The RI-A5IPBAC is a BACnet IP add-on module for the RI-F500 series power analysers. Its object list is about 1,000 objects: 4-20 mA and PT100 inputs and 4-20 mA outputs on extension modules, Analog Values for voltages, currents, power, energy (per phase, per quadrant, tariffs and monthly history), max/min and demand values, harmonics up to the 63rd order, pulse counters and event records, writable setup values (CT/PT, demand, limits, relay and AO configuration), plus digital input, relay output and alarm status objects.

This page lists 998 BACnet objects for the Rayleigh Instruments RI-F500 series power analyser with RI-A5IPBAC BACnet IP module — 175 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Rayleigh Instruments’s documentation hosted by Reseller Shopify CDN, not by Rayleigh Instruments itself, so treat it as unofficial.

Manufacturer
Rayleigh Instruments
Model
RI-F500 series power analyser with RI-A5IPBAC BACnet IP module
Equipment
Power analyser / multifunction meter
Equipment type
Thermostats, sensors & meters
BACnet objects
998 (175 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
RI-A5IPBAC, RI-F500, RI-F500 series, Rayleigh RI-F500 BACnet, RI-F500 BACnet/IP
Source document
RI-A5IPBAC (Bacnet module - TCP-IP) Communication Manual · V2 (unofficial copy, hosted by Reseller Shopify CDN)
Download CSV 998 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Rayleigh Instruments’s current documentation and the live device before use. Not official Rayleigh Instruments information. Terms of use.

BMS integration notes: Rayleigh Instruments RI-F500 series power analyser with RI-A5IPBAC BACnet IP module

Integration in brief

Configure the module's network settings from the RI-F500 front panel, then read total power, energy and the main voltages and currents. Set CT and PT values on the meter (or AV 788-793) before trusting the readings.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 27Import Active Energy EP+Import active energy, kWhRead
AV 13Total active power-PTotal active power, kWRead
AV 17Total reactive power-QTotal reactive power, kvarRead
AV 0Phase voltage-V1Phase voltage L1, VRead
AV 3Line voltage-V12Line voltage L1-L2, VRead
AV 6Phase current-I1Phase current L1, ARead
AV 721Present demand value -PPresent active power demand, kWRead
BV 3High voltage alarmHigh voltage alarm (1 = alarm)Read
BV 0Phase SequencePhase sequence abnormal (1)Read

Network setup

Watch out for

Rayleigh Instruments RI-F500 series power analyser with RI-A5IPBAC BACnet IP module BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

