Room operating unit / room controller · BACnet points list

S+S Regeltechnik RYMASKON 1000 room operating unit (Interface / Controller) BACnet points list

Updated 12 November 2026

Short answer

RYMASKON 1000 units are touch room operating units for temperature, fan, sun protection and lighting. The BACnet object list (vendor ID 1545) covers sensor values (temperature, humidity, CO2, VOC), setpoints, operating mode, fan level, presence, sun-protection and light commands and status, header icons, BMS lock and takeover values for the controller outputs, labels, date/time and many configuration values. Controller-only objects (internal controller outputs, Controller OpMode, BMS output overrides) apply to the RYM 13xxC/14xxC variants.

This page lists 335 BACnet objects for the S+S Regeltechnik RYMASKON 1000 room operating unit (Interface / Controller) — 253 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from S+S Regeltechnik’s own free documentation, linked below.

Manufacturer
S+S Regeltechnik
Model
RYMASKON 1000 room operating unit (Interface / Controller)
Equipment
Room operating unit / room controller
Equipment type
Thermostats, sensors & meters
BACnet objects
335 (253 writable)
Transport
BACnet MS/TP
Firmware
Application / firmware 2.00.2
Also known as
RYMASKON 1000, Rymaskon 1000, RYM 1301, RYM 1302, RYM 1401, RYM 1402, RYM 1321C, RYM 1322C, RYM 1361C, RYM 1362C, RYM 1431C, RYM 1432C, RYM 1461C, RYM 1462C, S+S Rymaskon BACnet
Source document
BACnet PIC - Rymaskon 1000 Interface / Controller BACnet · rev. 2026-09-14
Download CSV 335 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against S+S Regeltechnik’s current documentation and the live device before use. Not official S+S Regeltechnik information. Terms of use.

BMS integration notes: S+S Regeltechnik RYMASKON 1000 room operating unit (Interface / Controller)

Integration in brief

Set the MS/TP MAC address and baud rate on the unit (default 38400), then write the temperature setpoint, operating mode and fan level and read room temperature, presence and operating state. Use IV 409 / the BV lock objects if occupants must not change values the BMS controls.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
IV 404IV:OpMode_Status_404Operating mode: 0 Off, 1 Cooling, 2 HeatingWrite
AV 400AV:Setpoint_Temp_400Room temperature setpoint, °CWrite
IV 407IV:Setpoint_Fan_Level_407Fan level 0-5Write
IV 409IV:RCBBMS_409_bitFieldBMS lock of setpoint, fan and presence keysWrite
AI 1AI:TempS1Int_Value_1Room temperature (internal sensor)Read
BI 1BI:Presence_Status_1Presence: 1 = occupiedRead
AI 9AI:OpMode_Status_9Operating mode statusRead
AI 8AI:Setpoint_Temp_Absolut_8Absolute temperature setpoint in useRead
IV 2025IV:InternalError_2025_bitFieldInternal error bits (sensor, I2C)Read

Enable & remote start

Controller variants: IV 1607 Controller OpMode sets how the internal controller drives the outputs (0 Off, 1 cooling, 2 heating, 3 both). The BMS can take over each output with the BMS Contr. objects (AV 1608-1610, 1613; IV 1611, 1612, 1615); -1 returns an output to the internal controller.

Network setup

Watch out for

S+S Regeltechnik RYMASKON 1000 room operating unit (Interface / Controller) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

