The RI-A5IPBAC is a BACnet IP add-on module for the RI-F500 series power analysers. Its object list is about 1,000 objects: 4-20 mA and PT100 inputs and 4-20 mA outputs on extension modules, Analog Values for voltages, currents, power, energy (per phase, per quadrant, tariffs and monthly history), max/min and demand values, harmonics up to the 63rd order, pulse counters and event records, writable setup values (CT/PT, demand, limits, relay and AO configuration), plus digital input, relay output and alarm status objects.
This page lists 998 BACnet objects for the Rayleigh Instruments RI-F500 series power analyser with RI-A5IPBAC BACnet IP module — 175 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Rayleigh Instruments’s documentation hosted by Reseller Shopify CDN, not by Rayleigh Instruments itself, so treat it as unofficial.
- Manufacturer
- Rayleigh Instruments
- Model
- RI-F500 series power analyser with RI-A5IPBAC BACnet IP module
- Equipment
- Power analyser / multifunction meter
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 998 (175 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- RI-A5IPBAC, RI-F500, RI-F500 series, Rayleigh RI-F500 BACnet, RI-F500 BACnet/IP
- Source document
- RI-A5IPBAC (Bacnet module - TCP-IP) Communication Manual · V2 (unofficial copy, hosted by Reseller Shopify CDN)
Reference only, provided as-is: verify against Rayleigh Instruments’s current documentation and the live device before use. Not official Rayleigh Instruments information. Terms of use.
BMS integration notes: Rayleigh Instruments RI-F500 series power analyser with RI-A5IPBAC BACnet IP module
Configure the module's network settings from the RI-F500 front panel, then read total power, energy and the main voltages and currents. Set CT and PT values on the meter (or AV 788-793) before trusting the readings.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 27 | Import Active Energy EP+ | Import active energy, kWh | Read |
| AV 13 | Total active power-P | Total active power, kW | Read |
| AV 17 | Total reactive power-Q | Total reactive power, kvar | Read |
| AV 0 | Phase voltage-V1 | Phase voltage L1, V | Read |
| AV 3 | Line voltage-V12 | Line voltage L1-L2, V | Read |
| AV 6 | Phase current-I1 | Phase current L1, A | Read |
| AV 721 | Present demand value -P | Present active power demand, kW | Read |
| BV 3 | High voltage alarm | High voltage alarm (1 = alarm) | Read |
| BV 0 | Phase Sequence | Phase sequence abnormal (1) | Read |
Network setup
- The module's parameters are set through the RI-F500 meter, per the manual.
Watch out for
- Many objects only report data when the matching X1-X4 extension module is fitted.
- Configuration AVs (784 onward) change meter setup; do not write them cyclically.
Rayleigh Instruments RI-F500 series power analyser with RI-A5IPBAC BACnet IP module BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 0 | X1-AI1(4-20mA) | 0.001mA | Read | ||
| AI | 1 | X1-AI2(4-20mA) | 0.001mA | Read | ||
| AI | 2 | X2-AI1(4-20mA) | 0.001mA | Read | ||
| AI | 3 | X2-AI2(4-20mA) | 0.001mA | Read | ||
| AI | 4 | X3-AI1(4-20mA) | 0.001mA | Read | ||
| AI | 5 | X3-AI2(4-20mA) | 0.001mA | Read | ||
| AI | 6 | X4-AI1(4-20mA) | 0.001mA | Read | ||
| AI | 7 | X4-AI2(4-20mA) | 0.001mA | Read | ||
| AI | 8 | X1-AI1(PT100) | 1°C | Read | ||
| AI | 9 | X1-AI2(PT100) | 1°C | Read | ||
| AI | 10 | X2-AI1(PT100) | 1°C | Read | ||
| AI | 11 | X2-AI2(PT100) | 1°C | Read | ||
| AI | 12 | X3-AI1(PT100) | 1°C | Read | ||
| AI | 13 | X3-AI2(PT100) | 1°C | Read | ||
| AI | 14 | X4-AI1(PT100) | 1°C | Read | ||
| AI | 15 | X4-AI2(PT100) | 1°C | Read | ||
| AO | 0 | X1-AO1(4-20mA) | 0.001mA | Write | ||
| AO | 1 | X1-AO2(4-20mA) | 0.001mA | Write | ||
| AO | 2 | X2-AO1(4-20mA) | 0.001mA | Write | ||
| AO | 3 | X2-AO2(4-20mA) | 0.001mA | Write | ||
| AO | 4 | X3-AO1(4-20mA) | 0.001mA | Write | ||
| AO | 5 | X3-AO2(4-20mA) | 0.001mA | Write | ||
| AO | 6 | X4-AO1(4-20mA) | 0.001mA | Write | ||
| AO | 7 | X4-AO2(4-20mA) | 0.001mA | Write | ||
| AVmin | 0 | Phase voltage-V1 | V | Read | ||
| AV | 1 | Phase voltage-V2 | V | Read | ||
| AV | 2 | Phase voltage-V3 | V | Read | ||
| AVmin | 3 | Line voltage-V12 | V | Read | ||
| AV | 4 | Line voltage-V23 | V | Read | ||
| AV | 5 | Line voltage-V31 | V | Read | ||
| AVmin | 6 | Phase current-I1 | A | Read | ||
| AV | 7 | Phase current-I1 | A | Read | ||
| AV | 8 | Phase current-I3 | A | Read | ||
| AV | 9 | Current-In | A | Read | ||
| AV | 10 | Active power-P1 | kW | Read | ||
| AV | 11 | Active power-P2 | kW | Read | ||
| AV | 12 | Active power-P3 | kW | Read | ||
| AVmin | 13 | Total active power-P | kW | Read | ||
| AV | 14 | Reactive power-Q1 | kvar | Read | ||
| AV | 15 | Reactive power-Q2 | kvar | Read | ||
| AV | 16 | Reactive power-Q3 | kvar | Read | ||
| AVmin | 17 | Total reactive power-Q | kvar | Read | ||
| AV | 18 | Apparent power-S1 | kVA | Read | ||
| AV | 19 | Apparent power-S2 | kVA | Read | ||
| AV | 20 | Apparent power-S3 | kVA | Read | ||
| AV | 21 | Total apparent power-S | kVA | Read | ||
| AV | 22 | Power factor-PF1 | Read | |||
| AV | 23 | Power factor-PF2 | Read | |||
| AV | 24 | Power factor-PF3 | Read | |||
| AV | 25 | Total power factor-PF | Read | |||
| AV | 26 | Grid frequency-F | Hz | Read | ||
| AVmin | 27 | Import Active Energy EP+ | kWh | Read | ||
| AV | 28 | Export Active Energy EP- | kWh | Read | ||
| AV | 29 | Import Reactive Energy EQ+ | kvarh | Read | ||
| AV | 30 | Export Reactive Energy EQ- | kvarh | Read | ||
| AV | 31 | Apparent Energy | kVAh | Read | ||
| AV | 32 | 1st Quadrant Reactive Energy | kvarh | Read | ||
| AV | 33 | 2nd Quadrant Reactive Energy | kvarh | Read | ||
| AV | 34 | 3rd Quadrant Reactive Energy | kvarh | Read | ||
| AV | 35 | 4th Quadrant Reactive Energy | kvarh | Read | ||
| AV | 36 | Fundamental Import Active Energy | kWh | Read | ||
| AV | 37 | Fundamental Export Active Energy | kWh | Read | ||
| AV | 38 | Fundamental Import Reactive Energy | kvarh | Read | ||
| AV | 39 | Fundamental Export Reactive Energy | kvarh | Read | ||
| AV | 40 | Import Active Energy-L1 | kWh | Read | ||
| AV | 41 | Import Active Energy-L2 | kWh | Read | ||
| AV | 42 | Import Active Energy-L3 | kWh | Read | ||
| AV | 43 | Export Active Energy- L1 | kWh | Read | ||
| AV | 44 | Export Active Energy - L2 | kWh | Read | ||
| AV | 45 | Export Active Energy - L3 | kWh | Read | ||
| AV | 46 | Import Reactive Energy- L1 | kvarh | Read | ||
| AV | 47 | Import Reactive Energy- L2 | kvarh | Read | ||
| AV | 48 | Import Reactive Energy- L3 | kvarh | Read | ||
| AV | 49 | Export Reactive Energy - L1 | kvarh | Read | ||
| AV | 50 | Export Reactive Energy - L2 | kvarh | Read | ||
| AV | 51 | Export Reactive Energy - L3 | kvarh | Read | ||
| AV | 52 | Total import tariff energy | kWh | Read | ||
| AV | 53 | Tariff T1 import energy | kWh | Read | ||
| AV | 54 | Tariff T2 import energy | kWh | Read | ||
| AV | 55 | Tariff T3 import energy | kWh | Read | ||
| AV | 56 | Tariff T4 import energy | kWh | Read | ||
| AV | 57 | this month Total tariff import energy | kWh | Read | ||
| AV | 58 | this month Tariff T1 import energy | kWh | Read | ||
| AV | 59 | this month Tariff T2 import energy | kWh | Read | ||
| AV | 60 | this month Tariff T3 import energy | kWh | Read | ||
| AV | 61 | this month Tariff T4 import energy | kWh | Read | ||
| AV | 62 | One month before Total tariff import energy | kWh | Read | ||
| AV | 63 | One month before Tariff T1 import energy | kWh | Read | ||
| AV | 64 | One month before Tariff T2 import energy | kWh | Read | ||
| AV | 65 | One month before Tariff T3 import energy | kWh | Read | ||
| AV | 66 | One month before Tariff T4 import energy | kWh | Read | ||
| AV | 67 | two month before Total tariff import energy | kWh | Read | ||
| AV | 68 | two month before Tariff T1 import energy | kWh | Read | ||
| AV | 69 | two month before Tariff T2 import energy | kWh | Read | ||
| AV | 70 | two month before Tariff T3 import energy | kWh | Read | ||
| AV | 71 | two month before Tariff T4 import energy | kWh | Read | ||
| AV | 72 | three month before Total tariff import energy | kWh | Read | ||
| AV | 73 | three month before Tariff T1 import energy | kWh | Read | ||
| AV | 74 | three month before Tariff T2 import energy | kWh | Read | ||
| AV | 75 | three month before Tariff T3 import energy | kWh | Read | ||
| AV | 76 | three month before Tariff T4 import energy | kWh | Read | ||
| AV | 77 | four month before Total tariff import energy | kWh | Read | ||
| AV | 78 | four month before Tariff T1 import energy | kWh | Read | ||
| AV | 79 | four month before Tariff T2 import energy | kWh | Read | ||
| AV | 80 | four month before Tariff T3 import energy | kWh | Read | ||
| AV | 81 | four month before Tariff T4 import energy | kWh | Read | ||
| AV | 82 | five month before Total tariff import energy | kWh | Read | ||
| AV | 83 | five month before Tariff T1 import energy | kWh | Read | ||
| AV | 84 | five month before Tariff T2 import energy | kWh | Read | ||
| AV | 85 | five month before Tariff T3 import energy | kWh | Read | ||
| AV | 86 | five month before Tariff T4 import energy | kWh | Read | ||
| AV | 87 | six month before Total tariff import energy | kWh | Read | ||
| AV | 88 | six month before Tariff T1 import energy | kWh | Read | ||
| AV | 89 | six month before Tariff T2 import energy | kWh | Read | ||
| AV | 90 | six month before Tariff T3 import energy | kWh | Read | ||
| AV | 91 | six month before Tariff T4 import energy | kWh | Read | ||
| AV | 92 | seven month before Total tariff import energy | kWh | Read | ||
| AV | 93 | seven month before Tariff T1 import energy | kWh | Read | ||
| AV | 94 | seven month before Tariff T2 import energy | kWh | Read | ||
| AV | 95 | seven month before Tariff T3 import energy | kWh | Read | ||
| AV | 96 | seven month before Tariff T4 import energy | kWh | Read | ||
| AV | 97 | eight month before Total tariff import energy | kWh | Read | ||
| AV | 98 | eight month before Tariff T1 import energy | kWh | Read | ||
| AV | 99 | eight month before Tariff T2 import energy | kWh | Read | ||
| AV | 100 | eight month before Tariff T3 import energy | kWh | Read | ||
| AV | 101 | eight month before Tariff T4 import energy | kWh | Read | ||
| AV | 102 | nine month before Total tariff import energy | kWh | Read | ||
| AV | 103 | nine month before Tariff T1 import energy | kWh | Read | ||
| AV | 104 | nine month before Tariff T2 import energy | kWh | Read | ||
| AV | 105 | nine month before Tariff T3 import energy | kWh | Read | ||
| AV | 106 | nine month before Tariff T4 import energy | kWh | Read | ||
| AV | 107 | ten month before Total tariff import energy | kWh | Read | ||
| AV | 108 | ten month before Tariff T1 import energy | kWh | Read | ||
| AV | 109 | ten month before Tariff T2 import energy | kWh | Read | ||
| AV | 110 | ten month before Tariff T3 import energy | kWh | Read | ||
| AV | 111 | ten month before Tariff T4 import energy | kWh | Read | ||
| AV | 112 | eleven month before Total tariff import energy | kWh | Read | ||
| AV | 113 | eleven month before Tariff T1 import energy | kWh | Read | ||
| AV | 114 | eleven month before Tariff T2 import energy | kWh | Read | ||
| AV | 115 | eleven month before Tariff T3 import energy | kWh | Read | ||
| AV | 116 | eleven month before Tariff T4 import energy | kWh | Read | ||
| AV | 117 | High byte: year, Low byte: month | Read | |||
| AV | 118 | High byte: day, Low byte: hour | Read | |||
| AV | 119 | High byte: minute, Low byte: second | Read | |||
| AV | 120 | High byte:week, Low byte: ---- | Read | |||
| AV | 121 | High byte: X1 Extended Module Low byte: X2 Extended Module | Read | |||
| AV | 122 | High byte: X3 Extended Module Low byte: X4 Extended Module | Read | |||
| AV | 123 | Max. historical value-V1 | V | Read | ||
| AV | 124 | Max. historical value-V2 | V | Read | ||
| AV | 125 | Max. historical value-V3 | V | Read | ||
| AV | 126 | Max. historical value-V12 | V | Read | ||
| AV | 127 | Max. historical value-V23 | V | Read | ||
| AV | 128 | Max. historical value-V31 | V | Read | ||
| AV | 129 | Max. historical value-I1 | A | Read | ||
| AV | 130 | Max. historical value-I2 | A | Read | ||
| AV | 131 | Max. historical value-I3 | A | Read | ||
| AV | 132 | Max. historical value-In | A | Read | ||
| AV | 133 | Max. historical value-P | kW | Read | ||
| AV | 134 | Max. historical value-Q | kvar | Read | ||
| AV | 135 | Max. historical value-S | kVA | Read | ||
| AV | 136 | Max. historical value-PF | Read | |||
| AV | 137 | Max. historical value-F | Hz | Read | ||
| AV | 138 | Min. value-V1 | V | Read | ||
| AV | 139 | Min. value-V2 | V | Read | ||
| AV | 140 | Min. value-V3 | V | Read | ||
| AV | 141 | Min. value-V12 | V | Read | ||
| AV | 142 | Min. value-V23 | V | Read | ||
| AV | 143 | Min. value-V31 | V | Read | ||
| AV | 144 | Min. value-I1 | A | Read | ||
| AV | 145 | Min. value-I2 | A | Read | ||
| AV | 146 | Min. value-I3 | A | Read | ||
| AV | 147 | Min. value-In | A | Read | ||
| AV | 148 | Min. value-P | kW | Read | ||
| AV | 149 | Min. value-Q | kvar | Read | ||
| AV | 150 | Min. value-S | kVAh | Read | ||
| AV | 151 | Min. value-PF | Read | |||
| AV | 152 | Min. value-F | Hz | Read | ||
| AV | 153 | this month Max. historical value-V1 | V | Read | ||
| AV | 154 | this month Max. historical value-V2 | V | Read | ||
| AV | 155 | this month Max. historical value-V3 | V | Read | ||
| AV | 156 | this month Max. historical value-V12 | V | Read | ||
| AV | 157 | this month Max. historical value-V23 | V | Read | ||
| AV | 158 | this month Max. historical value-V31 | V | Read | ||
| AV | 159 | this month Max. historical value-I1 | A | Read | ||
| AV | 160 | this month Max. historical value-I2 | A | Read | ||