998 of 998 shown
Type
Access
Show
Rayleigh Instruments RI-F500 series power analyser with RI-A5IPBAC BACnet IP module BACnet Points List
DescriptionStates
AI0X1-AI1(4-20mA)0.001mARead
AI1X1-AI2(4-20mA)0.001mARead
AI2X2-AI1(4-20mA)0.001mARead
AI3X2-AI2(4-20mA)0.001mARead
AI4X3-AI1(4-20mA)0.001mARead
AI5X3-AI2(4-20mA)0.001mARead
AI6X4-AI1(4-20mA)0.001mARead
AI7X4-AI2(4-20mA)0.001mARead
AI8X1-AI1(PT100)1°CRead
AI9X1-AI2(PT100)1°CRead
AI10X2-AI1(PT100)1°CRead
AI11X2-AI2(PT100)1°CRead
AI12X3-AI1(PT100)1°CRead
AI13X3-AI2(PT100)1°CRead
AI14X4-AI1(PT100)1°CRead
AI15X4-AI2(PT100)1°CRead
AO0X1-AO1(4-20mA)0.001mAWrite
AO1X1-AO2(4-20mA)0.001mAWrite
AO2X2-AO1(4-20mA)0.001mAWrite
AO3X2-AO2(4-20mA)0.001mAWrite
AO4X3-AO1(4-20mA)0.001mAWrite
AO5X3-AO2(4-20mA)0.001mAWrite
AO6X4-AO1(4-20mA)0.001mAWrite
AO7X4-AO2(4-20mA)0.001mAWrite
AVmin0Phase voltage-V1VRead
AV1Phase voltage-V2VRead
AV2Phase voltage-V3VRead
AVmin3Line voltage-V12VRead
AV4Line voltage-V23VRead
AV5Line voltage-V31VRead
AVmin6Phase current-I1ARead
AV7Phase current-I1ARead
AV8Phase current-I3ARead
AV9Current-InARead
AV10Active power-P1kWRead
AV11Active power-P2kWRead
AV12Active power-P3kWRead
AVmin13Total active power-PkWRead
AV14Reactive power-Q1kvarRead
AV15Reactive power-Q2kvarRead
AV16Reactive power-Q3kvarRead
AVmin17Total reactive power-QkvarRead
AV18Apparent power-S1kVARead
AV19Apparent power-S2kVARead
AV20Apparent power-S3kVARead
AV21Total apparent power-SkVARead
AV22Power factor-PF1Read
AV23Power factor-PF2Read
AV24Power factor-PF3Read
AV25Total power factor-PFRead
AV26Grid frequency-FHzRead
AVmin27Import Active Energy EP+kWhRead
AV28Export Active Energy EP-kWhRead
AV29Import Reactive Energy EQ+kvarhRead
AV30Export Reactive Energy EQ-kvarhRead
AV31Apparent EnergykVAhRead
AV321st Quadrant Reactive EnergykvarhRead
AV332nd Quadrant Reactive EnergykvarhRead
AV343rd Quadrant Reactive EnergykvarhRead
AV354th Quadrant Reactive EnergykvarhRead
AV36Fundamental Import Active EnergykWhRead
AV37Fundamental Export Active EnergykWhRead
AV38Fundamental Import Reactive EnergykvarhRead
AV39Fundamental Export Reactive EnergykvarhRead
AV40Import Active Energy-L1kWhRead
AV41Import Active Energy-L2kWhRead
AV42Import Active Energy-L3kWhRead
AV43Export Active Energy- L1kWhRead
AV44Export Active Energy - L2kWhRead
AV45Export Active Energy - L3kWhRead
AV46Import Reactive Energy- L1kvarhRead
AV47Import Reactive Energy- L2kvarhRead
AV48Import Reactive Energy- L3kvarhRead
AV49Export Reactive Energy - L1kvarhRead
AV50Export Reactive Energy - L2kvarhRead
AV51Export Reactive Energy - L3kvarhRead
AV52Total import tariff energykWhRead
AV53Tariff T1 import energykWhRead
AV54Tariff T2 import energykWhRead
AV55Tariff T3 import energykWhRead
AV56Tariff T4 import energykWhRead
AV57this month Total tariff import energykWhRead
AV58this month Tariff T1 import energykWhRead
AV59this month Tariff T2 import energykWhRead
AV60this month Tariff T3 import energykWhRead
AV61this month Tariff T4 import energykWhRead
AV62One month before Total tariff import energykWhRead
AV63One month before Tariff T1 import energykWhRead
AV64One month before Tariff T2 import energykWhRead
AV65One month before Tariff T3 import energykWhRead
AV66One month before Tariff T4 import energykWhRead
AV67two month before Total tariff import energykWhRead
AV68two month before Tariff T1 import energykWhRead
AV69two month before Tariff T2 import energykWhRead
AV70two month before Tariff T3 import energykWhRead
AV71two month before Tariff T4 import energykWhRead
AV72three month before Total tariff import energykWhRead
AV73three month before Tariff T1 import energykWhRead
AV74three month before Tariff T2 import energykWhRead
AV75three month before Tariff T3 import energykWhRead
AV76three month before Tariff T4 import energykWhRead
AV77four month before Total tariff import energykWhRead
AV78four month before Tariff T1 import energykWhRead
AV79four month before Tariff T2 import energykWhRead
AV80four month before Tariff T3 import energykWhRead
AV81four month before Tariff T4 import energykWhRead
AV82five month before Total tariff import energykWhRead
AV83five month before Tariff T1 import energykWhRead
AV84five month before Tariff T2 import energykWhRead
AV85five month before Tariff T3 import energykWhRead
AV86five month before Tariff T4 import energykWhRead
AV87six month before Total tariff import energykWhRead
AV88six month before Tariff T1 import energykWhRead
AV89six month before Tariff T2 import energykWhRead
AV90six month before Tariff T3 import energykWhRead
AV91six month before Tariff T4 import energykWhRead
AV92seven month before Total tariff import energykWhRead
AV93seven month before Tariff T1 import energykWhRead
AV94seven month before Tariff T2 import energykWhRead
AV95seven month before Tariff T3 import energykWhRead
AV96seven month before Tariff T4 import energykWhRead
AV97eight month before Total tariff import energykWhRead
AV98eight month before Tariff T1 import energykWhRead
AV99eight month before Tariff T2 import energykWhRead
AV100eight month before Tariff T3 import energykWhRead
AV101eight month before Tariff T4 import energykWhRead
AV102nine month before Total tariff import energykWhRead
AV103nine month before Tariff T1 import energykWhRead
AV104nine month before Tariff T2 import energykWhRead
AV105nine month before Tariff T3 import energykWhRead
AV106nine month before Tariff T4 import energykWhRead
AV107ten month before Total tariff import energykWhRead
AV108ten month before Tariff T1 import energykWhRead
AV109ten month before Tariff T2 import energykWhRead
AV110ten month before Tariff T3 import energykWhRead
AV111ten month before Tariff T4 import energykWhRead
AV112eleven month before Total tariff import energykWhRead
AV113eleven month before Tariff T1 import energykWhRead
AV114eleven month before Tariff T2 import energykWhRead
AV115eleven month before Tariff T3 import energykWhRead
AV116eleven month before Tariff T4 import energykWhRead
AV117High byte: year, Low byte: monthRead
AV118High byte: day, Low byte: hourRead
AV119High byte: minute, Low byte: secondRead
AV120High byte:week, Low byte: ----Read
AV121High byte: X1 Extended Module Low byte: X2 Extended ModuleRead
AV122High byte: X3 Extended Module Low byte: X4 Extended ModuleRead
AV123Max. historical value-V1VRead
AV124Max. historical value-V2VRead
AV125Max. historical value-V3VRead
AV126Max. historical value-V12VRead
AV127Max. historical value-V23VRead
AV128Max. historical value-V31VRead
AV129Max. historical value-I1ARead
AV130Max. historical value-I2ARead
AV131Max. historical value-I3ARead
AV132Max. historical value-InARead
AV133Max. historical value-PkWRead
AV134Max. historical value-QkvarRead
AV135Max. historical value-SkVARead
AV136Max. historical value-PFRead
AV137Max. historical value-FHzRead
AV138Min. value-V1VRead
AV139Min. value-V2VRead
AV140Min. value-V3VRead
AV141Min. value-V12VRead
AV142Min. value-V23VRead
AV143Min. value-V31VRead
AV144Min. value-I1ARead
AV145Min. value-I2ARead
AV146Min. value-I3ARead
AV147Min. value-InARead
AV148Min. value-PkWRead
AV149Min. value-QkvarRead
AV150Min. value-SkVAhRead
AV151Min. value-PFRead
AV152Min. value-FHzRead
AV153this month Max. historical value-V1VRead
AV154this month Max. historical value-V2VRead
AV155this month Max. historical value-V3VRead
AV156this month Max. historical value-V12VRead
AV157this month Max. historical value-V23VRead
AV158this month Max. historical value-V31VRead
AV159this month Max. historical value-I1ARead
