Power meter via BACnet gateway · BACnet points list
SATEC EM133 power meter (ProtoNode profile) BACnet points list
Updated 7 November 2026
The ProtoNode profile for the EM133 publishes 89 analog inputs: voltages, currents, kW, kvar, kVA and power factor per phase and in total, voltage and current THD, K-factor and TDD, averages, neutral current, frequency, unbalance, block and sliding demands and the energy totals by quadrant.
This page lists 89 BACnet objects for the SATEC EM133 power meter (ProtoNode profile) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from SATEC’s own free documentation, linked below.
- Manufacturer
- SATEC
- Model
- EM133 power meter (ProtoNode profile)
- Equipment
- Power meter via BACnet gateway
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 89 (0 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Not stated
- Default device instance
- 50000 + Modbus Node-ID
- Also known as
- EM133, EM 133, ProtoNode FPC-N34, ProtoNode FPC-N35
Reference only, provided as-is: verify against SATEC’s current documentation and the live device before use. Not official SATEC information. Terms of use.
BMS integration notes: SATEC EM133 power meter (ProtoNode profile)
Read-only. Give the meter a Modbus Node-ID, add it in the ProtoNode web configurator, then map voltages, currents, total kW and PF, frequency and the energy registers.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 1 | V1/V12 Voltage | V1/V12 voltage | Read |
| AI 4 | I1 Current | Phase 1 current | Read |
| AI 34 | Total kW | Total kW | Read |
| AI 37 | Total PF | Total power factor | Read |
| AI 48 | Frequency | Frequency | Read |
| AI 79 | kWh import | kWh import | Read |
Network setup
- Set every meter on the ProtoNode's RS-485 port to Modbus RTU 9600 baud, 8 data bits, no parity, 1 stop bit, with a unique Node-ID (1-255).
- Each meter on the ProtoNode is its own BACnet device: Device Instance = the meter's Modbus Node-ID + Node_Offset (default 50,000).
- BACnet MS/TP: set the ProtoNode MAC address (1-127) on the A bank DIP switches and the baud rate on the B bank.
- BACnet IP: set the ProtoNode IP address in its web GUI (FST Web GUI).
Watch out for
- The devices on one FPC-N34 must not add up to more than 1500 Modbus registers (this profile uses 89).
SATEC EM133 power meter (ProtoNode profile) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | V1/V12 Voltage | Read | |||
| AI | 2 | V2/V23 Voltage | Read | |||
| AI | 3 | V3/V31 Voltage | Read | |||
| AImin | 4 | I1 Current | Read | |||
| AI | 5 | I2 Current | Read | |||
| AI | 6 | I3 Current | Read | |||
| AI | 7 | kW L1 | Read | |||
| AI | 8 | kW L2 | Read | |||
| AI | 9 | kW L3 | Read | |||
| AI | 10 | kvar L1 | Read | |||
| AI | 11 | kvar L2 | Read | |||
| AI | 12 | kvar L3 | Read | |||
| AI | 13 | kVA L1 | Read | |||
| AI | 14 | kVA L2 | Read | |||
| AI | 15 | kVA L3 | Read | |||
| AI | 16 | Power factor L1 | Read | |||
| AI | 17 | Power factor L2 | Read | |||
| AI | 18 | Power factor L3 | Read | |||
| AI | 19 | V1/V12 Voltage THD | Read | |||