335 of 335 shown
Type
Access
Show
S+S Regeltechnik RYMASKON 1000 room operating unit (Interface / Controller) BACnet Points List
DescriptionStates
AImin1AI:TempS1Int_Value_1Temp Sensor 1 int. value; -20…50°C (0...122,0 °F)Read
AI2AI:HumS1Int_Value_2Humidity Sensor 1 int. Value; 0 to 100.0 % RHRead
AI3AI:CO2S1Int_Value_3CO2 Sensor 1 int. value; 0…2000 ppmRead
AI4AI:VOCS1Int_ppb_Value_4VOC Sensor 1 int. value ppb; 0...30000 ppbRead
AI5AI:VOCS1Int_%_Value_5VOC Sensor 1 int.value %; 0...100 %Read
AI7AI:TempS2Ext_Value_7Temp Sensor 2 ext. value; -20…50°C (0...122,0 °F)Read
AI11AI:D1Input_Status_11D1 Input StatusRead0=DI1 open (default); 1=DI1 closed
AI12AI:D2Input_Status_12D2 Input StatusRead0=DI2 open (default); 1=DI2 closed
AImin8AI:Setpoint_Temp_Absolut_8Temp Setpoint Absolute; -18...60°C (0..140°F)Read
AImin9AI:OpMode_Status_9OpMode StatusRead0=Off (default); 1=Cooling; 2=Heating
AI10AI:Setpoint_Fan_Level_10Fan LevelRead0=Off; 1=Level 1 (Default); 2=Level 2; 3=Level 3; 4=Level 4; 5=Level 5
AI13AI:SP1_KeyStatus_13Sun protect 1 key statusRead0=Button not pressed (default); 1=DOWN button pressed briefly; 2=DOWN button pressed and held down; 3=UP button pressed briefly; 4=UP button pressed and held down; 5=DOWN button pressed (only mode hold key); 6=UP button pressed (only mode hold key)
AI14AI:SP1_Position_Value_14Sun protect 1 position value; 0.0…100.0 % (default 0%)Read
AI15AI:SP1_Angle_Value_15Sun protect 1 angle value; -180°…180° (default 0°)Read
AI16AI:SP2_KeyStatus_16Sun Protest 2 key statusRead0=Button not pressed (default); 1=DOWN button pressed briefly; 2=DOWN button pressed and held down; 3=UP button pressed briefly; 4=UP button pressed and held down; 5=DOWN button pressed (only mode hold key); 6=UP button pressed (only mode hold key)
AI17AI:SP2_Position_Value_17Sun protect 2 position value; 0.0…100.0 % (default 0%)Read
AI18AI:SP1_Angle_Value_15Sun protect 2 angle value; -180°…180° (default 0°)Read
AI73AI:L1_KeyStatus_73Light 1 key statusRead0=Button not pressed (default); 1=DOWN button pressed briefly; 2=DOWN button pressed and held down; 3=UP button pressed briefly; 4=UP button pressed and held down; 5=DOWN button pressed (only mode hold key); 6=UP button pressed (only mode hold key)
AI74AI:L1_DimmValue_74Light 1 dimm value; 0…100 % (default 0%)Read
AI79AI:L2_KeyStatus_79Light 2 key statusRead0=Button not pressed (default); 1=DOWN button pressed briefly; 2=DOWN button pressed and held down; 3=UP button pressed briefly; 4=UP button pressed and held down; 5=DOWN button pressed (only mode hold key); 6=UP button pressed (only mode hold key)
AI80AI:L1_DimmValue_80Light 2 dimm value; 0…100 % (default 0%)Read
AI193AI:ChangeOver_Status_193Change-Over StatusRead0=Change-Over inactive (default); 1=Cooling Mode (Heating blocked); 2=Heatinge Mode (Cooling blocked
AI198AI:ContrOpMode_Setpoint_198Controller OpModeRead0=OFF; 1=Cooling Auto (Heating blocked); 2=Heating Auto (Cooling deaktiviert); 3=Cooling and Heating Auto
AI199AI:AO_OutHeat_BMSContr_199AO Output Heating BMS Contr.; 0…10V -1 = internal controller active (default)Read
AI200AI:AO_OutCool_BMSContr_200AO Output Cooling BMS Contr.; 0…10V -1 = internal controller active (default)Read
AI201AI:AO_Out6WayValve_BMSContr_201AO Output 6-Way-Valve BMS Contr; 0…10V -1 = internal controller active (default)Read
AI202AI:RODO_OutHeat_BMSContr_202RO/DO Output Heating BMS Contr.Read0=RO / DO Heating open; 1=RO / DO Heating closed; -1=internal controller active (default)
AI203AI:RODO_OutCool_BMSContr_203RO/DO Output Cooling BMS Contr.Read0=RO / DO Cooling open; 1=RO / DO Cooling closed; -1=internal controller active (default)
AI204AI:AO_OutFan_BMSContr_204AO Output Fan BMS Contr.; 0…10V -1 = internal controller active (default)Read
AI205AI:RODO_OutFan_BMSContr_205RO/DO Output Fan BMS Contr.Read0=OFF; 1=Level 1; 2=Level 2; 3=Level 3; -1=internal controller active (default)
AI206AI:Controller_Setpoint_Temp_206Controller Setpoint Temp; 0...122,0 °C/°FRead
AI207AI:AO_Heat_Value_207AO Heating; 0...10VRead
AI208AI:AO_Cool_Value_208AO Cooling; 0...10VRead
AI209AI:AO_6WayValve_Value_209AO 6-Way-Valve; 0...10VRead
AI210AI:RODO_Heat_Value_210RO/DO HeatingRead0=open; 1=closed
AI211AI:RODO_Cool_Value_211RO/DO CoolingRead0=open; 1=closed
AI212AI:AO_Fan_Value_212AO Fan; 0...10VRead
AI213AI:RODO_Fan_Level_212RODO FanRead0=all Relays open (fan off); 1=Relay 1 closed (fan level 1); 2=Relay 2 closed (fan level 2); 3=Relay 3 closed (fan level 3)
AV100AV:TempS1Int_Value_100Temp Sensor 1 int. value; -20.0…50.0°C (0.0...122.0 °F)Read
AV101AV:HumS1Int_Value_101Humidity Sensor 1 int. Value; 0,0...100.0 % RHRead
AV102AV:CO2S1Int_Value_102CO2 Sensor 1 int. value; 0…2000 ppmRead
AV103AV:VOCS1Int_ppb_Value_103VOC Sensor 1 int. value ppb; 0...2383 ppbRead
AV104AV:VOCS1Int_%_Value_104VOC Sensor 1 int.value %; 0...100 %Read
AV106AV:TempS2Ext_Value_106Temp Sensor 2 ext. value; -20.0…50.0°C (0.0...122.0 °F)Read
AV120AV:TempS3Bus_Value_120Temp Sensor 3 bus value; -20.0…50.0°C (0.0...122.0 °F)Write
AV121AV:HumS3Bus_Value_121Humidity Sensor 2 bus value; 0.0...100.0 % RHWrite
AV122AV:CO2S2Bus_Value_122CO2 Sensor 2 bus value; 0…5000 ppmWrite
AV123AV:VOCS2Bus_Value_123VOC Sensor 2 bus value; 0...60000 ppbWrite
AV124AV:PMS2Bus_Value_124PM Sensor 2 bus value; 0...1000 µg/m³Write
AV125AV:PressureS2Bus_Value_125Pressure Sensor 2 bus value; mbar, hPa und Pa 0…10000 inWC 0…500Write
AVmin400AV:Setpoint_Temp_400Temp Setpoint; -20.0…50.0°C (0.0...122.0 °F) default 21.0°C (70.0°F)Write
AV401AV:Setpoint_Temp_Offset_401Temp Setpoint Offset; -18.0…18.0 °C/°F (default 0 °C/°F)Write
AV402AV:Setpoint_Temp_Absolut_402Temp Setpoint Absolute; -18.0…140.0 °C/°FRead
AV403AV:Setpoint_Temp_Offset_MinMax_403Temp Setpoint Offset Min-Max; 0.0…18.0 °C/F° (default 3°C / 6°F)Write
AV721AV:SP1_Position_Value_721Sun protect 1 position value; 0.0…100.0 % (default 0%)Write
AV722AV:SP1_Angle_Value_722Sun protect 1 angle value; -180°…180° (default 0°)Write
AV731AV:SP2_Position_Value_731Sun protect 2 position value; 0.0…100.0 % (default 0%)Write
AV732AV:SP2_Angle_Value_732Sun protect 2 angle value; -180°…180° (default 0°)Write
AV1121AV:L1_Dimm_Value_1121Light 1 dimm value; 0…100 % (default 0%)Write
AV1131AV:L2_Dimm_Value_1131Light 2 dimm value; 0…100 % (default 0%)Write
AV1608AV:AO_OutHeat_BMSContr_1608AO Output Heating BMS Contr.; 0…10V -1 = internal controller active (default)Write
