Fan inlet airflow and temperature monitor (airflow measuring station) · BACnet points list

Ruskin TDFi-Rt Electronic Fan Inlet Monitor BACnet points list

Updated 4 November 2026

Short answer

The TDFi-Rt measures airflow and air temperature at fan inlets with thermal dispersion sensors and reports them over BACnet MS/TP. It exposes only Analog Value objects: a fan summary temperature and airflow, then one temperature and one airflow object per fan for up to 16 fans, plus a Notification Class for alarms. All values are read-only.

This page lists 35 BACnet objects for the Ruskin TDFi-Rt Electronic Fan Inlet Monitor — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Ruskin’s own free documentation, linked below.

Manufacturer
Ruskin
Model
TDFi-Rt Electronic Fan Inlet Monitor
Equipment
Fan inlet airflow and temperature monitor (airflow measuring station)
Equipment type
Thermostats, sensors & meters
BACnet objects
35 (0 writable)
Transport
BACnet MS/TP
Firmware
1.0.3 (application 1.1.0)
Also known as
TDFi-Rt, TDFi-RT, TDFi Rt, Ruskin fan inlet airflow monitor
Source document
Advanced Thermal Dispersion Communications for Fan Inlet Air Monitoring (PICS) · PICS v1.0.1 · rev. 2021-12
Download CSV 35 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Ruskin’s current documentation and the live device before use. Not official Ruskin information. Terms of use.

BMS integration notes: Ruskin TDFi-Rt Electronic Fan Inlet Monitor

Integration in brief

A read-only measuring device: set its MS/TP address and baud in the device menu, then read the fan summary airflow and temperature, plus per-fan values if you need them. Choose the airflow units (velocity or volume, actual or standard) on the device before mapping, since the object names and units follow that setting.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 2Fan Summary ACT AirflowTotal/average airflow across the monitored fansRead
AV 1Fan Summary TemperatureAverage air temperature across the fansRead
AV 4Fan 1 Actual Airflow VolumeFan 1 airflow (repeat for each fan)Read

Network setup

Watch out for

Ruskin TDFi-Rt Electronic Fan Inlet Monitor BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

