Boiler controller gateway · BACnet points list

Raypak VERSA IC - ProtoNode RER/LER (B-85 / B-86) BACnet points list

Updated 28 October 2026

Short answer

The ProtoNode RER reads one or more Raypak VERSA IC controls over Modbus RTU and makes each one a separate BACnet IP or BACnet MS/TP device. The Master profile used for single boilers and cascade masters has 173 objects: system temperatures and calls, a 29-point block for each of up to 4 boilers, writable setpoint, outdoor reset, DHW, tank and pool settings, and on/off commands per boiler. Cascade followers use a smaller Follower profile.

This page lists 173 BACnet objects for the Raypak VERSA IC - ProtoNode RER/LER (B-85 / B-86) — 32 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Raypak’s own free documentation, linked below.

Manufacturer
Raypak
Model
VERSA IC - ProtoNode RER/LER (B-85 / B-86)
Equipment
Boiler controller gateway
Equipment type
Boilers & water heaters
BACnet objects
173 (32 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
50000 + VERSA IC Modbus node ID (BN_Node_Offset default 50000)
Also known as
VERSA IC, Versa IC, ProtoNode RER, ProtoNode LER, FPC-N34, FPC-N35, B-85, B-86, 241515
Source document
Installation & Operating Instructions - ProtoNode RER and ProtoNode LER (FPC N34 / FPC N35) B-85 / B-86 · P/N 241515 Rev. 5 · rev. Effective 08-25-23
Download CSV 173 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Raypak VERSA IC - ProtoNode RER/LER (B-85 / B-86)

Integration in brief

Add a Master profile in the ProtoNode Web Configurator for each VERSA IC (Follower profile for cascade followers) with its Modbus node ID, then find each one as its own BACnet device. Turn boilers on with the Blr On/Off BVs and set the target with Target Mode plus Setpoint Target or Target Mod Rate; read supply temperature, boiler outlet temperature, modulation rate, ignition status and error code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 162Blr 1 On/OffBoiler 1 on/off command (BV 163-165 for 2-4)Write
BV 134Target ModeSelects which target applies (values not documented)Write
AV 135Setpoint TargetTarget water setpointWrite
AV 160Target Mod RateTarget modulation rateWrite
AI 25Blr 1 Ignition StatusBoiler 1 ignition state codeRead
AI 2System Supply TemperatureSystem supply water temperatureRead
AI 18Blr 1 Outlet temperatureBoiler 1 outlet water temperatureRead
AI 23Blr 1 Mod RateBoiler 1 modulation rateRead
AI 30Blr 1 Error CodeBoiler 1 active error codeRead

Enable & remote start

The Master profile has writable on/off BVs per boiler (BV 162-165) and a Target Mode BV with Setpoint Target (AV 135), Target temperature (AV 158) and Target Mod Rate (AV 160). The manual does not explain the Target Mode values or which target applies in each mode.

Network setup

Watch out for

Raypak VERSA IC - ProtoNode RER/LER (B-85 / B-86) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