AV1609AV:AO_OutCool_BMSContr_1609AO Output Cooling BMS Contr.; 0…10V -1 = internal controller active (default)Write
AV1610AV:AO_Out6WayValve_BMSContr_1610AO Output 6-Way-Valve BMS Contr.; 0…10V -1 = internal controller active (default)Write
AV1613AV:AO_OutFan_BMSContr_1613AO Output Fan BMS Contr.; 0…10V -1 = internal controller active (default)Write
AV1616AV:Controller_Setpoint_Temp_1616Controller Setpoint Temp (TSetpoint; 0...122,0 °C/°F (default 21°C / 70°F)Read
AV1617AV:AO_Heat_Value_1617AO Heating AO Heating; 0...10VRead
AV1618AV:AO_Cool_Value_1618AO Cooling AO Cooling; 0...10VRead
AV1619AV:AO_6WayValve_Value_1619AO 6-Way-Valve AO 6-Way-Valve; 0...10VRead
AV1622AV:AO_Fan_Value_1622AO Fan AO Fan; 0...10VRead
AV2312AV:TempS1Int_Offset_2312Temp Sensor 1 int. Offset; -20°…+20° (default 0)Write
AV2314AV:TempS1Int_ColourScale_Start_2314Temp Sensor 1 int. Colour Scale Start; 0...122,0 °C/°F (default 16°C / 61°F)Write
AV2315AV:TempS1Int_ColourScale_End_2315Temp Sensor 1 int. Colour Scale End; 0...122,0 °C/°F (default 24°C / 82°F)Write
AV2412AV:HumS1Int_Offset_2412Humidity Sensor 1 int. Offset; -20…+20 % (default 0)Write
AV2414AV:HumS1Int_ColourScale_Start_2414Humidity Sensor 1 int. Colour Scale; 0...100.0 % RH (default 0)Write
AV2415AV:HumS1Int_ColourScale_End_2415Humidity Sensor 1 int. Colour Scale End; 0...100.0 % RH (default 100)Write
AV2512AV:CO2S1Int_Offset_2512CO2 Sensor 1 int. Offset; -500…+500 ppm (default 0)Write
AV2514AV:CO2S1Int_ColourScale_Start_2514CO2 Sensor 1 int. Colour Scale Start; 0...2000 ppm (default 0)Write
AV2515AV:CO2S1Int_ColourScale_End_2515CO2 Sensor 1 int. Colour Scale End; 0...2000 ppm (default 2000)Write
AV2614AV:VOCS1Int_ColourScale_Start_2614VOC Sensor 1 int. Colour Scale Start; 0…100 % (default 0%)Write
AV2615AV:VOCS1Int_ColourScale_End_2615VOC Sensor 1 int. Colour Scale End; 0…100 % (default 100%)Write
AV2912AV:TempS2Ext_Offset_2912Temp Sensor 2 ext. Offset; -20°…+20° (default 0)Write
AV2914AV:TempS2Ext_ColourScale_Start_2914Temp Sensor 2 ext. Colour Scale Start; 0...122,0 °C/°F (default 16°C / 61°F)Write
AV2915AV:TempS2Ext_ColourScale_End_2915Temp Sensor 2 ext. Colour Scale End; 0...122,0 °C/°F (default 24°C / 82°F)Write
AV3014AV:TempS3Bus_ColourScale_Start_3014Temp Sensor 3 bus Colour Scale Start; 0...122,0 °C/°F (default 16°C / 61°F)Write
AV3015AV:TempS3Bus_ColourScale_End_3015Temp Sensor 3 bus Colour Scale End; 0...122,0 °C/°F (default 24°C / 82°F)Write
AV3114AV:HumS2Bus_ColourScale_Start_3114Humidity Sensor 2 bus Colour Scale; 0...100.0 % RH (default 0)Write
AV3115AV:HumS2Bus_ColourScale_End_3115Humidity Sensor 2 bus Colour Scale End; 0...100.0 % RH (default 100)Write
AV3214AV:CO2S2Bus_ColourScale_Start_3214CO2 Sensor 2 bus Colour Scale Start; 0...5000 ppm (default 0)Write
AV3215AV:CO2S2Bus_ColourScale_End_3215CO2 Sensor 2 bus Colour Scale End; 0...5000 ppm (default 2000)Write
AV3314AV:VOCS2Bus_ColourScale_Start_3314VOC Sensor 2 bus Colour Scale Start; 0...60000 (default 0)Write
AV3315AV:VOCS2Bus_ColourScale_End_3315VOC Sensor 2 bus Colour Scale End; 0...60000 (default 100)Write
AV3414AV:PMS2Bus_ColourScale_Start_3414PM Sensor 2 bus Colour Scale Start; 0...1000 µg/m³ (default 0)Write
AV3415AV:PMS2Bus_ColourScale_End_3415PM Sensor 2 bus Colour Scale End; 0...1000 µg/m³ (default 1000)Write
AV3514AV:PressureS2Bus_ColourScale_Start_3514Pressure 2 bus Colour Scale Start; 0…10000 (default = 1000 hPa)Write
AV3515AV:PressureS2Bus_ColourScale_End_3515Pressure 2 bus Colour Scale End; 0…10000 (default = 1050 hPa)Write
AV3603AV:Setpoint_Temp_AfterReboot_3603Temp Setpoint After Reboot; 0...122,0 °C/°F (default 21°C / 70°F)Write
AV3604AV:Setpoint_Temp_Offset_MinMax_AfterReboot_3604Temp Setpoint Offset Min-Max After; 0…18,0 °C/F° (default 3°C / 6°F)Write
AV4265AV:SP1_PositionStepSize_4265Sun Protect 1 Position Step Size; 0.1… 100% (default 0.5%)Write
AV4266AV:SP1_AngleStepSize_4266Sun Protect 1 Angle Step Size; 1… 90° (default 10°)Write
AV4267AV:SP1_PositionMin_4267Sun Protect 1 Position Min; 0…100 % (default 0%)Write
AV4268AV:SP1_PositionMax_4268Sun Protect 1 Position Max; 0…100 % (default 100%)Write
AV4269AV:SP1_AngleMin_4269Sun Protect 1 Angle Min; -90°…90° (default 0°)Write
AV4270AV:SP1_AngleMax_4270Sun Protect 1 Angle max; -90°…90° (default 80°)Write
AV4315AV:SP2_PositionStepSize_4315Sun Protect 2 Position Step Size; 0.1… 100% (default 0.5%)Write
AV4316AV:SP2_AngleStepSize_4316Sun Protect 2 Angle Step Size; 1… 90° (default 10°)Write
AV4317AV:SP2_PositionMin_4317Sun Protect 2 Position Min; 0…100 % (default 0%)Write
AV4318AV:SP2_PositionMax_4318Sun Protect 2 Position Max; 0…100 % (default 100%)Write
AV4319AV:SP2_AngleMin_4319Sun Protect 2 Angle Min; -90°…90° (default 0°)Write
AV4320AV:SP2_AngleMax_4320Sun Protect 2 Angle Max; -90°…90° (default 80°)Write
AV5368AV:L1_DimmStepSize_5368Light 1 Dimm Step Size; 1… 100% (default 10%)Write
AV5418AV:L2_DimmStepSize_5418Light 2 Dimm Step Size; 1… 100% (default 10%)Write
AV8000AV:Setpoint_TempShift_Unocc_8000Setpoint_TempShift_Unocc_8000; 0…18 °C/F° (default 0°C / 0°F)Write
AV8006AV:DeadBand_Comfort_8006Dead Band Comfort (PI Temp Contol; 0…27,0 °C/F° (default 1°C / 2°F)Write
AV8007AV:DeadBand_ECO_8007Dead Band ECO (PI Temp Contol Loop); 0…27,0 °C/F° (default 4°C / 7°F)Write
AV8008AV:Hyst_TempContr_8008Hysteresis Temp Control (ON/OFF Temp; 0…27,0 °C/F° (default 1°C / 2°F)Write
AV8009AV:PropBand_XpCool_8009Proportional Band Xp Cooling; 0,1…27,0 °C/F° (default 2°C / 4°F)Write
AV8010AV:ResetTime_Ti_Cool_8010Reset Time Ti Cooling; 0…1200 minutes (default 20 minutes)Write
AV8011AV:ManipVarMin_Cool_8011Manipulated Variable Min. Cooling; 0…100% (default 0%)Write
AV8012AV:ManipVarMax_Cool_8012Manipulated Variable Max. Cooling; 0…100% (default 100%)Write
AV8013AV:PropBand_XpHeat_8013Proportional Band Xp Heating; 0,1…27,0 °C/F° (default 2°C / 4 °F)Write
AV8014AV:ResetTime_Ti_Heat_8014Reset Time Ti Heating; 0…1200 minutes (default 20 minutes)Write
AV8015AV:ManipVarMin_Heat_8015Manipulated Variable Min. Heating; 0…100% (default 0%)Write
AV8016AV:ManipVarMax_Heat_8016Manipulated Variable Max. Heating; 0…100% (default 100%)Write
AV8018AV:Y_MinDev_PIContolLoop_8018Y Min Deviation PI Temp Contol Loop; 0…10 % (default 0,2 %)Write
AV8021AV:6WayValveGen_Cool100%_80216-Way-Valve Generic Cooling 100%; 0…10,0V (default 2,0 V)Write
AV8022AV:6WayValveGen_Cool0%_80226-Way-Valve Generic Cooling 0%; 0…10,0V (default 5,0 V)Write
AV8023AV:6WayValveGen_Heat100%_80236-Way-Valve Generic Heating 100%; 0…10,0V (default 7,0 V)Write