| AV | 161 | this month Max. historical value-I3 | A | Read | ||
| AV | 162 | this month Max. historical value-In | A | Read | ||
| AV | 163 | this month Max. historical value-P | kW | Read | ||
| AV | 164 | this month Max. historical value-Q | kvar | Read | ||
| AV | 165 | this month Max. historical value-S | kVA | Read | ||
| AV | 166 | this month Max. historical value-PF | Read | |||
| AV | 167 | this month Max. historical value-F | Hz | Read | ||
| AV | 168 | this month Min. value-V1 | V | Read | ||
| AV | 169 | this month Min. value-V2 | V | Read | ||
| AV | 170 | this month Min. value-V3 | V | Read | ||
| AV | 171 | this month Min. value-V12 | V | Read | ||
| AV | 172 | this month Min. value-V23 | V | Read | ||
| AV | 173 | this month Min. value-V31 | V | Read | ||
| AV | 174 | this month Min. value-I1 | A | Read | ||
| AV | 175 | this month Min. value-I2 | A | Read | ||
| AV | 176 | this month Min. value-I3 | A | Read | ||
| AV | 177 | this month Min. value-In | A | Read | ||
| AV | 178 | this month Min. value-P | kW | Read | ||
| AV | 179 | this month Min. value-Q | kvar | Read | ||
| AV | 180 | this month Min. value-S | kVA | Read | ||
| AV | 181 | this month Min. value-PF | Read | |||
| AV | 182 | this month Min. value-F | Hz | Read | ||
| AV | 183 | last month Max. historical value-V1 | V | Read | ||
| AV | 184 | last month Max. historical value-V2 | V | Read | ||
| AV | 185 | last month Max. historical value-V3 | V | Read | ||
| AV | 186 | last month Max. historical value-V12 | V | Read | ||
| AV | 187 | last month Max. historical value-V23 | V | Read | ||
| AV | 188 | last month Max. historical value-V31 | V | Read | ||
| AV | 189 | last month Max. historical value-I1 | A | Read | ||
| AV | 190 | last month Max. historical value-I2 | A | Read | ||
| AV | 191 | last month Max. historical value-I3 | A | Read | ||
| AV | 192 | last month Max. historical value-In | A | Read | ||
| AV | 193 | last month Max. historical value-P | kW | Read | ||
| AV | 194 | last month Max. historical value-Q | kvar | Read | ||
| AV | 195 | last month Max. historical value-S | kVA | Read | ||
| AV | 196 | last month Max. historical value-PF | Read | |||
| AV | 197 | last month Max. historical value-F | Hz | Read | ||
| AV | 198 | last month Min. value-V1 | V | Read | ||
| AV | 199 | last month Min. value-V2 | V | Read | ||
| AV | 200 | last month Min. value-V3 | V | Read | ||
| AV | 201 | last month Min. value-V12 | V | Read | ||
| AV | 202 | last month Min. value-V23 | V | Read | ||
| AV | 203 | last month Min. value-V31 | V | Read | ||
| AV | 204 | last month Min. value-I1 | A | Read | ||
| AV | 205 | last month Min. value-I2 | A | Read | ||
| AV | 206 | last month Min. value-I3 | A | Read | ||
| AV | 207 | last month Min. value-In | A | Read | ||
| AV | 208 | last month Min. value-P | kW | Read | ||
| AV | 209 | last month Min. value-Q | kvar | Read | ||
| AV | 210 | last month Min. value-S | kVA | Read | ||
| AV | 211 | last month Min. value-PF | Read | |||
| AV | 212 | last month Min. value-F | Hz | Read | ||
| AV | 213 | two months before Max. historical value-V1 | V | Read | ||
| AV | 214 | two months before Max. historical value-V2 | V | Read | ||
| AV | 215 | two months before Max. historical value-V3 | V | Read | ||
| AV | 216 | two months before Max. historical value-V12 | V | Read | ||
| AV | 217 | two months before Max. historical value-V23 | V | Read | ||
| AV | 218 | two months before Max. historical value-V31 | V | Read | ||
| AV | 219 | two months before Max. historical value-I1 | A | Read | ||
| AV | 220 | two months before Max. historical value-I2 | A | Read | ||
| AV | 221 | two months before Max. historical value-I3 | A | Read | ||
| AV | 222 | two months before Max. historical value-In | A | Read | ||
| AV | 223 | two months before Max. historical value-P | kW | Read | ||
| AV | 224 | two months before Max. historical value-Q | kvar | Read | ||
| AV | 225 | two months before Max. historical value-S | kVA | Read | ||
| AV | 226 | two months before Max. historical value-PF | Read | |||
| AV | 227 | two months before Max. historical value-F | Hz | Read | ||
| AV | 228 | two months before Min. value-V1 | V | Read | ||
| AV | 229 | two months before Min. value-V2 | V | Read | ||
| AV | 230 | two months before Min. value-V3 | V | Read | ||
| AV | 231 | two months before Min. value-V12 | V | Read | ||
| AV | 232 | two months before Min. value-V23 | V | Read | ||
| AV | 233 | two months before Min. value-V31 | V | Read | ||
| AV | 234 | two months before Min. value-I1 | A | Read | ||
| AV | 235 | two months before Min. value-I2 | A | Read | ||
| AV | 236 | two months before Min. value-I3 | A | Read | ||
| AV | 237 | two months before Min. value-In | A | Read | ||
| AV | 238 | two months before Min. value-P | kW | Read | ||
| AV | 239 | two months before Min. value-Q | kvar | Read | ||
| AV | 240 | two months before Min. value-S | kVA | Read | ||
| AV | 241 | two months before Min. value-PF | Read | |||
| AV | 242 | two months before Min. value-F | Hz | Read | ||
| AV | 243 | Positive-sequence component of voltage | V | Read | ||
| AV | 244 | Negative-sequence component of voltage | V | Read | ||
| AV | 245 | Zero-sequence component of voltage | V | Read | ||
| AV | 246 | Unbalance factor of voltage | Read | |||
| AV | 247 | Positive-sequence component of current | A | Read | ||
| AV | 248 | Negative-sequence component of current | A | Read | ||
| AV | 249 | Zero-sequence component of current | A | Read | ||
| AV | 250 | Unbalance factor of current | Read | |||
| AV | 251 | Avg-Vln | V | Read | ||
| AV | 252 | Avg-Vll | V | Read | ||
| AV | 253 | Avg-I | A | Read | ||
| AV | 254 | Avg-P | kW | Read | ||
| AV | 255 | Avg-Q | kvar | Read | ||
| AV | 256 | Avg-S | kVA | Read | ||
| AV | 257 | Deviation-V1 | V | Read | ||
| AV | 258 | Deviation-V2 | V | Read | ||
| AV | 259 | Deviation-V3 | V | Read | ||
| AV | 260 | Deviation-V12 | V | Read | ||
| AV | 261 | Deviation-V23 | V | Read | ||
| AV | 262 | Deviation-V31 | V | Read | ||
| AV | 263 | Deviation-F | Hz | Read | ||
| AV | 264 | Fundamental value -V1 | V | Read | ||
| AV | 265 | Fundamental value -V2 | V | Read | ||
| AV | 266 | Fundamental value -V3 | V | Read | ||
| AV | 267 | Fundamental value -I1 | A | Read | ||
| AV | 268 | Fundamental value -I2 | A | Read | ||
| AV | 269 | Fundamental value -I3 | A | Read | ||
| AV | 270 | Harmonic content -V1 | V | Read | ||
| AV | 271 | Harmonic content -V2 | V | Read | ||
| AV | 272 | Harmonic content -V3 | V | Read | ||
| AV | 273 | Harmonic content -I1 | A | Read | ||
| AV | 274 | Harmonic content -I2 | A | Read | ||
| AV | 275 | Harmonic content -I3 | A | Read | ||
| AV | 276 | Fundamental value -P1 | kW | Read | ||
| AV | 277 | Fundamental value -P2 | kW | Read | ||
| AV | 278 | Fundamental value -P3 | kW | Read | ||
| AV | 279 | Fundamental value -P1 | kW | Read | ||
| AV | 280 | Fundamental value -Q1 | kvar | Read | ||
| AV | 281 | Fundamental value -Q2 | kvar | Read | ||
| AV | 282 | Fundamental value -Q3 | kvar | Read | ||
| AV | 283 | Fundamental value -Q | kvar | Read | ||
| AV | 284 | Fundamental value -S1 | kVA | Read | ||
| AV | 285 | Fundamental value -S2 | kVA | Read | ||
| AV | 286 | Fundamental value -S3 | kVA | Read | ||
| AV | 287 | Fundamental value -S | kVA | Read | ||
| AV | 288 | Fundamental value -PF1 | Read | |||
| AV | 289 | Fundamental value -PF2 | Read | |||
| AV | 290 | Fundamental value -PF3 | Read | |||
| AV | 291 | Fundamental value -PF | Read | |||
| AV | 292 | Meter running time | s | Read | ||
| AV | 293 | On-load running time | s | Read | ||
| AV | 294 | V1-Short term severity | Read | |||
| AV | 295 | V2-Short term severity | Read | |||
| AV | 296 | V3-Short term severity | Read | |||
| AV | 297 | V1-Long term severity | Read | |||
| AV | 298 | V2-Long term severity | Read | |||
| AV | 299 | V3-Long term severity | Read | |||
| AV | 300 | V1-Voltage fluctuation | V | Read | ||
| AV | 301 | V2-Voltage fluctuation | V | Read | ||
| AV | 302 | V3-Voltage fluctuation | V | Read | ||
| AV | 303 | Phase angle of V1(default 0°) | 0.1° | Read | ||
| AV | 304 | Phase angle of V2 | 0.1° | Read | ||
| AV | 305 | Phase angle of V3 | 0.1° | Read | ||
| AV | 306 | Phase angle of I1 | 0.1° | Read | ||
| AV | 307 | Phase angle of I2 | 0.1° | Read | ||
| AV | 308 | Phase angle of I3 | 0.1° | Read | ||
| AV | 309 | Crest factor V1 | 0.001 | Read | ||
| AV | 310 | Crest factor V2 | 0.001 | Read | ||
| AV | 311 | Crest factor V3 | 0.001 | Read | ||
| AV | 312 | K-factor I1 | 0.001 | Read | ||
| AV | 313 | K-factor I2 | 0.001 | Read | ||
| AV | 314 | K-factor I3 | 0.001 | Read | ||
| AV | 315 | Derating factor of transformer | 0.10% | Read | ||
| AV | 316 | Load percentage I1 | 0.10% | Read | ||
| AV | 317 | Load percentage I2 | 0.10% | Read | ||
| AV | 318 | Load percentage I3 | 0.10% | Read | ||
| AV | 319 | Load percentage P | 0.10% | Read | ||
| AV | 320 | Voltage qualification rate | 0.10% | Read | ||
| AV | 321 | Frequency qualification rate | 0.10% | Read | ||
| AV | 322 | THD-V1 | 0.01% | Read | ||
| AV | 323 | THD-V2 | 0.01% | Read | ||
| AV | 324 | THD-V3 | 0.01% | Read | ||
| AV | 325 | THD-I1 | 0.01% | Read | ||
| AV | 326 | THD-I2 | 0.01% | Read | ||
| AV | 327 | THD-I3 | 0.01% | Read | ||
| AV | 328 | 2nd harmonic ratio-V1 | 0.01% | Read | ||
| AV | 329 | 2nd harmonic ratio-V2 | 0.01% | Read | ||
| AV | 330 | 2nd harmonic ratio-V3 | 0.01% | Read | ||
| AV | 331 | 2nd harmonic ratio-I1 | 0.01% | Read | ||
| AV | 332 | 2nd harmonic ratio-I2 | 0.01% | Read | ||
| AV | 333 | 2nd harmonic ratio-I3 | 0.01% | Read | ||
| AV | 334 | 3rd harmonic ratio-V1 | 0.01% | Read | ||
| AV | 335 | 3rd harmonic ratio-V2 | 0.01% | Read | ||
| AV | 336 | 3rd harmonic ratio-V3 | 0.01% | Read | ||
| AV | 337 | 3rd harmonic ratio-I1 | 0.01% | Read | ||
| AV | 338 | 3rd harmonic ratio-I2 | 0.01% | Read | ||
| AV | 339 | 3rd harmonic ratio-I3 | 0.01% | Read | ||
| AV | 340 | 4th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 341 | 4th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 342 | 4th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 343 | 4th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 344 | 4th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 345 | 4th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 346 | 5th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 347 | 5th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 348 | 5th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 349 | 5th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 350 | 5th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 351 | 5th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 352 | 6th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 353 | 6th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 354 | 6th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 355 | 6th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 356 | 6th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 357 | 6th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 358 | 7th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 359 | 7th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 360 | 7th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 361 | 7th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 362 | 7th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 363 | 7th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 364 | 8th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 365 | 8th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 366 | 8th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 367 | 8th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 368 | 8th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 369 | 8th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 370 | 9th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 371 | 9th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 372 | 9th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 373 | 9th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 374 | 9th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 375 | 9th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 376 | 10th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 377 | 10th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 378 | 10th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 379 | 10th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 380 | 10th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 381 | 10th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 382 | 11th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 383 | 11th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 384 | 11th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 385 | 11th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 386 | 11th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 387 | 11th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 388 | 12th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 389 | 12th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 390 | 12th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 391 | 12th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 392 | 12th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 393 | 12th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 394 | 13th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 395 | 13th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 396 | 13th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 397 | 13th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 398 | 13th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 399 | 13th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 