| AI | 20 | V2/V23 Voltage THD | Read | |||
| AI | 21 | V3/V31 Voltage THD | Read | |||
| AI | 22 | I1 Current THD | Read | |||
| AI | 23 | I2 Current THD | Read | |||
| AI | 24 | I3 Current THD | Read | |||
| AI | 25 | I1 K-Factor | Read | |||
| AI | 26 | I2 K-Factor | Read | |||
| AI | 27 | I3 K-Factor | Read | |||
| AI | 28 | I1 Current TDD | Read | |||
| AI | 29 | I2 Current TDD | Read | |||
| AI | 30 | I3 Current TDD | Read | |||
| AI | 31 | V12 Voltage | Read | |||
| AI | 32 | V23 Voltage | Read | |||
| AI | 33 | V31 Voltage | Read | |||
| AImin | 34 | Total kW | Read | |||
| AI | 35 | Total kvar | Read | |||
| AI | 36 | Total kVA | Read | |||
| AImin | 37 | Total PF | Read | |||
| AI | 38 | Total PF lag | Read | |||
| AI | 39 | Total PF lead | Read | |||
| AI | 40 | Total kW import | Read | |||
| AI | 41 | Total kW export | Read | |||
| AI | 42 | Total kvar import | Read | |||
| AI | 43 | Total kvar export | Read | |||
| AI | 44 | 3-phase average L-N/L-L voltage | Read | |||
| AI | 45 | 3-phase average L-L voltage | Read | |||
| AI | 46 | 3-phase average current | Read | |||
| AI | 47 | In (neutral) Current | Read | |||
| AImin | 48 | Frequency | Read | |||
| AI | 49 | Voltage unbalance | Read | |||
| AI | 50 | Current unbalance | Read | |||
| AI | 51 | V1/V12 Volt dem | Read | |||
| AI | 52 | V2/V23 Volt dem | Read | |||
| AI | 53 | V3/V31 Volt dem | Read | |||
| AI | 54 | I1 Ampere dem | Read | |||
| AI | 55 | I2 Ampere dem | Read | |||
| AI | 56 | I3 Ampere dem | Read | |||
| AI | 57 | kW import block dem | Read | |||
| AI | 58 | kvar import block dem | Read | |||
| AI | 59 | kVA block dem | Read | |||
| AI | 60 | kW import sliding wndw dem | Read | |||
| AI | 61 | kvar import sliding wndw dem | Read | |||
| AI | 62 | kVA sliding wndw dem | Read | |||
| AI | 63 | kW import accumulated dem | Read | |||
| AI | 64 | kvar import accumulated dem | Read | |||
| AI | 65 | kVA accumulated dem | Read | |||
| AI | 66 | kW import predicted sliding wndw dem | Read | |||
| AI | 67 | kvar import predicted sliding wndw dem | Read | |||
| AI | 68 | kVA predicted sliding wndw dem | Read | |||
| AI | 69 | PF (import) at Max. kVA slid wndw dem | Read | |||
| AI | 70 | kW export block dem | Read | |||
| AI | 71 | kvar export block dem | Read | |||
| AI | 72 | kW export sliding wndw dem | Read | |||
| AI | 73 | kvar export sliding wndw dem | Read | |||
| AI | 74 | kW export accumulated dem | Read | |||
| AI | 75 | kvar export accumulated dem | Read | |||
| AI | 76 | kW export predicted sliding wndw dem | Read | |||
| AI | 77 | kvar export predicted sliding wndw dem | Read | |||
| AI | 78 | In Ampere dem | Read | |||
| AImin | 79 | kWh import | Read | |||
| AI | 80 | kWh export | Read | |||
| AI | 81 | kvarh import | Read | |||
| AI | 82 | kvarh export | Read | |||
| AI | 83 | kVAh total | Read | |||
| AI | 84 | kVAh import | Read | |||
| AI | 85 | kVAh export | Read | |||
| AI | 86 | kvarh Q1 | Read | |||
| AI | 87 | kvarh Q2 | Read | |||
| AI | 88 | kvarh Q3 | Read | |||
| AI | 89 | kvarh Q4 | Read |
No points match these filters.