AV160this month Max. historical value-I2ARead
AV161this month Max. historical value-I3ARead
AV162this month Max. historical value-InARead
AV163this month Max. historical value-PkWRead
AV164this month Max. historical value-QkvarRead
AV165this month Max. historical value-SkVARead
AV166this month Max. historical value-PFRead
AV167this month Max. historical value-FHzRead
AV168this month Min. value-V1VRead
AV169this month Min. value-V2VRead
AV170this month Min. value-V3VRead
AV171this month Min. value-V12VRead
AV172this month Min. value-V23VRead
AV173this month Min. value-V31VRead
AV174this month Min. value-I1ARead
AV175this month Min. value-I2ARead
AV176this month Min. value-I3ARead
AV177this month Min. value-InARead
AV178this month Min. value-PkWRead
AV179this month Min. value-QkvarRead
AV180this month Min. value-SkVARead
AV181this month Min. value-PFRead
AV182this month Min. value-FHzRead
AV183last month Max. historical value-V1VRead
AV184last month Max. historical value-V2VRead
AV185last month Max. historical value-V3VRead
AV186last month Max. historical value-V12VRead
AV187last month Max. historical value-V23VRead
AV188last month Max. historical value-V31VRead
AV189last month Max. historical value-I1ARead
AV190last month Max. historical value-I2ARead
AV191last month Max. historical value-I3ARead
AV192last month Max. historical value-InARead
AV193last month Max. historical value-PkWRead
AV194last month Max. historical value-QkvarRead
AV195last month Max. historical value-SkVARead
AV196last month Max. historical value-PFRead
AV197last month Max. historical value-FHzRead
AV198last month Min. value-V1VRead
AV199last month Min. value-V2VRead
AV200last month Min. value-V3VRead
AV201last month Min. value-V12VRead
AV202last month Min. value-V23VRead
AV203last month Min. value-V31VRead
AV204last month Min. value-I1ARead
AV205last month Min. value-I2ARead
AV206last month Min. value-I3ARead
AV207last month Min. value-InARead
AV208last month Min. value-PkWRead
AV209last month Min. value-QkvarRead
AV210last month Min. value-SkVARead
AV211last month Min. value-PFRead
AV212last month Min. value-FHzRead
AV213two months before Max. historical value-V1VRead
AV214two months before Max. historical value-V2VRead
AV215two months before Max. historical value-V3VRead
AV216two months before Max. historical value-V12VRead
AV217two months before Max. historical value-V23VRead
AV218two months before Max. historical value-V31VRead
AV219two months before Max. historical value-I1ARead
AV220two months before Max. historical value-I2ARead
AV221two months before Max. historical value-I3ARead
AV222two months before Max. historical value-InARead
AV223two months before Max. historical value-PkWRead
AV224two months before Max. historical value-QkvarRead
AV225two months before Max. historical value-SkVARead
AV226two months before Max. historical value-PFRead
AV227two months before Max. historical value-FHzRead
AV228two months before Min. value-V1VRead
AV229two months before Min. value-V2VRead
AV230two months before Min. value-V3VRead
AV231two months before Min. value-V12VRead
AV232two months before Min. value-V23VRead
AV233two months before Min. value-V31VRead
AV234two months before Min. value-I1ARead
AV235two months before Min. value-I2ARead
AV236two months before Min. value-I3ARead
AV237two months before Min. value-InARead
AV238two months before Min. value-PkWRead
AV239two months before Min. value-QkvarRead
AV240two months before Min. value-SkVARead
AV241two months before Min. value-PFRead
AV242two months before Min. value-FHzRead
AV243Positive-sequence component of voltageVRead
AV244Negative-sequence component of voltageVRead
AV245Zero-sequence component of voltageVRead
AV246Unbalance factor of voltageRead
AV247Positive-sequence component of currentARead
AV248Negative-sequence component of currentARead
AV249Zero-sequence component of currentARead
AV250Unbalance factor of currentRead
AV251Avg-VlnVRead
AV252Avg-VllVRead
AV253Avg-IARead
AV254Avg-PkWRead
AV255Avg-QkvarRead
AV256Avg-SkVARead
AV257Deviation-V1VRead
AV258Deviation-V2VRead
AV259Deviation-V3VRead
AV260Deviation-V12VRead
AV261Deviation-V23VRead
AV262Deviation-V31VRead
AV263Deviation-FHzRead
AV264Fundamental value -V1VRead
AV265Fundamental value -V2VRead
AV266Fundamental value -V3VRead
AV267Fundamental value -I1ARead
AV268Fundamental value -I2ARead
AV269Fundamental value -I3ARead
AV270Harmonic content -V1VRead
AV271Harmonic content -V2VRead
AV272Harmonic content -V3VRead
AV273Harmonic content -I1ARead
AV274Harmonic content -I2ARead
AV275Harmonic content -I3ARead
AV276Fundamental value -P1kWRead
AV277Fundamental value -P2kWRead
AV278Fundamental value -P3kWRead
AV279Fundamental value -P1kWRead
AV280Fundamental value -Q1kvarRead
AV281Fundamental value -Q2kvarRead
AV282Fundamental value -Q3kvarRead
AV283Fundamental value -QkvarRead
AV284Fundamental value -S1kVARead
AV285Fundamental value -S2kVARead
AV286Fundamental value -S3kVARead
AV287Fundamental value -SkVARead
AV288Fundamental value -PF1Read
AV289Fundamental value -PF2Read
AV290Fundamental value -PF3Read
AV291Fundamental value -PFRead
AV292Meter running timesRead
AV293On-load running timesRead
AV294V1-Short term severityRead
AV295V2-Short term severityRead
AV296V3-Short term severityRead
AV297V1-Long term severityRead
AV298V2-Long term severityRead
AV299V3-Long term severityRead
AV300V1-Voltage fluctuationVRead
AV301V2-Voltage fluctuationVRead
AV302V3-Voltage fluctuationVRead
AV303Phase angle of V1(default 0°)0.1°Read
AV304Phase angle of V20.1°Read
AV305Phase angle of V30.1°Read
AV306Phase angle of I10.1°Read
AV307Phase angle of I20.1°Read
AV308Phase angle of I30.1°Read
AV309Crest factor V10.001Read
AV310Crest factor V20.001Read
AV311Crest factor V30.001Read
AV312K-factor I10.001Read
AV313K-factor I20.001Read
AV314K-factor I30.001Read
AV315Derating factor of transformer0.10%Read
AV316Load percentage I10.10%Read
AV317Load percentage I20.10%Read
AV318Load percentage I30.10%Read
AV319Load percentage P0.10%Read
AV320Voltage qualification rate0.10%Read
AV321Frequency qualification rate0.10%Read
AV322THD-V10.01%Read
AV323THD-V20.01%Read
AV324THD-V30.01%Read
AV325THD-I10.01%Read
AV326THD-I20.01%Read
AV327THD-I30.01%Read
AV3282nd harmonic ratio-V10.01%Read
AV3292nd harmonic ratio-V20.01%Read
AV3302nd harmonic ratio-V30.01%Read
AV3312nd harmonic ratio-I10.01%Read
AV3322nd harmonic ratio-I20.01%Read
AV3332nd harmonic ratio-I30.01%Read
AV3343rd harmonic ratio-V10.01%Read
AV3353rd harmonic ratio-V20.01%Read
AV3363rd harmonic ratio-V30.01%Read
AV3373rd harmonic ratio-I10.01%Read
AV3383rd harmonic ratio-I20.01%Read
AV3393rd harmonic ratio-I30.01%Read
AV3404th harmonic ratio-V10.01%Read
AV3414th harmonic ratio-V20.01%Read
AV3424th harmonic ratio-V30.01%Read
AV3434th harmonic ratio-I10.01%Read
AV3444th harmonic ratio-I20.01%Read
AV3454th harmonic ratio-I30.01%Read
AV3465th harmonic ratio-V10.01%Read
AV3475th harmonic ratio-V20.01%Read
AV3485th harmonic ratio-V30.01%Read
AV3495th harmonic ratio-I10.01%Read
AV3505th harmonic ratio-I20.01%Read
AV3515th harmonic ratio-I30.01%Read
AV3526th harmonic ratio-V10.01%Read
AV3536th harmonic ratio-V20.01%Read
AV3546th harmonic ratio-V30.01%Read
AV3556th harmonic ratio-I10.01%Read
AV3566th harmonic ratio-I20.01%Read
AV3576th harmonic ratio-I30.01%Read
AV3587th harmonic ratio-V10.01%Read
AV3597th harmonic ratio-V20.01%Read
AV3607th harmonic ratio-V30.01%Read
AV3617th harmonic ratio-I10.01%Read
AV3627th harmonic ratio-I20.01%Read