400 | 14th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 401 | 14th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 402 | 14th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 403 | 14th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 404 | 14th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 405 | 14th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 406 | 15th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 407 | 15th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 408 | 15th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 409 | 15th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 410 | 15th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 411 | 15th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 412 | 16th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 413 | 16th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 414 | 16th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 415 | 16th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 416 | 16th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 417 | 16th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 418 | 17th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 419 | 17th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 420 | 17th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 421 | 17th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 422 | 17th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 423 | 17th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 424 | 18th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 425 | 18th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 426 | 18th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 427 | 18th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 428 | 18th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 429 | 18th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 430 | 19th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 431 | 19th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 432 | 19th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 433 | 19th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 434 | 19th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 435 | 19th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 436 | 20th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 437 | 20th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 438 | 20th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 439 | 20th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 440 | 20th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 441 | 20th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 442 | 21th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 443 | 21th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 444 | 21th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 445 | 21th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 446 | 21th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 447 | 21th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 448 | 22th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 449 | 22th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 450 | 22th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 451 | 22th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 452 | 22th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 453 | 22th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 454 | 23th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 455 | 23th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 456 | 23th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 457 | 23th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 458 | 23th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 459 | 23th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 460 | 24th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 461 | 24th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 462 | 24th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 463 | 24th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 464 | 24th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 465 | 24th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 466 | 25th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 467 | 25th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 468 | 25th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 469 | 25th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 470 | 25th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 471 | 25th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 472 | 26th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 473 | 26th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 474 | 26th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 475 | 26th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 476 | 26th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 477 | 26th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 478 | 27th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 479 | 27th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 480 | 27th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 481 | 27th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 482 | 27th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 483 | 27th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 484 | 28th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 485 | 28th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 486 | 28th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 487 | 28th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 488 | 28th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 489 | 28th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 490 | 29th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 491 | 29th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 492 | 29th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 493 | 29th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 494 | 29th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 495 | 29th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 496 | 30th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 497 | 30th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 498 | 30th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 499 | 30th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 500 | 30th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 501 | 30th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 502 | 31th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 503 | 31th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 504 | 31th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 505 | 31th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 506 | 31th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 507 | 31th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 508 | 32th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 509 | 32th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 510 | 32th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 511 | 32th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 512 | 32th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 513 | 32th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 514 | 33th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 515 | 33th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 516 | 33th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 517 | 33th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 518 | 33th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 519 | 33th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 520 | 34th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 521 | 34th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 522 | 34th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 523 | 34th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 524 | 34th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 525 | 34th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 526 | 35th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 527 | 35th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 528 | 35th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 529 | 35th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 530 | 35th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 531 | 35th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 532 | 36th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 533 | 36th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 534 | 36th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 535 | 36th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 536 | 36th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 537 | 36th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 538 | 37th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 539 | 37th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 540 | 37th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 541 | 37th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 542 | 37th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 543 | 37th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 544 | 38th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 545 | 38th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 546 | 38th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 547 | 38th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 548 | 38th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 549 | 38th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 550 | 39th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 551 | 39th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 552 | 39th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 553 | 39th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 554 | 39th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 555 | 39th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 556 | 40th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 557 | 40th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 558 | 40th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 559 | 40th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 560 | 40th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 561 | 40th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 562 | 41th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 563 | 41th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 564 | 41th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 565 | 41th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 566 | 41th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 567 | 41th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 568 | 42th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 569 | 42th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 570 | 42th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 571 | 42th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 572 | 42th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 573 | 42th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 574 | 43th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 575 | 43th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 576 | 43th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 577 | 43th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 578 | 43th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 579 | 43th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 580 | 44th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 581 | 44th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 582 | 44th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 583 | 44th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 584 | 44th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 585 | 44th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 586 | 45th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 587 | 45th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 588 | 45th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 589 | 45th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 590 | 45th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 591 | 45th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 592 | 46th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 593 | 46th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 594 | 46th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 595 | 46th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 596 | 46th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 597 | 46th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 598 | 47th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 599 | 47th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 600 | 47th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 601 | 47th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 602 | 47th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 603 | 47th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 604 | 48th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 605 | 48th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 606 | 48th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 607 | 48th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 608 | 48th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 609 | 48th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 610 | 49th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 611 | 49th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 612 | 49th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 613 | 49th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 614 | 