Thermostat (2-stage heat / cool, heat pump) · BACnet points list

Quest Controls BACnet T-Stat BACnet points list

Updated 7 November 2026Unofficial source

Short answer

The Quest Controls BACnet T-Stat is a BACnet MS/TP thermostat with zone and supply air thermistors, fan proving and a built-in weekly schedule of two occupied windows per day. Setpoints, delays, offsets and the schedule are analog values; fan modes and an occupied override are binary values; HVAC type, control mode and operating stage are multistate inputs; the G, Y1, Y2, W1/B, W2 and O outputs are commandable binary outputs.

This page lists 73 BACnet objects for the Quest Controls BACnet T-Stat — 66 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Quest Controls’s documentation hosted by Internet Archive (manualzilla), not by Quest Controls itself, so treat it as unofficial.

Manufacturer
Quest Controls
Model
BACnet T-Stat
Equipment
Thermostat (2-stage heat / cool, heat pump)
Equipment type
Heat pumps
BACnet objects
73 (66 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
MS/TP network (AV 1) x 1000 + MAC address (AV 0)
Also known as
Quest BACnet T-Stat, Quest Controls T-Stat
Source document
BACnet T-Stat by Quest Controls User's Manual · Rev 1.1 · rev. 2011-07-28 (unofficial copy, hosted by Internet Archive (manualzilla))
Download CSV 73 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Quest Controls’s current documentation and the live device before use. Not official Quest Controls information. Terms of use.

BMS integration notes: Quest Controls BACnet T-Stat

Integration in brief

Set the control mode with MI 2, write the occupied and unoccupied setpoints AV 5-8 and use BV 3 to force occupied mode from the BMS (or program the schedule windows AV 25-52). Read AV 19 zone temperature, the active setpoints AV 23 / AV 24, MI 3 operating stage, AV 22 occupancy status and BI 0 fan proof.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 3Force Occupied ModeBACnet occupied override (1 = force occupied)Write
MI 2Control ModeMode: 1 auto, 2 cool only, 3 heat only, 4 offWrite
AV 5Occupied Cool SptOccupied stage 1 cooling setpointWrite
AV 7Occupied Heat SptOccupied stage 1 heating setpointWrite
AV 19Zone ReadingZone temperature with offset appliedWrite
AV 23Cool Stage 1 SptActive stage 1 cooling setpointRead
AV 24Heat Stage 1 SptActive stage 1 heating setpointRead
MI 3Operation Mode StatusOperating stage: off, cooling or heating stageRead
AV 22Occupied Mode StatusOccupied status bits: BACnet, panel, scheduleRead
BI 0Fan ProofFan proof inputRead

Enable & remote start

BV 3 Force Occupied Mode puts the thermostat in occupied mode from the BMS; 0 removes the BACnet override. The internal schedule (AV 25-52) runs otherwise.

Network setup

Watch out for

Quest Controls BACnet T-Stat BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