AV8024AV:6WayValveGen_Heat0%_80246-Way-Valve Generic Heating 0 %; 0…10,0V (default 10,0 V)Write
AV8029AV:RODO_MinRuntime_HeatCool_8029RODO Min. Runtime Heat/Cool; 0…120 minutes (default 0 minutes)Write
AV8030AV:DelaySwitch_Heat/Cool_8030Delay Switch Heat/Cool; 0…900 s (default 0s)Write
AV8032AV:AO_FanMin_8032AO Fan Min.; 0…10V (default 0V)Write
AV8033AV:AO_FanMax_8033AO Fan Max.; 0…10V (default 10V)Write
AV8034AV:Fan_ManipVar_Start_8034Fan Manipulated Variable Start; 0-30 % (default 0%)Write
AV8035AV:Fan_StartUpTime_8035Fan StartUp Time; 0…25s (default 1s)Write
AV8036AV:Fan_FollwUpTime_8036Fan FollwUp Time; 0…500s (default 1s)Write
AV8037AV:FanGradient_AO_8037Fan Gradient AO; 0…36 °C/°F (default 4°C / 7°F)Write
AV8038AV:DeltaT_FanLevel1RO_8038Delta T Fan Level 1 RO; 0…36 °C/°F (default 0°C / 0°F)Write
AV8039AV:DeltaT_FanLevel2RO_8039Delta T Fan Level 2 RO; 0…36 °C/°F (default 2°C / 4°F)Write
AV8040AV:DeltaT_FanLevel3RO_8040Delta T Fan Level 3 RO; 0…36 °C/°F (default 4°C / 7°F)Write
AV8041AV:Frost_Protection_8041Frost Protection; 0…60,0 °C/°F (default 8°C / 46°F)Write
AV8042AV:Heat_Protection_8042Heat Protection; 0…140,0 °C/°F (default 35°C / 95°F)Write
AV8045AV:2.ContrLoop_PropBandXp_80452. Control Loop Proportional Band Xp; 0,1…27,0 °C/F° (default 2°C / 4°F)Write
AV8046AV:2.ContrLoop_ResTimeTi_80462. Control Loop Reset Time Ti; 0…1200 minutes (default 20 minutes)Write
AV8047AV:2.ContrLoop_ManipVariableMin_80472. Control Loop Manipulated Variable; 0…100% (default 0%)Write
AV8048AV:2.ContrLoop_ManipVariableMax_80482. Control Loop Manipulated Variable; 0…100% (default 100%)Write
AV8049AV:2.ContrLoop_SetTempOffset_80492. Control Loop Setpoint Temp Offset; -25,0…25,0 °C/°F (default 0°C / 0°F)Write
AV8051AV:UnderfloorHeatProtection_Limit_8051Underfloor Heat Protection Limit; 0...122,0 °C/°F (default 34°C / 93°F)Write
AV8052AV:Anti-Jam_8052Anti-Jam (Valve Protection); 0… 60 days (default 3 days)Write
AV8055AV:CangeOver_TempCooling_8055Cange-Over Temp Cooling; 0...122,0 °C/°F (default 22°C / 72°F)Write
AV8056AV:CangeOver_TempHeating_8056Change-Over Temp Heating; 0...122,0 °C/°F (default 25°C / 77°F)Write
AV8200AV:Setpoint_RCV_8200Setpoint RCV; 0…30.000 (default 1000)Write
AV8202AV:PropBand_XpRCV_8202Proportional Band Xp RCV; 1…10.000 (default 100)Write
AV8203AV:ResetTime_Ti_RCV_8203Reset Time Ti RCV; 0…60.000 s (default 420 s)Write
AV8204AV:Hyst_RCVContr_8204Hysteresis RCV Control; 0…30.000 (default 50)Write
AV8205AV:DeltaRCV_FanLevel1RO_8205Delta RCV Fan Level 1 RO; 0…30.000 (default 0)Write
AV8206AV:DeltaRCV_FanLevel2RO_8206Delta RCV Fan Level 2 RO; 0…30.000 (default 100)Write
AV8207AV:DeltaRCV_FanLevel3RO_8207Delta RCV Fan Level 3 RO; 0…30.000 (default 200)Write
AV8209AV:YRCV_MinDev_PIContolLoop_8209Y_RCV Min Deviation PI Contol Loop; 0…50 % (default 5 %)Write
BImin1BI:Presence_Status_1Presence StatusRead0=unoccupied; 1=occupied (default)
BI2BI:HeaderIconStatus_FrostProtection_2Header Icon Frost ProtectionRead0=inactive (default); 1=active
BI3BI:HeaderIconStatus_WindowContact_3Header Icon Window ContactRead0=inactive (default); 1=active
BI4BI:HeaderIconStatus_DewPoint_4Header Icon Dew Point (condensation)Read0=inactive (default); 1=active
BI5BI:HeaderIconStatus_ECO_5Header Icon ECORead0=inactive (default); 1=active
BI6BI:HeaderIconStatus_Error_6Header Icon ErrorRead0=inactive (default); 1=active
BI7BI:HeaderIconStatus_ConfigMode_7Header Icon Config ModeRead0=inactive (default); 1=active
BV12BV:RCBBMS_Temp_Lock_12Temp LockWrite0=inactive (default); 1=active
BV13BV:RCBBMS_Fan_Lock_13Fan LockWrite0=inactive (default); 1=active
BV14BV:RCBBMS_Presence_Lock_14Presence LockWrite0=inactive (default); 1=active
BV196BV:Fan_AutoMode_196Fan Auto ModeWrite0=Manual; 1=Auto (default)
BV199BV:Enable_PresenceDI_199Presence Enable DIWrite0=disable; 1=enable
BV200BV:HeaderIconModbus_FrostProtection_200Icon Modbus frost protectionWrite0=inactive (default); 1=active
BV201BV:HeaderIconModbus_WindowContact_201Icon Modbus window contactWrite0=inactive (default); 1=active
BV202BV:HeaderIconModbus_DewPoint_202Icon Modbus dew point (condensation)Write0=inactive (default); 1=active
BV203BV:HeaderIconModbus_ECO_203Icon Modbus ECOWrite0=inactive (default); 1=active
BV204BV:HeaderIconModbus_Error_204Icon Modbus ErrorWrite0=inactive (default); 1=active
BV205BV:HeaderIconModbus_ConfigMode_205Icon Modbus Config ModeWrite0=inactive (default); 1=active
BV210BV:Enable_FrostProtectionDI_210Icon DI frost protectionWrite0=disable; 1=enable
BV211BV:Enable_WindowContactDI_211Icon DI window contactWrite0=disable; 1=enable
BV212BV:Enable_DewPointDI_212Icon DI dew pointWrite0=disable; 1=enable
BV213BV:Enable_ECODI_213Icon DI ECOWrite0=disable; 1=enable
BV214BV:Enable_ErrorDI_214Icon DI ErrorWrite0=disable; 1=enable
BV96BV:SP1_AutoMode_96Sun Protect 1 automaticWrite0=automatic inactive (default); 1=automatic active
BV97BV:SP2_AutoMode_97Sun Protect 2 automaticWrite0=automatic inactive (default); 1=automatic active
BV116BV:L1_AutoMode_116Light 1 automaticWrite0=automatic inactive (default); 1=automatic active
BV117BV:L2_AutoMode_117Light 2 automaticWrite0=automatic inactive (default); 1=automatic active
BV136BV:L1_LightStatus_136Light 1 statusWrite0=Light off (default); 1=Light on
BV137BV:L2_LightStatus_137Light 2 statusWrite0=Light off (default); 1=Light on
CSV2300CSV:TempS1Int_Label_2300Temp Sensor 1 int. Label; Max. 12 characters. One register in UTF16 format, Latin and CyrillicWrite
CSV2400CSV:HumS1Int_Label_2400Humidity Sensor 1 int. Label; Max. 12 characters. One register in UTF16 format, Latin and CyrillicWrite
CSV2500CSV:CO2S1Int_Label_2500CO2 Sensor 1 int. Label; Max. 12 characters. One register in UTF16 format, Latin and CyrillicWrite
CSV2600CSV:VOCS1Int_Label_2600VOC Sensor 1 int. Label; Max. 12 characters. One register in UTF16 format, Latin and CyrillicWrite
CSV2900CSV:TempS2Ext_Label_2900Temp Sensor 2 ext. Label; Max. 12 characters. One register in UTF16 format, Latin and CyrillicWrite
CSV3000CSV:TempS3Bus_Label_3000Temp Sensor 3 bus Label; Max. 12 characters. One register in UTF16 format, Latin and CyrillicWrite
CSV3100CSV:HumS2Bus_Label_3100Humidity Sensor 2 bus Label; Max. 12 characters. One register in UTF16 format, Latin and CyrillicWrite
CSV3200CSV:CO2S2Bus_Label_3200CO2 Sensor 2 bus Label; Max. 12 characters. One register in UTF16 format, Latin and CyrillicWrite