49th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 615 | 49th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 616 | 50th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 617 | 50th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 618 | 50th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 619 | 50th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 620 | 50th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 621 | 50th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 622 | 51th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 623 | 51th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 624 | 51th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 625 | 51th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 626 | 51th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 627 | 51th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 628 | 52th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 629 | 52th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 630 | 52th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 631 | 52th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 632 | 52th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 633 | 52th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 634 | 53th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 635 | 53th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 636 | 53th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 637 | 53th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 638 | 53th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 639 | 53th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 640 | 54th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 641 | 54th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 642 | 54th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 643 | 54th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 644 | 54th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 645 | 54th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 646 | 55th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 647 | 55th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 648 | 55th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 649 | 55th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 650 | 55th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 651 | 55th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 652 | 56th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 653 | 56th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 654 | 56th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 655 | 56th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 656 | 56th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 657 | 56th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 658 | 57th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 659 | 57th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 660 | 57th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 661 | 57th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 662 | 57th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 663 | 57th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 664 | 58th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 665 | 58th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 666 | 58th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 667 | 58th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 668 | 58th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 669 | 58th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 670 | 59th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 671 | 59th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 672 | 59th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 673 | 59th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 674 | 59th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 675 | 59th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 676 | 60th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 677 | 60th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 678 | 60th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 679 | 60th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 680 | 60th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 681 | 60th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 682 | 61th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 683 | 61th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 684 | 61th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 685 | 61th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 686 | 61th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 687 | 61th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 688 | 62th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 689 | 62th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 690 | 62th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 691 | 62th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 692 | 62th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 693 | 62th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 694 | 63th harmonic ratio-V1 | 0.01% | Read | ||
| AV | 695 | 63th harmonic ratio-V2 | 0.01% | Read | ||
| AV | 696 | 63th harmonic ratio-V3 | 0.01% | Read | ||
| AV | 697 | 63th harmonic ratio-I1 | 0.01% | Read | ||
| AV | 698 | 63th harmonic ratio-I2 | 0.01% | Read | ||
| AV | 699 | 63th harmonic ratio-I3 | 0.01% | Read | ||
| AV | 700 | X1-channel1 pulse counter | Read | |||
| AV | 701 | X1-channel2 pulse counter | Read | |||
| AV | 702 | X1-channel3 pulse counter | Read | |||
| AV | 703 | X1-channel4 pulse counter | Read | |||
| AV | 704 | X2-channel1 pulse counter | Read | |||
| AV | 705 | X2-channel2 pulse counter | Read | |||
| AV | 706 | X2-channel3 pulse counter | Read | |||
| AV | 707 | X2-channel4 pulse counter | Read | |||
| AV | 708 | X3-channel1 pulse counter | Read | |||
| AV | 709 | X3-channel2 pulse counter | Read | |||
| AV | 710 | X3-channel3 pulse counter | Read | |||
| AV | 711 | X3-channel4 pulse counter | Read | |||
| AV | 712 | X4-channel1 pulse counter | Read | |||
| AV | 713 | X4-channel2 pulse counter | Read | |||
| AV | 714 | X4-channel3 pulse counter | Read | |||
| AV | 715 | X4-channel4 pulse counter | Read | |||
| AV | 716 | Main boby-channel1 pulse counter | Read | |||
| AV | 717 | Main boby-channel2 pulse counter | Read | |||
| AV | 718 | Present demand value -I1 | 1A | Read | ||
| AV | 719 | Present demand value -I2 | A | Read | ||
| AV | 720 | Present demand value -I3 | A | Read | ||
| AVmin | 721 | Present demand value -P | kW | Read | ||
| AV | 722 | Present demand value -Q | kvar | Read | ||
| AV | 723 | Present demand value -S | kVA | Read | ||
| AV | 724 | Previous demand value -I1 | 1A | Read | ||
| AV | 725 | Previous demand value -I2 | A | Read | ||
| AV | 726 | Previous demand value -I3 | A | Read | ||
| AV | 727 | Previous demand value -P | kW | Read | ||
| AV | 728 | Previous demand value -Q | kvar | Read | ||
| AV | 729 | Previous demand value -S | kVA | Read | ||
| AV | 730 | Max. demand value -I1 | A | Read | ||
| AV | 731 | Max. demand value -I2 | A | Read | ||
| AV | 732 | Max. demand value -I3 | A | Read | ||
| AV | 733 | Max. demand value -P | kW | Read | ||
| AV | 734 | Max. demand value -Q | kvar | Read | ||
| AV | 735 | Max. demand value -S | kVA | Read | ||
| AV | 736 | this month Max. demand value -I1 | A | Read | ||
| AV | 737 | this month Max. demand value -I2 | A | Read | ||
| AV | 738 | this month Max. demand value -I3 | A | Read | ||
| AV | 739 | this month Max. demand value -P | kW | Read | ||
| AV | 740 | this month Max. demand value -Q | kvar | Read | ||
| AV | 741 | this month Max. demand value -S | kVA | Read | ||
| AV | 742 | last month Max. demand value -I1 | A | Read | ||
| AV | 743 | last month Max. demand value -I2 | A | Read | ||
| AV | 744 | last month Max. demand value -I3 | A | Read | ||
| AV | 745 | last month Max. demand value -P | kW | Read | ||
| AV | 746 | last month Max. demand value -Q | kvar | Read | ||
| AV | 747 | last month Max. demand value -S | kVA | Read | ||
| AV | 748 | two months before Max. demand value -I1 | A | Read | ||
| AV | 749 | two months before Max. demand value -I2 | A | Read | ||
| AV | 750 | two months before Max. demand value -I3 | A | Read | ||
| AV | 751 | two months before Max. demand value -P | kW | Read | ||
| AV | 752 | two months before Max. demand value -Q | kvar | Read | ||
| AV | 753 | two months before Max. demand value -S | kVA | Read | ||
| AV | 754 | Record: Power On High byte: year, Low byte: month | Read | |||
| AV | 755 | High byte: day, Low byte: hour | Read | |||
| AV | 756 | High byte: minute, Low byte: second | Read | |||
| AV | 757 | Power On Number | Read | |||
| AV | 758 | Record: Power Off High byte: year, Low byte: month | Read | |||
| AV | 759 | High byte: day, Low byte: hour | Read | |||
| AV | 760 | High byte: minute, Low byte: second | Read | |||
| AV | 761 | Power Off Number | Read | |||
| AV | 762 | Record: Setup parameter High byte: year, Low byte: month | Read | |||
| AV | 763 | High byte: day, Low byte: hour | Read | |||
| AV | 764 | High byte: minute, Low byte: second | Read | |||
| AV | 765 | Setup parameter Number | Read | |||
| AV | 766 | Record: Clear demand High byte: year, Low byte: month | Read | |||
| AV | 767 | High byte: day, Low byte: hour | Read | |||
| AV | 768 | High byte: minute, Low byte: second | Read | |||
| AV | 769 | Clear demand resetting times | Read | |||
| AV | 770 | Record: Clear energy High byte: year, Low byte: month | Read | |||
| AV | 771 | High byte: day, Low byte: hour | Read | |||
| AV | 772 | High byte: minute, Low byte: second | Read | |||
| AV | 773 | High byte: minute, Low byte: second | Read | |||
| AV | 774 | High byte: Over voltage record number Low byte: ---- | Read | |||
| AV | 775 | High byte: under voltage record number Low byte: ---- | Read | |||
| AV | 776 | High byte: Over current record number Low byte: ---- | Read | |||
| AV | 777 | High byte: under current record number Low byte: ---- | Read | |||
| AV | 778 | High byte: Over active power record number Low byte: ---- | Read | |||
| AV | 779 | High byte: under active power record number Low byte: ---- | Read | |||
| AV | 780 | High byte: SOE event record number Low byte: ---- | Read | |||
| AV | 781 | High byt:e: Voltage swell record number Low byte: ---- | Read | |||
| AV | 782 | High byte: Voltage dip record number Low byte: ---- | Read | |||
| AV | 783 | High byte: Voltage interrupt record number Low byte: ---- | Read | |||
| AV | 784 | Main boby:Slave address | 1-247 | Write | ||
| AV | 785 | Main boby:baudrate | Write | |||
| AV | 786 | Main boby:Data format | Write | |||
| AV | 787 | High byte: Wiring Low byte: Grid frequency | Write | |||
| AV | 788 | PT secondary | 1~660V | Write | ||
| AV | 789 | CT secondary | 1~6A | Write | ||
| AV | 790 | Secondary side neutral current rating | 1~6A | Write | ||
| AV | 791 | PT primary | 1~999999V | Write | ||
| AV | 792 | CT primary | 1~999999A | Write | ||
| AV | 793 | Primary side neutral current rating | 1~999999A | Write | ||
| AV | 794 | Demand item | Defaulted as; I1/I2/I3/P/Q/S | Write | ||
| AV | 795 | Mode of demand | 0: slip block mode; 1: fixed block mode | Write | ||
| AV | 796 | Slip time(t) | 1~9999s | Write | ||
| AV | 797 | Demand period(T) | 1~30t | Write | ||
| AV | 798 | Voltage qualification rate upper limit | Secondary grid data | Write | ||
| AV | 799 | Voltage qualification rate lower limit | Secondary grid data | Write | ||
| AV | 800 | Frequency qualification rate upper limit | 0.01Hz | Write | ||
| AV | 801 | Frequency qualification rate lower limit | 0.01Hz | Write | ||
| AV | 802 | Relay output Main body-DO1 mode | Write | |||
| AV | 803 | Relay output Main body-DO1 Pulse width | Write | |||
| AV | 804 | Relay output Main body-DO1 Alarm item select | Write | |||
| AV | 805 | Relay output Main unit-DO1 limit value | Write | |||
| AV | 806 | Relay output Main unit-DO1 hysteresis | Write | |||
| AV | 807 | Relay output Main body-DO1 Alarm delay time | Write | |||
| AV | 808 | Relay output Main body-DO2 mode | Write | |||
| AV | 809 | Relay output Main body-DO2 Pulse width | Write | |||
| AV | 810 | Relay output Main body-DO2 Alarm item select | Write | |||
| AV | 811 | Relay output Main unit–DO2 limit value | Write | |||
| AV | 812 | Relay output Main unit-DO2 hysteresis | Write | |||
| AV | 813 | Relay output Main body-DO2 Alarm delay time | Write | |||
| AV | 814 | High byte: Main body DI1 mode Low byte: Main body DI2 mode | Write | |||
| AV | 815 | Voltage upper limit value | Secondary grid data: 0.1V | Write | ||
| AV | 816 | Voltage upper limit hysteresis value | Secondary grid data: 0.1V | Write | ||
| AV | 817 | Voltage lower limit value | Secondary grid data: 0.1V | Write | ||
| AV | 818 | Voltage lower limit hysteresis value | Secondary grid data: 0.1V | Write | ||
| AV | 819 | Current upper limit value | Secondary grid data: 0.001A | Write | ||
| AV | 820 | Current upper limit hysteresis value | Secondary grid data: 0.001A | Write | ||
| AV | 821 | Current lower limit value | Secondary grid data: 0.001A | Write | ||
| AV | 822 | Current lower limit hysteresis value | Secondary grid data: 0.001A | Write | ||
| AV | 823 | Active power upper limit value | Secondary grid data:; 1W/var/VA | Write | ||
| AV | 824 | Active power upper limit hysteresis value | Secondary grid data:; 1W/var/VA | Write | ||
| AV | 825 | Active power lower limit value | Secondary grid data:; 1W/var/VA | Write | ||
| AV | 826 | Active power lower limit hysteresis value | Secondary grid data:; 1W/var/VA | Write | ||
| AV | 827 | Voltage qualification rate upper limit value | Secondary grid data: 0.1V | Write | ||