AV3637th harmonic ratio-I30.01%Read
AV3648th harmonic ratio-V10.01%Read
AV3658th harmonic ratio-V20.01%Read
AV3668th harmonic ratio-V30.01%Read
AV3678th harmonic ratio-I10.01%Read
AV3688th harmonic ratio-I20.01%Read
AV3698th harmonic ratio-I30.01%Read
AV3709th harmonic ratio-V10.01%Read
AV3719th harmonic ratio-V20.01%Read
AV3729th harmonic ratio-V30.01%Read
AV3739th harmonic ratio-I10.01%Read
AV3749th harmonic ratio-I20.01%Read
AV3759th harmonic ratio-I30.01%Read
AV37610th harmonic ratio-V10.01%Read
AV37710th harmonic ratio-V20.01%Read
AV37810th harmonic ratio-V30.01%Read
AV37910th harmonic ratio-I10.01%Read
AV38010th harmonic ratio-I20.01%Read
AV38110th harmonic ratio-I30.01%Read
AV38211th harmonic ratio-V10.01%Read
AV38311th harmonic ratio-V20.01%Read
AV38411th harmonic ratio-V30.01%Read
AV38511th harmonic ratio-I10.01%Read
AV38611th harmonic ratio-I20.01%Read
AV38711th harmonic ratio-I30.01%Read
AV38812th harmonic ratio-V10.01%Read
AV38912th harmonic ratio-V20.01%Read
AV39012th harmonic ratio-V30.01%Read
AV39112th harmonic ratio-I10.01%Read
AV39212th harmonic ratio-I20.01%Read
AV39312th harmonic ratio-I30.01%Read
AV39413th harmonic ratio-V10.01%Read
AV39513th harmonic ratio-V20.01%Read
AV39613th harmonic ratio-V30.01%Read
AV39713th harmonic ratio-I10.01%Read
AV39813th harmonic ratio-I20.01%Read
AV39913th harmonic ratio-I30.01%Read
AV40014th harmonic ratio-V10.01%Read
AV40114th harmonic ratio-V20.01%Read
AV40214th harmonic ratio-V30.01%Read
AV40314th harmonic ratio-I10.01%Read
AV40414th harmonic ratio-I20.01%Read
AV40514th harmonic ratio-I30.01%Read
AV40615th harmonic ratio-V10.01%Read
AV40715th harmonic ratio-V20.01%Read
AV40815th harmonic ratio-V30.01%Read
AV40915th harmonic ratio-I10.01%Read
AV41015th harmonic ratio-I20.01%Read
AV41115th harmonic ratio-I30.01%Read
AV41216th harmonic ratio-V10.01%Read
AV41316th harmonic ratio-V20.01%Read
AV41416th harmonic ratio-V30.01%Read
AV41516th harmonic ratio-I10.01%Read
AV41616th harmonic ratio-I20.01%Read
AV41716th harmonic ratio-I30.01%Read
AV41817th harmonic ratio-V10.01%Read
AV41917th harmonic ratio-V20.01%Read
AV42017th harmonic ratio-V30.01%Read
AV42117th harmonic ratio-I10.01%Read
AV42217th harmonic ratio-I20.01%Read
AV42317th harmonic ratio-I30.01%Read
AV42418th harmonic ratio-V10.01%Read
AV42518th harmonic ratio-V20.01%Read
AV42618th harmonic ratio-V30.01%Read
AV42718th harmonic ratio-I10.01%Read
AV42818th harmonic ratio-I20.01%Read
AV42918th harmonic ratio-I30.01%Read
AV43019th harmonic ratio-V10.01%Read
AV43119th harmonic ratio-V20.01%Read
AV43219th harmonic ratio-V30.01%Read
AV43319th harmonic ratio-I10.01%Read
AV43419th harmonic ratio-I20.01%Read
AV43519th harmonic ratio-I30.01%Read
AV43620th harmonic ratio-V10.01%Read
AV43720th harmonic ratio-V20.01%Read
AV43820th harmonic ratio-V30.01%Read
AV43920th harmonic ratio-I10.01%Read
AV44020th harmonic ratio-I20.01%Read
AV44120th harmonic ratio-I30.01%Read
AV44221th harmonic ratio-V10.01%Read
AV44321th harmonic ratio-V20.01%Read
AV44421th harmonic ratio-V30.01%Read
AV44521th harmonic ratio-I10.01%Read
AV44621th harmonic ratio-I20.01%Read
AV44721th harmonic ratio-I30.01%Read
AV44822th harmonic ratio-V10.01%Read
AV44922th harmonic ratio-V20.01%Read
AV45022th harmonic ratio-V30.01%Read
AV45122th harmonic ratio-I10.01%Read
AV45222th harmonic ratio-I20.01%Read
AV45322th harmonic ratio-I30.01%Read
AV45423th harmonic ratio-V10.01%Read
AV45523th harmonic ratio-V20.01%Read
AV45623th harmonic ratio-V30.01%Read
AV45723th harmonic ratio-I10.01%Read
AV45823th harmonic ratio-I20.01%Read
AV45923th harmonic ratio-I30.01%Read
AV46024th harmonic ratio-V10.01%Read
AV46124th harmonic ratio-V20.01%Read
AV46224th harmonic ratio-V30.01%Read
AV46324th harmonic ratio-I10.01%Read
AV46424th harmonic ratio-I20.01%Read
AV46524th harmonic ratio-I30.01%Read
AV46625th harmonic ratio-V10.01%Read
AV46725th harmonic ratio-V20.01%Read
AV46825th harmonic ratio-V30.01%Read
AV46925th harmonic ratio-I10.01%Read
AV47025th harmonic ratio-I20.01%Read
AV47125th harmonic ratio-I30.01%Read
AV47226th harmonic ratio-V10.01%Read
AV47326th harmonic ratio-V20.01%Read
AV47426th harmonic ratio-V30.01%Read
AV47526th harmonic ratio-I10.01%Read
AV47626th harmonic ratio-I20.01%Read
AV47726th harmonic ratio-I30.01%Read
AV47827th harmonic ratio-V10.01%Read
AV47927th harmonic ratio-V20.01%Read
AV48027th harmonic ratio-V30.01%Read
AV48127th harmonic ratio-I10.01%Read
AV48227th harmonic ratio-I20.01%Read
AV48327th harmonic ratio-I30.01%Read
AV48428th harmonic ratio-V10.01%Read
AV48528th harmonic ratio-V20.01%Read
AV48628th harmonic ratio-V30.01%Read
AV48728th harmonic ratio-I10.01%Read
AV48828th harmonic ratio-I20.01%Read
AV48928th harmonic ratio-I30.01%Read
AV49029th harmonic ratio-V10.01%Read
AV49129th harmonic ratio-V20.01%Read
AV49229th harmonic ratio-V30.01%Read
AV49329th harmonic ratio-I10.01%Read
AV49429th harmonic ratio-I20.01%Read
AV49529th harmonic ratio-I30.01%Read
AV49630th harmonic ratio-V10.01%Read
AV49730th harmonic ratio-V20.01%Read
AV49830th harmonic ratio-V30.01%Read
AV49930th harmonic ratio-I10.01%Read
AV50030th harmonic ratio-I20.01%Read
AV50130th harmonic ratio-I30.01%Read
AV50231th harmonic ratio-V10.01%Read
AV50331th harmonic ratio-V20.01%Read
AV50431th harmonic ratio-V30.01%Read
AV50531th harmonic ratio-I10.01%Read
AV50631th harmonic ratio-I20.01%Read
AV50731th harmonic ratio-I30.01%Read
AV50832th harmonic ratio-V10.01%Read
AV50932th harmonic ratio-V20.01%Read
AV51032th harmonic ratio-V30.01%Read
AV51132th harmonic ratio-I10.01%Read
AV51232th harmonic ratio-I20.01%Read
AV51332th harmonic ratio-I30.01%Read
AV51433th harmonic ratio-V10.01%Read
AV51533th harmonic ratio-V20.01%Read
AV51633th harmonic ratio-V30.01%Read
AV51733th harmonic ratio-I10.01%Read
AV51833th harmonic ratio-I20.01%Read
AV51933th harmonic ratio-I30.01%Read
AV52034th harmonic ratio-V10.01%Read
AV52134th harmonic ratio-V20.01%Read
AV52234th harmonic ratio-V30.01%Read
AV52334th harmonic ratio-I10.01%Read
AV52434th harmonic ratio-I20.01%Read
AV52534th harmonic ratio-I30.01%Read
AV52635th harmonic ratio-V10.01%Read
AV52735th harmonic ratio-V20.01%Read
AV52835th harmonic ratio-V30.01%Read
AV52935th harmonic ratio-I10.01%Read
AV53035th harmonic ratio-I20.01%Read
AV53135th harmonic ratio-I30.01%Read
AV53236th harmonic ratio-V10.01%Read
AV53336th harmonic ratio-V20.01%Read
AV53436th harmonic ratio-V30.01%Read
AV53536th harmonic ratio-I10.01%Read
AV53636th harmonic ratio-I20.01%Read
AV53736th harmonic ratio-I30.01%Read
AV53837th harmonic ratio-V10.01%Read
AV53937th harmonic ratio-V20.01%Read
AV54037th harmonic ratio-V30.01%Read
AV54137th harmonic ratio-I10.01%Read
AV54237th harmonic ratio-I20.01%Read
AV54337th harmonic ratio-I30.01%Read
AV54438th harmonic ratio-V10.01%Read
AV54538th harmonic ratio-V20.01%Read
AV54638th harmonic ratio-V30.01%Read
AV54738th harmonic ratio-I10.01%Read
AV54838th harmonic ratio-I20.01%Read
AV54938th harmonic ratio-I30.01%Read
AV55039th harmonic ratio-V10.01%Read
AV55139th harmonic ratio-V20.01%Read
AV55239th harmonic ratio-V30.01%Read
AV55339th harmonic ratio-I10.01%Read
AV55439th harmonic ratio-I20.01%Read
AV55539th harmonic ratio-I30.01%Read
AV55640th harmonic ratio-V10.01%Read
AV55740th harmonic ratio-V20.01%Read
AV55840th harmonic ratio-V30.01%Read
AV55940th harmonic ratio-I10.01%Read
AV56040th harmonic ratio-I20.01%Read
AV56140th harmonic ratio-I30.01%Read
AV56241th harmonic ratio-V10.01%Read
AV56341th harmonic ratio-V20.01%Read
AV56441th harmonic ratio-V30.01%Read