CSV3300CSV:VOCS2Bus_Label_3300VOC Sensor 2 bus Label; Max. 12 characters. One register in UTF16 format, Latin and CyrillicWrite
CSV3400CSV:PMS2Bus_Label_3400PM Sensor 2 bus Label; Max. 12 characters. One register in UTF16 format, Latin and CyrillicWrite
CSV3500CSV:PressureS2Bus_Label_3500Pressure 2 bus Label; Max. 12 characters. One register in UTF16 format, Latin and Cyrillic alphabetWrite
CSV3750CSV:Fan_Label_3750Fan Label; Max. 12 characters. One register in UTF16 format, Latin and Cyrillic alphabet per characterWrite
CSV4250CSV:SP1_Label_4250Sun Protect 1 Label; Max. 12 characters. One register in UTF16 format, Latin and Cyrillic alphabetWrite
CSV4300CSV:SP2_Label_4300Sun Protect 2 Label; Max. 12 characters. One register in UTF16 format, Latin and Cyrillic alphabetWrite
CSV5350CSV:L1_Label_5350-5361Light 1 Label; Max. 12 characters. One register in UTF16 format, Latin and Cyrillic alphabet perWrite
CSV5400CSV:L2_Label_5400Light 2 Label; Max. 12 characters. One register in UTF16 format, Latin and Cyrillic alphabet perWrite
DTV2018DTV:Date_Time_2018Date Time (winter time); 01.01.2000 00:00:00 – 31.12.2100 23:59:59 (no wildcard and special values)Write
IV2000IV:Device_Type_2000Device Type; 0..2 = internally assigned 3 = RYMASKON 130x interface, no control outputs 4 =Read
IV2001IV:Firmware_2001Firmware; 1011…9999Read
IV2002IV:ProdDate_2002Prod. Date (month/year); 123…1260Read
IV2003IV:OperationDays_2003Operation Days (in days); 0…15000 daysRead
IV2004IV:BusAddress_2004Bus Address; 0…127 (default 0)Read
IV2005IV:Baudrate_2005BaudrateRead0=9600 Bd; 1=19200 Bd; 2=38400 Bd (default); 3=57600 Bd; 4=115200 Bd
IV2006IV:Parity_StopBits_2006Parity / Stop BitsRead0=None (none, 1 stop bit, default); 1=EVEN (even); 2=ODD (odd); 3=None (none, 2 stop bits)
IV3749IV:Fan_Control_3749Fan ControlRead0=no fan control; 1=with fan control
IV4200IV:SP_NumOfCircuits_4200Sun Protect circuitsRead0=no sun protect adjustment; 1=1 sun protect circuit; 2=2 sun protect circuits
IV5300IV:L_NumOfCircuits_5300Light CircuitsRead0=no light adjustment; 1=1 light circuit; 2=2 light circuits
IVmin2025IV:InternalError_2025_bitFieldInternal ErrorRead0=no error (default); 1=error
IV126IV:D1Input_Status_126D1 Input StatusRead0=DI1 open (default); 1=DI1 closed
IV127IV:D2Input_Status_127D2 Input StatusRead0=DI2 open (default); 1=DI2 closed
IV300IV:CO2S1Int_ResetAutozero_300CO2 Sensor 1 int. reset auto zeroWrite0=OFF; 1=ON
IV302IV:CO2S1Int_AutoCalibr_302CO2 Sensor 1 int. auto calibrationWrite0=OFF; 1=ON (default)
IVmin404IV:OpMode_Status_404OpMode StatusWrite0=Off (default); 1=Cooling; 2=Heating
IV405IV:Presence_Status_405Presence StatusRead0=unoccupied; 1=occupied (default)
IV406IV:Fan_AutoMode_406Fan Auto ModeWrite0=Manual; 1=Auto (default)
IVmin407IV:Setpoint_Fan_Level_407Fan LevelWrite0=Off; 1=Level 1 (Default); 2=Level 2; 3=Level 3; 4=Level 4; 5=Level 5
IV408IV:HeaderIconStatus_408_bitFieldHeader Icon/StatusRead
IVmin409IV:RCBBMS_409_bitFieldRoom Climate Controlled By BMSWrite
IV410IV:Presence_Mod_410Presence ModbusWrite0=unoccupied; 1=occupied; 2=occupied via unit (default)
IV411IV:HeaderIconModbus_411_bitFieldHeader Icon ModbusRead
IV412IV:Enable_PresenceDI_412Enable Presence DIWrite0=disable; 1=enable (default)
IV413IV:Enable_IconDI_413_bitFieldEnable Icons DIRead
IV700IV:SP_AutoMode_700_bitFieldSun protect auto modeRead
IV720IV:SP1_KeyStatus_720Sun protect 1 key statusWrite0=no key pressed (default); 1=down short press; 2=down long press; 3=up short press; 4=up long press; 5=down pressed (only mode hold key); 6=up pressed (only mode hold key)
IV730IV:SP2_KeyStatus_730Sun protect 2 key statusWrite0=no key pressed (default); 1=down short press; 2=down long press; 3=up short press; 4=up long press; 5=down pressed (only mode hold key); 6=up pressed (only mode hold key)
IV1100IV:L_AutoMode_1100_bitFieldLight auto modeRead
IV1102IV:L_LightStatus_1102_bitFieldLight statusRead
IV1120IV:L1_KeyStatus_1120Light 1 key statusWrite0=no key pressed (default); 1=down short press; 2=down long press; 3=up short press; 4=up long press; 5=down pressed (only mode hold key); 6=up pressed (only mode hold key)
IV1130IV:L2_KeyStatus_1130Light 2 key statusWrite0=no key pressed (default); 1=down short press; 2=down long press; 3=up short press; 4=up long press; 5=down pressed (only mode hold key); 6=up pressed (only mode hold key)
IV1600IV:ChangeOver_Status_1600Change-Over StatusRead0=Change-Over inactive (default); 1=Cooling Mode (Heating blocked); 2=Heatinge Mode (Cooling blocked)
IV1602IV:ChangeOver_Modbus_1602Change-Over ModbusWrite0=Change-Over inactive; 1=Cooling Mode (Heating blocked); 2=Heatinge Mode (Cooling blocked); 3=Change-Over by DI/Temp (default)
IV1607IV:ContrOpMode_Setpoint_1607Controller OpModeWrite0=OFF; 1=Cooling Auto (Heating blocked); 2=Heating Auto (Cooling deaktiviert); 3=Cooling and Heating Auto
IV1611IV:RODO_OutHeat_BMSContr_1611RO/DO Output Heating BMS Contr.Write0=RO / DO Heating open; 1=RO / DO Heating closed
IV1612IV:RO/DO_OutCool_BMSContr_1612RO/DO Output Cooling BMS Contr.Write0=RO / DO Cooling open; 1=RO / DO Cooling closed
IV1615IV:RO/DO_OutFan_BMSContr_1615RO/DO Output Fan BMS Contr.Write0=OFF; 1=Level 1; 2=Level 2; 3=Level 3
IV1620IV:RODO_Heat_Value_1620RO/DO HeatingRead0=open; 1=closed
IV1621IV:RODO_Cool_Value_1621RO/DO CoolingRead0=open; 1=closed
IV1623IV:RODO_Fan_Level_1623RODO FanRead0=all Relays open (fan off); 1=Relay 1 closed (fan level 1); 2=Relay 2 closed (fan level 2); 3=Relay 3 closed (fan level 3)
IV2008IV:PIN_2008PIN for the display menu; 0000…9999 (default 1111)Write
IV2009IV:Language_2009LanguageWrite0=German; 1=English (default); 2=Spanish; 3=French; 4=Italian; 5=Russian
IV2010IV:Temp_Unit_2010Temp UnitWrite0=°F; 1=°C (default)
IV2011IV:Display_Brightness_2011Display Brightness (when active)Write0=auto (default) 1…100 %
IV2012IV:ScreenSaver_Timeout_2012Screen Saver TimeoutWrite0=deactivated 1…60=1…60s (default 20s)
IV2013IV:SaveToEEPROM_2013Save To NVRAM (EEPROM)Write0=normal (default); 1=save
IV2015IV:Time_Format_2015Time FormatWrite0=12h (am/pm); 1=24h (default); 2=nothing displayed
IV2016IV:Date_Format_2016Date FormatWrite0=week day DD.MM. (default); 1=week day MM.DD; 2=nothing displayed
IV2017IV:Time_SetSummerWinter_2017Summer Time Region (Summer / Winter)Write0=Europe; 1=USA; 2=no time change (default, winter time)
IV2024IV:Display_Darkmode_2024DarkmodeWrite0=Light display mode (default); 1=Dark display mode (darkmode)