| AV | 828 | Voltage qualification rate lower limit value | Secondary grid data: 0.1V | Write | ||
| AV | 829 | frequency qualification rate upper limit value | Secondary grid data: 0.01Hz | Write | ||
| AV | 830 | Frequency qualification rate lower limit value | Secondary grid data: 0.01Hz | Write | ||
| AV | 831 | Voltage sag limit value | Secondary grid data: 0.1V | Write | ||
| AV | 832 | Voltage sag hysteresis value | Secondary grid data: 0.1V | Write | ||
| AV | 833 | Voltage swell limit value | Secondary grid data: 0.1V | Write | ||
| AV | 834 | Voltage swell hysteresis value | Secondary grid data: 0.1V | Write | ||
| AV | 835 | Voltage interruption Limit value | Secondary grid data: 0.1V | Write | ||
| AV | 836 | Voltage interruption hysteresis value | Secondary grid data: 0.1V | Write | ||
| AV | 837 | Overvoltage start value of fault recording | Secondary grid data: 0.1V | Write | ||
| AV | 838 | Overvoltage hysteresis value of fault recording | Secondary grid data: 0.1V | Write | ||
| AV | 839 | undervoltage start value of fault recording | Secondary grid data: 0.1V | Write | ||
| AV | 840 | undervoltage hysteresis value of fault recording | Secondary grid data: 0.1V | Write | ||
| AV | 841 | overcurrent start value of fault recording | Secondary grid data: 0.001A | Write | ||
| AV | 842 | overcurrent hysteresis value of fault recording | Secondary grid data: 0.001A | Write | ||
| AV | 843 | Voltage sag and Voltage swell enable | 0: Close, 1: enabled | Write | ||
| AV | 844 | fault recording enable | 0: Close, 1: enabled | Write | ||
| AV | 845 | X1-AO1: Item | 0: Off; 1:V1; 2:V2; 3:V3; 4:V12; 5:V23; 6:V31; 7:I1; 8:I2; 9:I3; 10:In; 11:P1; 12:P2; ... | Write | ||
| AV | 846 | X1-AO1: Mode | 0:4~20 mA; 1:0~20 mA; 2:4~12~20 mA | Write | ||
| AV | 847 | X1-AO1: Down scale | Secondary grid data ratio; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01Hz | Write | ||
| AV | 848 | X1-AO1: Full scale | Secondary grid data ratio; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01Hz | Write | ||
| AV | 849 | X1-AO2: Item | 0:Off; 1:V1; 2:V2; 3:V3; 4:V12; 5:V23; 6:V31; 7:I1; 8:I2; 9:I3; 10:In; 11:P1; 12:P2; 13:P3; ... | Write | ||
| AV | 850 | X1-AO2: Mode | 0:4~20 mA; 1:0~20 mA; 2:4~12~20 mA | Write | ||
| AV | 851 | X1-AO2: Down scale | Secondary grid data ratio; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01Hz | Write | ||
| AV | 852 | X1-AO2: Full scale | Secondary grid data ratio; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01Hz | Write | ||
| AV | 853 | X2-AO1: Item | 0:Off; 1:V1; 2:V2; 3:V3; 4:V12; 5:V23; 6:V31; 7:I1; 8:I2; 9:I3; 10:In; 11:P1; 12:P2; 13:P3; ... | Write | ||
| AV | 854 | X2-AO1: Mode | 0:4~20 mA; 1:0~20 mA; 2:4~12~20 mA | Write | ||
| AV | 855 | X2-AO1: Down scale | Secondary grid data ratio; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01Hz | Write | ||
| AV | 856 | X2-AO1: Full scale | Secondary grid data ratio; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01Hz | Write | ||
| AV | 857 | X2-AO2: Item | 0:Off; 0: Off; 1:V1; 2:V2; 3:V3; 4:V12; 5:V23; 6:V31; 7:I1; 8:I2; 9:I3; 10:In; 11:P1; ... | Write | ||
| AV | 858 | X2-AO2: Mode | 0:4~20 mA; 1:0~20 mA; 2:4~12~20 mA | Write | ||
| AV | 859 | X2-AO2: Down scale | Secondary grid data ratio; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01Hz | Write | ||
| AV | 860 | X2-AO2: Full scale | Secondary grid data ratio; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01Hz | Write | ||
| AV | 861 | X3-AO1: Item | 0:Off; 0: Off; 1:V1; 2:V2; 3:V3; 4:V12; 5:V23; 6:V31; 7:I1; 8:I2; 9:I3; 10:In; 11:P1; ... | Write | ||
| AV | 862 | X3-AO1: Mode | 0:4~20 mA; 1:0~20 mA; 2:4~12~20 mA | Write | ||
| AV | 863 | X3-AO1: Down scale | Secondary grid data ratio; Voltage: 0.1V,; Current: 0.001A,; Power: 1W/var/VA,; PF: 0.001; F: 0.01Hz | Write | ||
| AV | 864 | X3-AO1: Full scale | Secondary grid data ratio; Voltage: 0.1V,; Current: 0.001A,; Power: 1W/var/VA,; PF: 0.001; F: 0.01Hz | Write | ||
| AV | 865 | X3-AO2: Item | 0:Off; 0: Off; 1:V1; 2:V2; 3:V3; 4:V12; 5:V23; 6:V31; 7:I1; 8:I2; 9:I3; 10:In; 11:P1; ... | Write | ||
| AV | 866 | X3-AO2: Mode | 0:4~20 mA; 1:0~20 mA; 2:4~12~20 mA | Write | ||
| AV | 867 | X3-AO2: Down scale | Secondary grid data ratio; Voltage: 0.1V,; Current: 0.001A,; Power:1W/var/VA,; PF: 0.001,; F: 0.01Hz | Write | ||
| AV | 868 | X3-AO2: Full scale | Secondary grid data ratio; Voltage: 0.1V,; Current: 0.001A,; Power:1W/var/VA,; PF: 0.001,; F: 0.01Hz | Write | ||
| AV | 869 | X4-AO1: Item | 0:Off; 0: Off; 1:V1; 2:V2; 3:V3; 4:V12; 5:V23; 6:V31; 7:I1; 8:I2; 9:I3; 10:In; 11:P1; ... | Write | ||
| AV | 870 | X4-AO1: Mode | 0:4~20 mA; 1:0~20 mA; 2:4~12~20 mA | Write | ||
| AV | 871 | X4-AO1: Down scale | Secondary grid data ratio; Voltage: 0.1V,; Current: 0.001A,; Power:1W/var/VA,; PF: 0.001,; F: 0.01Hz | Write | ||
| AV | 872 | X4-AO1: Full scale | Secondary grid data ratio; Voltage: 0.1V,; Current: 0.001A,; Power:1W/var/VA,; PF: 0.001,; F: 0.01Hz | Write | ||
| AV | 873 | X4-AO2: Item | 0:Off; 0: Off; 1:V1; 2:V2; 3:V3; 4:V12; 5:V23; 6:V31; 7:I1; 8:I2; 9:I3; 10:In; 11:P1; ... | Write | ||
| AV | 874 | X4-AO2: Mode | 0:4~20 mA; 1:0~20 mA; 2:4~12~20 mA | Write | ||
| AV | 875 | X4-AO2: Down scale | Secondary grid data ratio; Voltage: 0.1V,; Current: 0.001A,; Power:1W/var/VA,; PF: 0.001,; F: 0.01Hz | Write | ||
| AV | 876 | X4-AO2: Full scale | Secondary grid data ratio; Voltage: 0.1V,; Current: 0.001A,; Power:1W/var/VA,; PF: 0.001,; F: 0.01Hz | Write | ||
| AV | 877 | Switch input High byte: X1-DI1: Mode Low byte: X1-DI2: Mode | 0: state monitor; 1: pulse counter | Write | ||
| AV | 878 | Switch input High byte: X1-DI3: Mode Low byte: X1-DI4: Mode | 0: state monitor; 1: pulse counter | Write | ||
| AV | 879 | Switch input High byte: X2-DI1: Mode Low byte: X2-DI2: Mode | 0: state monitor; 1: pulse counter | Write | ||
| AV | 880 | Switch input High byte: X2-DI3: Mode Low byte: X2-DI4: Mode | 0: state monitor; 1: pulse counter | Write | ||
| AV | 881 | Switch input High byte: X3-DI1: Mode Low byte: X3-DI2: Mode | 0: state monitor; 1: pulse counter | Write | ||
| AV | 882 | Switch input High byte: X3-DI3: Mode Low byte: X3-DI4: Mode | 0: state monitor; 1: pulse counter | Write | ||
| AV | 883 | Switch input High byte: X4-DI1: Mode Low byte: X4-DI2: Mode | 0: state monitor; 1: pulse counter | Write | ||
| AV | 884 | Switch input High byte: X4-DI3: Mode Low byte: X4-DI4: Mode | 0: state monitor; 1: pulse counter | Write | ||
| AV | 885 | Relay output X1-DO1 mode | 0: OFF; 1: remote control; 2: alarm | Write | ||
| AV | 886 | Relay output X1-DO1 pulse width | 0.0: no pulse; Pulse width : 0.1~99.99s | Write | ||
| AV | 887 | Relay output X1-DO1 alarm select | Alarm Item:; 0: V1 >; 1: V1 <; 2: V2 >; 3: V2 <; ... | Write | ||
| AV | 888 | Relay output X1-DO1 limit value | Data ratio; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01Hz; Uunb/Iunb: 0.1%; ... | Write | ||
| AV | 889 | Relay output X1-DO1 hysteresis | The ratio is the same as above.; Item is switch linkage:; 0: When the ... | Write | ||
| AV | 890 | Relay output X1-DO1 pulse width | 0.0: no pulse; 0.1~99.99s | Write | ||
| AV | 891 | Relay output X1-DO2 mode | 0: OFF; 1: remote control; 2: alarm | Write | ||
| AV | 892 | Relay output X1-DO2 pulse width | 0.0: no pulse; pulse width : 0.1~99.99s | Write | ||
| AV | 893 | Relay output X1-DO2 alarm select | Alarm Item:; 0: V1 >; 1: V1 <; 2: V2 >; 3: V2 <; ... | Write | ||
| AV | 894 | Relay output X1-DO2 limit value | Data ratio; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01Hz; Uunb/Iunb: 0.1%; ... | Write | ||
| AV | 895 | Relay output X1-DO2 hysteresis | The ratio is the same as above.; Item is switch linkage:; 0: When the ... | Write | ||
| AV | 896 | Relay output X1-DO2 pulse width | 0.0: no pulse; 0.1~99.99s | Write | ||
| AV | 897 | Relay output X2-DO1 mode | 0: OFF; 1: remote control; 2: alarm | Write | ||
| AV | 898 | Relay output X2-DO1 pulse width | 0.0: no pulse; pulse width : 0.1~99.99s | Write | ||
| AV | 899 | Relay output X2-DO1 alarm select | Alarm Item:; 0: V1 >; 1: V1 <; 2: V2 >; 3: V2 <; ... | Write | ||
| AV | 900 | Relay output X2-DO1 limit value | Data ratio,; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01Hz; Uunb/Iunb: 0.1%; ... | Write | ||
| AV | 901 | Relay output X2-DO1 hysteresis | The ratio is the same as above.; Item is switch linkage:; 0: When the ... | Write | ||
| AV | 902 | Relay output X2-DO1 pulse width | 0.0: no pulse; 0.1~99.99s | Write | ||
| AV | 903 | Relay output X2-DO2 mode | 0: OFF; 1: remote control; 2: alarm | Write | ||
| AV | 904 | Relay output X2-DO2 pulse width | 0.0: no pulse; pulse width : 0.1~99.99s | Write | ||
| AV | 905 | Relay output X2-DO2 alarm select | Alarm Item:; 0: V1 >; 1: V1 <; 2: V2 >; 3: V2 <; ... | Write | ||
| AV | 906 | Relay output X2-DO2 limit value | Data ratio; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01Hz; Uunb/Iunb: 0.1%; ... | Write | ||
| AV | 907 | Relay output X2-DO2 hysteresis | The ratio is the same as above.; Item is switch linkage:; 0: When the ... | Write | ||
| AV | 908 | Relay output X2-DO2 pulse width | 0.0: no pulse; 0.1~99.99s | Write | ||
| AV | 909 | Relay output X3-DO1 mode | 0: OFF; 1: remote control; 2: alarm | Write | ||
| AV | 910 | Relay output X3-DO1 pulse width | 0.0: no pulse; pulse width : 0.1~99.99s | Write | ||
| AV | 911 | Relay output X3-DO1 alarm select | Alarm Item:; 0: V1 >; 1: V1 <; 2: V2 >; 3: V2 <; ... | Write | ||
| AV | 912 | Relay output X3-DO1 limit value | Data ratio; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01Hz; Uunb/Iunb: 0.1%; ... | Write | ||
| AV | 913 | Relay output X3-DO1 hysteresis | The ratio is the same as above.; Item is switch linkage:; 0: When the ... | Write | ||
| AV | 914 | Relay output X3-DO1 pulse width | 0.0: no pulse; 0.1~99.99s | Write | ||
| AV | 915 | Relay output X3-DO2 mode | 0: OFF; 1: remote control; 2: alarm | Write | ||
| AV | 916 | Relay output X3-DO2 pulse width | 0.0: no pulse; pulse width : 0.1~99.99s | Write | ||
| AV | 917 | Relay output X3-DO2 alarm select | Alarm Item:; 0: V1 >; 1: V1 <; 2: V2 >; 3: V2 <; ... | Write | ||
| AV | 918 | Relay output X3-DO2 limit value | Data ratio; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01Hz; Uunb/Iunb: 0.1%; ... | Write | ||
| AV | 919 | Relay output X3-DO2 hysteresis | The ratio is the same as above.; Item is switch linkage:; 0: When the ... | Write | ||
| AV | 920 | Relay output X3-DO2 pulse width | 0.0: no pulse; 0.1~99.99s | Write | ||
| AV | 921 | Relay output X4-DO1 mode | 0: OFF; 1: remote control; 2: alarm | Write | ||
| AV | 922 | Relay output X4-DO1 pulse width | 0.0: no pulse; pulse width : 0.1~99.99s | Write | ||
| AV | 923 | Relay output X4-DO1 alarm select | Alarm Item:; 0: V1 >; 1: V1 <; 2: V2 >; 3: V2 <; ... | Write | ||
| AV | 924 | Relay output X4-DO1 limit value | Data ratio; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01Hz; Uunb/Iunb: 0.1%; ... | Write | ||
| AV | 925 | Relay output X4-DO1 hysteresis | The ratio is the same as above.; Item is switch linkage:; 0: When the ... | Write | ||
| AV | 926 | Relay output X4-DO1 pulse width | 0.0: no pulse; 0.1~99.99s | Write | ||
| AV | 927 | Relay output X4-DO2 mode | 0: OFF; 1: remote control; 2: alarm | Write | ||
| AV | 928 | Relay output X4-DO2 pulse width | 0.0: no pulse; pulse width : 0.1~99.99s | Write | ||
| AV | 929 | Relay output X4-DO2 alarm select | Alarm Item:; 0: V1 >; 1: V1 <; 2: V2 >; 3: V2 <; ... | Write | ||
| AV | 930 | Relay output X4-DO2 limit value | Data ratio; Voltage: 0.1V,; Current: 0.001A; Power: 1W/var/VA; PF: 0.001; F: 0.01Hz; Uunb/Iunb: 0.1%; ... | Write | ||
| AV | 931 | Relay output X4-DO2 hysteresis | The ratio is the same as above.; Item is switch linkage:; 0: When the ... | Write | ||
| AV | 932 | Relay output X4-DO2 pulse width | 0.0: no pulse; 0.1~99.99s | Write | ||
| BI | 0 | Subject-DO1 | Write | |||
| BI | 1 | Subject-DO2 | Write | |||
| BI | 2 | X1-DI1 | Write | |||
| BI | 3 | X1-DI2 | Write | |||
| BI | 4 | X1-DI3 | Write | |||
| BI | 5 | X1-DI4 | Write | |||
| BI | 6 | X2-DI1 | Write | |||
| BI | 7 | X2-DI2 | Write | |||
| BI | 8 | X2-DI3 | Write | |||
| BI | 9 | X2-DI4 | Write | |||
| BI | 10 | X3-DI1 | Write | |||
| BI | 11 | X3-DI2 | Write | |||
| BI | 12 | X3-DI3 | Write | |||
| BI | 13 | X3-DI4 | Write | |||
| BI | 14 | X4-DI1 | Write | |||
| BI | 15 | X4-DI2 | Write | |||
| BI | 16 | X4-DI3 | Write | |||
| BI | 17 | X4-DI4 | Write | |||
| BO | 0 | Subject-DO1 | Read | |||
| BO | 1 | Subject-DO2 | Read | |||
| BO | 2 | X1-DO1 | Read | |||
| BO | 3 | X1-DO2 | Read | |||
| BO | 4 | X2-DO1 | Read | |||
| BO | 5 | X2-DO2 | Read | |||
| BO | 6 | X3-DO1 | Read | |||
| BO | 7 | X3-DO2 | Read | |||
| BO | 8 | X4-DO1 | Read | |||
| BO | 9 | X4-DO2 | Read | |||
| BVmin | 0 | Phase Sequence | Read | 0: normal;1: abnormal | ||
| BV | 1 | frequency status | Read | 0: normal;1: abnormal | ||
| BV | 2 | Voltage qualification state | Read | 0: normal;1: abnormal | ||
| BVmin | 3 | High voltage alarm | Read | 0: no alarm occurs; 1: alarm occurs | ||
| BV | 4 | Low voltage alarm | Read | 0: no alarm occurs; 1: alarm occurs | ||
| BV | 5 | High current alarm | Read | 0: no alarm occurs; 1: alarm occurs | ||
| BV | 6 | Low current alarm | Read | 0: no alarm occurs; 1: alarm occurs | ||
| BV | 7 | High active power alarm | Read | 0: no alarm occurs; 1: alarm occurs | ||
| BV | 8 | Low active power alarm | Read | 0: no alarm occurs; 1: alarm occurs | ||
| BV | 9 | X1 Extended status | Read | 0: no; 1: yes | ||
| BV | 10 | X2 Extended status | Read | 0: no; 1: yes | ||
| BV | 11 | X3 Extended status | Read | 0: no; 1: yes | ||
| BV | 12 | X4 Extended status | Read | 0: no; 1: yes |
No points match these filters.