173 of 173 shown
Type
Access
Show
Raypak VERSA IC - ProtoNode RER/LER (B-85 / B-86) BACnet Points List
DescriptionStates
AI1MODBUSRead
AImin2System Supply TemperatureSystem supply water temperatureRead
AI3Outdoor TemperatureOutdoor air temperatureRead
AI4DHW TemperatureDHW tank temperatureRead
AI5Aux 1 TemperatureAuxiliary sensor 1 temperatureRead
AI6Aux 2 TemperatureAuxiliary sensor 2 temperatureRead
AI7System PumpSystem pump stateRead
AI8System Pump RuntimeSystem pump run timeRead
AI9DHW PumpDHW pump stateRead
AI10DHW Pump RuntimeDHW pump run timeRead
AI11SetbackSetback stateRead
AI12CH CallCentral heat callRead
AI13DHW CallDHW callRead
AI14Target temperatureCurrent target water temperatureRead
AI15Target rateCurrent target firing rateRead
BI16Auto DiffRead
BI17Blr 1 detectedBoiler 1 detected on the busRead
AImin18Blr 1 Outlet temperatureBoiler 1 outlet water temperatureRead
AI19Blr 1 Inlet temperatureBoiler 1 inlet water temperatureRead
AI20Blr 1 Vent temperatureBoiler 1 vent (flue) temperatureRead
AI21Blr 1 High Limit temperatureBoiler 1 high limit sensor temperatureRead
AI22Blr 1 Operator temperatureBoiler 1 operator sensor temperatureRead
AImin23Blr 1 Mod RateBoiler 1 modulation rateRead
AI24Blr 1 Mix RateBoiler 1 mix rateRead
AImin25Blr 1 Ignition StatusBoiler 1 ignition status codeRead
AI26Blr 1 RuntimeBoiler 1 burner run timeRead
AI27Blr 1 CyclesBoiler 1 burner cyclesRead
AI28Blr 1 PumpBoiler 1 pump stateRead
AI29Blr 1 Pump RuntimeBoiler 1 pump run timeRead
AImin30Blr 1 Error CodeBoiler 1 active error codeRead
AI31Blr 1 Error History 1Boiler 1 error history entry 1Read
AI32Blr 1 Error History 2Boiler 1 error history entry 2Read
AI33Blr 1 Error History 3Boiler 1 error history entry 3Read
AI34Blr 1 Error History 4Boiler 1 error history entry 4Read
AI35Blr 1 Error History 5Boiler 1 error history entry 5Read
AI36Blr 1 Error History 6Boiler 1 error history entry 6Read
AI37Blr 1 Error History 7Boiler 1 error history entry 7Read
AI38Blr 1 Error History 8Boiler 1 error history entry 8Read
AI39Blr 1 Error History 9Boiler 1 error history entry 9Read
AI40Blr 1 Error History 10Boiler 1 error history entry 10Read
AI41Blr 1 Error History 11Boiler 1 error history entry 11Read
AI42Blr 1 Error History 12Boiler 1 error history entry 12Read
AI43Blr 1 Error History 13Boiler 1 error history entry 13Read
AI44Blr 1 Error History 14Boiler 1 error history entry 14Read
AI45Blr 1 Error History 15Boiler 1 error history entry 15Read
BI46Blr 2 detectedBoiler 2 detected on the busRead
AI47Blr 2 Outlet temperatureBoiler 2 outlet water temperatureRead
AI48Blr 2 Inlet temperatureBoiler 2 inlet water temperatureRead
AI49Blr 2 Vent temperatureBoiler 2 vent (flue) temperatureRead
AI50Blr 2 High Limit temperatureBoiler 2 high limit sensor temperatureRead
AI51Blr 2 Operator temperatureBoiler 2 operator sensor temperatureRead
AI52Blr 2 Mod RateBoiler 2 modulation rateRead
AI53Blr 2 Mix RateBoiler 2 mix rateRead
AI54Blr 2 Ignition StatusBoiler 2 ignition status codeRead
AI55Blr 2 RuntimeBoiler 2 burner run timeRead
AI56Blr 2 CyclesBoiler 2 burner cyclesRead
AI57Blr 2 PumpBoiler 2 pump stateRead
AI58Blr 2 Pump RuntimeBoiler 2 pump run timeRead
AI59Blr 2 Error CodeBoiler 2 active error codeRead
AI60Blr 2 Error History 1Boiler 2 error history entry 1Read
AI61Blr 2 Error History 2Boiler 2 error history entry 2Read
AI62Blr 2 Error History 3Boiler 2 error history entry 3Read
AI63Blr 2 Error History 4Boiler 2 error history entry 4Read
AI64Blr 2 Error History 5Boiler 2 error history entry 5Read
AI65Blr 2 Error History 6Boiler 2 error history entry 6Read
AI66Blr 2 Error History 7Boiler 2 error history entry 7Read
AI67Blr 2 Error History 8Boiler 2 error history entry 8Read
AI68Blr 2 Error History 9Boiler 2 error history entry 9Read
AI69Blr 2 Error History 10Boiler 2 error history entry 10Read
AI70Blr 2 Error History 11Boiler 2 error history entry 11Read
AI71Blr 2 Error History 12Boiler 2 error history entry 12Read
AI72Blr 2 Error History 13Boiler 2 error history entry 13Read
AI73Blr 2 Error History 14Boiler 2 error history entry 14Read
AI74Blr 2 Error History 15Boiler 2 error history entry 15Read
BI75Blr 3 detectedBoiler 3 detected on the busRead
AI76Blr 3 Outlet temperatureBoiler 3 outlet water temperatureRead
AI77Blr 3 Inlet temperatureBoiler 3 inlet water temperatureRead
AI78Blr 3 Vent temperatureBoiler 3 vent (flue) temperatureRead
AI79Blr 3 High Limit temperatureBoiler 3 high limit sensor temperatureRead
AI80Blr 3 Operator temperatureBoiler 3 operator sensor temperatureRead
AI81Blr 3 Mod RateBoiler 3 modulation rateRead
AI82Blr 3 Mix RateBoiler 3 mix rateRead
AI83Blr 3 Ignition StatusBoiler 3 ignition status codeRead
AI84Blr 3 RuntimeBoiler 3 burner run timeRead
AI85Blr 3 CyclesBoiler 3 burner cyclesRead
AI86Blr 3 PumpBoiler 3 pump stateRead
AI87Blr 3 Pump RuntimeBoiler 3 pump run timeRead
AI88Blr 3 Error CodeBoiler 3 active error codeRead