IV2313IV:TempS1Int_AveragingTime_2313Temp Sensor 1 int. Averaging TimeWrite0=4s (default); 1=8s; 2=16s; 3=32s
IV2317IV:TempS1Int_EnableInSensorMenu_2317Temp Sensor 1 int. Enable in Sensor MenuWrite0=disable (default); 1=enable
IV2318IV:TempS1Int_EnableColourScale_2318Temp Sensor 1 int. Show Colour ScaleWrite0=disable; 1=enable (default)
IV2413IV:HumS1Int_AveragingTime_2413Humidity Sensor 1 int. Averaging TimeWrite0=4s (default); 1=8s; 2=16s; 3=32s
IV2417IV:HumS1Int_EnableInSensorMenu_2417Humidity Sensor 1 int. Enable in SensorWrite0=disable; 1=enable (default)
IV2418IV:HumS1Int_EnableColourScale_2418Humidity Sensor 1 int. Show Colour ScaleWrite0=disable; 1=enable (default)
IV2513IV:CO2S1Int_AveragingTime_2513CO2 Sensor 1 int. Averaging TimeWrite0=4s (default); 1=8s; 2=16s; 3=32s
IV2517IV:CO2S1Int_EnableInSensorMenu_2517CO2 Sensor 1 int. Enable in Sensor MenuWrite0=disable; 1=enable (default)
IV2518IV:CO2S1Int_EnableColourScale_2518CO2 Sensor 1 int. Show Colour ScaleWrite0=disable; 1=enable (default)
IV2613IV:VOCS1Int_AveragingTime_2613VOC Sensor 1 int. Averaging TimeWrite0=4s (default); 1=8s; 2=16s; 3=32s
IV2617IV:VOCS1Int_EnableInSensorMenu_2617VOC Sensor 1 int. Enable in Sensor MenuWrite0=disable; 1=enable (default)
IV2618IV:VOCS1Int_EnableColourScale_2618VOC Sensor 1 int. Show Colour ScaleWrite0=disable; 1=enable (default)
IV2913IV:TempS2Ext_AveragingTime_2913Temp Sensor 2 ext. Averaging TimeWrite0=4s (default); 1=8s; 2=16s; 3=32s
IV2917IV:TempS2Ext_EnableInSensorMenu_2917Temp Sensor 2 ext. Enable in Sensor MenuWrite0=disable; 1=enable (default)
IV2918IV:TempS2Ext_EnableColourScale_2918Temp Sensor 2 ext. Show Colour ScaleWrite0=disable; 1=enable (default)
IV3017IV:TempS3Bus_EnableInSensorMenu_3017Temp Sensor 3 bus Enable in Sensor menuWrite0=disable; 1=enable (default)
IV3018IV:TempS3Bus_EnableColourScale_3018Temp Sensor 3 bus Show Colour ScaleWrite0=disable; 1=enable (default)
IV3117IV:HumS2Bus_EnableInSensorMenu_3117Humidity Sensor 2 bus Enable in SensorWrite0=disable; 1=enable (default)
IV3118IV:HumS2Bus_EnableColourScale_3118Humidity Sensor 2 bus Show Colour ScaleWrite0=disable; 1=enable (default)
IV3217IV:CO2S2Bus_EnableInSensorMenu_3217CO2 Sensor 2 bus Enable in Sensor MenuWrite0=disable; 1=enable (default)
IV3218IV:CO2S2Bus_EnableColourScale_3218CO2 Sensor 2 bus Enable in Sensor MenuWrite0=disable; 1=enable (default)
IV3316IV:VOCS2Bus_Unit_3316VOC Sensor 2 bus unitWrite0=ppb; 1=% (default)
IV3317IV:VOCS2Bus_EnableInSensorMenu_3317VOC Sensor 2 bus Enable in Sensor MenuWrite0=disable; 1=enable (default)
IV3318IV:VOCS2Bus_EnableColourScale_3318VOC Sensor 2 bus Show Colour ScaleWrite0=disable; 1=enable (default)
IV3417IV:PMS2Bus_EnableInSensorMenu_3417PM Sensor 2 bus Enable in Sensor MenuWrite0=disable; 1=enable (default)
IV3418IV:PMS2Bus_EnableColourScale_3418PM Sensor 2 bus Show Colour ScaleWrite0=disable; 1=enable (default)
IV3516IV:PressureS2Bus_Unit_3516Pressure 2 bus UnitWrite0=Pa; 1=hPa (default); 2=mbar; 3=inWC
IV3517IV:PressureS2Bus_EnableInSensorMenu_3517Pressure 2 bus Enable in Sensor MenuWrite0=disable; 1=enable (default)
IV3518IV:PressureS2Bus_EnableColourScale_3518Pressure 2 bus Show Colour ScaleWrite0=disable; 1=enable (default)
IV3600IV:Setpoint_Temp_Offset_StepSize_3600Temp Setpoint Offset Step SizeWrite0=0,1°; 1=0,2°; 2=0,5° (default, bei °C); 3=1° (default °F)
IV3601IV:OpMode_Display_3601Display OpModeWrite0=disabled Icon; 1=enabled Icon with color change in red, blue, gray (default); 2=enabled Icon without color change (gray only)
IV3602IV:Setpoint_Temp_Display_3602Display Temp SetpointWrite0=nothing displayed; 1=Temp Setpoint Absolute (default); 2=Temp Setpoint Offset Alternative:; 3=Display Humidity Sensor 1 int; 4=Display CO2 Sensor 1 int; 5=Display VOC Sensor 1 int ppb; 6=Display VOC Sensor 1 int %; 7=reserved; 8=Display Temp Sensor 2 ext; 9=Display Temp Sensor 3 Bus; 10=Display Humidity Sensor 2 Bus; 11=Display CO2 Sensor 2 Bus; 12=Display VOC Sensor Bus ppb; 13=Display PM Sensor 2 Bus; 14=Display Pressure Sensor 2 Bus
IV3650IV:CurrentTemp_Mapping_3650Current Temp MappingWrite0=internal temperature sensor (default); 1=external temperature sensor (input must be configured accordingly); 2=Bus
IV3651IV:CurrentTemp_Display_3651Display Current TempWrite0=nothing displayed; 1=Display Current Temp (default); 2=Display Humidity Sensor 1 int; 3=Display CO2 Sensor 1 int; 4=reserved; 5=Display VOC Sensor 1 Int %; 6=reserved; 7=reserved; 8=reserved; 9=Display Humidity Sensor 2 Bus; 10=Display CO2 Sensor 2 Bus; 11=Display VOC Sensor Bus ppb; 12=Display PM Sensor 2 Bus; 13=Display Pressure Sensor 2 Bus
IV3762IV:Fan_NumberOfSteps_3762Number of Fan StepsWrite1=1; 2=1 - 2; 3=1 - 2 - 3; 4=1 - 2 - 3 - 4; 5=1 - 2 - 3 - 4 - 5 (Default)
IV3763IV:Fan_EnableAutoOff_3763Enable Fan Auto/OffWrite0=disable; 1=OFF; 2=Auto; 3=Auto + OFF (Default)
IV3764IV:Fan_DisplayInTempMenu_3764Display Fan In Temp MenuWrite0=disabled (default); 1=enabled
IV3800IV:Presence_Function_3800Presence FunctionWrite0=(default) If Presence Status is "unoccupied", the touch keys for temperature, fan and light/sun protection are blocked for value chang . Navigation through all menus and waking up from the screen saver are retained. Changing Presence Status to "occupied" and enabling all keys for value chang is carried out by presence touch key, by bus or by configured DI input.; 1=If Presence Status is "unoccupied", all buttons remain active (value change and navigation through the menus). Pressing any touch key changes the status to "occupied".; 2=If Presence Status is "unoccupied", the touch keys for temperature, fan and light/sunshade as well as the sensor touch key remain full active (changing values and navigating through the menus). The Presence Status remains "unoccupied" until the presence button, bus or a configured DI input changes to "occupied".
IV3801IV:Enable_PresenceDI_Reboot_3801Presence Enable DI RebootWrite0=disable; 1=enable (default)
IV3802IV:Enable_IconDI_Reboot_3802_bitFieldIcon Enable DI RebootRead
IV3900IV:Input1_Config_3900Input 1 ConfigWrite0=deactivated (default); 1=External temperature sensor NTC10K; 2=DI as pure bus value; 3=DI window contact NO contact; 4=DI window contact NC contact; 5=DI dew point monitors NO contact; 6=DI dew point monitors NC contact; 7=DI presence contact NO contact; 8=DI presence contact NC contact; 9=DI keycard NO contact; 10=DI keycard NC contact; 11=DI alarm NO contact; 12=DI alarm NC contact; 13=DI antifreeze protection NO contact; 14=DI antifreeze protection NC contact; 15=DI ECO NO contact; 16=DI ECO NC contact; 17=Change Over - Cooling (Contact open), Heating (contact closed); 18=Change Over - Heating (Contact open), Cooling (contact closed)