Object ID lookup: Rayleigh Instruments RI-F500 series power analyser with RI-A5IPBAC BACnet IP module point IDs by name
AI0X1-AI1(4-20mA)AI1X1-AI2(4-20mA)AI2X2-AI1(4-20mA)AI3X2-AI2(4-20mA)AI4X3-AI1(4-20mA)AI5X3-AI2(4-20mA)AI6X4-AI1(4-20mA)AI7X4-AI2(4-20mA)AI8X1-AI1(PT100)AI9X1-AI2(PT100)AI10X2-AI1(PT100)AI11X2-AI2(PT100)AI12X3-AI1(PT100)AI13X3-AI2(PT100)AI14X4-AI1(PT100)AI15X4-AI2(PT100)AO0X1-AO1(4-20mA)AO1X1-AO2(4-20mA)AO2X2-AO1(4-20mA)AO3X2-AO2(4-20mA)AO4X3-AO1(4-20mA)AO5X3-AO2(4-20mA)AO6X4-AO1(4-20mA)AO7X4-AO2(4-20mA)AV0Phase voltage-V1AV1Phase voltage-V2AV2Phase voltage-V3AV3Line voltage-V12AV4Line voltage-V23AV5Line voltage-V31AV6Phase current-I1AV7Phase current-I1AV8Phase current-I3AV9Current-InAV10Active power-P1AV11Active power-P2AV12Active power-P3AV13Total active power-PAV14Reactive power-Q1AV15Reactive power-Q2AV16Reactive power-Q3AV17Total reactive power-QAV18Apparent power-S1AV19Apparent power-S2AV20Apparent power-S3AV21Total apparent power-SAV22Power factor-PF1AV23Power factor-PF2AV24Power factor-PF3AV25Total power factor-PFAV26Grid frequency-FAV27Import Active Energy EP+AV28Export Active Energy EP-AV29Import Reactive Energy EQ+AV30Export Reactive Energy EQ-AV31Apparent EnergyAV321st Quadrant Reactive EnergyAV332nd Quadrant Reactive EnergyAV343rd Quadrant Reactive EnergyAV354th Quadrant Reactive EnergyAV36Fundamental Import Active EnergyAV37Fundamental Export Active EnergyAV38Fundamental Import Reactive EnergyAV39Fundamental Export Reactive EnergyAV40Import Active Energy-L1AV41Import Active Energy-L2AV42Import Active Energy-L3AV43Export Active Energy- L1AV44Export Active Energy - L2AV45Export Active Energy - L3AV46Import Reactive Energy- L1AV47Import Reactive Energy- L2AV48Import Reactive Energy- L3AV49Export Reactive Energy - L1AV50Export Reactive Energy - L2AV51Export Reactive Energy - L3AV52Total import tariff energyAV53Tariff T1 import energyAV54Tariff T2 import energyAV55Tariff T3 import energyAV56Tariff T4 import energyAV57this month Total tariff import energyAV58this month Tariff T1 import energyAV59this month Tariff T2 import energyAV60this month Tariff T3 import energyAV61this month Tariff T4 import energyAV62One month before Total tariff import energyAV63One month before Tariff T1 import energyAV64One month before Tariff T2 import energyAV65One month before Tariff T3 import energyAV66One month before Tariff T4 import energyAV67two month before Total tariff import energyAV68two month before Tariff T1 import energyAV69two month before Tariff T2 import energyAV70two month before Tariff T3 import energyAV71two month before Tariff T4 import energyAV72three month before Total tariff import energyAV73three month before Tariff T1 import energyAV74three month before Tariff T2 import energyAV75three month before Tariff T3 import energyAV76three month before Tariff T4 import energyAV77four month before Total tariff import energyAV78four month before Tariff T1 import energyAV79four month before Tariff T2 import energyAV80four month before Tariff T3 import energyAV81four month before Tariff T4 import energyAV82five month before Total tariff import energyAV83five month before Tariff T1 import energyAV84five month before Tariff T2 import energyAV85five month before Tariff T3 import energyAV86five month before Tariff T4 import energyAV87six month before Total tariff import energyAV88six month before Tariff T1 import energyAV89six month before Tariff T2 import energyAV90six month before Tariff T3 import energyAV91six month before Tariff T4 import energyAV92seven month before Total tariff import energyAV93seven month before Tariff T1 import energyAV94seven month before Tariff T2 import energyAV95seven month before Tariff T3 import energyAV96seven month before Tariff T4 import energyAV97eight month before Total tariff import energyAV98eight month before Tariff T1 import energyAV99eight month before Tariff T2 import energyAV100eight month before Tariff T3 import energyAV101eight month before Tariff T4 import energyAV102nine month before Total tariff import energyAV103nine month before Tariff T1 import energyAV104nine month before Tariff T2 import energyAV105nine month before Tariff T3 import energyAV106nine month before Tariff T4 import energyAV107ten month before Total tariff import energyAV108ten month before Tariff T1 import energyAV109ten month before Tariff T2 import energyAV110ten month before Tariff T3 import energyAV111ten month before Tariff T4 import energyAV112eleven month before Total tariff import energyAV113eleven month before Tariff T1 import energyAV114eleven month before Tariff T2 import energyAV115eleven month before Tariff T3 import energyAV116eleven month before Tariff T4 import energyAV117High byte: year, Low byte: monthAV118High byte: day, Low byte: hourAV119High byte: minute, Low byte: secondAV120High byte:week, Low byte: ----AV121High byte: X1 Extended Module Low byte: X2 Extended ModuleAV122High byte: X3 Extended Module Low byte: X4 Extended ModuleAV123Max. historical value-V1AV124Max. historical value-V2AV125Max. historical value-V3AV126Max. historical value-V12AV127Max. historical value-V23AV128Max. historical value-V31AV129Max. historical value-I1AV130Max. historical value-I2AV131Max. historical value-I3AV132Max. historical value-InAV133Max. historical value-PAV134Max. historical value-QAV135Max. historical value-SAV136Max. historical value-PFAV137Max. historical value-FAV138Min. value-V1AV139Min. value-V2AV140Min. value-V3AV141Min. value-V12AV142Min. value-V23AV143Min. value-V31AV144Min. value-I1AV145Min. value-I2AV146Min. value-I3AV147Min. value-InAV148Min. value-PAV149Min. value-QAV150Min. value-SAV151Min. value-PFAV152Min. value-FAV153this month Max. historical value-V1AV154this month Max. historical value-V2AV155this month Max. historical value-V3AV156this month Max. historical value-V12AV157this month Max. historical value-V23AV158this month Max. historical value-V31AV159this month Max. historical value-I1AV160this month Max. historical value-I2AV161this month Max. historical value-I3AV162this month Max. historical value-InAV163this month Max. historical value-PAV164this month Max. historical value-QAV165this month Max. historical value-SAV166this month Max. historical value-PFAV167this month Max. historical value-FAV168this month Min. value-V1AV169this month Min. value-V2AV170this month Min. value-V3AV171this month Min. value-V12AV172this month Min. value-V23AV173this month Min. value-V31AV174this month Min. value-I1AV175this month Min. value-I2AV176this month Min. value-I3AV177this month Min. value-InAV178this month Min. value-PAV179this month Min. value-QAV180this month Min. value-SAV181this month Min. value-PFAV182this month Min. value-FAV183last month Max. historical value-V1AV184last month Max. historical value-V2AV185last month Max. historical value-V3AV186last month Max. historical value-V12AV187last month Max. historical value-V23AV188last month Max. historical value-V31AV189last month Max. historical value-I1AV190last month Max. historical value-I2AV191last month Max. historical value-I3AV192last month Max. historical value-InAV193last month Max. historical value-PAV194last month Max. historical value-QAV195last month Max. historical value-SAV196last month Max. historical value-PFAV197last month Max. historical value-FAV198last month Min. value-V1AV199last month Min. value-V2AV200last month Min. value-V3AV201last month Min. value-V12AV202last month Min. value-V23AV203last month Min. value-V31AV204last month Min. value-I1AV205last month Min. value-I2AV206last month Min. value-I3AV207last month Min. value-InAV208last month Min. value-PAV209last month Min. value-QAV210last month Min. value-SAV211last month Min. value-PFAV212last month Min. value-FAV213two months before Max. historical value-V1AV214two months before Max. historical value-V2AV215two months before Max. historical value-V3AV216two months before Max. historical value-V12AV217two months before Max. historical value-V23AV218two months before Max. historical value-V31AV219two months before Max. historical value-I1AV220two months before Max. historical value-I2AV221two months before Max. historical value-I3AV222two months before Max. historical value-InAV223two months before Max. historical value-PAV224two months before Max. historical value-QAV225two months before Max. historical value-SAV226two months before Max. historical value-PFAV227two months before Max. historical value-FAV228two months before Min. value-V1AV229two months before Min. value-V2AV230two months before Min. value-V3AV231two months before Min. value-V12AV232two months before Min. value-V23AV233two months before Min. value-V31AV234two months before Min. value-I1AV235two months before Min. value-I2AV236two months before Min. value-I3AV237two months before Min. value-InAV238two months before Min. value-PAV239two months before Min. value-QAV240two months before Min. value-SAV241two months before Min. value-PFAV242two months before Min. value-FAV243Positive-sequence component of voltageAV244Negative-sequence component of voltageAV245Zero-sequence component of voltageAV246Unbalance factor of voltageAV247Positive-sequence component of currentAV248Negative-sequence component of currentAV249Zero-sequence component of currentAV250Unbalance factor of currentAV251Avg-VlnAV252Avg-VllAV253Avg-IAV254Avg-PAV255Avg-QAV256Avg-SAV257Deviation-V1AV258Deviation-V2AV259Deviation-V3AV260Deviation-V12AV261Deviation-V23AV262Deviation-V31AV263Deviation-FAV264Fundamental value -V1AV265Fundamental value -V2AV266Fundamental value -V3AV267Fundamental value -I1AV268Fundamental value -I2AV269Fundamental value -I3AV270Harmonic content -V1AV271Harmonic content -V2AV272Harmonic content -V3AV273Harmonic content -I1AV274Harmonic content -I2AV275Harmonic content -I3AV276Fundamental value -P1AV277Fundamental value -P2AV278Fundamental value -P3AV279Fundamental value -P1AV280Fundamental value -Q1AV281Fundamental value -Q2AV282Fundamental value -Q3AV283Fundamental value -QAV284Fundamental value -S1AV285Fundamental value -S2AV286Fundamental value -S3AV287Fundamental value -SAV288Fundamental value -PF1AV289Fundamental value -PF2AV290Fundamental value -PF3AV291Fundamental value -PFAV292Meter running timeAV293On-load running timeAV294V1-Short term severityAV295V2-Short term severityAV296V3-Short term severityAV297V1-Long term severityAV298V2-Long term severityAV299V3-Long term severityAV300V1-Voltage fluctuationAV301V2-Voltage fluctuationAV302V3-Voltage fluctuationAV303Phase angle of V1(default 0°)AV304Phase angle of V2AV305Phase angle of V3AV306Phase angle of I1AV307Phase angle of I2AV308Phase angle of I3AV309Crest factor V1AV310Crest factor V2AV311Crest factor V3AV312K-factor I1AV313K-factor I2AV314K-factor I3AV315Derating factor of transformerAV316Load percentage I1AV317Load percentage I2AV318Load percentage I3AV319Load percentage PAV320Voltage qualification rateAV321Frequency qualification