CWrite
AVmin1Humidity Setpoint35-85 %; Std: NE/NP/NV/NW/OA%Write
AVmin2Pool Temperature Setpoint60-108 °F (16-42 °C); opt: NE/NP°F / °CWrite
AV3Heat Recovery SetpointOA temp that starts heat recovery pump; 40-70 °F°F / °CWrite
AV4Purge SetpointReturn air temp that ends purge; 40-70 °F°F / °CWrite
AV5Economizer Min OA SetpointLowest OA temp for economizer; 40-90 °F°F / °CWrite
AV6Pool 2 Temperature Setpoint60-108 °F (16-42 °C); opt: NE/NP°F / °CWrite
AV7Freezestat SetpointOA temp that trips freezestat; 20-55 °F°F / °CWrite
AV9Supply Air Dry Bulb Summer SetpointSupply temp where cooling starts; 50-95 °F°F / °CWrite
AV10Supply Air Dry Bulb Winter SetpointSupply temp where heating starts; 50-95 °F°F / °CWrite
AV11Max Dew Point40-70 °F (5-21 °C); Std: OA°F / °CWrite
AV12A/C Summer Only Setpoint40-70 °F (5-21 °C); Std: NE/NP°F / °CWrite
AV13Humidity Floating SetpointRead-only; set by wall temperature; Std: NE/NP%Read
AV256Modulated HeatOutput, 0-100 %; Std: NE/NP/NV/NW/OA%Read
AV257Blower SpeedOutput, 0-100 %; Std: NW/OA%Read
AV258Head Pressure Control, Compressor 1Output, 0-100 %; Std: NE/NP/OA%Read
AV259Head Pressure Control, Compressor 2Output, 0-100 %; Not marked for any series%Read
AV260Outdoor Air Damper 1Output, 0-100 %; Std: NV; opt: NE/NP%Read
AV261Outdoor Air Damper 2Output, 0-100 %; Std: NV%Read
AV262Exhaust FansOutput, 0-100 %; Std: NV%Read
AV264Exhaust Fan 1Output, 0-100 %; opt: NE/NP%Read
AV512Purge IntervalPurge run time, 0-60 min (0 = until stopped)minWrite
AV513Exhaust LevelStd: NV%Read
AV515Heartbeat TimerBMS sensor timeout, 0-600 s (0 = off)sWrite
AV516Reheat LevelStd: NP/OA%Read
AV517Elapsed Purge Timeopt: NE/NP/NV/NWminRead
AVmin518Alarm CountNumber of alarmsRead
AV519Alert CountNumber of alertsRead
BVmin0Blower ContactorOutput status; Std: NE/NP/NV/NW/OARead
BV1Compressor Contactor, Compressor 1Output status; Std: NE/NP/OARead
BV2Reheat Valve, Compressor 1Output status; Std: NERead
BV3A/C Valve, Compressor 1Output status; Std: NERead
BV4Pump Down Valve, Compressor 1Output status; Std: NE/NP/OARead
BV5Pool Heating ValveOutput status; opt: NE/NPRead
BV7Compressor Contactor, Compressor 2Output status; opt: NE/NPRead
BV8Reheat Valve, Compressor 2Output status; opt: NERead
BV9A/C Valve, Compressor 2Output status; opt: NERead
BV10Pump Down Valve, Compressor 2Output status; opt: NE/NPRead
BV11Bypass Damper Adjust OpenOutput status; Std: NE/NPRead
BV12Bypass Damper Adjust CloseOutput status; Std: NE/NPRead
BV13Heat Recovery PumpOutput status; Std: NE/NP/NV/NWRead
BV14Auxiliary Pool HeaterOutput status; opt: NE/NPRead
BV17Outdoor Air Condenser Fan 1Output status; Std: NE/NP/OARead
BV18Outdoor Air DamperOutput status; Std: NE/NP/NW/OARead
BV19Exhaust Fan 1Output status; Std: NWRead
BV20Exhaust Fan 2Output status; opt: NWRead
BV21Stage 1 HeatOutput status; Std: NE/NP/NV/NW/OARead
BV22Stage 2 HeatOutput status; Std: NE/NP/NV/NW/OARead
BV33Pool Heating Valve, Pool 2Output status; opt: NE/NPRead
BV34Auxiliary Pool Heater, Pool 2Output status; opt: NE/NPRead
BV38Compressor Cooler, Pre-coolerOutput status; Std: NW/OARead
BV39Pump Down Valve, Pre-coolerOutput status; Std: OARead
BV42Exhaust Damper 1Output status; Std: NE/NP/NVRead
BV44Exhaust Damper 2Output status; Std: NV; opt: NE/NPRead
BV45Return Air DamperOutput status; Std: NVRead
BV46Outdoor Air Condenser Fan 2Output status; opt: NE/NPRead
BV47Compressor PumpOutput status; Std: NPRead