IV3901IV:Input2_Config_3901Input 2 ConfigWrite0=deactivated (default); 1=reserved; 2=DI as pure bus value; 3=DI window contact NO contact; 4=DI window contact NC contact; 5=DI dew point monitors NO contact; 6=DI dew point monitors NC contact; 7=DI presence contact NO contact; 8=DI presence contact NC contact; 9=DI keycard NO contact; 10=DI keycard NC contact; 11=DI alarm NO contact; 12=DI alarm NC contact; 13=DI antifreeze protection NO contact; 14=DI antifreeze protection NC contact; 15=DI ECO NO contact; 16=DI ECO NC contact; 17=Change Over - Cooling (Contact open), Heating (contact closed); 18=Change Over - Heating (Contact open), Cooling (contact closed)
IV4201IV:SP_Display_4201Sun protect displayWrite0=Position and angle shown on the display deactivated; 1=Position and angle shown on the display activated (default)
IV4263IV:SP1_OpMode_4263Sun Protect 1 OpModeWrite0=short-long key (default); 1=hold key; 2=setpoint mode
IV4264IV:SP1_Type_4264Sun Protect 1 TypeWrite0=Sun protection position; 1=Slat angle; 2=Sun protection position + slat angle (default)
IV4313IV:SP2_OpMode_4313Sun Protect 2 OpModeWrite0=short-long key (default); 1=hold key; 2=setpoint mode
IV4314IV:SP2_Type_4314Sun Protect 2 TypeWrite0=Sun protection position; 1=Slat angle; 2=Sun protection position + slat angle (default)
IV5301IV:L_Display_5301Light displayWrite0=Display of the dimming value or ON/OFF on the display deactivated; 1=Display of the dimming value or ON/OFF on the display activated (default)
IV5363IV:L1_Dimmable_5363Light 1 DimmableWrite0=Light dimming deactivated; 1=Light dimming activated (default)
IV5364IV:L1_OpMode_5364Light 1 OpModeWrite0=short-long key (default); 1=hold key; 2=setpoint mode
IV5413IV:L2_Dimmable_5413Light 2 DimmableWrite0=Light dimming deactivated; 1=Light dimming activated (default)
IV5414IV:L2_OpMode_5414Light 2 OpModeWrite0=short-long key (default); 1=hold key; 2=Setpoint mode
IV7040IV:TP1_Activate_7040Time Programm 1 ActivateWrite0=disable (default); 1=enable
IV7041IV:TP1_EventDay_7041Time Programm 1 Event DayWrite
IV7044IV:TP1_RegisterAddress_7044Time Programm 1 Register Address; n/aWrite
IV7045IV:TP1_RegisterNewValue_7045Time Programm 1 Register New Value; n/aWrite
IV7510IV:TP1_Activate_7510Time Programm 48 ActivateWrite0=disable (default); 1=enable
IV7511IV:TP1_EventDay_7511Time Programm 48 Event Day; 0…127, days are bit codedWrite
IV7514IV:TP1_RegisterAddress_7514Time Programm 48 Register Address; n/aWrite
IV7515IV:TP1_RegisterNewValue_7515Time Programm 48 Register New Value; n/aWrite
IV8001IV:Setpoint_Temp_Offs_PresChange_8001Setpoint Temp Offset Presence ChangeWrite0=Reset Setpoint Temp; 1=Reset Setpoint Temp
IV8002IV:Occupied_OverrECO_8002Setpoint Temp Offset Presence ChangeWrite0=Presence has no effect; 1=Presence (occupied)
IV8003IV:ContrTyp_Heating_8003Controller Typ HeatingWrite0=PI controller (default); 1=ON/OFF controller
IV8004IV:ContrTyp_Cooling_8004Controller Typ CoolingWrite0=PI controller (default); 1=ON/OFF controller
IV8005IV:PWM_CycleTime_8005PWM Cycle Time; 5…60 minutes (default 30Write
IV8019IV:ManipVarMin_Behave_8019Manipulated Variable Min. BehaviorWrite0=At least the set minimum; 1=Heating/cooling power is
IV8020IV:Out6WayValve_8020Output 6-Way-ValveWrite0=6-way valve inactive (default); 1=6-way valve general; 2=cooling…heating=2…10 V (e.g. Belimo); 3=heating…cooling=2…10 V (e.g. Belimo, inverted); 4=cooling…heating=0…10 V (DN15, e.g. Sauter); 5=heating…cooling=0…10 V (DN15, e.g. Sauter, inverted); 6=cooling…heating=0…10 V (DN20, e.g. Sauter); 7=heating…cooling=0…10 V (DN20, e.g. Sauter, inverted); 8=0...100% heating=0…10 V; 9=0...100% cooling=0…10 V; 10=0...100% heating=10…0 V; 11=0...100% cooling=10…0 V
IV8025IV:AODirection_Heating_8025AO Direction HeatingWrite0=0…10 V (NC actuators,; 1=10…0 V (NO actuators)
IV8026IV:AODirection_Cooling_8026AO Direction CoolingWrite0=0…10 V (NC actuators,; 1=10…0 V (NO actuators)
IV8027IV:RODODirection_Heating_8027Wirkrichtung RODO HeizenWrite0=Normally open (NC; 1=Normally closed (NO
IV8028IV:RODODirection_Cooling_8028RODO Direction HeatingWrite0=Normally open (NC; 1=Normally closed (NO
IV8031IV:FanMapping_8031Fan MappingWrite0=no assignment to a controller; 1=cooling and heating (default); 2=cooling; 3=heating; 4=humidity (internal sensor); 5=humidity (external sensor); 6=CO2 (internal sensor); 7=CO2 (external sensor); 8=VOC % (internal sensor); 9=VOC (external sensor)
IV8043IV:2.ContrLoop_SensMapping_80432. Control Sensor MappingWrite1=external temperature sensor (default); 2=bus temperature sensor
IV8044IV:2.ContrLoopType_80442. Control Loop TypeWrite0=PI controller; 1=ON/OFF controller; 2=secondary control loop inactive (default)
IV8050IV:UnderfloorHeatProtection_Sensor_8050Underfloor Heat Protection SensorWrite0=none (Temp limit for underfloor heating inactive, default); 1=external temperature sensor; 2=bus temperature sensor
IV8053IV:ContrOpMode_AfterReboot_8053Controller OpMode After RebootWrite0=OFF; 1=Cooling Auto (Heating blocked); 2=Heating Auto (Cooling deaktiviert); 3=Cooling and Heating Auto (default)
IV8054IV:CangeOver_DITemp_8054Cange-Over_DI-TempWrite0=Change-Over inactive (default); 1=DI 1 - Cooling (Contact open), Heating (contact closed); 2=DI 1 - Heating (Contact open), Cooling (contact closed); 3=DI 2 - Cooling (Contact open), Heating (contact closed); 4=DI 2 - Heating (Contact open), Cooling (contact closed); 5=external temperature sensor; 6=bus temperature sensor
IV8201IV:ContrTyp_RCV_8201Control Type RCVWrite0=PI controller (default); 1=ON/OFF controller
Other7042TV:TP1_EventHour_7042Time Programm 1 Event Hour and Minute; 00:00…23:59 (no wildcard and special value)Write
Other7512TV:TP48_EventHour_7042Time Programm 48 Event Hour and Minute; 00:00…23:59 (no wildcard and special value)Write
Object ID lookup: S+S Regeltechnik RYMASKON 1000 room operating unit point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the RYMASKON 1000 room operating unit (Interface / Controller) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the S+S Regeltechnik RYMASKON 1000 room operating unit (Interface / Controller)