AV56541th harmonic ratio-I10.01%Read
AV56641th harmonic ratio-I20.01%Read
AV56741th harmonic ratio-I30.01%Read
AV56842th harmonic ratio-V10.01%Read
AV56942th harmonic ratio-V20.01%Read
AV57042th harmonic ratio-V30.01%Read
AV57142th harmonic ratio-I10.01%Read
AV57242th harmonic ratio-I20.01%Read
AV57342th harmonic ratio-I30.01%Read
AV57443th harmonic ratio-V10.01%Read
AV57543th harmonic ratio-V20.01%Read
AV57643th harmonic ratio-V30.01%Read
AV57743th harmonic ratio-I10.01%Read
AV57843th harmonic ratio-I20.01%Read
AV57943th harmonic ratio-I30.01%Read
AV58044th harmonic ratio-V10.01%Read
AV58144th harmonic ratio-V20.01%Read
AV58244th harmonic ratio-V30.01%Read
AV58344th harmonic ratio-I10.01%Read
AV58444th harmonic ratio-I20.01%Read
AV58544th harmonic ratio-I30.01%Read
AV58645th harmonic ratio-V10.01%Read
AV58745th harmonic ratio-V20.01%Read
AV58845th harmonic ratio-V30.01%Read
AV58945th harmonic ratio-I10.01%Read
AV59045th harmonic ratio-I20.01%Read
AV59145th harmonic ratio-I30.01%Read
AV59246th harmonic ratio-V10.01%Read
AV59346th harmonic ratio-V20.01%Read
AV59446th harmonic ratio-V30.01%Read
AV59546th harmonic ratio-I10.01%Read
AV59646th harmonic ratio-I20.01%Read
AV59746th harmonic ratio-I30.01%Read
AV59847th harmonic ratio-V10.01%Read
AV59947th harmonic ratio-V20.01%Read
AV60047th harmonic ratio-V30.01%Read
AV60147th harmonic ratio-I10.01%Read
AV60247th harmonic ratio-I20.01%Read
AV60347th harmonic ratio-I30.01%Read
AV60448th harmonic ratio-V10.01%Read
AV60548th harmonic ratio-V20.01%Read
AV60648th harmonic ratio-V30.01%Read
AV60748th harmonic ratio-I10.01%Read
AV60848th harmonic ratio-I20.01%Read
AV60948th harmonic ratio-I30.01%Read
AV61049th harmonic ratio-V10.01%Read
AV61149th harmonic ratio-V20.01%Read
AV61249th harmonic ratio-V30.01%Read
AV61349th harmonic ratio-I10.01%Read
AV61449th harmonic ratio-I20.01%Read
AV61549th harmonic ratio-I30.01%Read
AV61650th harmonic ratio-V10.01%Read
AV61750th harmonic ratio-V20.01%Read
AV61850th harmonic ratio-V30.01%Read
AV61950th harmonic ratio-I10.01%Read
AV62050th harmonic ratio-I20.01%Read
AV62150th harmonic ratio-I30.01%Read
AV62251th harmonic ratio-V10.01%Read
AV62351th harmonic ratio-V20.01%Read
AV62451th harmonic ratio-V30.01%Read
AV62551th harmonic ratio-I10.01%Read
AV62651th harmonic ratio-I20.01%Read
AV62751th harmonic ratio-I30.01%Read
AV62852th harmonic ratio-V10.01%Read
AV62952th harmonic ratio-V20.01%Read
AV63052th harmonic ratio-V30.01%Read
AV63152th harmonic ratio-I10.01%Read
AV63252th harmonic ratio-I20.01%Read
AV63352th harmonic ratio-I30.01%Read
AV63453th harmonic ratio-V10.01%Read
AV63553th harmonic ratio-V20.01%Read
AV63653th harmonic ratio-V30.01%Read
AV63753th harmonic ratio-I10.01%Read
AV63853th harmonic ratio-I20.01%Read
AV63953th harmonic ratio-I30.01%Read
AV64054th harmonic ratio-V10.01%Read
AV64154th harmonic ratio-V20.01%Read
AV64254th harmonic ratio-V30.01%Read
AV64354th harmonic ratio-I10.01%Read
AV64454th harmonic ratio-I20.01%Read
AV64554th harmonic ratio-I30.01%Read
AV64655th harmonic ratio-V10.01%Read
AV64755th harmonic ratio-V20.01%Read
AV64855th harmonic ratio-V30.01%Read
AV64955th harmonic ratio-I10.01%Read
AV65055th harmonic ratio-I20.01%Read
AV65155th harmonic ratio-I30.01%Read
AV65256th harmonic ratio-V10.01%Read
AV65356th harmonic ratio-V20.01%Read
AV65456th harmonic ratio-V30.01%Read
AV65556th harmonic ratio-I10.01%Read
AV65656th harmonic ratio-I20.01%Read
AV65756th harmonic ratio-I30.01%Read
AV65857th harmonic ratio-V10.01%Read
AV65957th harmonic ratio-V20.01%Read
AV66057th harmonic ratio-V30.01%Read
AV66157th harmonic ratio-I10.01%Read
AV66257th harmonic ratio-I20.01%Read
AV66357th harmonic ratio-I30.01%Read
AV66458th harmonic ratio-V10.01%Read
AV66558th harmonic ratio-V20.01%Read
AV66658th harmonic ratio-V30.01%Read
AV66758th harmonic ratio-I10.01%Read
AV66858th harmonic ratio-I20.01%Read
AV66958th harmonic ratio-I30.01%Read
AV67059th harmonic ratio-V10.01%Read
AV67159th harmonic ratio-V20.01%Read
AV67259th harmonic ratio-V30.01%Read
AV67359th harmonic ratio-I10.01%Read
AV67459th harmonic ratio-I20.01%Read
AV67559th harmonic ratio-I30.01%Read
AV67660th harmonic ratio-V10.01%Read
AV67760th harmonic ratio-V20.01%Read
AV67860th harmonic ratio-V30.01%Read
AV67960th harmonic ratio-I10.01%Read
AV68060th harmonic ratio-I20.01%Read
AV68160th harmonic ratio-I30.01%Read
AV68261th harmonic ratio-V10.01%Read
AV68361th harmonic ratio-V20.01%Read
AV68461th harmonic ratio-V30.01%Read
AV68561th harmonic ratio-I10.01%Read
AV68661th harmonic ratio-I20.01%Read
AV68761th harmonic ratio-I30.01%Read
AV68862th harmonic ratio-V10.01%Read
AV68962th harmonic ratio-V20.01%Read
AV69062th harmonic ratio-V30.01%Read
AV69162th harmonic ratio-I10.01%Read
AV69262th harmonic ratio-I20.01%Read
AV69362th harmonic ratio-I30.01%Read
AV69463th harmonic ratio-V10.01%Read
AV69563th harmonic ratio-V20.01%Read
AV69663th harmonic ratio-V30.01%Read
AV69763th harmonic ratio-I10.01%Read
AV69863th harmonic ratio-I20.01%Read
AV69963th harmonic ratio-I30.01%Read
AV700X1-channel1 pulse counterRead
AV701X1-channel2 pulse counterRead
AV702X1-channel3 pulse counterRead
AV703X1-channel4 pulse counterRead
AV704X2-channel1 pulse counterRead
AV705X2-channel2 pulse counterRead
AV706X2-channel3 pulse counterRead
AV707X2-channel4 pulse counterRead
AV708X3-channel1 pulse counterRead
AV709X3-channel2 pulse counterRead
AV710X3-channel3 pulse counterRead
AV711X3-channel4 pulse counterRead
AV712X4-channel1 pulse counterRead
AV713X4-channel2 pulse counterRead
AV714X4-channel3 pulse counterRead
AV715X4-channel4 pulse counterRead
AV716Main boby-channel1 pulse counterRead
AV717Main boby-channel2 pulse counterRead
AV718Present demand value -I11ARead
AV719Present demand value -I2ARead
AV720Present demand value -I3ARead
AVmin721Present demand value -PkWRead
AV722Present demand value -QkvarRead
AV723Present demand value -SkVARead
AV724Previous demand value -I11ARead
AV725Previous demand value -I2ARead
AV726Previous demand value -I3ARead
AV727Previous demand value -PkWRead
AV728Previous demand value -QkvarRead
AV729Previous demand value -SkVARead
AV730Max. demand value -I1ARead
AV731Max. demand value -I2ARead
AV732Max. demand value -I3ARead
AV733Max. demand value -PkWRead
AV734Max. demand value -QkvarRead
AV735Max. demand value -SkVARead
AV736this month Max. demand value -I1ARead
AV737this month Max. demand value -I2ARead
AV738this month Max. demand value -I3ARead
AV739this month Max. demand value -PkWRead
AV740this month Max. demand value -QkvarRead
AV741this month Max. demand value -SkVARead
AV742last month Max. demand value -I1ARead
AV743last month Max. demand value -I2ARead
AV744last month Max. demand value -I3ARead
AV745last month Max. demand value -PkWRead
AV746last month Max. demand value -QkvarRead
AV747last month Max. demand value -SkVARead
AV748two months before Max. demand value -I1ARead
AV749two months before Max. demand value -I2ARead
AV750two months before Max. demand value -I3ARead
AV751two months before Max. demand value -PkWRead
AV752two months before Max. demand value -QkvarRead
AV753two months before Max. demand value -SkVARead
AV754Record: Power On High byte: year, Low byte: monthRead
AV755High byte: day, Low byte: hourRead
AV756High byte: minute, Low byte: secondRead
AV757Power On NumberRead
AV758Record: Power Off High byte: year, Low byte: monthRead
AV759High byte: day, Low byte: hourRead
AV760High byte: minute, Low byte: secondRead
AV761Power Off NumberRead