BV257Service ModeMode status; Std: NE/NP/NV/NW/OARead
BV259PurgingMode status; opt: NE/NP/NV/NWRead
BVmin260Dehumidification ModeMode status; Std: NE/NP/NV/NW/OARead
BV261A/C ModeMode status; Std: NE/NP/NV/NW/OARead
BV262Heating ModeMode status; Std: NE/NP/NV/NW/OARead
BV263Pool Heating ModeMode status; opt: NE/NPRead
BV264Compressor 1 AvailableMode status; Std: NE/NP/OARead
BV265Compressor 2 AvailableMode status; Std: NE/NPRead
BV266Compressor Cooler AvailableMode status; Std: OARead
BVmin512Blower EnabledStart/stop the main blower (stops the unit)WriteInactive=Off, Active=On
BV513PurgeStart/stop purgeWriteInactive=Off, Active=On
BV515Compressors EnabledEnable/disable all compressorsWriteInactive=Off, Active=On
BVmin516OccupiedOccupied/unoccupied from the BMSWriteInactive=Unoccupied, Active=Occupied
BV518Space HeaterEnable/disable the space heaterWriteInactive=Off, Active=On
BV519A/C EnabledEnable/disable air conditioningWriteInactive=Off, Active=On
BV520Pool 1 HeaterEnable/disable pool 1 heatingWriteInactive=Off, Active=On
BV521Pool 2 HeaterEnable/disable pool 2 heatingWriteInactive=Off, Active=On
BV522Emergency HeatCompressor heating with space heater outWriteInactive=Off, Active=On
BV523Blower OverrideRun a two-speed blower at max speedWriteInactive=Off, Active=On
BV524A/C OverrideBMS takes over room temperature (cooling)WriteInactive=Off, Active=On
BV525Heat OverrideBMS takes over room temperature (heating)WriteInactive=Off, Active=On
BV526Spectator ModeCommand; opt: NE/NP/NVWriteInactive=Off, Active=On
BV768Blower OverloadAlarm; Std: NE/NP/NV/NW/OARead
BV769No AirflowAlarm; Std: NE/NP/NV/NW/OARead
BV770Firestat AlarmAlarm; Std: NE/NP/NV/NW/OARead
BV771Freezestat AlarmAlarm; Std: NE/NP/NV/NW/OARead
BV772Dirty FilterAlarm; opt: NE/NP/NV/NW/OARead
BV773Pool 1 Water Flow FaultAlarm; opt: NE/NPRead
BV774Compressor 1 High PressureAlarm; Std: NE/NP/OARead
BV775Compressor 1 Low PressureAlarm; Std: NE/NP/OARead
BV776Compressor 1 Oil FaultAlarm; Std: NE/NP/OARead
BV777Compressor 1 High Discharge TempAlarm; Std: NE/NP/OARead
BV778Compressor 2 High PressureAlarm; opt: NE/NPRead
BV779Compressor 2 Low PressureAlarm; opt: NE/NPRead
BV780Compressor 2 Oil FaultAlarm; opt: NE/NPRead
BV781Compressor 2 High Discharge TempAlarm; opt: NE/NPRead
BV792Voltage FaultAlarm; Std: NE/NP/NV/NW/OARead
BV793Purge AlarmAlarm; opt: NE/NP/NV/NWRead
BV794Outdoor Air Condenser 1 OverloadAlarm; Std: NE/NP/OARead
BV795Outdoor Air Condenser 2 OverloadAlarm; opt: NE/NPRead
BV797Compressor 1 Low SuperheatAlarm; Std: NE/NP/OARead
BV798Compressor 2 Low SuperheatAlarm; opt: NE/NPRead
BV801Bad BatteryAlarm; Std: NE/NP/NV/NW/OARead
BV802Exhaust Fan 1 OverloadAlarm; Std: NE/NP/NV/NWRead
BV803Pool 2 Water Flow FaultAlarm; opt: NE/NPRead
BV804Compressor 1 Pressure FaultAlarm; Std: NE/NP/OARead
BV805Compressor 2 Pressure FaultAlarm; opt: NE/NPRead
BV809Compressor Pump FaultAlarm; Std: NPRead
BV810Freezestat 2 AlarmAlarm; Std: NE/NP/NV/NW/OARead
BV811Compressor Cooler FaultAlarm; Std: OARead
BV812Exhaust Fan 2 OverloadAlarm; Std: NV; opt: NE/NP/NWRead
BV813Compressor 1 High Suction TempAlarm; Std: NE/NP/OARead
BV814Compressor 2 High Suction TempAlarm; opt: NE/NPRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CommandCenter Dehumidifier Controller - BACnet Objects 5.8.0 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Seresco CommandCenter Dehumidifier Controller - BACnet Objects 5.8.0