Object ID lookup: SATEC EM133 power meter point IDs by name
AI1V1/V12 VoltageAI2V2/V23 VoltageAI3V3/V31 VoltageAI4I1 CurrentAI5I2 CurrentAI6I3 CurrentAI7kW L1AI8kW L2AI9kW L3AI10kvar L1AI11kvar L2AI12kvar L3AI13kVA L1AI14kVA L2AI15kVA L3AI16Power factor L1AI17Power factor L2AI18Power factor L3AI19V1/V12 Voltage THDAI20V2/V23 Voltage THDAI21V3/V31 Voltage THDAI22I1 Current THDAI23I2 Current THDAI24I3 Current THDAI25I1 K-FactorAI26I2 K-FactorAI27I3 K-FactorAI28I1 Current TDDAI29I2 Current TDDAI30I3 Current TDDAI31V12 VoltageAI32V23 VoltageAI33V31 VoltageAI34Total kWAI35Total kvarAI36Total kVAAI37Total PFAI38Total PF lagAI39Total PF leadAI40Total kW importAI41Total kW exportAI42Total kvar importAI43Total kvar exportAI443-phase average L-N/L-L voltageAI453-phase average L-L voltageAI463-phase average currentAI47In (neutral) CurrentAI48FrequencyAI49Voltage unbalanceAI50Current unbalanceAI51V1/V12 Volt demAI52V2/V23 Volt demAI53V3/V31 Volt demAI54I1 Ampere demAI55I2 Ampere demAI56I3 Ampere demAI57kW import block demAI58kvar import block demAI59kVA block demAI60kW import sliding wndw demAI61kvar import sliding wndw demAI62kVA sliding wndw demAI63kW import accumulated demAI64kvar import accumulated demAI65kVA accumulated demAI66kW import predicted sliding wndw demAI67kvar import predicted sliding wndw demAI68kVA predicted sliding wndw demAI69PF (import) at Max. kVA slid wndw demAI70kW export block demAI71kvar export block demAI72kW export sliding wndw demAI73kvar export sliding wndw demAI74kW export accumulated demAI75kvar export accumulated demAI76kW export predicted sliding wndw demAI77kvar export predicted sliding wndw demAI78In Ampere demAI79kWh importAI80kWh exportAI81kvarh importAI82kvarh exportAI83kVAh totalAI84kVAh importAI85kVAh exportAI86kvarh Q1AI87kvarh Q2AI88kvarh Q3AI89kvarh Q4
Integration notes
- All objects are read-only analog inputs; the guide gives no units, scaling or Modbus registers for them (the Lon columns read TBD).
- The same profile serves BACnet MS/TP, BACnet IP, Metasys N2 and LonWorks; the N2 point addresses match the BACnet instances.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the EM133 power meter (ProtoNode profile) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the SATEC EM133 power meter (ProtoNode profile)
How many BACnet points does the SATEC EM133 power meter (ProtoNode profile) have?
This list has 89 BACnet objects: 89 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which SATEC EM133 power meter (ProtoNode profile) BACnet points are writable?
None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.
Where is the official SATEC EM133 power meter (ProtoNode profile) BACnet documentation?
The source is ProtoNode FPC-N34 and ProtoNode FPC-N35 Startup Guide For Interfacing Satec Products: BFM136 and EM133, revision Document Revision 1 (effective May 2014), published free by SATEC at https://satec-global.com.au/wp-content/uploads/2022/01/ProtoNode-Startup-Guide-for-Satec.Rev-1.pdf.
What are the minimum BACnet points to integrate the SATEC EM133 power meter (ProtoNode profile)?
Start with AI 1 V1/V12 Voltage (V1/V12 voltage); AI 4 I1 Current (Phase 1 current); AI 34 Total kW (Total kW); AI 37 Total PF (Total power factor); AI 48 Frequency (Frequency); AI 79 kWh import (kWh import).
How do I check these points on the real EM133 power meter (ProtoNode profile)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More SATEC BACnet points lists
Source: ProtoNode FPC-N34 and ProtoNode FPC-N35 Startup Guide For Interfacing Satec Products: BFM136 and EM133 · rev. Document Revision 1 (effective May 2014). Object names, instances and units are reproduced as published; descriptions are our own.