AV762Record: Setup parameter High byte: year, Low byte: monthRead
AV763High byte: day, Low byte: hourRead
AV764High byte: minute, Low byte: secondRead
AV765Setup parameter NumberRead
AV766Record: Clear demand High byte: year, Low byte: monthRead
AV767High byte: day, Low byte: hourRead
AV768High byte: minute, Low byte: secondRead
AV769Clear demand resetting timesRead
AV770Record: Clear energy High byte: year, Low byte: monthRead
AV771High byte: day, Low byte: hourRead
AV772High byte: minute, Low byte: secondRead
AV773High byte: minute, Low byte: secondRead
AV774High byte: Over voltage record number Low byte: ----Read
AV775High byte: under voltage record number Low byte: ----Read
AV776High byte: Over current record number Low byte: ----Read
AV777High byte: under current record number Low byte: ----Read
AV778High byte: Over active power record number Low byte: ----Read
AV779High byte: under active power record number Low byte: ----Read
AV780High byte: SOE event record number Low byte: ----Read
AV781High byt:e: Voltage swell record number Low byte: ----Read
AV782High byte: Voltage dip record number Low byte: ----Read
AV783High byte: Voltage interrupt record number Low byte: ----Read
AV784Main boby:Slave address1-247Write
AV785Main boby:baudrateWrite
AV786Main boby:Data formatWrite
AV787High byte: Wiring Low byte: Grid frequencyWrite
AV788PT secondary1~660VWrite
AV789CT secondary1~6AWrite
AV790Secondary side neutral current rating1~6AWrite
AV791PT primary1~999999VWrite
AV792CT primary1~999999AWrite
AV793Primary side neutral current rating1~999999AWrite
AV794Demand itemDefaulted as; I1/I2/I3/P/Q/SWrite
AV795Mode of demand0: slip block mode; 1: fixed block modeWrite
AV796Slip time(t)1~9999sWrite
AV797Demand period(T)1~30tWrite
AV798Voltage qualification rate upper limitSecondary grid dataWrite
AV799Voltage qualification rate lower limitSecondary grid dataWrite
AV800Frequency qualification rate upper limit0.01HzWrite
AV801Frequency qualification rate lower limit0.01HzWrite
AV802Relay output Main body-DO1 modeWrite
AV803Relay output Main body-DO1 Pulse widthWrite
AV804Relay output Main body-DO1 Alarm item selectWrite
AV805Relay output Main unit-DO1 limit valueWrite
AV806Relay output Main unit-DO1 hysteresisWrite
AV807Relay output Main body-DO1 Alarm delay timeWrite
AV808Relay output Main body-DO2 modeWrite
AV809Relay output Main body-DO2 Pulse widthWrite
AV810Relay output Main body-DO2 Alarm item selectWrite
AV811Relay output Main unit–DO2 limit valueWrite
AV812Relay output Main unit-DO2 hysteresisWrite
AV813Relay output Main body-DO2 Alarm delay timeWrite
AV814High byte: Main body DI1 mode Low byte: Main body DI2 modeWrite
AV815Voltage upper limit valueSecondary grid data: 0.1VWrite
AV816Voltage upper limit hysteresis valueSecondary grid data: 0.1VWrite
AV817Voltage lower limit valueSecondary grid data: 0.1VWrite
AV818Voltage lower limit hysteresis valueSecondary grid data: 0.1VWrite
AV819Current upper limit valueSecondary grid data: 0.001AWrite
AV820Current upper limit hysteresis valueSecondary grid data: 0.001AWrite
AV821Current lower limit valueSecondary grid data: 0.001AWrite
AV822Current lower limit hysteresis valueSecondary grid data: 0.001AWrite
AV823Active power upper limit valueSecondary grid data:; 1W/var/VAWrite
AV824Active power upper limit hysteresis valueSecondary grid data:; 1W/var/VAWrite
AV825Active power lower limit valueSecondary grid data:; 1W/var/VAWrite
AV826Active power lower limit hysteresis valueSecondary grid data:; 1W/var/VAWrite
AV827Voltage qualification rate upper limit valueSecondary grid data: 0.1VWrite
AV828Voltage qualification rate lower limit valueSecondary grid data: 0.1VWrite
AV829frequency qualification rate upper limit valueSecondary grid data: 0.01HzWrite
AV830Frequency qualification rate lower limit valueSecondary grid data: 0.01HzWrite
AV831Voltage sag limit valueSecondary grid data: 0.1VWrite
AV832Voltage sag hysteresis valueSecondary grid data: 0.1VWrite
AV833Voltage swell limit valueSecondary grid data: 0.1VWrite
AV834Voltage swell hysteresis valueSecondary grid data: 0.1VWrite
AV835Voltage interruption Limit valueSecondary grid data: 0.1VWrite
AV836Voltage interruption hysteresis valueSecondary grid data: 0.1VWrite
AV837Overvoltage start value of fault recordingSecondary grid data: 0.1VWrite
AV838Overvoltage hysteresis value of fault recordingSecondary grid data: 0.1VWrite
AV839undervoltage start value of fault recordingSecondary grid data: 0.1VWrite
AV840undervoltage hysteresis value of fault recordingSecondary grid data: 0.1VWrite
AV841overcurrent start value of fault recordingSecondary grid data: 0.001AWrite
AV842overcurrent hysteresis value of fault recordingSecondary grid data: 0.001AWrite
AV843Voltage sag and Voltage swell enable0: Close, 1: enabledWrite
AV844fault recording enable0: Close, 1: enabledWrite
AV845X1-AO1: Item0: Off; 1:V1; 2:V2; 3:V3; 4:V12; 5:V23; 6:V31; 7:I1; 8:I2; 9:I3; 10:In; 11:P1; 12:P2; ...Write
AV846X1-AO1: Mode0:4~20 mA; 1:0~20 mA; 2:4~12~20 mAWrite
AV847X1-AO1: Down scaleSecondary grid data ratio; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01HzWrite
AV848X1-AO1: Full scaleSecondary grid data ratio; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01HzWrite
AV849X1-AO2: Item0:Off; 1:V1; 2:V2; 3:V3; 4:V12; 5:V23; 6:V31; 7:I1; 8:I2; 9:I3; 10:In; 11:P1; 12:P2; 13:P3; ...Write
AV850X1-AO2: Mode0:4~20 mA; 1:0~20 mA; 2:4~12~20 mAWrite
AV851X1-AO2: Down scaleSecondary grid data ratio; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01HzWrite
AV852X1-AO2: Full scaleSecondary grid data ratio; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01HzWrite
AV853X2-AO1: Item0:Off; 1:V1; 2:V2; 3:V3; 4:V12; 5:V23; 6:V31; 7:I1; 8:I2; 9:I3; 10:In; 11:P1; 12:P2; 13:P3; ...Write
AV854X2-AO1: Mode0:4~20 mA; 1:0~20 mA; 2:4~12~20 mAWrite
AV855X2-AO1: Down scaleSecondary grid data ratio; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01HzWrite
AV856X2-AO1: Full scaleSecondary grid data ratio; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01HzWrite
AV857X2-AO2: Item0:Off; 0: Off; 1:V1; 2:V2; 3:V3; 4:V12; 5:V23; 6:V31; 7:I1; 8:I2; 9:I3; 10:In; 11:P1; ...Write
AV858X2-AO2: Mode0:4~20 mA; 1:0~20 mA; 2:4~12~20 mAWrite
AV859X2-AO2: Down scaleSecondary grid data ratio; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01HzWrite
AV860X2-AO2: Full scaleSecondary grid data ratio; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01HzWrite
AV861X3-AO1: Item0:Off; 0: Off; 1:V1; 2:V2; 3:V3; 4:V12; 5:V23; 6:V31; 7:I1; 8:I2; 9:I3; 10:In; 11:P1; ...Write
AV862X3-AO1: Mode0:4~20 mA; 1:0~20 mA; 2:4~12~20 mAWrite
AV863X3-AO1: Down scaleSecondary grid data ratio; Voltage: 0.1V,; Current: 0.001A,; Power: 1W/var/VA,; PF: 0.001; F: 0.01HzWrite
AV864X3-AO1: Full scaleSecondary grid data ratio; Voltage: 0.1V,; Current: 0.001A,; Power: 1W/var/VA,; PF: 0.001; F: 0.01HzWrite
AV865X3-AO2: Item0:Off; 0: Off; 1:V1; 2:V2; 3:V3; 4:V12; 5:V23; 6:V31; 7:I1; 8:I2; 9:I3; 10:In; 11:P1; ...Write
AV866X3-AO2: Mode0:4~20 mA; 1:0~20 mA; 2:4~12~20 mAWrite
AV867X3-AO2: Down scaleSecondary grid data ratio; Voltage: 0.1V,; Current: 0.001A,; Power:1W/var/VA,; PF: 0.001,; F: 0.01HzWrite
AV868X3-AO2: Full scaleSecondary grid data ratio; Voltage: 0.1V,; Current: 0.001A,; Power:1W/var/VA,; PF: 0.001,; F: 0.01HzWrite
AV869X4-AO1: Item0:Off; 0: Off; 1:V1; 2:V2; 3:V3; 4:V12; 5:V23; 6:V31; 7:I1; 8:I2; 9:I3; 10:In; 11:P1; ...Write
AV870X4-AO1: Mode0:4~20 mA; 1:0~20 mA; 2:4~12~20 mAWrite