35 of 35 shown
Type
AnalogOther
Show
Ruskin TDFi-Rt Electronic Fan Inlet Monitor BACnet Points List
DescriptionStates
NC1Notification ClassNotification class for alarm/event recipientsRead
AVmin1Fan Summary TemperatureFan Summary Average Temperature°F or °C (display setting)Read
AVmin2Fan Summary ACT AirflowFan Summary airflow velocity or volumefpm, cfm or metric equivalent (display setting)Read
AV3Fan 1 TemperatureIndividual Fan 1 Temperature°F or °C (display setting)Read
AVmin4Fan 1 Actual Airflow VolumeIndividual Fan 1 airflow velocity or volumefpm, cfm or metric equivalent (display setting)Read
AV5Fan 2 TemperatureIndividual Fan 2 Temperature°F or °C (display setting)Read
AV6Fan 2 Actual Airflow VolumeIndividual Fan 2 airflow velocity or volumefpm, cfm or metric equivalent (display setting)Read
AV7Fan 3 TemperatureIndividual Fan 3 Temperature°F or °C (display setting)Read
AV8Fan 3 Actual Airflow VolumeIndividual Fan 3 airflow velocity or volumefpm, cfm or metric equivalent (display setting)Read
AV9Fan 4 TemperatureIndividual Fan 4 Temperature°F or °C (display setting)Read
AV10Fan 4 Actual Airflow VolumeIndividual Fan 4 airflow velocity or volumefpm, cfm or metric equivalent (display setting)Read
AV11Fan 5 TemperatureIndividual Fan 5 Temperature°F or °C (display setting)Read
AV12Fan 5 Actual Airflow VolumeIndividual Fan 5 airflow velocity or volumefpm, cfm or metric equivalent (display setting)Read
AV13Fan 6 TemperatureIndividual Fan 6 Temperature°F or °C (display setting)Read
AV14Fan 6 Actual Airflow VolumeIndividual Fan 6 airflow velocity or volumefpm, cfm or metric equivalent (display setting)Read
AV15Fan 7 TemperatureIndividual Fan 7 Temperature°F or °C (display setting)Read
AV16Fan 7 Actual Airflow VolumeIndividual Fan 7 airflow velocity or volumefpm, cfm or metric equivalent (display setting)Read
AV17Fan 8 TemperatureIndividual Fan 8 Temperature°F or °C (display setting)Read
AV18Fan 8 Actual Airflow VolumeIndividual Fan 8 airflow velocity or volumefpm, cfm or metric equivalent (display setting)Read
AV19Fan 9 TemperatureIndividual Fan 9 Temperature°F or °C (display setting)Read
AV20Fan 9 Actual Airflow VolumeIndividual Fan 9 airflow velocity or volumefpm, cfm or metric equivalent (display setting)Read
AV21Fan 10 TemperatureIndividual Fan 10 Temperature°F or °C (display setting)Read
AV22Fan 10 Actual Airflow VolumeIndividual Fan 10 airflow velocity or volumefpm, cfm or metric equivalent (display setting)Read
AV23Fan 11 TemperatureIndividual Fan 11 Temperature°F or °C (display setting)Read
AV24Fan 11 Actual Airflow VolumeIndividual Fan 11 airflow velocity or volumefpm, cfm or metric equivalent (display setting)Read
AV25Fan 12 TemperatureIndividual Fan 12 Temperature°F or °C (display setting)Read
AV26Fan 12 Actual Airflow VolumeIndividual Fan 12 airflow velocity or volumefpm, cfm or metric equivalent (display setting)Read
AV27Fan 13 TemperatureIndividual Fan 13 Temperature°F or °C (display setting)Read
AV28Fan 13 Actual Airflow VolumeIndividual Fan 13 airflow velocity or volumefpm, cfm or metric equivalent (display setting)Read
AV29Fan 14 TemperatureIndividual Fan 14 Temperature°F or °C (display setting)Read
AV30Fan 14 Actual Airflow VolumeIndividual Fan 14 airflow velocity or volumefpm, cfm or metric equivalent (display setting)Read
AV31Fan 15 TemperatureIndividual Fan 15 Temperature°F or °C (display setting)Read
AV32Fan 15 Actual Airflow VolumeIndividual Fan 15 airflow velocity or volumefpm, cfm or metric equivalent (display setting)Read
AV33Fan 16 TemperatureIndividual Fan 16 Temperature°F or °C (display setting)Read
AV34Fan 16 Actual Airflow VolumeIndividual Fan 16 airflow velocity or volumefpm, cfm or metric equivalent (display setting)Read
Object ID lookup: Ruskin TDFi-Rt Electronic Fan Inlet Monitor point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TDFi-Rt Electronic Fan Inlet Monitor and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Ruskin TDFi-Rt Electronic Fan Inlet Monitor

How many BACnet points does the Ruskin TDFi-Rt Electronic Fan Inlet Monitor have?

This list has 35 BACnet objects: 34 analog values, 1 notification class. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Ruskin TDFi-Rt Electronic Fan Inlet Monitor BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official Ruskin TDFi-Rt Electronic Fan Inlet Monitor BACnet documentation?

The source is Advanced Thermal Dispersion Communications for Fan Inlet Air Monitoring (PICS) (PICS v1.0.1), revision 2021-12, published free by Ruskin at https://www.ruskin.com/doc/Id/9818.

What are the minimum BACnet points to integrate the Ruskin TDFi-Rt Electronic Fan Inlet Monitor?

Start with AV 2 Fan Summary ACT Airflow (Total/average airflow across the monitored fans); AV 1 Fan Summary Temperature (Average air temperature across the fans); AV 4 Fan 1 Actual Airflow Volume (Fan 1 airflow (repeat for each fan)).

How do I check these points on the real TDFi-Rt Electronic Fan Inlet Monitor?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.