rateAV322THD-V1AV323THD-V2AV324THD-V3AV325THD-I1AV326THD-I2AV327THD-I3AV3282nd harmonic ratio-V1AV3292nd harmonic ratio-V2AV3302nd harmonic ratio-V3AV3312nd harmonic ratio-I1AV3322nd harmonic ratio-I2AV3332nd harmonic ratio-I3AV3343rd harmonic ratio-V1AV3353rd harmonic ratio-V2AV3363rd harmonic ratio-V3AV3373rd harmonic ratio-I1AV3383rd harmonic ratio-I2AV3393rd harmonic ratio-I3AV3404th harmonic ratio-V1AV3414th harmonic ratio-V2AV3424th harmonic ratio-V3AV3434th harmonic ratio-I1AV3444th harmonic ratio-I2AV3454th harmonic ratio-I3AV3465th harmonic ratio-V1AV3475th harmonic ratio-V2AV3485th harmonic ratio-V3AV3495th harmonic ratio-I1AV3505th harmonic ratio-I2AV3515th harmonic ratio-I3AV3526th harmonic ratio-V1AV3536th harmonic ratio-V2AV3546th harmonic ratio-V3AV3556th harmonic ratio-I1AV3566th harmonic ratio-I2AV3576th harmonic ratio-I3AV3587th harmonic ratio-V1AV3597th harmonic ratio-V2AV3607th harmonic ratio-V3AV3617th harmonic ratio-I1AV3627th harmonic ratio-I2AV3637th harmonic ratio-I3AV3648th harmonic ratio-V1AV3658th harmonic ratio-V2AV3668th harmonic ratio-V3AV3678th harmonic ratio-I1AV3688th harmonic ratio-I2AV3698th harmonic ratio-I3AV3709th harmonic ratio-V1AV3719th harmonic ratio-V2AV3729th harmonic ratio-V3AV3739th harmonic ratio-I1AV3749th harmonic ratio-I2AV3759th harmonic ratio-I3AV37610th harmonic ratio-V1AV37710th harmonic ratio-V2AV37810th harmonic ratio-V3AV37910th harmonic ratio-I1AV38010th harmonic ratio-I2AV38110th harmonic ratio-I3AV38211th harmonic ratio-V1AV38311th harmonic ratio-V2AV38411th harmonic ratio-V3AV38511th harmonic ratio-I1AV38611th harmonic ratio-I2AV38711th harmonic ratio-I3AV38812th harmonic ratio-V1AV38912th harmonic ratio-V2AV39012th harmonic ratio-V3AV39112th harmonic ratio-I1AV39212th harmonic ratio-I2AV39312th harmonic ratio-I3AV39413th harmonic ratio-V1AV39513th harmonic ratio-V2AV39613th harmonic ratio-V3AV39713th harmonic ratio-I1AV39813th harmonic ratio-I2AV39913th harmonic ratio-I3AV40014th harmonic ratio-V1AV40114th harmonic ratio-V2AV40214th harmonic ratio-V3AV40314th harmonic ratio-I1AV40414th harmonic ratio-I2AV40514th harmonic ratio-I3AV40615th harmonic ratio-V1AV40715th harmonic ratio-V2AV40815th harmonic ratio-V3AV40915th harmonic ratio-I1AV41015th harmonic ratio-I2AV41115th harmonic ratio-I3AV41216th harmonic ratio-V1AV41316th harmonic ratio-V2AV41416th harmonic ratio-V3AV41516th harmonic ratio-I1AV41616th harmonic ratio-I2AV41716th harmonic ratio-I3AV41817th harmonic ratio-V1AV41917th harmonic ratio-V2AV42017th harmonic ratio-V3AV42117th harmonic ratio-I1AV42217th harmonic ratio-I2AV42317th harmonic ratio-I3AV42418th harmonic ratio-V1AV42518th harmonic ratio-V2AV42618th harmonic ratio-V3AV42718th harmonic ratio-I1AV42818th harmonic ratio-I2AV42918th harmonic ratio-I3AV43019th harmonic ratio-V1AV43119th harmonic ratio-V2AV43219th harmonic ratio-V3AV43319th harmonic ratio-I1AV43419th harmonic ratio-I2AV43519th harmonic ratio-I3AV43620th harmonic ratio-V1AV43720th harmonic ratio-V2AV43820th harmonic ratio-V3AV43920th harmonic ratio-I1AV44020th harmonic ratio-I2AV44120th harmonic ratio-I3AV44221th harmonic ratio-V1AV44321th harmonic ratio-V2AV44421th harmonic ratio-V3AV44521th harmonic ratio-I1AV44621th harmonic ratio-I2AV44721th harmonic ratio-I3AV44822th harmonic ratio-V1AV44922th harmonic ratio-V2AV45022th harmonic ratio-V3AV45122th harmonic ratio-I1AV45222th harmonic ratio-I2AV45322th harmonic ratio-I3AV45423th harmonic ratio-V1AV45523th harmonic ratio-V2AV45623th harmonic ratio-V3AV45723th harmonic ratio-I1AV45823th harmonic ratio-I2AV45923th harmonic ratio-I3AV46024th harmonic ratio-V1AV46124th harmonic ratio-V2AV46224th harmonic ratio-V3AV46324th harmonic ratio-I1AV46424th harmonic ratio-I2AV46524th harmonic ratio-I3AV46625th harmonic ratio-V1AV46725th harmonic ratio-V2AV46825th harmonic ratio-V3AV46925th harmonic ratio-I1AV47025th harmonic ratio-I2AV47125th harmonic ratio-I3AV47226th harmonic ratio-V1AV47326th harmonic ratio-V2AV47426th harmonic ratio-V3AV47526th harmonic ratio-I1AV47626th harmonic ratio-I2AV47726th harmonic ratio-I3AV47827th harmonic ratio-V1AV47927th harmonic ratio-V2AV48027th harmonic ratio-V3AV48127th harmonic ratio-I1AV48227th harmonic ratio-I2AV48327th harmonic ratio-I3AV48428th harmonic ratio-V1AV48528th harmonic ratio-V2AV48628th harmonic ratio-V3AV48728th harmonic ratio-I1AV48828th harmonic ratio-I2AV48928th harmonic ratio-I3AV49029th harmonic ratio-V1AV49129th harmonic ratio-V2AV49229th harmonic ratio-V3AV49329th harmonic ratio-I1AV49429th harmonic ratio-I2AV49529th harmonic ratio-I3AV49630th harmonic ratio-V1AV49730th harmonic ratio-V2AV49830th harmonic ratio-V3AV49930th harmonic ratio-I1AV50030th harmonic ratio-I2AV50130th harmonic ratio-I3AV50231th harmonic ratio-V1AV50331th harmonic ratio-V2AV50431th harmonic ratio-V3AV50531th harmonic ratio-I1AV50631th harmonic ratio-I2AV50731th harmonic ratio-I3AV50832th harmonic ratio-V1AV50932th harmonic ratio-V2AV51032th harmonic ratio-V3AV51132th harmonic ratio-I1AV51232th harmonic ratio-I2AV51332th harmonic ratio-I3AV51433th harmonic ratio-V1AV51533th harmonic ratio-V2AV51633th harmonic ratio-V3AV51733th harmonic ratio-I1AV51833th harmonic ratio-I2AV51933th harmonic ratio-I3AV52034th harmonic ratio-V1AV52134th harmonic ratio-V2AV52234th harmonic ratio-V3AV52334th harmonic ratio-I1AV52434th harmonic ratio-I2AV52534th harmonic ratio-I3AV52635th harmonic ratio-V1AV52735th harmonic ratio-V2AV52835th harmonic ratio-V3AV52935th harmonic ratio-I1AV53035th harmonic ratio-I2AV53135th harmonic ratio-I3AV53236th harmonic ratio-V1AV53336th harmonic ratio-V2AV53436th harmonic ratio-V3AV53536th harmonic ratio-I1AV53636th harmonic ratio-I2AV53736th harmonic ratio-I3AV53837th harmonic ratio-V1AV53937th harmonic ratio-V2AV54037th harmonic ratio-V3AV54137th harmonic ratio-I1AV54237th harmonic ratio-I2AV54337th harmonic ratio-I3AV54438th harmonic ratio-V1AV54538th harmonic ratio-V2AV54638th harmonic ratio-V3AV54738th harmonic ratio-I1AV54838th harmonic ratio-I2AV54938th harmonic ratio-I3AV55039th harmonic ratio-V1AV55139th harmonic ratio-V2AV55239th harmonic ratio-V3AV55339th harmonic ratio-I1AV55439th harmonic ratio-I2AV55539th harmonic ratio-I3AV55640th harmonic ratio-V1AV55740th harmonic ratio-V2AV55840th harmonic ratio-V3AV55940th harmonic ratio-I1AV56040th harmonic ratio-I2AV56140th harmonic ratio-I3AV56241th harmonic ratio-V1AV56341th harmonic ratio-V2AV56441th harmonic ratio-V3AV56541th harmonic ratio-I1AV56641th harmonic ratio-I2AV56741th harmonic ratio-I3AV56842th harmonic ratio-V1AV56942th harmonic ratio-V2AV57042th harmonic ratio-V3AV57142th harmonic ratio-I1AV57242th harmonic ratio-I2AV57342th harmonic ratio-I3AV57443th harmonic ratio-V1AV57543th harmonic ratio-V2AV57643th harmonic ratio-V3AV57743th harmonic ratio-I1AV57843th harmonic ratio-I2AV57943th harmonic ratio-I3AV58044th harmonic ratio-V1AV58144th harmonic ratio-V2AV58244th harmonic ratio-V3AV58344th harmonic ratio-I1AV58444th harmonic ratio-I2AV58544th harmonic ratio-I3AV58645th harmonic ratio-V1AV58745th harmonic ratio-V2AV58845th harmonic ratio-V3AV58945th harmonic ratio-I1AV59045th harmonic ratio-I2AV59145th harmonic ratio-I3AV59246th harmonic ratio-V1AV59346th harmonic ratio-V2AV59446th harmonic ratio-V3AV59546th harmonic ratio-I1AV59646th harmonic ratio-I2AV59746th harmonic ratio-I3AV59847th harmonic ratio-V1AV59947th harmonic ratio-V2AV60047th harmonic ratio-V3AV60147th harmonic ratio-I1AV60247th harmonic ratio-I2AV60347th harmonic ratio-I3AV60448th harmonic ratio-V1AV60548th harmonic ratio-V2AV60648th harmonic ratio-V3AV60748th harmonic ratio-I1AV60848th harmonic ratio-I2AV60948th harmonic ratio-I3AV61049th harmonic ratio-V1AV61149th harmonic ratio-V2AV61249th harmonic ratio-V3AV61349th harmonic ratio-I1AV61449th harmonic ratio-I2AV61549th harmonic ratio-I3AV61650th harmonic ratio-V1AV61750th harmonic ratio-V2AV61850th harmonic ratio-V3AV61950th harmonic ratio-I1AV62050th harmonic ratio-I2AV62150th harmonic ratio-I3AV62251th harmonic ratio-V1AV62351th harmonic ratio-V2AV62451th harmonic ratio-V3AV62551th harmonic ratio-I1AV62651th harmonic ratio-I2AV62751th harmonic ratio-I3AV62852th harmonic ratio-V1AV62952th harmonic ratio-V2AV63052th harmonic ratio-V3AV63152th harmonic ratio-I1AV63252th harmonic ratio-I2AV63352th harmonic ratio-I3AV63453th harmonic ratio-V1AV63553th harmonic ratio-V2AV63653th harmonic ratio-V3AV63753th harmonic ratio-I1AV63853th harmonic ratio-I2AV63953th harmonic ratio-I3AV64054th harmonic ratio-V1AV64154th harmonic ratio-V2AV64254th harmonic ratio-V3AV64354th harmonic ratio-I1AV64454th harmonic ratio-I2AV64554th harmonic ratio-I3AV64655th harmonic ratio-V1AV64755th harmonic ratio-V2AV64855th harmonic ratio-V3AV64955th harmonic ratio-I1AV65055th harmonic ratio-I2AV65155th harmonic ratio-I3AV65256th harmonic ratio-V1AV65356th harmonic ratio-V2AV65456th harmonic ratio-V3AV65556th harmonic ratio-I1AV65656th harmonic ratio-I2AV65756th harmonic ratio-I3AV65857th harmonic ratio-V1AV65957th harmonic ratio-V2AV66057th harmonic ratio-V3AV66157th harmonic ratio-I1AV66257th harmonic ratio-I2AV66357th harmonic ratio-I3AV66458th harmonic ratio-V1AV66558th harmonic ratio-V2AV66658th harmonic ratio-V3AV66758th harmonic ratio-I1AV66858th harmonic ratio-I2AV66958th harmonic ratio-I3AV67059th harmonic ratio-V1AV67159th harmonic ratio-V2AV67259th harmonic ratio-V3AV67359th harmonic ratio-I1AV67459th harmonic ratio-I2AV67559th harmonic ratio-I3AV67660th harmonic ratio-V1AV67760th harmonic ratio-V2AV67860th harmonic ratio-V3AV67960th harmonic ratio-I1AV68060th harmonic ratio-I2AV68160th harmonic ratio-I3AV68261th harmonic ratio-V1AV68361th harmonic ratio-V2AV68461th harmonic ratio-V3AV68561th harmonic ratio-I1AV68661th harmonic ratio-I2AV68761th harmonic ratio-I3AV68862th harmonic ratio-V1AV68962th harmonic ratio-V2AV69062th harmonic ratio-V3AV69162th harmonic ratio-I1AV69262th harmonic ratio-I2AV69362th harmonic ratio-I3AV69463th harmonic ratio-V1AV69563th harmonic ratio-V2AV69663th harmonic ratio-V3AV69763th harmonic ratio-I1AV69863th harmonic ratio-I2AV69963th harmonic ratio-I3AV700X1-channel1 pulse counterAV701X1-channel2 pulse counterAV702X1-channel3 pulse counterAV703X1-channel4 pulse counterAV704X2-channel1 pulse counterAV705X2-channel2 pulse counterAV706X2-channel3 pulse counterAV707X2-channel4 pulse counterAV708X3-channel1 pulse counterAV709X3-channel2 pulse counterAV710X3-channel3 pulse counterAV711X3-channel4 pulse counterAV712X4-channel1 pulse counterAV713X4-channel2 pulse counterAV714X4-channel3 pulse counterAV715X4-channel4 pulse counterAV716Main boby-channel1 pulse counterAV717Main boby-channel2 pulse counterAV718Present demand value -I1AV719Present demand value -I2AV720Present demand value -I3AV721Present demand value -PAV722Present demand value -QAV723Present demand value -SAV724Previous demand value -I1AV725Previous demand value -I2AV726Previous demand value -I3AV727Previous demand value -PAV728Previous demand value -QAV729Previous