AV871X4-AO1: Down scaleSecondary grid data ratio; Voltage: 0.1V,; Current: 0.001A,; Power:1W/var/VA,; PF: 0.001,; F: 0.01HzWrite
AV872X4-AO1: Full scaleSecondary grid data ratio; Voltage: 0.1V,; Current: 0.001A,; Power:1W/var/VA,; PF: 0.001,; F: 0.01HzWrite
AV873X4-AO2: Item0:Off; 0: Off; 1:V1; 2:V2; 3:V3; 4:V12; 5:V23; 6:V31; 7:I1; 8:I2; 9:I3; 10:In; 11:P1; ...Write
AV874X4-AO2: Mode0:4~20 mA; 1:0~20 mA; 2:4~12~20 mAWrite
AV875X4-AO2: Down scaleSecondary grid data ratio; Voltage: 0.1V,; Current: 0.001A,; Power:1W/var/VA,; PF: 0.001,; F: 0.01HzWrite
AV876X4-AO2: Full scaleSecondary grid data ratio; Voltage: 0.1V,; Current: 0.001A,; Power:1W/var/VA,; PF: 0.001,; F: 0.01HzWrite
AV877Switch input High byte: X1-DI1: Mode Low byte: X1-DI2: Mode0: state monitor; 1: pulse counterWrite
AV878Switch input High byte: X1-DI3: Mode Low byte: X1-DI4: Mode0: state monitor; 1: pulse counterWrite
AV879Switch input High byte: X2-DI1: Mode Low byte: X2-DI2: Mode0: state monitor; 1: pulse counterWrite
AV880Switch input High byte: X2-DI3: Mode Low byte: X2-DI4: Mode0: state monitor; 1: pulse counterWrite
AV881Switch input High byte: X3-DI1: Mode Low byte: X3-DI2: Mode0: state monitor; 1: pulse counterWrite
AV882Switch input High byte: X3-DI3: Mode Low byte: X3-DI4: Mode0: state monitor; 1: pulse counterWrite
AV883Switch input High byte: X4-DI1: Mode Low byte: X4-DI2: Mode0: state monitor; 1: pulse counterWrite
AV884Switch input High byte: X4-DI3: Mode Low byte: X4-DI4: Mode0: state monitor; 1: pulse counterWrite
AV885Relay output X1-DO1 mode0: OFF; 1: remote control; 2: alarmWrite
AV886Relay output X1-DO1 pulse width0.0: no pulse; Pulse width : 0.1~99.99sWrite
AV887Relay output X1-DO1 alarm selectAlarm Item:; 0: V1 >; 1: V1 <; 2: V2 >; 3: V2 <; ...Write
AV888Relay output X1-DO1 limit valueData ratio; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01Hz; Uunb/Iunb: 0.1%; ...Write
AV889Relay output X1-DO1 hysteresisThe ratio is the same as above.; Item is switch linkage:; 0: When the ...Write
AV890Relay output X1-DO1 pulse width0.0: no pulse; 0.1~99.99sWrite
AV891Relay output X1-DO2 mode0: OFF; 1: remote control; 2: alarmWrite
AV892Relay output X1-DO2 pulse width0.0: no pulse; pulse width : 0.1~99.99sWrite
AV893Relay output X1-DO2 alarm selectAlarm Item:; 0: V1 >; 1: V1 <; 2: V2 >; 3: V2 <; ...Write
AV894Relay output X1-DO2 limit valueData ratio; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01Hz; Uunb/Iunb: 0.1%; ...Write
AV895Relay output X1-DO2 hysteresisThe ratio is the same as above.; Item is switch linkage:; 0: When the ...Write
AV896Relay output X1-DO2 pulse width0.0: no pulse; 0.1~99.99sWrite
AV897Relay output X2-DO1 mode0: OFF; 1: remote control; 2: alarmWrite
AV898Relay output X2-DO1 pulse width0.0: no pulse; pulse width : 0.1~99.99sWrite
AV899Relay output X2-DO1 alarm selectAlarm Item:; 0: V1 >; 1: V1 <; 2: V2 >; 3: V2 <; ...Write
AV900Relay output X2-DO1 limit valueData ratio,; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01Hz; Uunb/Iunb: 0.1%; ...Write
AV901Relay output X2-DO1 hysteresisThe ratio is the same as above.; Item is switch linkage:; 0: When the ...Write
AV902Relay output X2-DO1 pulse width0.0: no pulse; 0.1~99.99sWrite
AV903Relay output X2-DO2 mode0: OFF; 1: remote control; 2: alarmWrite
AV904Relay output X2-DO2 pulse width0.0: no pulse; pulse width : 0.1~99.99sWrite
AV905Relay output X2-DO2 alarm selectAlarm Item:; 0: V1 >; 1: V1 <; 2: V2 >; 3: V2 <; ...Write
AV906Relay output X2-DO2 limit valueData ratio; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01Hz; Uunb/Iunb: 0.1%; ...Write
AV907Relay output X2-DO2 hysteresisThe ratio is the same as above.; Item is switch linkage:; 0: When the ...Write
AV908Relay output X2-DO2 pulse width0.0: no pulse; 0.1~99.99sWrite
AV909Relay output X3-DO1 mode0: OFF; 1: remote control; 2: alarmWrite
AV910Relay output X3-DO1 pulse width0.0: no pulse; pulse width : 0.1~99.99sWrite
AV911Relay output X3-DO1 alarm selectAlarm Item:; 0: V1 >; 1: V1 <; 2: V2 >; 3: V2 <; ...Write
AV912Relay output X3-DO1 limit valueData ratio; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01Hz; Uunb/Iunb: 0.1%; ...Write
AV913Relay output X3-DO1 hysteresisThe ratio is the same as above.; Item is switch linkage:; 0: When the ...Write
AV914Relay output X3-DO1 pulse width0.0: no pulse; 0.1~99.99sWrite
AV915Relay output X3-DO2 mode0: OFF; 1: remote control; 2: alarmWrite
AV916Relay output X3-DO2 pulse width0.0: no pulse; pulse width : 0.1~99.99sWrite
AV917Relay output X3-DO2 alarm selectAlarm Item:; 0: V1 >; 1: V1 <; 2: V2 >; 3: V2 <; ...Write
AV918Relay output X3-DO2 limit valueData ratio; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01Hz; Uunb/Iunb: 0.1%; ...Write
AV919Relay output X3-DO2 hysteresisThe ratio is the same as above.; Item is switch linkage:; 0: When the ...Write
AV920Relay output X3-DO2 pulse width0.0: no pulse; 0.1~99.99sWrite
AV921Relay output X4-DO1 mode0: OFF; 1: remote control; 2: alarmWrite
AV922Relay output X4-DO1 pulse width0.0: no pulse; pulse width : 0.1~99.99sWrite
AV923Relay output X4-DO1 alarm selectAlarm Item:; 0: V1 >; 1: V1 <; 2: V2 >; 3: V2 <; ...Write
AV924Relay output X4-DO1 limit valueData ratio; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01Hz; Uunb/Iunb: 0.1%; ...Write
AV925Relay output X4-DO1 hysteresisThe ratio is the same as above.; Item is switch linkage:; 0: When the ...Write
AV926Relay output X4-DO1 pulse width0.0: no pulse; 0.1~99.99sWrite
AV927Relay output X4-DO2 mode0: OFF; 1: remote control; 2: alarmWrite
AV928Relay output X4-DO2 pulse width0.0: no pulse; pulse width : 0.1~99.99sWrite
AV929Relay output X4-DO2 alarm selectAlarm Item:; 0: V1 >; 1: V1 <; 2: V2 >; 3: V2 <; ...Write
AV930Relay output X4-DO2 limit valueData ratio; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01Hz; Uunb/Iunb: 0.1%; ...Write
AV931Relay output X4-DO2 hysteresisThe ratio is the same as above.; Item is switch linkage:; 0: When the ...Write
AV932Relay output X4-DO2 pulse width0.0: no pulse; 0.1~99.99sWrite
BI0Subject-DO1Write
BI1Subject-DO2Write
BI2X1-DI1Write
BI3X1-DI2Write
BI4X1-DI3Write
BI5X1-DI4Write
BI6X2-DI1Write
BI7X2-DI2Write
BI8X2-DI3Write
BI9X2-DI4Write
BI10X3-DI1Write
BI11X3-DI2Write
BI12X3-DI3Write
BI13X3-DI4Write
BI14X4-DI1Write
BI15X4-DI2Write
BI16X4-DI3Write
BI17X4-DI4Write
BO0Subject-DO1Read
BO1Subject-DO2Read
BO2X1-DO1Read
BO3X1-DO2Read
BO4X2-DO1Read
BO5X2-DO2Read
BO6X3-DO1Read
BO7X3-DO2Read
BO8X4-DO1Read
BO9X4-DO2Read
BVmin0Phase SequenceRead0: normal;1: abnormal
BV1frequency statusRead0: normal;1: abnormal
BV2Voltage qualification stateRead0: normal;1: abnormal
BVmin3High voltage alarmRead0: no alarm occurs; 1: alarm occurs
BV4Low voltage alarmRead0: no alarm occurs; 1: alarm occurs
BV5High current alarmRead0: no alarm occurs; 1: alarm occurs
BV6Low current alarmRead0: no alarm occurs; 1: alarm occurs
BV7High active power alarmRead0: no alarm occurs; 1: alarm occurs
BV8Low active power alarmRead0: no alarm occurs; 1: alarm occurs
BV9X1 Extended statusRead0: no; 1: yes
BV10X2 Extended statusRead0: no; 1: yes
BV11X3 Extended statusRead0: no; 1: yes
BV12X4 Extended statusRead0: no; 1: yes
Object ID lookup: Rayleigh Instruments RI-F500 series power analyser with RI-A5IPBAC BACnet IP module point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the RI-F500 series power analyser with RI-A5IPBAC BACnet IP module and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Rayleigh Instruments RI-F500 series power analyser with RI-A5IPBAC BACnet IP module

