Fire / smoke damper actuator controller · BACnet points list

RFT IXI-R2-230 universal field controller for two 230 V damper actuators BACnet points list

Updated 12 November 2026

Short answer

The IXI-R2-230 drives two 230 V damper actuators and reads their open and closed end switches. Over BACnet it exposes each damper's relay command, position, moving and end-switch flags, a status code, test functions and the local manual-override input. Objects come in pairs, one per damper.

This page lists 43 BACnet objects for the RFT IXI-R2-230 universal field controller for two 230 V damper actuators — 15 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from RFT’s own free documentation, linked below.

Manufacturer
RFT
Model
IXI-R2-230 universal field controller for two 230 V damper actuators
Equipment
Fire / smoke damper actuator controller
Equipment type
Valves & actuators
BACnet objects
43 (15 writable)
Transport
—
Firmware
Not stated
Default device instance
804XXX
Also known as
IXI-R2-230, IXI R2 230, RFT IXI, IXI-R2
Source document
IXI R2 230 BACnet Object List · rev. 08/2017
Download CSV 43 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against RFT’s current documentation and the live device before use. Not official RFT information. Terms of use.

BMS integration notes: RFT IXI-R2-230 universal field controller for two 230 V damper actuators

Integration in brief

Command each damper through its relay BO (BO 4, BO 5) and read the end switches, moving flags and MV status per damper. BV 16/17 start a full automatic test and BV 19 clears messages.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 4Relay Damper-Damper 1Damper 1 actuator command (BO 5 for damper 2)Write
BV 19Clear Message- Both DampersClears damper messagesWrite
BV 13Damper Open-Damper 1Damper 1 openRead
BV 12Damper Close-Damper 1Damper 1 closedRead
BV 6ManualOverride_Effective-Damper 1Local manual override active on damper 1Read
MV 1Status Damper 1Status; 2 = end position not reached (MV 2 = damper 2)Read

Network setup

Watch out for

RFT IXI-R2-230 universal field controller for two 230 V damper actuators BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