AI89Blr 3 Error History 1Boiler 3 error history entry 1Read
AI90Blr 3 Error History 2Boiler 3 error history entry 2Read
AI91Blr 3 Error History 3Boiler 3 error history entry 3Read
AI92Blr 3 Error History 4Boiler 3 error history entry 4Read
AI93Blr 3 Error History 5Boiler 3 error history entry 5Read
AI94Blr 3 Error History 6Boiler 3 error history entry 6Read
AI95Blr 3 Error History 7Boiler 3 error history entry 7Read
AI96Blr 3 Error History 8Boiler 3 error history entry 8Read
AI97Blr 3 Error History 9Boiler 3 error history entry 9Read
AI98Blr 3 Error History 10Boiler 3 error history entry 10Read
AI99Blr 3 Error History 11Boiler 3 error history entry 11Read
AI100Blr 3 Error History 12Boiler 3 error history entry 12Read
AI101Blr 3 Error History 13Boiler 3 error history entry 13Read
AI102Blr 3 Error History 14Boiler 3 error history entry 14Read
AI103Blr 3 Error History 15Boiler 3 error history entry 15Read
BI104Blr 4 detectedBoiler 4 detected on the busRead
AI105Blr 4 Outlet temperatureBoiler 4 outlet water temperatureRead
AI106Blr 4 Inlet temperatureBoiler 4 inlet water temperatureRead
AI107Blr 4 Vent temperatureBoiler 4 vent (flue) temperatureRead
AI108Blr 4 High Limit temperatureBoiler 4 high limit sensor temperatureRead
AI109Blr 4 Operator temperatureBoiler 4 operator sensor temperatureRead
AI110Blr 4 Mod RateBoiler 4 modulation rateRead
AI111Blr 4 Mix RateBoiler 4 mix rateRead
AI112Blr 4 Ignition StatusBoiler 4 ignition status codeRead
AI113Blr 4 RuntimeBoiler 4 burner run timeRead
AI114Blr 4 CyclesBoiler 4 burner cyclesRead
AI115Blr 4 PumpBoiler 4 pump stateRead
AI116Blr 4 Pump RuntimeBoiler 4 pump run timeRead
AI117Blr 4 Error CodeBoiler 4 active error codeRead
AI118Blr 4 Error History 1Boiler 4 error history entry 1Read
AI119Blr 4 Error History 2Boiler 4 error history entry 2Read
AI120Blr 4 Error History 3Boiler 4 error history entry 3Read
AI121Blr 4 Error History 4Boiler 4 error history entry 4Read
AI122Blr 4 Error History 5Boiler 4 error history entry 5Read
AI123Blr 4 Error History 6Boiler 4 error history entry 6Read
AI124Blr 4 Error History 7Boiler 4 error history entry 7Read
AI125Blr 4 Error History 8Boiler 4 error history entry 8Read
AI126Blr 4 Error History 9Boiler 4 error history entry 9Read
AI127Blr 4 Error History 10Boiler 4 error history entry 10Read
AI128Blr 4 Error History 11Boiler 4 error history entry 11Read
AI129Blr 4 Error History 12Boiler 4 error history entry 12Read
AI130Blr 4 Error History 13Boiler 4 error history entry 13Read
AI131Blr 4 Error History 14Boiler 4 error history entry 14Read
AI132Blr 4 Error History 15Boiler 4 error history entry 15Read
BVmin134Target ModeTarget mode selectionWrite
AVmin135Setpoint TargetTarget setpointWrite
AV136Outdoor StartOutdoor reset: outdoor start temperatureWrite
AV137Outdoor DesignOutdoor reset: outdoor design temperatureWrite
AV138Boil StartOutdoor reset: boiler water start temperatureWrite
AV139Boil DesignOutdoor reset: boiler water design temperatureWrite
AV140Manual DifferentialDifferential settingWrite
AV141DHW ExchangeDHW exchange temperatureWrite
AV142DHW TankDHW tank settingWrite
AV143DHW DifferentialDHW differentialWrite
BV144DHW PriorityDHW priority on/offWrite
BV145DHW During UnOccDHW during unoccupied on/offWrite
AV146WWSD During OccWarm weather shutdown temperature, occupiedWrite
AV147WWSD During UnOccWarm weather shutdown temperature, unoccupiedWrite
AV148Tank SetpointTank setpointWrite
AV149Tank DifferentialTank differentialWrite
BV150Tank During UnOccTank heating during unoccupied on/offWrite
AV151Pool SetpointPool setpointWrite
AV152Pool DifferentialPool differentialWrite
AV153Pool Supply MaxPool maximum supply temperatureWrite
BV154Pool During UnOccPool heating during unoccupied on/offWrite
AV155System PumpSystem pump settingWrite
AV156DHW PumpDHW pump settingWrite
AV157Boiler PumpBoiler pump settingWrite
AV158Target temperatureTarget water temperature (writable)Write
AV159Manual DifferentialTemperature differential settingWrite
AVmin160Target Mod RateTarget modulation rateWrite
AV161Target Mix RateTarget mix rateWrite
BVmin162Blr 1 On/OffBoiler 1 on/off commandWrite
BV163Blr 2 On/OffBoiler 2 on/off commandWrite
BV164Blr 3 On/OffBoiler 3 on/off commandWrite
BV165Blr 4 On/OffBoiler 4 on/off commandWrite
AI166Blr 1 Flow SensorBoiler 1 flow sensor valueRead
AI167Blr 2 Flow SensorBoiler 2 flow sensor valueRead
AI168Blr 3 Flow SensorBoiler 3 flow sensor valueRead
AI169Blr 4 Flow SensorBoiler 4 flow sensor valueRead
AI170Override GovernorRead
AI171Blr 1 Flame CurrentBoiler 1 flame currentRead
AI172Blr 2 Flame CurrentBoiler 2 flame currentRead
AI173Blr 3 Flame CurrentBoiler 3 flame currentRead
AI174Blr 4 Flame CurrentBoiler 4 flame currentRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VERSA IC - ProtoNode RER/LER (B-85 / B-86) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Raypak VERSA IC - ProtoNode RER/LER (B-85 / B-86)