How many BACnet points does the Rayleigh Instruments RI-F500 series power analyser with RI-A5IPBAC BACnet IP module have?

This list has 998 BACnet objects: 16 analog inputs, 8 analog outputs, 933 analog values, 18 binary inputs, 10 binary outputs, 13 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Rayleigh Instruments RI-F500 series power analyser with RI-A5IPBAC BACnet IP module BACnet points are writable?

175 of the 998 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Rayleigh Instruments RI-F500 series power analyser with RI-A5IPBAC BACnet IP module BACnet documentation?

Rayleigh Instruments does not publish it on its own website. This list comes from RI-A5IPBAC (Bacnet module - TCP-IP) Communication Manual (V2), a copy hosted by Reseller Shopify CDN at https://cdn.shopify.com/s/files/1/0556/0283/9744/files/RI-A5IPBAC_user_manual_V2.pdf. Ask Rayleigh Instruments or its representative for the current revision.

What are the minimum BACnet points to integrate the Rayleigh Instruments RI-F500 series power analyser with RI-A5IPBAC BACnet IP module?

Start with AV 27 Import Active Energy EP+ (Import active energy, kWh); AV 13 Total active power-P (Total active power, kW); AV 17 Total reactive power-Q (Total reactive power, kvar); AV 0 Phase voltage-V1 (Phase voltage L1, V); AV 3 Line voltage-V12 (Line voltage L1-L2, V); AV 6 Phase current-I1 (Phase current L1, A); AV 721 Present demand value -P (Present active power demand, kW); BV 3 High voltage alarm (High voltage alarm (1 = alarm)); BV 0 Phase Sequence (Phase sequence abnormal (1)).

How do I check these points on the real RI-F500 series power analyser with RI-A5IPBAC BACnet IP module?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: RI-A5IPBAC (Bacnet module - TCP-IP) Communication Manual · V2. Object names, instances and units are reproduced as published; descriptions are our own.