How many BACnet points does the Seresco CommandCenter Dehumidifier Controller - BACnet Objects 5.8.0 have?

This list has 137 BACnet objects: 27 analog inputs, 28 analog values, 82 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Seresco CommandCenter Dehumidifier Controller - BACnet Objects 5.8.0 BACnet points are writable?

27 of the 137 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Seresco CommandCenter Dehumidifier Controller - BACnet Objects 5.8.0 BACnet documentation?

The source is Seresco BACnet Objects (BACnetObjects_5.8.0), revision 2012-01-03, published free by Seresco at https://serescodehumidifiers.com/documents/commandcenter/BACnetObjects_5.8.0.pdf.

What are the minimum BACnet points to integrate the Seresco CommandCenter Dehumidifier Controller - BACnet Objects 5.8.0?

Start with BV 512 Blower Enabled (Start/stop the blower; stopping it stops the unit); BV 516 Occupied (Occupancy command (active = occupied)); AV 0 Room Temperature Setpoint (Room air setpoint, 55-95 °F); AV 1 Humidity Setpoint (Room RH setpoint, 35-85 %); AV 2 Pool Temperature Setpoint (Pool water setpoint, 60-108 °F (pool units)); BV 0 Blower Contactor (Blower running); BV 260 Dehumidification Mode (Unit is dehumidifying); AI 0 Return Air Humidity (Return (space) air RH, %); AI 1 Return Air Temperature (Return (space) air temperature); AV 518 Alarm Count (Alarm count; nonzero means an alarm).

How do I enable BMS control of the Seresco CommandCenter Dehumidifier Controller - BACnet Objects 5.8.0?

Command objects (BV 512-526) only work after they are enabled at the unit itself. BV 512 Blower Enabled starts and stops the main blower; stopping it stops all other components except a pool unit's auxiliary pool heater. BV 516 Occupied replaces the built-in occupancy scheduler. BV 524/525 A/C and Heat Override take over room temperature control and stay in effect until the unit restarts.

Does the Seresco CommandCenter Dehumidifier Controller - BACnet Objects 5.8.0 need a BACnet heartbeat or have a communication timeout?

AV 515 Heartbeat Timer (0-600 s) applies when the BMS supplies sensor values. With a value above 0, the unit returns to its own sensors if no BACnet message arrives within that time, so BMS-written sensor values must be refreshed within the timer even if unchanged. 0 disables the fallback.

Can the BMS supply sensor values to the Seresco CommandCenter Dehumidifier Controller - BACnet Objects 5.8.0?

Any AI sensor can be taken over by setting its Out_Of_Service property to True and writing Present_Value from the BMS. Set AV 515 above 0 so the unit falls back to its installed sensors if BACnet communication stops.

How do I check these points on the real CommandCenter Dehumidifier Controller - BACnet Objects 5.8.0?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: Seresco BACnet Objects · BACnetObjects_5.8.0 · rev. 2012-01-03. Object names, instances and units are reproduced as published; descriptions are our own.