How many BACnet points does the S+S Regeltechnik RYMASKON 1000 room operating unit (Interface / Controller) have?

This list has 335 BACnet objects: 38 analog inputs, 120 analog values, 7 binary inputs, 22 binary values, 16 characterstring values, 1 datetime value, 129 integer values, 2 others. The exact set on a given unit depends on its firmware, installed options and configuration.

Which S+S Regeltechnik RYMASKON 1000 room operating unit (Interface / Controller) BACnet points are writable?

253 of the 335 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official S+S Regeltechnik RYMASKON 1000 room operating unit (Interface / Controller) BACnet documentation?

The source is BACnet PIC - Rymaskon 1000 Interface / Controller BACnet, revision 2026-09-14, published free by S+S Regeltechnik at https://www.spluss.com/cdn/shop/files/RYM-1000__BACnet_Objects_GB.pdf.

What are the minimum BACnet points to integrate the S+S Regeltechnik RYMASKON 1000 room operating unit (Interface / Controller)?

Start with IV 404 IV:OpMode_Status_404 (Operating mode: 0 Off, 1 Cooling, 2 Heating); AV 400 AV:Setpoint_Temp_400 (Room temperature setpoint, °C); IV 407 IV:Setpoint_Fan_Level_407 (Fan level 0-5); IV 409 IV:RCBBMS_409_bitField (BMS lock of setpoint, fan and presence keys); AI 1 AI:TempS1Int_Value_1 (Room temperature (internal sensor)); BI 1 BI:Presence_Status_1 (Presence: 1 = occupied); AI 9 AI:OpMode_Status_9 (Operating mode status); AI 8 AI:Setpoint_Temp_Absolut_8 (Absolute temperature setpoint in use); IV 2025 IV:InternalError_2025_bitField (Internal error bits (sensor, I2C)).

How do I enable BMS control of the S+S Regeltechnik RYMASKON 1000 room operating unit (Interface / Controller)?

Controller variants: IV 1607 Controller OpMode sets how the internal controller drives the outputs (0 Off, 1 cooling, 2 heating, 3 both). The BMS can take over each output with the BMS Contr. objects (AV 1608-1610, 1613; IV 1611, 1612, 1615); -1 returns an output to the internal controller.

How do I check these points on the real RYMASKON 1000 room operating unit (Interface / Controller)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: BACnet PIC - Rymaskon 1000 Interface / Controller BACnet · rev. 2026-09-14. Object names, instances and units are reproduced as published; descriptions are our own.