73 of 73 shown
Type
Multi-state
Access
Show
Quest Controls BACnet T-Stat BACnet Points List
DescriptionStates
AI0Raw Zone TempRaw thermistor reading, no offset; -25 °F = open, 150 °F = shorted°FRead
AI1Raw Supply AirRaw thermistor reading, no offset; -25 °F = open, 150 °F = shorted°FRead
AV0MAC AddressRange 1..127, default 1Write
AV1MSTP NetworkRange 0..4194, default 0Write
AV2Zone OffsetRange -9F..9F, default 0°FWrite
AV3Supply OffsetRange -9F..9F, default 0°FWrite
AV4Residual Fan DelayRange 0..180, default 30sWrite
AVmin5Occupied Cool SptRange 42F..90F, default 74F°FWrite
AV6Unoccupied Cool SptRange 42F..90F, default 85F°FWrite
AVmin7Occupied Heat SptRange 40F..88F, default 68F°FWrite
AV8Unoccupied Heat SptRange 40F..88F, default 55F°FWrite
AV9Cool 2 Stage DeltaRange 1F..9F, default 2F°FWrite
AV10Heat 2 Stage DeltaRange 1F..9F, default 2F°FWrite
AV11Cool Heat Min DiffRange 2F..9F, default 4F°FWrite
AV12Cool Min On TimeRange 60..600, default 120sWrite
AV13Cool Min Off TimeRange 60..600, default 120sWrite
AV14Heat Min On TimeRange 60..600, default 120sWrite
AV15Heat Min Off TimeRange 60..600, default 120sWrite
AV16Max User Spt AdjustRange 0..5F, default 5F°FWrite
AV17Occupied Override TimeRange 0..240, default 60minWrite
AV18Override Time LeftRange 0..(AV 17 x 60)sWrite
AVmin19Zone ReadingRange -25F..150F°FWrite
AV20Supply ReadingRange -25F..150F°FWrite
AV21Restart DelayRange 0..900, default 0sWrite
AVmin22Occupied Mode StatusBit 0 BACnet override, bit 1 front panel override, bit 2 scheduleRead
AVmin23Cool Stage 1 Spt°FRead
AVmin24Heat Stage 1 Spt°FRead
AV25Mon Sched Win 1 StartRange 0..1440, default 0minWrite
AV26Mon Sched Win 1 EndRange 0..1440, default 0minWrite
AV27Mon Sched Win 2 StartRange 0..1440, default 0minWrite
AV28Mon Sched Win 2 EndRange 0..1440, default 0minWrite
AV29Tue Sched Win 1 StartRange 0..1440, default 0minWrite
AV30Tue Sched Win 1 EndRange 0..1440, default 0minWrite
AV31Tue Sched Win 2 StartRange 0..1440, default 0minWrite
AV32Tue Sched Win 2 EndRange 0..1440, default 0minWrite
AV33Wed Sched Win 1 StartRange 0..1440, default 0minWrite
AV34Wed Sched Win 1 EndRange 0..1440, default 0minWrite
AV35Wed Sched Win 2 StartRange 0..1440, default 0minWrite
AV36Wed Sched Win 2 EndRange 0..1440, default 0minWrite
AV37Thu Sched Win 1 StartRange 0..1440, default 0minWrite
AV38Thu Sched Win 1 EndRange 0..1440, default 0minWrite
AV39Thu Sched Win 2 StartRange 0..1440, default 0minWrite
AV40Thu Sched Win 2 EndRange 0..1440, default 0minWrite
AV41Fri Sched Win 1 StartRange 0..1440, default 0minWrite
AV42Fri Sched Win 1 EndRange 0..1440, default 0minWrite
AV43Fri Sched Win 2 StartRange 0..1440, default 0minWrite
AV44Fri Sched Win 2 EndRange 0..1440, default 0minWrite
AV45Sat Sched Win 1 StartRange 0..1440, default 0minWrite
AV46Sat Sched Win 1 EndRange 0..1440, default 0minWrite
AV47Sat Sched Win 2 StartRange 0..1440, default 0minWrite
AV48Sat Sched Win 2 EndRange 0..1440, default 0minWrite
AV49Sun Sched Win 1 StartRange 0..1440, default 0minWrite
AV50Sun Sched Win 1 EndRange 0..1440, default 0minWrite
AV51Sun Sched Win 2 StartRange 0..1440, default 0minWrite
AV52Sun Sched Win 2 EndRange 0..1440, default 0minWrite
AV53Curr User Spt AdjustRange 0..AV16°FWrite
AV54Front Panel CodeRange 0,11..99, default 0Write
BImin0Fan ProofFan proof inputRead
BV0Temperature UnitsWrite0=Use Fahrenheit, 1=Use Celsius
BV1Occupied Fan ModeWrite0=Fan mode auto, 1=Fan mode always on
BV2Unoccupied Fan ModeWrite0=Fan mode auto, 1=Fan mode always on
BVmin3Force Occupied ModeWrite0=Remove BACnet occupied override, 1=Enable BACnet occupied override
BV4Zone Sensor LocationWrite0=Use onboard zone thermistor, 1=Use remote mounted zone thermistor
BO0Output GCommand0=De-energize Output, 1=Energize Output, 255=Remove bypass
BO1Output Y1Command0=De-energize Output, 1=Energize Output, 255=Remove bypass
BO2Output Y2Command0=De-energize Output, 1=Energize Output, 255=Remove bypass
BO3Output W1/BCommand0=De-energize Output, 1=Energize Output, 255=Remove bypass
BO4Output W2Command0=De-energize Output, 1=Energize Output, 255=Remove bypass
BO5Output OCommand0=De-energize Output, 1=Energize Output, 255=Remove bypass
MI0Baud RateMS/TP baud rate; default 3 (38400)Write1=9600, 2=19200, 3=38400, 4=57600, 5=76800
MI1HVAC TypeEquipment type; default 1Write1=Single Stage Conventional, 2=Dual Stage Conventional, 3=Heat Pump 1, 4=Heat Pump 2, 5=Gas Heat 1, 6=Gas Heat 2
MImin2Control ModeHeat/cool mode; default 1 (auto)Write1=Auto, 2=Cooling only, 3=Heating only, 4=Off
MImin3Operation Mode StatusCurrent operating stageRead1=Off, 2=Cooling stage 1, 3=Cooling stage 2, 4=Heating stage 1, 5=Heating stage 2, 6=Heating stage 3
Object ID lookup: Quest Controls BACnet T-Stat point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the BACnet T-Stat and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Quest Controls BACnet T-Stat

How many BACnet points does the Quest Controls BACnet T-Stat have?

This list has 73 BACnet objects: 2 analog inputs, 55 analog values, 1 binary input, 6 binary outputs, 5 binary values, 4 multi-state inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Quest Controls BACnet T-Stat BACnet points are writable?

66 of the 73 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Quest Controls BACnet T-Stat BACnet documentation?

Quest Controls does not publish it on its own website. This list comes from BACnet T-Stat by Quest Controls User's Manual (Rev 1.1), revision 2011-07-28, a copy hosted by Internet Archive (manualzilla) at https://archive.org/download/manualzilla-id-7322454/7322454.pdf. Ask Quest Controls or its representative for the current revision.

What are the minimum BACnet points to integrate the Quest Controls BACnet T-Stat?

Start with BV 3 Force Occupied Mode (BACnet occupied override (1 = force occupied)); MI 2 Control Mode (Mode: 1 auto, 2 cool only, 3 heat only, 4 off); AV 5 Occupied Cool Spt (Occupied stage 1 cooling setpoint); AV 7 Occupied Heat Spt (Occupied stage 1 heating setpoint); AV 19 Zone Reading (Zone temperature with offset applied); AV 23 Cool Stage 1 Spt (Active stage 1 cooling setpoint); AV 24 Heat Stage 1 Spt (Active stage 1 heating setpoint); MI 3 Operation Mode Status (Operating stage: off, cooling or heating stage); AV 22 Occupied Mode Status (Occupied status bits: BACnet, panel, schedule); BI 0 Fan Proof (Fan proof input).

How do I enable BMS control of the Quest Controls BACnet T-Stat?

BV 3 Force Occupied Mode puts the thermostat in occupied mode from the BMS; 0 removes the BACnet override. The internal schedule (AV 25-52) runs otherwise.

How do I check these points on the real BACnet T-Stat?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: BACnet T-Stat by Quest Controls User's Manual · Rev 1.1 · rev. 2011-07-28. Object names, instances and units are reproduced as published; descriptions are our own.