How many BACnet points does the Raypak VERSA IC - ProtoNode RER/LER (B-85 / B-86) have?

This list has 173 BACnet objects: 136 analog inputs, 23 analog values, 5 binary inputs, 9 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Raypak VERSA IC - ProtoNode RER/LER (B-85 / B-86) BACnet points are writable?

32 of the 173 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Raypak VERSA IC - ProtoNode RER/LER (B-85 / B-86) BACnet documentation?

The source is Installation & Operating Instructions - ProtoNode RER and ProtoNode LER (FPC N34 / FPC N35) B-85 / B-86 (P/N 241515 Rev. 5), revision Effective 08-25-23, published free by Raypak at https://s3.amazonaws.com/AWSProd/sites/raypakcom/documents/241515.pdf.

What are the minimum BACnet points to integrate the Raypak VERSA IC - ProtoNode RER/LER (B-85 / B-86)?

Start with BV 162 Blr 1 On/Off (Boiler 1 on/off command (BV 163-165 for 2-4)); BV 134 Target Mode (Selects which target applies (values not documented)); AV 135 Setpoint Target (Target water setpoint); AV 160 Target Mod Rate (Target modulation rate); AI 25 Blr 1 Ignition Status (Boiler 1 ignition state code); AI 2 System Supply Temperature (System supply water temperature); AI 18 Blr 1 Outlet temperature (Boiler 1 outlet water temperature); AI 23 Blr 1 Mod Rate (Boiler 1 modulation rate); AI 30 Blr 1 Error Code (Boiler 1 active error code).

How do I enable BMS control of the Raypak VERSA IC - ProtoNode RER/LER (B-85 / B-86)?

The Master profile has writable on/off BVs per boiler (BV 162-165) and a Target Mode BV with Setpoint Target (AV 135), Target temperature (AV 158) and Target Mod Rate (AV 160). The manual does not explain the Target Mode values or which target applies in each mode.

How do I check these points on the real VERSA IC - ProtoNode RER/LER (B-85 / B-86)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: Installation & Operating Instructions - ProtoNode RER and ProtoNode LER (FPC N34 / FPC N35) B-85 / B-86 · P/N 241515 Rev. 5 · rev. Effective 08-25-23. Object names, instances and units are reproduced as published; descriptions are our own.