demand value -SAV730Max. demand value -I1AV731Max. demand value -I2AV732Max. demand value -I3AV733Max. demand value -PAV734Max. demand value -QAV735Max. demand value -SAV736this month Max. demand value -I1AV737this month Max. demand value -I2AV738this month Max. demand value -I3AV739this month Max. demand value -PAV740this month Max. demand value -QAV741this month Max. demand value -SAV742last month Max. demand value -I1AV743last month Max. demand value -I2AV744last month Max. demand value -I3AV745last month Max. demand value -PAV746last month Max. demand value -QAV747last month Max. demand value -SAV748two months before Max. demand value -I1AV749two months before Max. demand value -I2AV750two months before Max. demand value -I3AV751two months before Max. demand value -PAV752two months before Max. demand value -QAV753two months before Max. demand value -SAV754Record: Power On High byte: year, Low byte: monthAV755High byte: day, Low byte: hourAV756High byte: minute, Low byte: secondAV757Power On NumberAV758Record: Power Off High byte: year, Low byte: monthAV759High byte: day, Low byte: hourAV760High byte: minute, Low byte: secondAV761Power Off NumberAV762Record: Setup parameter High byte: year, Low byte: monthAV763High byte: day, Low byte: hourAV764High byte: minute, Low byte: secondAV765Setup parameter NumberAV766Record: Clear demand High byte: year, Low byte: monthAV767High byte: day, Low byte: hourAV768High byte: minute, Low byte: secondAV769Clear demand resetting timesAV770Record: Clear energy High byte: year, Low byte: monthAV771High byte: day, Low byte: hourAV772High byte: minute, Low byte: secondAV773High byte: minute, Low byte: secondAV774High byte: Over voltage record number Low byte: ----AV775High byte: under voltage record number Low byte: ----AV776High byte: Over current record number Low byte: ----AV777High byte: under current record number Low byte: ----AV778High byte: Over active power record number Low byte: ----AV779High byte: under active power record number Low byte: ----AV780High byte: SOE event record number Low byte: ----AV781High byt:e: Voltage swell record number Low byte: ----AV782High byte: Voltage dip record number Low byte: ----AV783High byte: Voltage interrupt record number Low byte: ----AV784Main boby:Slave addressAV785Main boby:baudrateAV786Main boby:Data formatAV787High byte: Wiring Low byte: Grid frequencyAV788PT secondaryAV789CT secondaryAV790Secondary side neutral current ratingAV791PT primaryAV792CT primaryAV793Primary side neutral current ratingAV794Demand itemAV795Mode of demandAV796Slip time(t)AV797Demand period(T)AV798Voltage qualification rate upper limitAV799Voltage qualification rate lower limitAV800Frequency qualification rate upper limitAV801Frequency qualification rate lower limitAV802Relay output Main body-DO1 modeAV803Relay output Main body-DO1 Pulse widthAV804Relay output Main body-DO1 Alarm item selectAV805Relay output Main unit-DO1 limit valueAV806Relay output Main unit-DO1 hysteresisAV807Relay output Main body-DO1 Alarm delay timeAV808Relay output Main body-DO2 modeAV809Relay output Main body-DO2 Pulse widthAV810Relay output Main body-DO2 Alarm item selectAV811Relay output Main unit–DO2 limit valueAV812Relay output Main unit-DO2 hysteresisAV813Relay output Main body-DO2 Alarm delay timeAV814High byte: Main body DI1 mode Low byte: Main body DI2 modeAV815Voltage upper limit valueAV816Voltage upper limit hysteresis valueAV817Voltage lower limit valueAV818Voltage lower limit hysteresis valueAV819Current upper limit valueAV820Current upper limit hysteresis valueAV821Current lower limit valueAV822Current lower limit hysteresis valueAV823Active power upper limit valueAV824Active power upper limit hysteresis valueAV825Active power lower limit valueAV826Active power lower limit hysteresis valueAV827Voltage qualification rate upper limit valueAV828Voltage qualification rate lower limit valueAV829frequency qualification rate upper limit valueAV830Frequency qualification rate lower limit valueAV831Voltage sag limit valueAV832Voltage sag hysteresis valueAV833Voltage swell limit valueAV834Voltage swell hysteresis valueAV835Voltage interruption Limit valueAV836Voltage interruption hysteresis valueAV837Overvoltage start value of fault recordingAV838Overvoltage hysteresis value of fault recordingAV839undervoltage start value of fault recordingAV840undervoltage hysteresis value of fault recordingAV841overcurrent start value of fault recordingAV842overcurrent hysteresis value of fault recordingAV843Voltage sag and Voltage swell enableAV844fault recording enableAV845X1-AO1: ItemAV846X1-AO1: ModeAV847X1-AO1: Down scaleAV848X1-AO1: Full scaleAV849X1-AO2: ItemAV850X1-AO2: ModeAV851X1-AO2: Down scaleAV852X1-AO2: Full scaleAV853X2-AO1: ItemAV854X2-AO1: ModeAV855X2-AO1: Down scaleAV856X2-AO1: Full scaleAV857X2-AO2: ItemAV858X2-AO2: ModeAV859X2-AO2: Down scaleAV860X2-AO2: Full scaleAV861X3-AO1: ItemAV862X3-AO1: ModeAV863X3-AO1: Down scaleAV864X3-AO1: Full scaleAV865X3-AO2: ItemAV866X3-AO2: ModeAV867X3-AO2: Down scaleAV868X3-AO2: Full scaleAV869X4-AO1: ItemAV870X4-AO1: ModeAV871X4-AO1: Down scaleAV872X4-AO1: Full scaleAV873X4-AO2: ItemAV874X4-AO2: ModeAV875X4-AO2: Down scaleAV876X4-AO2: Full scaleAV877Switch input High byte: X1-DI1: Mode Low byte: X1-DI2: ModeAV878Switch input High byte: X1-DI3: Mode Low byte: X1-DI4: ModeAV879Switch input High byte: X2-DI1: Mode Low byte: X2-DI2: ModeAV880Switch input High byte: X2-DI3: Mode Low byte: X2-DI4: ModeAV881Switch input High byte: X3-DI1: Mode Low byte: X3-DI2: ModeAV882Switch input High byte: X3-DI3: Mode Low byte: X3-DI4: ModeAV883Switch input High byte: X4-DI1: Mode Low byte: X4-DI2: ModeAV884Switch input High byte: X4-DI3: Mode Low byte: X4-DI4: ModeAV885Relay output X1-DO1 modeAV886Relay output X1-DO1 pulse widthAV887Relay output X1-DO1 alarm selectAV888Relay output X1-DO1 limit valueAV889Relay output X1-DO1 hysteresisAV890Relay output X1-DO1 pulse widthAV891Relay output X1-DO2 modeAV892Relay output X1-DO2 pulse widthAV893Relay output X1-DO2 alarm selectAV894Relay output X1-DO2 limit valueAV895Relay output X1-DO2 hysteresisAV896Relay output X1-DO2 pulse widthAV897Relay output X2-DO1 modeAV898Relay output X2-DO1 pulse widthAV899Relay output X2-DO1 alarm selectAV900Relay output X2-DO1 limit valueAV901Relay output X2-DO1 hysteresisAV902Relay output X2-DO1 pulse widthAV903Relay output X2-DO2 modeAV904Relay output X2-DO2 pulse widthAV905Relay output X2-DO2 alarm selectAV906Relay output X2-DO2 limit valueAV907Relay output X2-DO2 hysteresisAV908Relay output X2-DO2 pulse widthAV909Relay output X3-DO1 modeAV910Relay output X3-DO1 pulse widthAV911Relay output X3-DO1 alarm selectAV912Relay output X3-DO1 limit valueAV913Relay output X3-DO1 hysteresisAV914Relay output X3-DO1 pulse widthAV915Relay output X3-DO2 modeAV916Relay output X3-DO2 pulse widthAV917Relay output X3-DO2 alarm selectAV918Relay output X3-DO2 limit valueAV919Relay output X3-DO2 hysteresisAV920Relay output X3-DO2 pulse widthAV921Relay output X4-DO1 modeAV922Relay output X4-DO1 pulse widthAV923Relay output X4-DO1 alarm selectAV924Relay output X4-DO1 limit valueAV925Relay output X4-DO1 hysteresisAV926Relay output X4-DO1 pulse widthAV927Relay output X4-DO2 modeAV928Relay output X4-DO2 pulse widthAV929Relay output X4-DO2 alarm selectAV930Relay output X4-DO2 limit valueAV931Relay output X4-DO2 hysteresisAV932Relay output X4-DO2 pulse widthBI0Subject-DO1BI1Subject-DO2BI2X1-DI1BI3X1-DI2BI4X1-DI3BI5X1-DI4BI6X2-DI1BI7X2-DI2BI8X2-DI3BI9X2-DI4BI10X3-DI1BI11X3-DI2BI12X3-DI3BI13X3-DI4BI14X4-DI1BI15X4-DI2BI16X4-DI3BI17X4-DI4BO0Subject-DO1BO1Subject-DO2BO2X1-DO1BO3X1-DO2BO4X2-DO1BO5X2-DO2BO6X3-DO1BO7X3-DO2BO8X4-DO1BO9X4-DO2BV0Phase SequenceBV1frequency statusBV2Voltage qualification stateBV3High voltage alarmBV4Low voltage alarmBV5High current alarmBV6Low current alarmBV7High active power alarmBV8Low active power alarmBV9X1 Extended statusBV10X2 Extended statusBV11X3 Extended statusBV12X4 Extended status
Integration notes
- Object names are the descriptions printed in the manual's object list; most are long, and the event-record objects repeat names like 'High byte: minute, Low byte: second'.
- AV 7 is printed 'Phase current-I1' (same as AV 6); it is presumably I2.
- Harmonic ratio objects are in 0.01 %; X1-X4 objects only work with the matching extension module fitted.
- Writable configuration AVs pack options as integers (often high byte / low byte pairs); descriptions give the start of the printed option list.
- BI objects for digital inputs are printed with access R/W.
- BV status objects print the state meanings after the name (e.g. 'High voltage alarm, 0: no alarm occurs, 1: alarm occurs'); the name is the part before the first comma.
- Source is a reseller's copy of the manual; no copy was found on rayleigh.com.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the RI-F500 series power analyser with RI-A5IPBAC BACnet IP module and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Rayleigh Instruments RI-F500 series power analyser with RI-A5IPBAC BACnet IP module
How many BACnet points does the Rayleigh Instruments RI-F500 series power analyser with RI-A5IPBAC BACnet IP module have?
This list has 998 BACnet objects: 16 analog inputs, 8 analog outputs, 933 analog values, 18 binary inputs, 10 binary outputs, 13 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Rayleigh Instruments RI-F500 series power analyser with RI-A5IPBAC BACnet IP module BACnet points are writable?
175 of the 998 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Rayleigh Instruments RI-F500 series power analyser with RI-A5IPBAC BACnet IP module BACnet documentation?
Rayleigh Instruments does not publish it on its own website. This list comes from RI-A5IPBAC (Bacnet module - TCP-IP) Communication Manual (V2), a copy hosted by Reseller Shopify CDN at https://cdn.shopify.com/s/files/1/0556/0283/9744/files/RI-A5IPBAC_user_manual_V2.pdf. Ask Rayleigh Instruments or its representative for the current revision.
What are the minimum BACnet points to integrate the Rayleigh Instruments RI-F500 series power analyser with RI-A5IPBAC BACnet IP module?
Start with AV 27 Import Active Energy EP+ (Import active energy, kWh); AV 13 Total active power-P (Total active power, kW); AV 17 Total reactive power-Q (Total reactive power, kvar); AV 0 Phase voltage-V1 (Phase voltage L1, V); AV 3 Line voltage-V12 (Line voltage L1-L2, V); AV 6 Phase current-I1 (Phase current L1, A); AV 721 Present demand value -P (Present active power demand, kW); BV 3 High voltage alarm (High voltage alarm (1 = alarm)); BV 0 Phase Sequence (Phase sequence abnormal (1)).
How do I check these points on the real RI-F500 series power analyser with RI-A5IPBAC BACnet IP module?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
Source: RI-A5IPBAC (Bacnet module - TCP-IP) Communication Manual · V2. Object names, instances and units are reproduced as published; descriptions are our own.