43 of 43 shown
Type
AnalogMulti-state
Access
Show
RFT IXI-R2-230 universal field controller for two 230 V damper actuators BACnet Points List
DescriptionStates
BI0DI1_ManualOverride-Physical Input-Damper 1Manual override input, damper 1Read0=Off, 1=On
BI1DI1_ManualOverride-Physical Input-Damper 2Manual override input, damper 2Read0=Off, 1=On
BO0LED_Close-Damper 1Closed LED, damper 1Read0=Off, 1=On
BO1LED_Close-Damper 2Closed LED, damper 2Read0=Off, 1=On
BO2LED_Open-Damper 1Open LED, damper 1Read0=Off, 1=On
BO3LED_Open-Damper 2Open LED, damper 2Read0=Off, 1=On
BOmin4Relay Damper-Damper 1Actuator relay, damper 1 (open/close command)Write0=Off, 1=On
BO5Relay Damper-Damper 2Actuator relay, damper 2 (open/close command)Write0=Off, 1=On
AV0DI1_ManualOverride_OnDelay-Damper 1Manual override on-delay, 0-180 ssWrite
AV1DI1_ManualOverride_OnDelay-Damper 2Manual override on-delay, 0-180 ssWrite
AV2BaudRateBaud rate / 10 (960, 1920, 3840, 7680)Read
AV3DamperPosition-Damper 1Damper position 0, 50 or 100 %%Read
AV4DamperPosition-Damper 2Damper position 0, 50 or 100 %%Read
AV5DamperCheckTime-Damper 1Damper travel check time, 0-360 ssWrite
AV6DamperCheckTime-Damper 2Damper travel check time, 0-360 ssWrite
AV7System Status-Damper 1Status code 1-8 (see MV 1)Read
AV8System Status-Damper 2Status code 1-8 (see MV 2)Read
AV9InternalParameters-Damper 1Internal parameter, 0-1024Read
AV10InternalParameters-Damper 2Internal parameter, 0-1024Read
AV11Device InstantDevice instance, 804XXXWrite
AV12Logic Alarm DelayLogic alarm delay, 0-360Write
AV13Logic AlarmLogic alarm, 0-1Write
BV0DI1_ManualOverride_Normally Close/Open-Damper 1Override input contact type, damper 1Write0=Off, 1=On
BV1DI1_ManualOverride_Normally Close/Open-Damper 2Override input contact type, damper 2Write0=Off, 1=On
BV2Dip Switch Selection – Fire Application-Damper 1DIP switch set for fire damper use, damper 1Read0=Off, 1=On
BV3Dip Switch Selection – Fire Application-Damper 2DIP switch set for fire damper use, damper 2Read0=Off, 1=On
BVmin6ManualOverride_Effective-Damper 1Manual override active, damper 1Read0=Off, 1=On
BV7ManualOverride_Effective-Damper 2Manual override active, damper 2Read0=Off, 1=On
BV8DamperMoving-Damper 1Damper 1 movingRead0=Off, 1=On
BV9DamperMoving-Damper 2Damper 2 movingRead0=Off, 1=On
BV10TestButton-Damper 1Test button pressed, damper 1Read0=Off, 1=On
BV11TestButton-Damper 2Test button pressed, damper 2Read0=Off, 1=On
BVmin12Damper Close-Damper 1Damper 1 closedRead0=Off, 1=On
BVmin13Damper Open-Damper 1Damper 1 openRead0=Off, 1=On
BV14Damper Close-Damper 2Damper 2 closedRead0=Off, 1=On
BV15Damper Open-Damper 2Damper 2 openRead0=Off, 1=On
BV16FullAutoTest-Damper 1Start full automatic test, damper 1Write0=Off, 1=On
BV17FullAutoTest-Damper 2Start full automatic test, damper 2Write0=Off, 1=On
BV18SetFactoryDefaultRestore factory defaultsWrite0=Off, 1=On
BVmin19Clear Message- Both DampersClear messages for both dampersWrite0=Off, 1=On
MV0BaudRateBaud rateRead9600, 19200, 38400, 76800
MVmin1Status Damper 1Damper 1 statusRead1=Normal, 2=Actuator Not Reach End Position, 3=Not In Use, 4=Not In Use, 5=Any Other Error, 6=Test In Progress, 7=Test Report Normal, 8=Test Report Error
MV2Status Damper 2Damper 2 statusRead1=Normal, 2=Actuator Not Reach End Position, 3=Not In Use, 4=Not In Use, 5=Any Other Error, 6=Test In Progress, 7=Test Report Normal, 8=Test Report Error
Object ID lookup: RFT IXI-R2-230 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IXI-R2-230 universal field controller for two 230 V damper actuators and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the RFT IXI-R2-230 universal field controller for two 230 V damper actuators

How many BACnet points does the RFT IXI-R2-230 universal field controller for two 230 V damper actuators have?

This list has 43 BACnet objects: 14 analog values, 2 binary inputs, 6 binary outputs, 18 binary values, 3 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which RFT IXI-R2-230 universal field controller for two 230 V damper actuators BACnet points are writable?

15 of the 43 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official RFT IXI-R2-230 universal field controller for two 230 V damper actuators BACnet documentation?

The source is IXI R2 230 BACnet Object List, revision 08/2017, published free by RFT at https://www.rft.eu/assets/PIM/DOCUMENTS/TECH_DATA/IXI-R2-230_BACnet%20Object%20List.pdf.

What are the minimum BACnet points to integrate the RFT IXI-R2-230 universal field controller for two 230 V damper actuators?

Start with BO 4 Relay Damper-Damper 1 (Damper 1 actuator command (BO 5 for damper 2)); BV 19 Clear Message- Both Dampers (Clears damper messages); BV 13 Damper Open-Damper 1 (Damper 1 open); BV 12 Damper Close-Damper 1 (Damper 1 closed); BV 6 ManualOverride_Effective-Damper 1 (Local manual override active on damper 1); MV 1 Status Damper 1 (Status; 2 = end position not reached (MV 2 = damper 2)).

How do I check these points on the real IXI-R2-230 universal field controller for two 230 V damper actuators?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: IXI R2 230 BACnet Object List · rev. 08/2017. Object names, instances and units are reproduced as published; descriptions are our own.